0% found this document useful (0 votes)
143 views

SNO-I-DS-001 - C1 Data Sheet For Shutdown and Blowdown Valves

This document provides a revision summary and index of shutdown and blowdown valves for the Senoro Gas Development Project. It lists 108 items including tag numbers, quantities, sizes, ratings, and pertinent P&IDs. Revisions between versions B, C, and C1 are noted, involving changes to valve types, standards, and additions or deletions to the index.

Uploaded by

ono_cze
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
143 views

SNO-I-DS-001 - C1 Data Sheet For Shutdown and Blowdown Valves

This document provides a revision summary and index of shutdown and blowdown valves for the Senoro Gas Development Project. It lists 108 items including tag numbers, quantities, sizes, ratings, and pertinent P&IDs. Revisions between versions B, C, and C1 are noted, involving changes to valve types, standards, and additions or deletions to the index.

Uploaded by

ono_cze
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 118

INSTRUMENT DATA SHEET FOR Doc. No.

SNO-I-DS-001
SHUTDOWN AND BLOWDOWN VALVES REV. C1 Page 2 of 118
SENORO GAS DEVELOPMENT PROJECT DATE. 23-May-13

REVISION SUMMARY

REV. DATE DESCRIPTION OF CHANGE

B 28-Jan-13 Issue for COMPANY Approval


C 12-Apr-13 Approved for Construction
- Tag No. & Line No. for all items have been checked
and revised as per P&ID
- SDV-4101A / 4101B is deleted, because of delete of
P&ID
- XV-6073E / XV-6030E is deleted because it will be
provided by Loading Arm Package
- XV-6070A / 6070B is added
- XV-6020A / 6020C is added
- XV-6020B / 6020D is added
- SDV-8032A / 8032B is added
C1 23-May-13 Approved for Construction
- Floating Type is changed to Trunnion Type
- Leakage Class (ANSI) is changed to Leakage Rate
(ISO 5208)
- Using Metal Seat for Hot Oil Service and High

Temperature (above 450℉)

- Anti Static is added


- ‘All SDV & BDV shall be designed & tested as per API
6D’ is added
- ‘Valve stem shall be Anti-Blowout Type’ is added
- SDV-3102B/3202B are added at the inlet of TEG
Contactor
- SDV-4032A, 4032, 4033, 4015B, 4035, 4013A are
added as per HTAS P&ID
ON-OFF VALVE INDEX

