INTRO MOD 8-Protection Rev2016
INTRO MOD 8-Protection Rev2016
8|System Protection
W E S T E R N E L E C T R I C I T Y C O O R D I N A T I N G C O U N C I L
Course Outline
1. Introduction to WECC
2. Fundamentals of Electricity
3. Power System Overview
4. Principles of Generation
5. Substation Overview
6. Transformers
7. Power Transmission
8. System Protection
9. Principles of System Operation
Overview
• Purpose of Protection Systems
• Characteristics of Protection Systems
• Types of Relay and Applications
Purpose
• Then we examine how a protection system
operates. The primary purpose of the
protection system is to detect faults and, as
rapidly as possible, "clear" faults.
• Faults are physical conditions that cause a
device, component, or element to fail to
perform in the required manner; for example,
a short circuit or a broken wire.
Causes of Faults
• Some of the common causes of faults are:
• A tree limb comes in contact with an energized
overhead wire.
• An overhead wire breaks due to snow or ice loading,
or because a car strikes the utility pole causing the
wire to come in contact with the ground.
• Power system components such as circuit breakers or
transformers malfunction; or the insulation fails due to
wear, age, or repeated operations.
• Lightning strikes an overhead wire, either causing
physical damage or creating charged air molecules
that serve as a path on which fault current can flow.
Protection System
• Rapid operation of the protection system
accomplishes the following:
• Maintains Safety
– Maintains Personnel and Public Safety. A downed
wire that has not been electrically isolated is still
energized. This presents a safety hazard to people
who may attempt to move it or who inadvertently
contact it.
Protection System
• Prevents Damage
– Prevents More Extensive Damage. Short circuit
currents during faults are many times the normal load
currents. If the flow of the current is not interrupted
quickly, components of the electric system may be
damaged. In addition, some faults can cause over-
voltages that exceed the rating of the insulation of
some components, resulting in further damage to the
equipment. The overvoltage's are usually transient
and are produced from simple circuit changes, such
as a circuit breaker opening or the grounding of a
conductor.
Protection System
• Prevents Stability Problems
– Prevents Power System Stability Problems. Faults
that remain on high-voltage transmission
equipment or on generators can cause system
stability problems. Power system stability is
discussed in more detail in Module 9: Principles
of Power System Operation.
Characteristics
• Protection systems have three major
components:
• 1) Measuring Devices
• 2) Protective Relays
• 3) Control Circuitry
Measuring Devices
• Most protection systems analyze power system
current flow and/or voltage to determine whether a
fault exists. Sudden changes in these quantities could
indicate that a fault exists.
• For example: either a sudden increase in current flow
to many times the normal load current, or a significant
increase or decrease in line voltage could indicate that
a fault exists somewhere.
• The protection system cannot directly use the voltage
and current measurements from the high-voltage
equipment as inputs. Therefore, these values must be
scaled down.
Measuring Devices
• The following devices perform this function:
– current transformers (CTs)
– voltage transformers (PTs)
– coupling capacitance voltage transformers
(CCVTs)
Current Transformer (CT)
• Power system current is measured by current
transformers; commonly called CTs. CTs
reduce or scale down the actual current to
proportional values of a few amperes for use
by the protection system.
• Most CTs are donut-shaped and are installed
over the bushings of power transformers,
circuit breakers, or generators.
Current Transformers (CTs)
• CTs produce a small secondary current flow (a
few amps) that is proportional to a larger
primary current flow in the power system.
• The turns ratio of the CT may be 2500:1. This
allows the current to be reduced to make it
useable for metering and relays.
Bushing Mounted (CT)
Metering CT’s
Current Transformer (External)
Metering CT’s
PT’s and CCVT’s
• Power system voltage is measured either by
voltage transformers or coupling capacitance
voltage transformers (CCVTs), depending on the
voltage level being measured. Both devices
reduce electric system voltage down to
proportional values of 120 volts or less.
• Voltage transformers are simple magnetic core,
wire-wound transformers. They are usually
referred to as PTs, short for potential
transformers. PTs operate in the same way as
step-down power or distribution transformers.
PT’s and CCVT’s
• At voltage levels of 100 kV or higher, the cost of
PTs becomes very high. At these voltage levels,
therefore, CCVTs are typically used. A CCVT is a
stack of capacitors connected between the points
of voltage measurement. The desired 120 voltage
level is obtained by voltage division.
The accuracy of CCVTs is less than that of PTs.
CCVTs may not be acceptable, where high accuracy
is required, such as for billing or metering
functions.
CCVT
Voltage measuring
transformers
69kV PT’s
San Luis Valley 115kV Bus “B” PT’s
Protective Relays
• Protective relays are protection system devices
which compare power system voltages and currents
to normally-expected values to determine whether
the protected device has a fault.
• The earliest types of protective relays, many of
which are still in use today, were built using
electromechanical components, such as gears,
springs, mechanical timers, and induction disks.
Protective Relays
Transfer Tripping
Directional Comparison
Phase Comparison
Pilot-Wire
DISTANCE RELAYING
ZONE 1
A B C
ZONE 2
DISTANCE RELAYING
ZONE 1
A B C
ZONE 2
DISTANCE RELAYING
A B C
A B C
A B
PHASE COMPARISON RELAYING
A B C
A
B
PHASE COMPARISON RELAYING
CURRENT FLOW
A B C
PHASE COMPARISON RELAYING
A B C
B
A
PHASE COMPARISON RELAYING
CURRENT FLOW
A B C
PHASE COMPARISON RELAYING
CURRENT FLOW
A B C
A
B
PHASE COMPARISON RELAYING
CURRENT FLOW
A B C
B
A
Pilot Wire
• Another commonly-used type of pilot
protection system is the pilot wire relay
system.
• This system compares the magnitude and
phase angle of the current flowing at each
end of the line to determine whether an
internal fault exists.
PILOT WIRE RELAYING
A B C
Out-of-Step
• Definition: Swings
• Protection systems must function properly
during power system "swings".
• Swings are oscillations of generators with
respect to other generators due to sudden
changes of load, switching, or faults.
• To function properly, out-of-step (OOS)
protection systems must be able to:
– trip for non-recoverable stability conditions and true
faults
– block tripping for recoverable swings
How Out-of-Step Works
• If the impedance decreases suddenly to the
relay's trip setting, a true fault has likely
occurred. Therefore, tripping is required.
• If the impedance decreases gradually to the
relay's trip setting, this most likely is due to
swinging generators rather than a fault in the
relay's protected zone. Therefore, the relay
holds off tripping until it determines whether
the system can recover from the swing.
How Out-of-Step Works
• If the impedance returns to normal within a
pre-determined time period, the relay
assumes that the system has recovered and
no tripping occurs.
• If the impedance stays low for a specified
time period and then gradually moves above
the trip setting, the system is probably
unstable, so tripping occurs.
Single Pole Relaying
• Definition: Single Pole Tripping
• Most transmission line faults are temporary
single-phase-to-ground faults.
• They can be cleared by opening and reclosing
only the faulted phase.
• This method is known as single pole tripping.
It leaves the other two phases intact and
minimizes the shock to the power system.
SINGLE POLE TRIPPING
G G
R R
I I
D D
SINGLE POLE TRIPPING
G G
R R
I I
D D
SINGLE POLE TRIPPING
G G
R R
I I
D D
SINGLE POLE TRIPPING
G G
R R
I I
D D
SINGLE POLE TRIPPING
G G
R R
I I
D D
SS SS SS SS SS SS
SS SS SS SS SS SS
SS SS
SS SS
SINGLE POLE TRIPPING
G G
R R
I I
D D
SS SS SS SS SS SS
SS SS SS SS SS SS
SS SS
SS SS
Relay Types - Practice
http://bsc-houdini.bsc.nodak.edu/onlinepres/ILTs/Transmission_Line_Relaying.swf
Substation Equipment Protection
• Shunt Equipment Protection
• Bus Protection
• Transformer Protection
• Circuit Breaker Failure Protection
• Underfrequency Load Shedding
Shunt Equipment Protection
• Shunt equipment, such as a capacitor bank, is
usually protected using:
– Time overcurrent or differential relays which open
circuit breakers or circuit switchers to de-energize
this equipment during a fault.
• Or
– Fuses that blow to de-energize the device when
high current flow occurs.
Bus Protection
• Substation buses usually have one or more
incoming lines that are sources of fault current,
and multiple outgoing lines, that may or may not
be sources of fault current.
Bus Protection
• Differential protection is the most sensitive
and reliable method for protecting substation
buses, because:
– all currents entering and leaving the bus are
added
– the difference between the incoming and
outgoing currents is the input to a sensitive
overcurrent relay.
Transformer Protection
• The most common forms of protection systems for
substation transformers are overcurrent, differential
and sudden pressure detection.
• Transformer overcurrent and differential protection
systems are similar in concept to the previously
discussed applications, in that:
– Transformer overcurrent relays detect abnormally high
current flow to the transformer.
– Transformer differential relays subtract the current leaving
the transformer from the current entering the
transformer, and then use the difference current to
determine if an internal fault exists.
Transformer Protection
• However, both of these schemes are complicated by
magnetizing in-rush current flow to the transformer.
• When a transformer is first energized, a transient
magnetizing or exciting current may flow.
• In-rush current can reach peak values of up to 30
times the full-load value, which is more than enough
to cause an overcurrent relay to operate.
Harmonics
• To prevent overcurrent and differential relays from
operating on inrush current, we must use special
relays with reduced sensitivity to inrush currents.
• Typically, such relays filter out the harmonic content of
the current before deciding whether a fault exists.
• Harmonics are electric currents that alternate at a
frequency other than 60 Hz.
• In some cases, the harmonic portion of the current
restrains the operation of the relay until the inrush
currents decay (die out) to an insignificantly small
value.
Transformer Sudden Pressure
• Transformer sudden pressure relays operate if
the gas pressure in the transformer abruptly
rises to a certain level.
• Sudden pressure increases indicate a fault.
• Transformer gas usually results when "arcing"
from internal faults breaks down the
transformer's insulating oil.
Breaker Failure Protection
• Problems can occur which prevent a circuit breaker
from operating when called upon by a protection
system.
• Faults that are not cleared by the primary protection
system and associated circuit breakers almost always
will eventually be cleared by protection systems in
adjacent protection zones.
• But the delay in clearing the fault can be intolerable
on high-voltage facilities.
Breaker Failure Protection
• Circuit breakers at
important high-
voltage facilities
are frequently
equipped with
circuit-breaker-
failure detection
circuitry.
Underfrequency Load Shedding
• In a stable power system, the generator
control systems usually maintain system
frequency very close to 60 Hz.
• Sudden or large changes in generating
capacity due to the loss of a large generator
or tie-line can cause a severe generation/load
imbalance, resulting in a frequency decline.
Generator Protection
• Although the frequency of generator faults is
low, the potential for severe damage and
consequently long outages is high.
• Therefore, some of the most complex and
sensitive protection systems are used for the
generators.
Generator Protection
• Some of the most common methods of
detecting faults in generators are:
– Winding Differential Protection
– Ground Fault Protection
– Detection of Unbalanced Faults
– Overload Protection
– Loss-of-Excitation Protection
– Generator Motoring Protection
– Generator Protection at Reduced Frequencies
Winding Differential
• With the winding differential protection
scheme, the currents in each phase on each
side of the machine are compared in a
differential circuit.
• Any significant difference in current is
interpreted as some form of fault and the
relay operates.
Ground Fault Protection
• It is difficult to detect small generator ground faults
before they become big ones. Current-type relays are
generally inadequate for detecting generator ground
faults.
• It is more common for the protection system to
measure the voltage of the generator neutral with
respect to ground.
• A sensitive over-voltage relay is connected across the
resistor of the generator neutral.
• A ground fault anywhere in the generator's protection
zone causes a voltage to appear across the neutral
resistor, operating the relay to trip the generator.
Detection of Unbalanced Faults
• We know from Module 2: Fundamentals of
Electricity, that electric power systems are three-
phase and normally balanced on all phases.
• Sometimes abnormal conditions exist on parts of
the system causing unbalanced conditions. These
include:
– single phase-to-ground faults
– line-to-line faults
– unbalanced voltages
– open circuits
Detection of Unbalanced Faults
• To protect the
generator from
damage caused by
unbalanced faults, a
relay system called
negative phase
sequence
(unbalance) relaying
is used to sense the
condition and trip
the machine.
Overload Protection
• Most large generators are equipped with
resistance temperature detectors (RTDs) that
detect overheating due to overload.
• Typically, the outputs from this RTD drive a
warning light to inform the plant operator of
the potential overload conditions.
• The RTD may also be used to provide a trip
signal.
Loss-of-Excitation
• Recall from Module 4: Principles of Power
Generation, that the function of the
generator excitation system is to provide
direct current for the generator rotor
windings (field windings). The generator
excitation system:
– maintains generator voltage
– controls reactive power flow
– assists in maintaining power system stability
Generator Motoring
• If an undetected prime mover problem occurs
(e.g., low steam or water flow), the input to the
turbine may be too low to meet all the losses in
the generator.
• The turbine compensates for this deficiency by
absorbing real power from the power system.
• Now, the machine is performing in a manner
similar to a synchronous motor.
• A protection system that detects reverse power
flow (into the machine) identifies generator
motoring.
Generator Protection at Reduced
Frequencies
Under-Frequency Over-Frequency Time Delay
Limit (Hz) Limits (Hz) Before Tripping
57.3-56.9 45 cycles