MiniWave Manual

The document provides an overview and user manual for the MiniWave ultrasonic level transmitter. It describes the operating principle of using ultrasonic pulses to measure liquid levels. Key details include dimensions and wiring of the unit, installation and mounting instructions, and commissioning via software. Specifications and troubleshooting tips are also included.

Uploaded by

Rafael Garcia
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
100 views

MiniWave Manual

The document provides an overview and user manual for the MiniWave ultrasonic level transmitter. It describes the operating principle of using ultrasonic pulses to measure liquid levels. Key details include dimensions and wiring of the unit, installation and mounting instructions, and commissioning via software. Specifications and troubleshooting tips are also included.

Uploaded by

Rafael Garcia
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 16

Sultan Sonar Manual Rev 1.

A Higher Level of Performance

User Manual

MiniWave
Ultrasonic Level Series >
Liquid Level Measurement

For more information, please visit >


www.hawkmeasure.com
Table Of Contents
MiniWave User Manual

Contents

Overview  3 HART  9

Overview  3 HART Universal /


Common Practice command list  9
Principle of Operation  3
Model Type  3 Troubleshooting  10

Dimensions & Wiring  4 Unit is displaying incorrect distance  10


Analogue trend is erratic/unstable  10
Dimensions  4
Unit is locked up or flat line measurement  10
Flange  4
PLC indication does not match measurement  10 >
Wiring  4
AutoSet fails  10 <
Installation  5
Model Types - Part Numbers  11
Mounting  5
Model Type  11
Powering The Unit  6
Accessories  11
Interface  6

Commissioning - Software  7 Specifications  12

Startup  7
Main Menu  7
Setup  7
AutoSet  7
Advanced Settings  8

2
Overview
MiniWave User Manual

Overview

MiniWave is a compact, loop-powered ultrasonic level transmitter for continuous measurement of liquids. As
a price leader, it does not compromise on good value; and provides effortless and intuitive operation. Easy
and flexible mounting combined with high chemical compatibility and 12-metre measuring range makes the
MiniWave suitable in multiple applications in all industries.

Principle of Operation

The MiniWave emits an ultrasonic pulse, which is reflected from the surface of the liquid being measured. The
reflected signal is processed using specially developed software to enhance the correct signal and reject false >
echoes.
<
Automatic sensitivity control allows the unit to dynamically adjust and improve the received echoes for the best
possible measurement outcome.

A
Model Type

MWN1A - MiniWave with 2” NPT thread

MWB1A - MiniWave with 2” BSPT thread B


C

A - Removable lid with viewing window

B - Electronics housing

C - M20 cable gland

D - NPT or BSPT thread

E - Transducer face

3
Dimensions & Wiring
MiniWave User Manual

Dimensions 85mm (3.4”) Wiring


85mm (3.4”)

85mm (3.4”)

M20
Cable
Gland

Flip Lid
-+ to access
185mm (7.3”)
185 mm (7.3”)

terminals
28mm (1.1”)
72mm (2.8”) 185mm (7.3”)

M20
Cable Gland
28mm (1.1”)

M20
25mm (1.0”)

Cable 2" BSPT


Gland or >
23mm
(0.9”)

2" BSP or
NPT THD
NPT THD
(2.8”)
(1.0”)

2" BSPT or M20 Blank Plug


M20 Blank Plug <
45mm (1.8”)
25mm

NPT THD
(2.8”)
72mm

M20 Blank Plug


47mm
(1.85”)
45mm (1.8”)
72mm

-+
2 wire loop
52mm (2”) 4-20mA with HART
24-28VDC
52mm
52mm (2”) Max 250ohm
(2”)

Flange

FA2NB-4 - 2” ANSI Polypropylene Flange for NPT threaded units

FA2BB-4 - 2” ANSI Polypropylene Flange for BSPT threaded units

4 x Ø19mm (0.75”) HOLES THROUGH


120mm (4.7”) P.C.D.