No Tag No Q'ty Size Rating P&ID No Tag No Q'ty Size Rating P&ID
1 SDV-0005G 1 6" ASME 1500# SNO-R-PI-003 60 SDV-6030A(Deleted) 1 20" ASME 150# SNO-R-PI-037
2 SDV-0016G 1 6" ASME 1500# SNO-R-PI-003 61 XV-6030E(Deleted) 1 2" ASME 150# SNO-R-PI-037
3 SDV-0001G 1 6" ASME 1500# SNO-R-PI-003 62 BDV-5041 1 4" ASME 600# SNO-R-PI-057
4 SDV-0007G 1 6" ASME 1500# SNO-R-PI-003 63 SDV-6007 1 3" ASME 150# SNO-R-PI-059
5 SDV-0017G 1 6" ASME 1500# SNO-R-PI-003 64 SDV-8065A 1 2" ASME 300# SNO-R-PI-101
6 SDV-0002G 1 16" ASME 1500# SNO-R-PI-003 65 SDV-8065B 1 6" ASME 600# SNO-R-PI-101
7 SDV-0030A 1 8" ASME 1500# SNO-R-PI-003 66 BDV-8065B 1 3" ASME 600# SNO-R-PI-101
8 BDV-0001N 1 2" ASME 1500# SNO-R-PI-003 67 BDV-8066A 1 2" ASME 300# SNO-R-PI-102
9 BDV-0001P 1 2" ASME 1500# SNO-R-PI-003 68 SDV-8145A / 8245A 2 10" ASME 300# SNO-R-PI-105
10 BDV-0001R 1 2" ASME 1500# SNO-R-PI-003 69 SDV-8145I / 8245I 2 10" ASME 300# SNO-R-PI-105
11 BDV-0001T 1 2" ASME 1500# SNO-R-PI-003 70 SDV-8026 1 4" ASME 900# SNO-R-PI-130
12 SDV-1101A 1 16" ASME 1500# SNO-R-PI-003B 71 SDV-8067B 1 4" ASME 300# SNO-R-PI-131
13 SDV-1201A 1 16" ASME 1500# SNO-R-PI-003B 72 SDV-8067C 1 2" ASME 150# SNO-R-PI-131
14 SDV-1103A / 1203A 2 8" ASME 1500# SNO-R-PI-004 73 SDV-6071A 1 3" ASME 900# SNO-R-PI-150
15 SDV-1102A /1202A 2 4" ASME 900# SNO-R-PI-005 74 SDV-6078A 1 6" ASME 1500# SNO-R-PI-150
16 SDV-1102B / 1202B 2 4" ASME 900# SNO-R-PI-005 75 BDV-6071E 1 3" ASME 900# SNO-R-PI-150
17 BDV-1102C / 1202C 2 3" ASME 900# SNO-R-PI-005 76 SDV-6075A 1 2" ASME 1500# SNO-R-PI-152
18 SDV-1104A / 1204A 2 3" ASME 900# SNO-R-PI-006 77 SDV-6073 1 4" ASME 600# SNO-R-PI-152
19 SDV-1104B / 1204B 2 3" ASME 900# SNO-R-PI-006 78 SDV-2102A / 2202A 2 12" ASME 900# SNO-R-PI-301
20 SDV-1104C / 1204C 2 10" ASME 900# SNO-R-PI-006 79 SDV-2102B / 2202B 2 12" ASME 600# SNO-R-PI-301
21 BDV-1104D / 1204D 2 2" ASME 1500# SNO-R-PI-006 80 SDV-2104C / 2204C 2 12" ASME 150# SNO-R-PI-302
22 SDV-1105A / 1205A 2 2" ASME 1500# SNO-R-PI-007 81 SDV-2104D / 2204D 2 2" ASME 150# SNO-R-PI-312
23 SDV-1105B / 1205B 2 12" ASME 900# SNO-R-PI-007 82 SDV-2106A 2206A 2 12" ASME 300# SNO-R-PI-304
24 BDV-1105C / 1205C 2 2" ASME 1500# SNO-R-PI-007 83 SDV-2106B / 2206B 2 12" ASME 300# SNO-R-PI-304
25 SDV-6101 / 6201 2 4" ASME 150# SNO-R-PI-008 84 SDV-2105A / 2205A 2 16" ASME 150# SNO-R-PI-305
26 SDV-6101A / 6201A 2 2" ASME 150# SNO-R-PI-008 85 SDV-2105B / 2205B 2 3" ASME 150# SNO-R-PI-305
27 BDV-6101B / 6201B 2 2" ASME 150# SNO-R-PI-008 86 SDV-2123F / 2223F 2 2" ASME 1500# SNO-R-PI-306
28 SDV-6101C / 6201C 2 3" ASME 150# SNO-R-PI-008 87 SDV-2123G / 2223G 2 12" ASME 600# SNO-R-PI-306
29 SDV-4101A(Deleted) 1 3" ASME 150# SNO-R-PI-010 88 BDV-2123G / 2223G 2 6" ASME 600# SNO-R-PI-306
30 SDV-4101B(Deleted)
SDV 4101B(D l d) 1 24" ASME 150# SNO-R-PI-010
SNO R PI 010 89 SDV-3102A / 3202A 2 2" ASME 600# SNO-R-PI-401
31 SDV-6073A (Deleted) 1 16" ASME 150# SNO-R-PI-010D 90 SDV-3102F / 3202F 2 3" ASME 600# SNO-R-PI-401
32 XV-6073E(Deleted) 1 2" ASME 150# SNO-R-PI-010D 91 SDV-3116A / 3216A 2 2" ASME 600# SNO-R-PI-402A
33 SDV-6105B / 6205B 2 6" ASME 300# SNO-R-PI-013 92 SDV-3116J / 3216J 2 12" ASME 600# SNO-R-PI-402A
34 SDV-6107B / 6207B 2 2" ASME 300# SNO-R-PI-014 93 BDV-3116K / 3216K 2 3" ASME 600# SNO-R-PI-402A
35 SDV-6107D 6207D 2 4" ASME 300# SNO-R-PI-014 94 SDV-3104A / 3204A 2 6" ASME 300# SNO-R-PI-403
36 BDV-6106A / 6206A 2 2" ASME 300# SNO-R-PI-014 95 SDV-3104B / 3204B 2 2" ASME 150# SNO-R-PI-403
37 SDV-6040B 1 2" ASME 300# SNO-R-PI-015 96 SDV-3110A / 3210A 2 3" ASME 150# SNO-R-PI-404
38 BDV-5102A / 5202A 2 3" ASME 600# SNO-R-PI-017 97 SDV-6051A 1 6" ASME 150# SNO-R-PI-602
39 SDV-5102B / 5202B 2 12" ASME 600# SNO-R-PI-017 98 SDV-6051B 1 4" ASME 300# SNO-R-PI-602
40 SDV-5104A / 5204A 2 2" ASME 1500# SNO-R-PI-018 99 SDV-6106A 1 6" ASME 300# SNO-R-PI-604
41 SDV-6104A / 6204A 2 4" ASME 300# SNO-R-PI-019 100 SDV-6105A 1 4" ASME 150# SNO-R-PI-605
42 XV-6005A 1 6" ASME 300# SNO-R-PI-020 101 SDV-6105B 1 2" ASME 150# SNO-R-PI-605
43 XV-6001A 1 12" ASME 150# SNO-R-PI-020 102 SDV-6123F 1 2" ASME 150# SNO-R-PI-606
44 XV-6002A 1 12" ASME 150# SNO-R-PI-021 103 SDV-6123G 1 6" ASME 150# SNO-R-PI-606
45 XV-6005B 1 6" ASME 300# SNO-R-PI-021 104 BDV-6123G 1 2" ASME 150# SNO-R-PI-606
46 BDV-5108A / 5208A 2 4" ASME 300# SNO-R-PI-023 105 XV-6070A / 6070B 2 4" ASME 150# SNO-R-PI-010B
47 BDV-5020A 1 2" ASME 600# SNO-R-PI-024 106 XV-6020A / 6020C 2 8" ASME 150# SNO-R-PI-034B
48 SDV-5020C 1 30" ASME 600# SNO-R-PI-024 107 XV-6020B / 6020D 2 24" ASME 150# SNO-R-PI-034B
49 XV-5020A 1 2" ASME 600# SNO-R-PI-024 108 SDV-8032A / 8032B 2 3" ASME 600# SNO-R-PI-126
50 SDV-6040A 1 8" ASME 150# SNO-R-PI-025 109 SDV-3102B / 3202B 2 3" ASME 600# SNO-R-PI-401
51 SDV-5030A 1 30" ASME 600# SNO-R-PI-027 110 SDV-4032A 1 24" ASME 150# SNO-R-PI-701
52 SDV-6050A 1 8" ASME 150# SNO-R-PI-028 111 SDV-4032 1 2" ASME 150# SNO-R-PI-701
53 XV-7002B 1 4" ASME 150# SNO-R-PI-031 112 SDV-4033 1 2" ASME 300# SNO-R-PI-701
54 SDV-7010A 1 4" ASME 1500# SNO-R-PI-032 113 SDV-4015B 1 2" ASME 150# SNO-R-PI-706
55 SDV-5010C 1 20" ASME 600# SNO-R-PI-033 114 SDV-4035 1 4" ASME 600# SNO-R-PI-714
56 XV-6010A 1 8" ASME 150# SNO-R-PI-034 115 SDV-4013A 1 12" ASME 600# SNO-R-PI-704
57 XV-6010B 1 24" ASME 150# SNO-R-PI-034
58 XV-6010C 1 8" ASME 150# SNO-R-PI-034
59 XV-6010D 1 24" ASME 150# SNO-R-PI-034

