Relay Generator Protection f1 BTG 2

This document provides a field test report for a Siemens 7UM62 relay generator for PT. Semen Tonasa. It includes settings for the differential elements, measurements of current and voltage metering accuracy under various test conditions, and settings and test results for overvoltage and undervoltage protection elements.

Uploaded by

beby nisa
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
151 views11 pages

Relay Generator Protection f1 BTG 2

This document provides a field test report for a Siemens 7UM62 relay generator for PT. Semen Tonasa. It includes settings for the differential elements, measurements of current and voltage metering accuracy under various test conditions, and settings and test results for overvoltage and undervoltage protection elements.

Uploaded by

beby nisa
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 11

Distribution : Controlled Uncontrolled Available On Computer

Document Status :
To. PT. SEMEN TONASA
( F.I ) For Information

( F.C ) For Comment

( F.E ) For Execution

( F.A ) For Application

Title :
SIEMENS 7UM62
Feeder :
RELAY GENERATOR F1
File Type : FIELD TEST REPORT

PT. SEMEN TONASA BTG 2

By
On
By
On
By
On
By BE BE SB
A 1
On
Revision Prepared Checked Approved Modification Sheets

PT. JAPA INDOTAMA


TEST REPORT RELAY GENERATOR
7UM62
PT. SEMEN TONASA
PT. JAPA INDOTAMA BTG 2 POWER PLANT BIRINGKASSI PT. SEMEN TONASA

1. SETTING

Diferential

I Diff Prot : ON
I-Diff> : 0,1 I.InO
T I-Diff> : 0,0 s
I-Diff>> : 5,0 I/InO
T I-Diff>> : 0,0 s
Slope 1 : 0,15
Slope 2 : 0,5

CHECKED

RATIO CT
Side 1 : 2500 / 1 A
Side 2 : 2500 / 1 A

2. DIFFERENTIAL ELEMENTS CHECKS

Current Pickup Drop Off Time (s)


Phase
Side Current (A) Current (A) Setting Measured
R 0,1 0,1 0,05 0,032

1 Side (I1) S 0,1 0,1 0,05 0,041

T 0,1 0,1 0,05 0,033

R 0,1 0,1 0,05 0,035

2 Side (I2) S 0,1 0,1 0,05 0,033

T 0,1 0,1 0,05 0,033


TEST REPORT RELAY GENERATOR
7UM62
PT. SEMEN TONASA
PT. JAPA INDOTAMA BTG 2 POWER PLANT BIRINGKASSI PT. SEMEN TONASA

PHASE R
Side 1 ( I1 ) 0,1 0,2 0,3 0,4 0,5 0,6 0,7
Side 2 ( I2 ) 0,2 0,3 0,4 0,5 0,6 0,7 0,8
I diff 0,1 0,1 0,1 0,1 0,1 0,1 0,1
I bias 0,31 0,51 0,73 0,91 1,11 1,25 1,4

SLOPE
1,6
1,4
1,2
1
0,8
0,6
0,4
0,2
0
1 2 3 4 5 6 7

I Diff

PHASE S
Side 1 ( I1 ) 0,1 0,2 0,3 0,4 0,5 0,6 0,7
Side 2 ( I2 ) 0,2 0,3 0,4 0,5 0,6 0,7 0,8
I diff 0,1 0,1 0,1 0,1 0,1 0,1 0,1
I bias 0,3 0,51 0,72 0,93 1,12 1,29 1,42

SLOPE

1,6
1,4
1,2
1
0,8
0,6
0,4
0,2
0
1 2 3 4 5 6 7

I Diff
TEST REPORT RELAY GENERATOR
7UM62
PT. SEMEN TONASA
PT. JAPA INDOTAMA BTG 2 POWER PLANT BIRINGKASSI PT. SEMEN TONASA

PHASE T

Side 1 ( I1 ) 0,1 0,2 0,3 0,4 0,5 0,6 0,7


Side 2 ( I2 ) 0,2 0,3 0,4 0,5 0,6 0,7 0,8
I diff 0,1 0,1 0,1 0,1 0,1 0,1 0,1
I bias 0,28 0,5 0,7 0,92 1,12 1,29 1,43

SLOPE
1,6
1,4
1,2
1
0,8
0,6
0,4
0,2
0
1 2 3 4 5 6 7

I Diff
TEST REPORT RELAY GENERATOR 7UM62
PT. SEMEN TONASA
BTG 2 POWER PLANT BIRINGKASSI
PT. JAPA INDOTAMA PT. SEMEN TONASA

Tanggal : 13/08/2020 Feeder : D02CHA10


Lokasi : PLTU BIRINGKASSI Alat Uji : OMICRON CMC 356

3. Metering Arus
CT Side 1 : 2500 ./ 1 A
Injection Arus (A) 0% 25% 50% 75% 100%
PHASE
Standart (A) 0,00 625 1250 1875 2500
Metering (A) 0,00 620 1230 1850 2460
L1
Error (%) 0,00 0,80 1,60 1,33 1,60
Metering (A) 0,00 620 1230 1850 2470
L2
Error (%) 0,00 0,80 1,60 1,33 1,20
Metering (A) 0,00 620 1230 1850 2450
L3
Error (%) 0,00 0,80 1,60 1,33 2,00