2" NPT or BSPT INTERNAL THREAD AutoSet


Set Lo Level
Set Hi Level

152mm (6.0”)
(0.60”)
15mm

4
Installation
MiniWave User Manual

Mounting

• Sensor should be mounted 1/3 the diameter of the 2” NPT (MWN1A)


vessel from the vessel wall or
2“ BSPT (MWB1A)
• Unit should never be closer than 250mm (10") to the
liquid surface
• Do not mount over or near objects which can interfere
with the unit measurement min. 250mm (10”)
• Do not mount in the centre of a curved roof to avoid
the potential of parabolic echoes
• Ensure appropriate UV protection.
>
These are examples of common INCORRECT mountings which can prevent the unit from
<
operating correctly.
Do NOT mount near infeed

min. 250mm (10”)

2” NPT (MWN1A)
or
2“ BSPT (MWB1A) Protect from UV
Do NOT mount over or adjacent to any obstacles

min. 250mm (10”)

Do NOT mount cone or transducer Do NOT mount on angle


face above roofline in liquid applications

min. 250mm (10”)

5
Installation
MiniWave User Manual

Powering The Unit

When power is applied, the unit will start up automatically. The LCD will scroll through its boot diagnostics and
display the serial numbers, software version and model types for the amplifier and transducer.

The selected Display Mode will be visible with a measurement.

The top right hand corner diagnostic indicates either the operating mode or the current output.

The unit will re-scan for the level whenever it is powered up.

Display Mode Diagnostic


>

17.2mA
17.2mA
CAL <
Space
Space
1.402m
1.402m RUN

u Setup Advanced Autoset


u Display Mode
Setup mini W
M wa v e Comms
Advanced Autoset
Display
Display Unit Mode Echo
CommsSize
Low
Display Level Unit Lock Code
Echo Size See (B) Autoset
Hi
LowLevelLevel Analogue
Lock Code
Damping Language See (B) Autoset
n Menu Hi Level
FailSafe Setup Analogue Advanced Autoset
Damping Language
Display Mode Comms
ced Interface FailSafe
Display Unit Echo Size
et Low Level Lock Code
See (B) Autoset
Hi Level Analogue
Button Action Navigation / Function
Set Lo Level Set Lo Level
Damping Language
SCANNING
No
Yes FailSafe
Press and release Access Main Menu
2.597m
Select / Proceed

Press and hold for 3 seconds Access AutoSet Menu

Press and release Cancel / Return


Re-activate unit

Press and Release Scroll between live diagnostics

Scroll between menu options

Adjust parameters

6
Commissioning - Software
MiniWave User Manual

Main Menu Setup Advanced Autoset


Setup Display Mode Comms
Advanced Main Menu Display Unit Setup Echo Size Advanced Autoset
AutosetSetup
Startup Low Level Display Mode Lock CodeComms
Advanced See (B) Autoset
Hi LevelDisplay Unit Analogue Echo Size
The MiniWave Autoset
uses automatic sensitivity control
DampingLow Level to detect and maintain the
Language level.
Lock CodeAfter applying power to the
unit allow 20-30 seconds for the unit to adjust to the application*.
See (B) Aut
FailSafe Hi Level Analogue
*For best results ensure there is a
Damping Language
liquid level present in the application
FailSafe
or flat surface below the transducer

Main Menu

To access the Main menu press


>
Flip Lid
To access AutoSet menu press and hold
to access for 3 seconds 17.2mA CAL
17.2mA <
terminals Space
Space
Setup 1.402m
1.402m RUN

Parameter Description Options


Display Mode Set LCD measurement display mode Level % Level Space Volume*

Display Unit Adjust displayed measurement unit MilMetre CenMetre Metres Feet Inches
mini wave
-+ Low Level Set Low level measurement point (4mA) Adjustable

High Level Set High level measurement point (20mA) Adjustable

Damping Adjust output response time & smoothness Adjustable in seconds


3.50mA 3.80mA 20.20mA
Failsafe Set failsafe output 4mA 20mA LastKnown

* Volume mode requires PC with GoshawkII software. Consult dedicated MiniWave GoshawkII Manual

AutoSet

Use AutoSet to scan and program the unit High or Low level to the distance detected. After the scan you will
be prompted to accept the distance measured. The High and Low level can also be manually adjusted in
'Setup'.

AutoSet Set Lo Level Set Lo Level


Set Lo Level No
SCANNING Yes
Set Hi Level
2.597m

7
Commissioning - Software
MiniWave User Manual

Advanced Settings

Parameter Description Options


Device ID BaudRate
Comms Adjust HART protocol settings.
Default 1 1200

Blanking is a dead-band / non measured range. The unit Adjustable - recommended default
Blanking
cannot measure within this range. 250mm (10")

Adjust tracking response time for application. The faster Slow


the tracking, the more responsive the measurement is, Medium
Tracking
but it is less smooth the output signal. Fast >
InstaTrack provides pulse by pulse live measurement. InstaTrack
<
Mapping creates a digital 'map' of false echoes
MappedDist
caused by problem mounting and structures. Select
Mapping 'ExecuteMap' to set a mapped distance, conduct or
delete Mapping. Select 'MappedDist' to view a previously ExecuteMap Set Map Dist
mapped distance.

