Tel: Ashrae Duct Fitting Database Fax: Version # 5. 00.00 27 June 2022

This document contains input and output data for a 45 degree entry branch tee duct fitting from the ASHRAE duct fitting database. The inputs include dimensions of the main duct, branch duct, and flow rates, and the outputs include velocities, pressure losses, and loss coefficients for the main and branch ducts.

Uploaded by

mano
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
591 views

Tel: Ashrae Duct Fitting Database Fax: Version # 5. 00.00 27 June 2022

This document contains input and output data for a 45 degree entry branch tee duct fitting from the ASHRAE duct fitting database. The inputs include dimensions of the main duct, branch duct, and flow rates, and the outputs include velocities, pressure losses, and loss coefficients for the main and branch ducts.

Uploaded by

mano
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Tel: ASHRAE DUCT FITTING DATABASE

Fax: Version # 5. 00.00 27 June 2022

(SR5-13) Tee, 45 Degree Entry Branch, Diverging (Brooks 1993)

INPUTS OUTPUTS

Height (H, mm) 400 Branch


Width (W, mm) 450 Velocity (Vb, m/s) 4.2
Height (Hs, mm) 400 Vel Pres at Vb (Pvb, Pa) 11
Width (Ws, mm) 450 Loss Coefficient (Cb) 1.35
Height (Hb, mm) 350 Branch Pressure Loss (Pa) 15
Width (Wb, mm) 350 Main
Flow Rate (Qc, L/s) 1038 Velocity (Vs, m/s) 2.9
Flow Rate (Qb, L/s) 519 Velocity (Vc, m/s) 5.8
Density (kg/m^3) 1.204 Vel Pres at Vs (Pvs, Pa) 5
Vel Pres at Vc (Pvc, Pa) 20
Loss Coefficient (Cs) 0.99
Main Pressure Loss (Pa) 5

06-27-2022 version: 5.00.00