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction
SHUTDOWN AND BLOWDOWN VALVES
C 12-Apr-13 SYL Approved for Construction
B 28-Jan-13 HDY Issue for Approval Sheet
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
1 Tag No. Quantity SDV-0005G 1 (One)
2 Manufacturer Model VTA VTA
3 Contract No. Requisition Item No.
4 Location Central Processing Plant
GENERAL
5 P&ID No. SNO-R-PI-003
6 Service From Well SN0-WH-0005 to Production and Test Manifold
C 7 Line No. 6"-HF-0034-15R
8 Area Classification Zone-2, Gr. IIB, T3
9 Valve Type Valve Code Trunnion Mounted Ball BA453
C 10 Body Size Body Form 6 in Ball
11 Body Material Port Size ASTM A182 F51 Full Bore
12 Connection Rating RTJ ASME 1500#
C1 13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
C 14 Packing Lubrication & Isolation Expanded Graphite VTA
15 Bonnet Bolt Bonnet Nuts UNS S31803 UNS S31803
16 Ball Material Stem Material ASTM A182 F51 ASTM A182 F51
C1 17 Leakage Rate Seat Material ISO 5028 Rate A PTFE OR NYLON
18 NACE Requirement Yes
C 19 Type Stroking Time Pneumatic Piston / Spring return 15 Seconds
C 20 Size Safety Factor VTA in 1.5
21 Actuator Orientation Actuator Form Horizontal Cylinder
22 Ingress Protection Electrical Protection IP65 Eex i
23 Instrument Air Supply 80-120 Psig
24 Action on Air Failure Action on Power Failure Closed Closed
ACTUATOR 25 Fireproofing No
26 Solenoid Valve Schematic Detail Yes Type-14
27 Limit Switch Closed Limit Swich Open Yes Yes
28 Mounting Position Solenoid Power Supply Top 24VDC
29 Manual Reset Yes
30 Mechanical Position Indicator Red Closed / Green Open
C 31 Partial Stroke Facility Yes
31 Signal Cable 1/2" NPT
ELECTRICAL 32 Control Cable -
CONNECTIONS 33 Solenoid Cable 3/4" NPT
34
35 Fluid
Fl id Hydrocarbon
H d b Fluid
Fl id
36 Phase Gas/Liquid/Aqueous
37 Operating Pressure 920 psig
38 Design Pressure 3200 psig
39 Operating Temperature 153 ºF
40 Design Temperature 250 ºF
PROCESS DATA
41 Max. Diff. Pressure for Actuator Size 3200 psig
42
C 43 Line Size and Sch. Inlet Outlet 6 in Sch. 80S 6 in Sch. 80S
44 Speed of Operation Design VTA
45 (Seconds) Actual VTA
46
Notes
1. VTA : Vendor to advice
2. Actuated ball valve and actuator shall be provided with 316 SS nameplate engraved or die stamped with Valve Tag No., Manufacturer's Name,
Model No., Valve Size & Rating.
3. Vendor shall be responsible for the proper design and selection of valve, actuator, and accessories based on the information furnished
C1 in this specification. This Data Sheet shall refer to SNO-I-ES-013, Instrument Specification for Shutdown and Blowdown Valve
4. Actuator shall be sized based on valve manufacturer's required Torque values with 130% minimum safety margin to open or close the valve
against full ANSI rated differential pressure at minimum pneumatic supply pressure of 60 psig.
5. Vendor shall provide Torque table containing breaking, running and seating torques for valves and actuator along with Quotation.
Vendor shall provide the torque table and calculation for COMPANY approval.
6. Actuator and accessories shall be supplied fully assembled, tubed and tested ready for installation.
7. Solenoid valve coil shall be provided with reverse polarity protection diodes, integral outlet box and terminal strip for cable connection.
8. Three way valve shall be universal type. Solenoid Coil shall be Class H.
Air filter regulator shall be 316 SS Material and equipped with pressure gauge on inlet and outlet of air filter regulator.
C1 9. All SDV & BDV shall be designed & tested as per API 6D
C1 10. Valve Stem Shall be Anti-Blowout Type.