The unit will target this echo size (measured in signal


voltage) during operation. High values can increase
0.4 - 2.49V
EchoSize stability but make the unit more susceptible to false
Default 0.59V
echoes. Lower values can make the unit less sensitive
and less likely to see false echoes.

Park 4mA
Adjust Analog output. Switch from 4-20mA to 20-4mA 4-20mA Tune 4mA
Analog Park 8mA
and fine tune both 4mA current and 20mA current. 20-4mA Tune 20mA
Park 12mA

0: Lowest
Increase or decrease the unit Automatic Sensitivity
Sensitivity 10: Default
Control range.
20: Highest

WaveBoost adds additional echo amplification on top


0: Lowest (default)
WaveBoost of the Automatic Sensitivity Control. WaveBoost should
20: Maximum
only be used if maximum Sensitivity is not sufficient.

Factry Reset Restore all parameters to factory default. Yes / No

Device Info Displays product type, serial number & software revision.

Enable /
Enable / Disable lock code. Disable
Lock Code 1-200
If enabled, select lock code number. Default
Disabled

8
HART
MiniWave User Manual

HART Universal / Common Practice command list

The MiniWave supports the following Universal and Common commands

Command No. Function


0 Read unique identifier
1 Read Primary Variable
2 Read current and percent of range
3 Read current and four predefined dynamic variables.
6 Write polling addr
7 Read loop configuration
>
8 Read Dynamic Variable Classifications
11 Read unique ident. associated with tag <
12 Read message
13 Read Tag, Description, Date
14 Read PV sensor information
15 Read output information
16 Read final assembly number
17 Write message
18 Write Tag, Description, Date
19 Write final assembly number
20 Read Long Tag
34 Write damping value
35 Write range values
36 Set Upper Range
37 Set Lower Range
38 Reset Configuration flag
40 Current fixed mode
45 Set 4 mA trim
46 Set 20 mA trim
44 Write PV units
57 Read unit tag, descriptor, date
58 Write unit tag, descriptor, date
59 Write number of response preambles
109 Burst mode control
110 Read all dynamic variables

9
Troubleshooting
MiniWave User Manual

Unit is displaying incorrect distance PLC indication does not match measurement

• Confirm display mode is suitable. • Connect a Multimeter in series with the powered
Space is measured from Sensor face to measured level. loop. Compare the 'mA' diagnostic on the display
Material is measured from Low Level to measured level. with the mA reading on the loop. If these values do
• If unit is measuring too deep increase Sensitivity. not match, disconnect the loop wires and measure
If the unit continues to measure too deep, increase the resistance across the loop. This should not
WaveBoost exceed specification.
• If unit is measuring too high, reduce Sensitivity and • Confirm High Level and Low Level are set to the
ensure WaveBoost is set to 0. same values in MiniWave and control system.
• Check if material is present to be measured. Unit
will output and display FailSafe reading if it cannot AutoSet fails >
detect a level within range.
• Increase 'Sensitivity' to a higher value. <
Analogue trend is erratic/unstable • Allow the unit to run for a longer time (one minute).

• Increase 'Damping' value for smoother trends. Re-attempt the AutoSet.

• Choose a slower 'Tracking' speed. • Increase WaveBoost and re-attempt the AutoSet.
• Check there are no objects interfering with the • Set High and Low level manually in 'Setup' menu.
transit pulse in the application (such as ladders and
cross beams).

If problems persist, install replacement


Unit is locked up or flat line measurement
MiniWave in the application.
• Confirm there is material within measurement 'Bench test' the problem unit in a controlled
range, the unit may go to Failsafe if there is no flat environment.
level available.
Difficult applications may be required a low
• If the unit is locked to a high level perform Mapping
frequency Acoustic Wave device. Contact
for distance beyond false echoes.
HAWK for information about the Sultan series.
• If the unit is locked higher than the real level check
for objects interfering with the transit pulse in the
application (such as ladders and cross beams).
Lower the Sensitivity/WaveBoost. Re-locate the
installation to avoid the interfering object.
• If the unit is locked lower than the real level confirm
the application is not within Blanking distance.
Increase Sensitivity/WaveBoost until unit
measures correct level.
• Tracking speed may be too slow for the application.
Increase Tracking speed.

