Instruction Chart For Co2 Fire Extinguishing System

This document provides instructions for operating a CO2 fire extinguishing system. It details the locations of CO2 bottles and release control cabinets. In the event of a fire in the engine or pump room, personnel should go to the control cabinets to operate the system. The emergency operation instructions explain how to open cylinder valves to release CO2 gas into the protected space if the main system fails. Personnel must evacuate first and then follow several steps including opening valves to flood the area with CO2 and extinguish the fire.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
84 views1 page

Instruction Chart For Co2 Fire Extinguishing System

This document provides instructions for operating a CO2 fire extinguishing system. It details the locations of CO2 bottles and release control cabinets. In the event of a fire in the engine or pump room, personnel should go to the control cabinets to operate the system. The emergency operation instructions explain how to open cylinder valves to release CO2 gas into the protected space if the main system fails. Personnel must evacuate first and then follow several steps including opening valves to flood the area with CO2 and extinguish the fire.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

INSTRUCTION CHART FOR CO2 FIRE EXTINGUISHING SYSTEM

FIRE CONTROL STATION CO2 ROOM PUMP ROOM


TOTAL : 248 BOTTLES 42 BOTTLES

ENGINE ROOM
248 BOTTLES

EMERGENCY OPERATION AFTER DISCHARGE


IN THE EVENT OF FIRE
IN CASE OF FAILURE IN OPERATION OF 1. ALLOW ENOUGH TIME FOR THE CO2
IN ENGINE ROOM IN PUMP ROOM THE SYSTEM FROM THE CONTROL GAS TO EXTINGUISH THE FIRE.
CABINET, GO TO THE CO2 ROOM. 2. DO NOT REOPEN THE SPACE UNTIL ALL
GO TO THE RELEASE CONTROL CABINETS GO TO THE RELEASE CONTROL CABINETS REASONABLE PRECAUTIONS HAVE BEEN
LOCATED AT CO2 ROOM OR FIRE LOCATED AT CO2 ROOM OR FIRE 1. ENSURE ALL PERSONNEL HAVE BEEN TAKEN TO ASCERTAIN THAT THE FIRE
CONTROL STATION. CONTROL STATION. EVACUATED FROM THE SPACE TO BE IS OUT.
FLOODED WITH CO2. 3. WHEN THE FIRE IS OUT, VENTILATE THE
1) KEY BOX 1) KEY BOX
2. CONFIRM ALL VENT FANS STOPPED, SPACE THOROUGHLY.
1. BREAK THE GLASS. 1. BREAK THE GLASS. DOORS AND HATCHES CLOSED. 4. PERSONS RE-ENTERING THE SPACE
2. TAKE THE KEY. 2. TAKE THE KEY. 3. OPEN THE RELEVANT MAIN VALVE. MUST WEAR THE COMPRESSED AIR
a. HAND WHEEL TYPE BREATHING APPARATUS UNTIL THE
2) RELEASE CONTROL CABINET 2) RELEASE CONTROL CABINET - OPEN BY ROTATING THE WHEEL TO ATMOSPHERE HAS BEEN CHECKED AND
1. OPEN THIS DOOR. 1. OPEN THIS DOOR. ANTI-CLOCKWISE. VERIFIED IN 21% OF OXYGEN CONTENT.
2. ENSURE ALL PERSONNEL HAVE 2. ENSURE ALL PERSONNEL HAVE 4. GO TO THE CYLINDER AND OPEN THE
VACATED THE PROTECTED SPACE. VACATED THE PROTECTED SPACE. CYLINDER VALVE.
- REMOVE THE SAFETY PIN OF
3. CLOSE ALL VENTS, DOORS AND 3. CLOSE ALL VENTS, DOORS AND
ACTUATOR FITTED ON CYLINDER VALVE.
HATCHES, FIRE DAMPERS AND FUEL HATCHES, FIRE DAMPERS AND FUEL
- PULL DOWN THE OPERATING LEVER
VALVE. VALVE. AND THE CO2 GAS IS DISCHARGED.
4. OPEN ONE CYLINDER VALVE. 4. OPEN ONE CYLINDER VALVE. 5. TAKE THE SAME ACTION RAPIDLY FOR
5. OPEN VALVE NO.1 & NO,2. 5. OPEN VALVE NO.1 & NO,2. THE REQUIRED QUANTITIES OF CO2
6. NOW SYSTEM IS OPERATED. 6. NOW SYSTEM IS OPERATED. CYLINDERS. MAIN VALVE
6. NOW THE SYSTEM IS IN OPERATION.
HAND WHEEL TYPE
IF NOT, FOLLOW EMERGENCY OPERATION IF NOT, FOLLOW EMERGENCY OPERATION
ON INSTRUCTION CHART. ON INSTRUCTION CHART.

CYLINDER VALVE ACTUATOR

- ROTATING THE
1. REMOVE SAFETY PIN. 2. TAKE DOWN LEVER. HAND WHEEL.

NK CO., LTD.

INSTRUCTION CHART

NK CO., LTD.