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 1 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
1 Tag No. Quantity SDV -0016G 1 (One)
2 Manufacturer Model VTA VTA
3 Contract No. Requisition Item No.
4 Location Central Processing Plant
GENERAL
5 P&ID No. SNO-R-PI-003
6 Service From Well SN0-WH-0016 to Production and Test Manifold
7 Line No. 6"-HF-0035-15R
8 Area Classification Zone-2, Gr. IIB, T3
9 Valve Type Valve Code Trunnion Mounted Ball BA453
10 Body Size Body Form 6 in Ball
11 Body Material Port Size ASTM A182 F51 Full Bore
12 Connection Rating RTJ ASME 1500#
C1 13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
C 14 Packing Lubrication & Isolation Expanded Graphite VTA
15 Bonnet Bolt Bonnet Nuts UNS S31803 UNS S31803
16 Ball Material Stem Material ASTM A182 F51 ASTM A182 F51
C1 17 Leakage Rate Seat Material ISO 5028 Rate A PTFE OR NYLON
18 NACE Requirement Yes
C 19 Type Stroking Time Pneumatic Piston / Spring return 12 Seconds
C 20 Size Safety Factor VTA in 1.5
21 Actuator Orientation Actuator Form Horizontal Cylinder
22 Ingress Protection Electrical Protection IP65 Eex i
23 Instrument Air Supply 80-120 Psig
24 Action on Air Failure Action on Power Failure Closed Closed
ACTUATOR 25 Fireproofing No
26 Solenoid Valve Schematic Detail Yes Type-14
27 Limit Switch Closed Limit Swich Open Yes Yes
28 Mounting Position Solenoid Power Supply Top 24VDC
29 Manual Reset Yes
30 Mechanical Position Indicator Red Closed / Green Open
C1 31 Partial Stroke Facility No
31 Signal Cable 1/2" NPT
ELECTRICAL 32 Control Cable -
CONNECTIONS 33 Solenoid Cable 3/4" NPT
34
35 Fluid
Fl id Hydrocarbon
H d b Fluid
Fl id
36 Phase Gas/Liquid/Aqueous
37 Operating Pressure 920 psig
38 Design Pressure 3200 psig
39 Operating Temperature 153 ºF
40 Design Temperature 250 ºF
PROCESS DATA
41 Max. Diff. Pressure for Actuator Size 3200 psig
42
43 Line Size and Sch. Inlet Outlet 6 in Sch. 80S 6 in Sch. 80S
44 Speed of Operation Design VTA
45 (Seconds) Actual VTA
46
Notes
1. VTA : Vendor to advice
2. Actuated ball valve and actuator shall be provided with 316 SS nameplate engraved or die stamped with Valve Tag No., Manufacturer's Name,
Model No., Valve Size & Rating.
3. Vendor shall be responsible for the proper design and selection of valve, actuator, and accessories based on the information furnished
C1 in this specification. This Data Sheet shall refer to SNO-I-ES-013, Instrument Specification for Shutdown and Blowdown Valve
4. Actuator shall be sized based on valve manufacturer's required Torque values with 130% minimum safety margin to open or close the valve
against full ANSI rated differential pressure at minimum pneumatic supply pressure of 60 psig.
5. Vendor shall provide Torque table containing breaking, running and seating torques for valves and actuator along with Quotation.
Vendor shall provide the torque table and calculation for COMPANY approval.
6. Actuator and accessories shall be supplied fully assembled, tubed and tested ready for installation.
7. Solenoid valve coil shall be provided with reverse polarity protection diodes, integral outlet box and terminal strip for cable connection.
8. Three way valve shall be universal type. Solenoid Coil shall be Class H.
Air filter regulator shall be 316 SS Material and equipped with pressure gauge on inlet and outlet of air filter regulator.
C1 9. All SDV & BDV shall be designed & tested as per API 6D
C1 10. Valve Stem Shall be Anti-Blowout Type.