CT Side 2 : 2500 ./ 1 A
Injection Arus (A) 0% 25% 50% 75% 100%
PHASE
Standart (A) 0,00 625 1250 1875 2500
Metering (A) 0,00 620 1250 1870 2500
L1
Error (%) 0,00 0,80 0,00 0,27 0,00
Metering (A) 0,00 620 1250 1870 2500
L2
Error (%) 0,00 0,80 0,00 0,27 0,00
Metering (A) 0,00 620 1250 1870 2500
L3
Error (%) 0,00 0,80 0,00 0,27 0,00

4. Metering Voltage
VT : 11000 ./ 100 V
Injection Voltage (V) 0% 50% 75% 100%
PHASE
Standart (V) 0 5500 8250 11000
Metering (V) 0 5500 8250 11000
L1
Error (%) 0,00 0,00 0,00 0,00
Metering (V) 0 5500 8250 11000
L2
Error (%) 0,00 0,00 0,00 0,00
Metering (V) 0 5500 8250 11000
L3
Error (%) 0,00 0,00 0,00 0,00

PT. JAPA INDOTAMA PT. SEMEN TONASA


Diuji Oleh: Diketahui Oleh: Disaksikan Oleh:
TEST REPORT RELAY GENERATOR 7UM62
PT. SEMEN TONASA
BTG 2 POWER PLANT BIRINGKASSI
PT. JAPA INDOTAMA PT. SEMEN TONASA

Tanggal : 13/08/2020 Feeder : D02CHA10


Lokasi : PLTU BIRINGKASSI Alat Uji : OMICRON CMC 356

5. Parameter Setting Overvoltage Protection - Long Time Trip (59.1)

No SETTING
1 U> : 110V
2 T U> : 10 Sec
3 Ratio VT : 11000 / 100 V
4 Indikasi : Alarm

Test Relay
Phase Injected UV Indikasi Time Record Remark
> Led Output 8 Menyala
RST 64,74 V 10,44 (s) OK
> PLC Led 4 Menyala

6. Parameter Setting Overvoltage Protection - Trip (59.2)

No SETTING
1 U>> : 130V
2 T U>> : 0,01 s
3 Ratio VT : 11000 / 100 V
4 Indikasi : Trip

Test Relay
Phase Injected UV Indikasi Trip Time Remark
> Led Output 8 Menyala
RST 75,74 V 0,055 (s) OK
> Binary Output 9 ON

7. Parameter Setting Undervoltage Protection - Alarm (27.1)

No SETTING
1 U< : 90V
2 T U<< : 5s
3 Ratio VT : 11000 / 100 V
4 Indikasi : Alarm

Test Relay
Phase Injected UV Indikasi Trip Time Remark
> Led Output 8 Menyala
RST 52 V 5,221 (s) OK
> PLC Led 4 Menyala

Note :
TEST REPORT RELAY GENERATOR 7UM62
PT. SEMEN TONASA
BTG 2 POWER PLANT BIRINGKASSI
PT. JAPA INDOTAMA PT. SEMEN TONASA

Tanggal : 13/08/2020 Feeder : D02CHA10


Lokasi : PLTU BIRINGKASSI Alat Uji : OMICRON CMC 356

8. Parameter Setting DT Stator OCR (51)

No SETTING
1 I> : 1,90 A
2 t I> : 0,10
3 Curve : DT
4 Side : 2

Test Relay
Phase Injected UV Indikasi Trip Time Remark
> Led Output 2 Menyala
R-S 1,90 A 0,103 s OK
> Binary Output 9 ON
> Led Output 2 Menyala
S-T 1,90 A 0,097 s OK
> Binary Output 9 ON
> Led Output 2 Menyala
T-R 1,90 A 0,104 s OK
> Binary Output 9 ON

9. Parameter Setting Instantaneous OCR - Directional (50)

No SETTING
1 I> : 0.3 A
2 t I> : 0,01
3 Curve : DT
4 Side : 1

Test Relay
Phase Injected UV Indikasi Trip Time Remark
> Led Output 2 Menyala
R-S 0,3 A 0,033 s OK
> Binary Output 9 ON
> Led Output 2 Menyala
S-T 0,3 A 0,035 s OK
> Binary Output 9 ON
> Led Output 2 Menyala
T-R 0,3 A 0,029 s OK
> Binary Output 9 ON

Note :
TEST REPORT RELAY GENERATOR 7UM62
PT. SEMEN TONASA
BTG 2 POWER PLANT BIRINGKASSI
PT. JAPA INDOTAMA PT. SEMEN TONASA

Tanggal : 13/08/2020 Feeder : D02CHA10


Lokasi : PLTU BIRINGKASSI Alat Uji : OMICRON CMC 356

10. Parameter Setting Reverse Power (32R.1,32R.2)

No SETTING
1 P> : -1,20%
2 T-SV-Open : 2s
3 tT-SV-Closed : 4,0 s
4 T-Hold : 0,00 s