10
Model Types - Part Numbers
MiniWave User Manual

Model Type

MWN1A - MiniWave with 2” NPT thread

MWB1A - MiniWave with 2” BSPT thread

Accessories

FA2NB-4 - 2” ANSI Polypropylene Flange for NPT threaded units

FA2BB-4 - 2” ANSI Polypropylene Flange for BSPT threaded units >

Hawklink-MiniUSB - PC connecter for GoshawkII <

11
Specifications
MiniWave User Manual

Frequency Automatic Temperature Compensation

• 50 kHz • Yes

Operating Voltage Beam Angle

• 7°
• 7 - 28VDC at the terminal
(residual ripple no greater than 100mV) Materials

Power Consumption • Transducer: PVDF

• 500mW @ 24VDC • Housing: Powder coated aluminum

Analog Output Display


>
• 4 -20mA modulating output module with HART • 4 line graphic display (128 x 64)
<
(Recommended 250 Ohm @ 24VDC) Keypad
Analog Resolution • 4 keys = CAL, RUN, UP, DOWN
• 14 bits Memory
Communications • >10 years data retention
• HART (Generic - Universal Commands only) Enclosure Sealing
• GoshawKII via HART. Full command list.
• IP67
Blanking Distance
Cable Entries
• 250 mm (10")
• M20 cable glands
Maximum Range
Mounting
• 12 metres (40ft)
• 2” BSPT Thread
Resolution
• 2” NPT Thread
• 1 mm (0.04”)
Typical Weight
Electronic Accuracy
• 1kg (2.2 pounds)
• +/- 0.25% of maximum range
Volume
Operating Temperature
• Pre-set common vessel shapes
• -40°C to 60°C (-40°F to 140°F) • 32 point programmable linearization table

Maximum Operating Pressure • Requires PC connection with GoshawkII software

• -0.5 to 3 bar (0 - 44 PSI)

12
Contact
MiniWave User Manual

>

<

13
Overview
MiniWave User Manual

>

<

14
Overview
MiniWave User Manual

>

<

15
Contact
MiniWave User Manual

HAWK, Since 1988 Remote Innovation

Hawk Measurement Systems Pty Ltd (HAWK) was HAWK understands the need for immediate technical
established in 1988. It's founding members saw the assistance.
universal requirement of various industries requiring The HawkLink 3G communication device allows
improved process control and efficiency in their any computer with internet access and our free
operations. GosHawk diagnostic & calibration software; to dial in,
calibrate, test, and check the performance of HAWK
We Can Help products. This innovative system allows our Global
Support Team to assist with commissioning and
HAWK understands the difficulties customers face
after sales service of HAWK equipment worldwide.
when seeking accurate level measurement. Every
Measurement problems are addressed as they <
application is different, involving a multitude of
happen; not days or weeks later.
environmental factors. This is where HAWK excels.
Our aim is to ensure that customers feel comfortable
Knowledge Sharing
with our technology, and are provided with long term
and reliable solutions. We believe that a combination HAWK believes that knowledge sharing is key to
of application and product expertise, as well as creating long term relationships. Empowering our
forward thinking and proactive support policies customers and our worldwide distribution network,
are the foundation of successful customer-supplier whilst being available at all times to lend a helping
relationships. hand, is the perfect recipe for long-term solutions and
relationships. HAWK openly extends an invitation to
Progressive Technical Support share our 25 years of level measurement experience,
and ensure that your day-to-day processes are
HAWK believes that the future of the Level
efficient, understood, and always working.
Measurement Industry revolves around the quality
of pre and post sales - support. Our aim is for all
sales & support staff to be product experts, and more
importantly application experts making our customers
applications as efficient and consistent as possible. All company or product names are registered trademarks or
trademarks of their respective owners.

Hawk Measurement Systems Hawk Measurement


DOC-MW-MAN Rev 1.11 0317

(Head Office) 90 Glenn Street


15 - 17 Maurice Court Suite 100B, Lawrence, MA 01843, USA
Nunawading VIC 3131, AUSTRALIA Phone: +1 888 HAWKLEVEL (1-888-429-5538)
Phone: +61 3 9873 4750 Phone: +1 978 304 3000
Fax: +61 3 9873 4538 Fax: +1 978 304 1462
[email protected] [email protected]

For more information and global representatives: www.hawkmeasure.com

You might also like