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 2 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
1 Tag No. Quantity SDV -0001G 1 (One)
2 Manufacturer Model VTA VTA
3 Contract No. Requisition Item No.
4 Location Central Processing Plant
GENERAL
5 P&ID No. SNO-R-PI-003
6 Service From Well SN0-WH-0001 to Production and Test Manifold
7 Line No. 6"-HF-0045-15R
8 Area Classification Zone-2, Gr. IIB, T3
9 Valve Type Valve Code Trunnion Mounted Ball BA453
10 Body Size Body Form 6 in Ball
11 Body Material Port Size ASTM A182 F51 Full Bore
12 Connection Rating RTJ ASME 1500#
C1 13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
C 14 Packing Lubrication & Isolation Expanded Graphite VTA
15 Bonnet Bolt Bonnet Nuts UNS S31803 UNS S31803
16 Ball Material Stem Material ASTM A182 F51 ASTM A182 F51
C1 17 Leakage Rate Seat Material ISO 5028 Rate A PTFE OR NYLON
18 NACE Requirement Yes
C 19 Type Stroking Time Pneumatic Piston / Spring return 12 Seconds
C 20 Size Safety Factor VTA in 1.5
21 Actuator Orientation Actuator Form Horizontal Cylinder
22 Ingress Protection Electrical Protection IP65 Eex i
23 Instrument Air Supply 80-120 Psig
24 Action on Air Failure Action on Power Failure Closed Closed
ACTUATOR 25 Fireproofing No
26 Solenoid Valve Schematic Detail Yes Type-14
27 Limit Switch Closed Limit Swich Open Yes Yes
28 Mounting Position Solenoid Power Supply Top 24VDC
29 Manual Reset Yes
30 Mechanical Position Indicator Red Closed / Green Open
C 31 Partial Stroke Facility Yes
31 Signal Cable 1/2" NPT
ELECTRICAL 32 Control Cable -
CONNECTIONS 33 Solenoid Cable 3/4" NPT
34
35 Fluid
Fl id Hydrocarbon
H d b Fluid
Fl id
36 Phase Gas/Liquid/Aqueous
37 Operating Pressure 920 psig
38 Design Pressure 3200 psig
39 Operating Temperature 153 ºF
40 Design Temperature 250 ºF
PROCESS DATA
41 Max. Diff. Pressure for Actuator Size 3200 psig
42
43 Line Size and Sch. Inlet Outlet 6 in Sch. 80S 6 in Sch. 80S
44 Speed of Operation Design VTA
45 (Seconds) Actual VTA
46
Notes
1. VTA : Vendor to advice
2. Actuated ball valve and actuator shall be provided with 316 SS nameplate engraved or die stamped with Valve Tag No., Manufacturer's Name,
Model No., Valve Size & Rating.
3. Vendor shall be responsible for the proper design and selection of valve, actuator, and accessories based on the information furnished
C1 in this specification. This Data Sheet shall refer to SNO-I-ES-013, Instrument Specification for Shutdown and Blowdown Valve
4. Actuator shall be sized based on valve manufacturer's required Torque values with 130% minimum safety margin to open or close the valve
against full ANSI rated differential pressure at minimum pneumatic supply pressure of 60 psig.
5. Vendor shall provide Torque table containing breaking, running and seating torques for valves and actuator along with Quotation.
Vendor shall provide the torque table and calculation for COMPANY approval.
6. Actuator and accessories shall be supplied fully assembled, tubed and tested ready for installation.
7. Solenoid valve coil shall be provided with reverse polarity protection diodes, integral outlet box and terminal strip for cable connection.
8. Three way valve shall be universal type. Solenoid Coil shall be Class H.
Air filter regulator shall be 316 SS Material and equipped with pressure gauge on inlet and outlet of air filter regulator.
C1 9. All SDV & BDV shall be designed & tested as per API 6D
C1 10. Valve Stem Shall be Anti-Blowout Type.

