Overview
MiniWave User Manual
Overview
MiniWave is a compact, loop-powered ultrasonic level transmitter for continuous measurement of liquids. As
a price leader, it does not compromise on good value; and provides effortless and intuitive operation. Easy
and flexible mounting combined with high chemical compatibility and 12-metre measuring range makes the
MiniWave suitable in multiple applications in all industries.
Principle of Operation
The MiniWave emits an ultrasonic pulse, which is reflected from the surface of the liquid being measured. The
reflected signal is processed using specially developed software to enhance the correct signal and reject false >
echoes.
<
Automatic sensitivity control allows the unit to dynamically adjust and improve the received echoes for the best
possible measurement outcome.
A
Model Type
B - Electronics housing
E - Transducer face
3
Dimensions & Wiring
MiniWave User Manual
85mm (3.4”)
M20
Cable
Gland
Flip Lid
-+ to access
185mm (7.3”)
185 mm (7.3”)
terminals
28mm (1.1”)
72mm (2.8”) 185mm (7.3”)
M20
Cable Gland
28mm (1.1”)
M20
25mm (1.0”)
2" BSP or
NPT THD
NPT THD
(2.8”)
(1.0”)
NPT THD
(2.8”)
72mm
-+
2 wire loop
52mm (2”) 4-20mA with HART
24-28VDC
52mm
52mm (2”) Max 250ohm
(2”)
Flange
152mm (6.0”)
(0.60”)
15mm
4
Installation
MiniWave User Manual
Mounting
2” NPT (MWN1A)
or
2“ BSPT (MWB1A) Protect from UV
Do NOT mount over or adjacent to any obstacles
5
Installation
MiniWave User Manual
When power is applied, the unit will start up automatically. The LCD will scroll through its boot diagnostics and
display the serial numbers, software version and model types for the amplifier and transducer.
The top right hand corner diagnostic indicates either the operating mode or the current output.
The unit will re-scan for the level whenever it is powered up.
17.2mA
17.2mA
CAL <
Space
Space
1.402m
1.402m RUN
Adjust parameters
6
Commissioning - Software
MiniWave User Manual
Main Menu
Display Unit Adjust displayed measurement unit MilMetre CenMetre Metres Feet Inches
mini wave
-+ Low Level Set Low level measurement point (4mA) Adjustable
* Volume mode requires PC with GoshawkII software. Consult dedicated MiniWave GoshawkII Manual
AutoSet
Use AutoSet to scan and program the unit High or Low level to the distance detected. After the scan you will
be prompted to accept the distance measured. The High and Low level can also be manually adjusted in
'Setup'.
7
Commissioning - Software
MiniWave User Manual
Advanced Settings
Blanking is a dead-band / non measured range. The unit Adjustable - recommended default
Blanking
cannot measure within this range. 250mm (10")
Park 4mA
Adjust Analog output. Switch from 4-20mA to 20-4mA 4-20mA Tune 4mA
Analog Park 8mA
and fine tune both 4mA current and 20mA current. 20-4mA Tune 20mA
Park 12mA
0: Lowest
Increase or decrease the unit Automatic Sensitivity
Sensitivity 10: Default
Control range.
20: Highest
Device Info Displays product type, serial number & software revision.
Enable /
Enable / Disable lock code. Disable
Lock Code 1-200
If enabled, select lock code number. Default
Disabled
8
HART
MiniWave User Manual
9
Troubleshooting
MiniWave User Manual
Unit is displaying incorrect distance PLC indication does not match measurement
• Confirm display mode is suitable. • Connect a Multimeter in series with the powered
Space is measured from Sensor face to measured level. loop. Compare the 'mA' diagnostic on the display
Material is measured from Low Level to measured level. with the mA reading on the loop. If these values do
• If unit is measuring too deep increase Sensitivity. not match, disconnect the loop wires and measure
If the unit continues to measure too deep, increase the resistance across the loop. This should not
WaveBoost exceed specification.
• If unit is measuring too high, reduce Sensitivity and • Confirm High Level and Low Level are set to the
ensure WaveBoost is set to 0. same values in MiniWave and control system.
• Check if material is present to be measured. Unit
will output and display FailSafe reading if it cannot AutoSet fails >
detect a level within range.
• Increase 'Sensitivity' to a higher value. <
Analogue trend is erratic/unstable • Allow the unit to run for a longer time (one minute).
• Choose a slower 'Tracking' speed. • Increase WaveBoost and re-attempt the AutoSet.
• Check there are no objects interfering with the • Set High and Low level manually in 'Setup' menu.
transit pulse in the application (such as ladders and
cross beams).
10
Model Types - Part Numbers
MiniWave User Manual
Model Type
Accessories
11
Specifications
MiniWave User Manual
• 50 kHz • Yes
• 7°
• 7 - 28VDC at the terminal
(residual ripple no greater than 100mV) Materials
12
Contact
MiniWave User Manual
>
<
13
Overview
MiniWave User Manual
>
<
14
Overview
MiniWave User Manual
>
<
15
Contact
MiniWave User Manual
Hawk Measurement Systems Pty Ltd (HAWK) was HAWK understands the need for immediate technical
established in 1988. It's founding members saw the assistance.
universal requirement of various industries requiring The HawkLink 3G communication device allows
improved process control and efficiency in their any computer with internet access and our free
operations. GosHawk diagnostic & calibration software; to dial in,
calibrate, test, and check the performance of HAWK
We Can Help products. This innovative system allows our Global
Support Team to assist with commissioning and
HAWK understands the difficulties customers face
after sales service of HAWK equipment worldwide.
when seeking accurate level measurement. Every
Measurement problems are addressed as they <
application is different, involving a multitude of
happen; not days or weeks later.
environmental factors. This is where HAWK excels.
Our aim is to ensure that customers feel comfortable
Knowledge Sharing
with our technology, and are provided with long term
and reliable solutions. We believe that a combination HAWK believes that knowledge sharing is key to
of application and product expertise, as well as creating long term relationships. Empowering our
forward thinking and proactive support policies customers and our worldwide distribution network,
are the foundation of successful customer-supplier whilst being available at all times to lend a helping
relationships. hand, is the perfect recipe for long-term solutions and
relationships. HAWK openly extends an invitation to
Progressive Technical Support share our 25 years of level measurement experience,
and ensure that your day-to-day processes are
HAWK believes that the future of the Level
efficient, understood, and always working.
Measurement Industry revolves around the quality