PM Check List - CB & Busbar
PM Check List - CB & Busbar
CIRCUIT BREAKER
W.O.No : Serial Number TAG NO:
Flowstation Platform Location
1. SPECIFICATION
Description Specification Description Specification
Feeder Name Voltage Rating
Brand/Manufacture Voltage Range Factor
Model/Type Closing Coil
Serial Number Tripping Coil
Nominal Current Frequency
Short Circuit Current Mech Type
4. MEASUREMENT TEST
CB INSULATION RESISTANCE - PHASE TO GROUND
INSULATION RESISTANCE (GΩ)
Phase to Ground 1 Min - Result (GΩ) 10 Min - Result (GΩ)
R - Gnd
S - Gnd
T - Gnd
CB CONTACT RESISTANCE
CONTACT RESISTANCE (µΩ)
Phase Result (µΩ) Notes
R
S
T
CB TIMING CONTACT
TIMING CONTACT (ms)
Phase Closing (ms) Opening (ms)
R
S
T
3 Sign & Date : Sign & Date : Sign & Date : Sign & Date :
6 COMMENT
3 Sign & Date : Sign & Date : Sign & Date : Sign & Date :
1. SPECIFICATION
SWITCHBOARD : TYPE : POWER :
TRIPPING/CLOSING COIL
INSERT/WITHDRAW
OPER. MECHANISM
SHUTTER SYSTEM
LOCKING SYSTEM
COMPARTEMENT
COMPARTMENT
COMPARTMENT
COMPARTMENT
COMPARTMENT
MAIN CONTACT
MAIN CONTACT
AUX. CONTACT
TERMINAL
BUSBAR
HV FUSE
CT'S
PT'S
Dust Removal.
Cleaning
Greas./Lub
Checking
Tightening
3. INSULATION TEST
CB CONTACT RESISTANCE
CONTACT RESISTANCE (µΩ)
Phase Result (µΩ) Notes
R
S
T
4. COMMENT:
3 Sign & Date : Sign & Date : Sign & Date : Sign & Date :
Minor problem in
the Allmost all of
Good condition of Some of function
compartment/dirty function
compartment, (withdraw,
, but good (withdraw,
withdraw, shutter, shutter, locking,
HV Compartment N/A locking,
condition of
mechanism &
shutter, locking,
withdraw, shutter, mechanism &
mechanism & main contact) was
locking, main contact) was
main contact found failed
mechanism & found failed
main contact
Cable &
Condition of cable Cable &
Good condition of compartment very
& compartment a compartment dirty
Cable Compartment N/A cable &
bit dirty/dust but limited dust
dirty/excessive
compartment dust
contamination contamination
contamination
Compartment
Compartment a Compartment very
Good condition of bit dirty/dust dirty/dust dirty/excessive
LV & PTS Compartment N/A compartment & contamination, contamination & dust
terminal but the terminal in the terminal not in contamination &
good condition good condition the terminal not in
good condition
CB Contact Resistance mΩ < 0.1 ≥ 0.1 ≤ 0.3 > 0.3 ≤ 0.4 > 0.4
CB Preventive CB Insulation Resistance MΩ >100 = 100 < 100 < 50
CB RST Contact Timing Shyncrone N/A Good Function - - Fail
Test &
Measurement
Thermal Overload Relay N/A Good Function N/A N/A Fail
Test & N/A Good Function N/A N/A Fail
Check interlock function
Measurement
Volt indicator N/A Good Function N/A N/A Fail
Ampere Indicator N/A Good Function N/A N/A Fail
Metering Preventive Frequency Indicator N/A Good Function N/A N/A Fail
CT/Current Transformer N/A Good Function N/A N/A Fail
PT/Potential Transformer N/A Good Function N/A N/A Fail
Bus-bar ( Temp. Max. Ref. 70 oC ) % Delta T oC < -20 -20 to -10 > -10 to 10 > 10
Temperature & Condition Base
Thermography Monitoring Cable & Terminal cable connection
% Delta T oC < -20 -20 to -10 > -10 to 10 > 10
( Temp. Max. Ref. 70 oC )
Medium High
Risk Category Switchgear Risk Category Risk Category Score Low Risk Medium Risk
Risk
High Risk