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 3 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
1 Tag No. Quantity SDV -0007G 1 (One)
2 Manufacturer Model VTA VTA
3 Contract No. Requisition Item No.
4 Location Central Processing Plant
GENERAL
5 P&ID No. SNO-R-PI-003
6 Service From Well SN0-WH-0007 to Production and Test Manifold
7 Line No. 6"-HF-0043-15R
8 Area Classification Zone-2, Gr. IIB, T3
9 Valve Type Valve Code Trunnion Mounted Ball BA453
10 Body Size Body Form 6 in Ball
11 Body Material Port Size ASTM A182 F51 Full Bore
12 Connection Rating RTJ ASME 1500#
C1 13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
C 14 Packing Lubrication & Isolation Expanded Graphite VTA
15 Bonnet Bolt Bonnet Nuts UNS S31803 UNS S31803
16 Ball Material Stem Material ASTM A182 F51 ASTM A182 F51
C1 17 Leakage Rate Seat Material ISO 5028 Rate A PTFE OR NYLON
18 NACE Requirement Yes
C 19 Type Stroking Time Pneumatic Piston / Spring return 12 Seconds
20 Size Safety Factor VTA in 1.3
21 Actuator Orientation Actuator Form Horizontal Cylinder
22 Ingress Protection Electrical Protection IP65 Eex i
23 Instrument Air Supply 80-120 Psig
24 Action on Air Failure Action on Power Failure Closed Closed
ACTUATOR 25 Fireproofing No
26 Solenoid Valve Schematic Detail Yes Type-14
27 Limit Switch Closed Limit Swich Open Yes Yes
28 Mounting Position Solenoid Power Supply Top 24VDC
29 Manual Reset Yes
30 Mechanical Position Indicator Red Closed / Green Open
C 31 Partial Stroke Facility No
31 Signal Cable 1/2" NPT
ELECTRICAL 32 Control Cable -
CONNECTIONS 33 Solenoid Cable 3/4" NPT
34
35 Fluid
Fl id Hydrocarbon
H d b Fluid
Fl id
36 Phase Gas/Liquid/Aqueous
37 Operating Pressure 920 psig
38 Design Pressure 3200 psig
39 Operating Temperature 153 ºF
40 Design Temperature 250 ºF
PROCESS DATA
41 Max. Diff. Pressure for Actuator Size 3200 psig
42
43 Line Size and Sch. Inlet Outlet 6 in Sch. 80S 6 in Sch. 80S
44 Speed of Operation Design VTA
45 (Seconds) Actual VTA
46
Notes
1. VTA : Vendor to advice
2. Actuated ball valve and actuator shall be provided with 316 SS nameplate engraved or die stamped with Valve Tag No., Manufacturer's Name,
Model No., Valve Size & Rating.
3. Vendor shall be responsible for the proper design and selection of valve, actuator, and accessories based on the information furnished
C1 in this specification. This Data Sheet shall refer to SNO-I-ES-013, Instrument Specification for Shutdown and Blowdown Valve
4. Actuator shall be sized based on valve manufacturer's required Torque values with 130% minimum safety margin to open or close the valve
against full ANSI rated differential pressure at minimum pneumatic supply pressure of 60 psig.
5. Vendor shall provide Torque table containing breaking, running and seating torques for valves and actuator along with Quotation.
Vendor shall provide the torque table and calculation for COMPANY approval.
6. Actuator and accessories shall be supplied fully assembled, tubed and tested ready for installation.
7. Solenoid valve coil shall be provided with reverse polarity protection diodes, integral outlet box and terminal strip for cable connection.
8. Three way valve shall be universal type. Solenoid Coil shall be Class H.
Air filter regulator shall be 316 SS Material and equipped with pressure gauge on inlet and outlet of air filter regulator.
C1 9. All SDV & BDV shall be designed & tested as per API 6D
C1 10. Valve Stem Shall be Anti-Blowout Type.