Test Relay
Injected Indikasi Trip Time Remark
> Led Output 11 Menyala
Tegangan 57,74 V
> Binary Output 9 ON

Arus 0,2 A 2,142 s OK

Sudut 0 vs 0

11. Parameter Setting Underfrequency Protection Stage 1 (81U.1)

No SETTING
1 f1 Pickup : 48 Hz
2 t f1 : 90 s
3 Ratio VT : 11000 / 100 V
4 Indikasi : Alarm

Test Relay
Phase Injected Hz Indikasi Time Record Remark
> Led Output 7 Menyala
RST 48 Hz 90,32 s OK
> PLC Led 4 Menyala

Note :
TEST REPORT RELAY GENERATOR 7UM62
PT. SEMEN TONASA
BTG 2 POWER PLANT BIRINGKASSI
PT. JAPA INDOTAMA PT. SEMEN TONASA

Tanggal : 13/08/2020 Feeder : D02CHA10


Lokasi : PLTU BIRINGKASSI Alat Uji : OMICRON CMC 356

12. Parameter Setting Underfrequency Protection Stage 2 (81U.2)

No SETTING
1 f2 Pickup : 46 Hz
2 t f2 : 0,2 s
3 Ratio VT : 11000 / 100 V
4 Indikasi : Trip

Test Relay
Phase Injected Hz Indikasi Trip Time Remark
> Led Output 7 Menyala
RST 46 Hz 0,562 s OK
> Binary Output 9 ON

13. Parameter Setting Overfrequency Protection Stage 1 (81O.1)

No SETTING
1 f1 Pickup : 52 Hz
2 t f1 : 100 s
3 Ratio VT : 11000 / 100 V
4 Indikasi : Alarm

Test Relay
Phase Injected Hz Indikasi Trip Time Remark
> Led Output 7 Menyala
RST 52 Hz 100,4 s OK
> PLC Led 4 Menyala

14. Parameter Setting Overfrequency Protection Stage 2 (81O.2)

No SETTING
1 f2 Pickup : 55,5 Hz
2 t f2 : 0,2 s
3 Ratio VT : 11000 / 100 V
4 Indikasi : Trip

Test Relay
Phase Injected Hz Indikasi Trip Time Remark
> Led Output 7 Menyala
RST 55,5 Hz 0,512 s OK
> Binary Output 9 ON

Note :
TEST REPORT RELAY GENERATOR 7UM62
PT. SEMEN TONASA
BTG 2 POWER PLANT BIRINGKASSI
PT. JAPA INDOTAMA PT. SEMEN TONASA

Tanggal : 13/08/2020 Feeder : D02CHA10


Lokasi : PLTU BIRINGKASSI Alat Uji : OMICRON CMC 356

15. Parameter Setting Underexcitation Protection - Alarm (40.1)

No SETTING
1 T Shrt Uex< : 0,1 s
2 1/xd Char. 1 : 0,5
3 Angle : 90
4 T Char. 1 : 2s
5 1/xd Char. 2 : 0,51
6 Angel 2 : 72
7 T Char . 2 : 2s
8 1/xd Char. 3 : 0,61
9 Angle 3 : 90
10 T Char 3 : s

Test Relay
Phase Injected V/Hz Indikasi Trip Time Remark
> Led Output 10 Menyala
RST 50V/48 Hz 2, 012 s OK
> PLC Led 4 Menyala

16. Parameter Setting Overexcitation (24.1,24.2,24.3)

No SETTING
1 u/f > : 1,07
2 T u/f > : 5s
3 u/f >> : 1,4
4 T u/f >> : 1s
5 t(U/f=1.40) : 2s
10 T Coll Down : 500 s

Test Relay
Phase Injected V/Hz Indikasi Trip Time Remark
> Led Output 10 Menyala
RST 63V/52 Hz 2, 142 s OK
> PLC Led 4 Menyala

Note :
TEST REPORT RELAY GENERATOR 7UM62
PT. SEMEN TONASA
BTG 2 POWER PLANT BIRINGKASSI
PT. JAPA INDOTAMA PT. SEMEN TONASA

Tanggal : 13/08/2020 Feeder : D02CHA10


Lokasi : PLTU BIRINGKASSI Alat Uji : OMICRON CMC 356

17. Parameter Setting Fault Of Generator CB (50BF)

No SETTING
1 Trip Intern : CFC
2 Circ. BR. I> : 0,2 A
3 Trip -timer : 0,2 s
4 CT : 2500 / 1 A

Test Relay
Phase Injected (A) Indikasi Trip Time Remark
> Led Output 12 Menyala
RST 0,2 0,214 s OK
> Binary Output 9 ON

18. Parameter Setting Fuse Failure Monitor (60FL)

No SETTING
1 failure > : 1 Pole Lose
2 failure >> : 2 Pole Lose
3 VT : 11000 / 100 V
4 Indikasi : Alarm

Test Relay
Phase Injected UV Indikasi Time record Remark
R 57,74
S 0 > Led Output 13 Menyala Alarm OK
T 57,74

Note :

PT. JAPA INDOTAMA PT. SEMEN TONASA


Diuji Oleh: Diketahui Oleh: Disaksikan Oleh: