Installation Instructions

TB/TS, TB/TS/K
Thermistor Room Temperature Sensors

Important: Retain these instructions

These instructions shall be used by trained service


personnel only. If the equipment is used in a manner not
specified by these instructions, the protection provided by the
equipment may be impaired. https://partners.trendcontrols.com

1 BOX CONTENTS 2 STORING

TB/TS, TB/TS/K Installation


-10 °C +50 °C 0 90 %RH
Instructions (TG200607)
(14 °F) (122 °F)
H2 O

3 INSTALLATION
It is recommended that the installation should comply
with the local electrical safety installation practices (e.g.
Dimensions
1
HSE Memorandum of Guidance on Electricity at Work
Regulations 1989, USA National Electric Code).
6 mm (0.24”)

Mounting Requirements
2
85 mm (3.35”)

- +
 

85 mm (3.35”)
26 mm (1.02”)

> 50 cm (20”)

1.5 m
(5 ft)

TB/TS, TB/TS/K Installation Instructions TG200607 Issue 5, 28-Feb-20181


TB/TS, TB/TS/K Installation Instructions

3 INSTALLATION 
(continued)

Requirements (continued)
2
-10 °C +50 °C
(14 °F) (122 °F)
0 °C
+40 °C measurment
(32 °F)
(104 °F)

0 %RH 90 %RH
H2 O

 





   


Remove backplate Mount backplate


3 4
BESA box

35 mm (1.38”)

35 mm (1.38”)

wall box or wall


60 mm (2.36”)

FR
ABS

35 mm (1.38”)

35 mm (1.38”)

Remove Cutout(s) (as required) Route cables


5 6

2 TB/TS, TB/TS/K Installation Instructions TG200607 Issue 5, 28-Feb-2018.


Installation Instructions TB/TS, TB/TS/K

3 INSTALLATION 
(continued)

Wire to Controller
7
Terminal size 0.5 to 2.5 mm2 (20 to 14 AWG)

IQecos with fixed strategies and IQLs must be connected as


described in the relevant strategy data sheet or installation
instructions.

TB/TS TB/TS/K

1 2 3
SENSOR IQ

Temperature analogue input


2 IN
(thermistor T)
TB/TS 0V
1 COM (0V)
SENSOR IQ

analogue input Knob analogue input


IN
(thermistor T) /K 3 IN
TB/TS (thermistor T)
COM (0V) 1 COM (0 V)

polarity independent
Note: Screened cable is not required for sensor wiring to IQLs.
Option Connect Terminals If screened cable is used, the screen must be terminated at
TB/TS 1*, 2* the controller to its supply cable earth.
TB/TS/K 1, 2, 3

* Note: The terminals are not numbered on TB/TS; they are


polarity independent. The equivalent numbering of TB/TS/K
is shown.

Assemble unit Set up strategies


8 9
For IQecos with fixed strategies and IQLs ignore steps (9)
and (10) and proceed to step (11).

‘click’ TB/TS Data Sheet (TA200603)

or

For TB/TS, /K options, configure the controller strategy using


the pre-configured strategy in SET’s Strategy Library (TB
TS KOSF), and only use the options required. If this is not
used write your own strategy, see data sheet for suggested
strategy.

TB/TS, TB/TS/K Installation Instructions TG200607 Issue 5, 28-Feb-20183


TB/TS, TB/TS/K Installation Instructions

3 INSTALLATION 
(continued)

Configure Controller
10
Use IQSET to configure the Sensor Type and External Sensor strategy modules as require actual sensor (Thermistor)
and Knob separately as required.

IQSET Manual (TE200147)


IQ4 Configuration Manual (TE201263)
IQ3 Configuration Manual (TE200768)
IQ Configuration Manual (90-1533)
IQeco Configuration Manual (TE201089)

Setting the Sensor Type


For the following controller types:

IQ4 Series
IQ3 Series
IQ2 Series
IQeco

Configure the Sensor Type by selecting one of the following Unique Sensor References.

Knob Thermistor

Knob TB 3 deg trim (Guaranteed ±3 trim) Thermistor TBTS (Value in °C)


Knob T 3 deg trim (±3 ±20% linear trim) Thermistor TBTS F (Value in °F)
Knob (Knob TB 05 deg trim) (10k Therm DegC TBTS) (Value in °C)
Type 102 - Potentiometer (-0.5 to + 0.5 deg trim) Type 101 - Thermistor °C
(10k Therm DegC TBTS)
Type 108 - Thermistor °F (Value in °F)

Test System
11

Controller

4 DISPOSAL

WEEE Directive:
At the end of their useful life the packaging and
product should be disposed of by a suitable
recycling centre.
Do not dispose of with normal household waste.
Do not burn.

Please send any comments about this or any other Trend technical
publication to [email protected]
 TR CU Certification
© 2018 Honeywell Technologies Sàrl, E&ES Division. All rights reserved. Manufactured for and on behalf of the Environmental & Energy Solutions
Division of Honeywell Technologies Sàrl, Z.A. La Pièce, 16, 1180 Rolle, Switzerland by its Authorized Representative, Trend Control Systems Limited.

Trend Control Systems Limited reserves the right to revise this publication from time to time and make changes to the content hereof without obligation
to notify any person of such revisions or changes.
Trend Control Systems Limited
St. Marks Court, North Street, Horsham, West Sussex, RH12 1BW, UK. Tel:+44 (0)1403 211888, www.trendcontrols.com

4 TB/TS, TB/TS/K Installation Instructions TG200607 Issue 5, 28-Feb-2018.