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 4 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
1 Tag No. Quantity SDV -0017G 1 (One)
2 Manufacturer Model VTA VTA
3 Contract No. Requisition Item No.
4 Location Central Processing Plant
GENERAL
5 P&ID No. SNO-R-PI-003
6 Service From Well SN0-WH-0017 to Production and Test Manifold
7 Line No. 6"-HF-0044-15R
8 Area Classification Zone-2, Gr. IIB, T3
9 Valve Type Valve Code Trunnion Mounted Ball BA453
10 Body Size Body Form 6 in Ball
11 Body Material Port Size ASTM A182 F51 Full Bore
12 Connection Rating RTJ ASME 1500#
C1 13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
C 14 Packing Lubrication & Isolation Expanded Graphite VTA
15 Bonnet Bolt Bonnet Nuts UNS S31803 UNS S31803
16 Ball Material Stem Material ASTM A182 F51 ASTM A182 F51
C1 17 Leakage Rate Seat Material ISO 5028 Rate A PTFE OR NYLON
18 NACE Requirement Yes
C 19 Type Stroking Time Pneumatic Piston / Spring return 12 Seconds
20 Size Safety Factor VTA in 1.3
21 Actuator Orientation Actuator Form Horizontal Cylinder
22 Ingress Protection Electrical Protection IP65 Eex i
23 Instrument Air Supply 80-120 Psig
24 Action on Air Failure Action on Power Failure Closed Closed
ACTUATOR 25 Fireproofing No
26 Solenoid Valve Schematic Detail Yes Type-14
27 Limit Switch Closed Limit Swich Open Yes Yes
28 Mounting Position Solenoid Power Supply Top 24VDC
29 Manual Reset Yes
30 Mechanical Position Indicator Red Closed / Green Open
C 31 Partial Stroke Facility No
31 Signal Cable 1/2" NPT
ELECTRICAL 32 Control Cable -
CONNECTIONS 33 Solenoid Cable 3/4" NPT
34
35 Fluid
Fl id Hydrocarbon
H d b Fluid
Fl id
36 Phase Gas/Liquid/Aqueous
37 Operating Pressure 920 psig
38 Design Pressure 3200 psig
39 Operating Temperature 153 ºF
40 Design Temperature 250 ºF
PROCESS DATA
41 Max. Diff. Pressure for Actuator Size 3200 psig
42
43 Line Size and Sch. Inlet Outlet 6 in Sch. 80S 6 in Sch. 80S
44 Speed of Operation Design VTA
45 (Seconds) Actual VTA
46
Notes
1. VTA : Vendor to advice
2. Actuated ball valve and actuator shall be provided with 316 SS nameplate engraved or die stamped with Valve Tag No., Manufacturer's Name,
Model No., Valve Size & Rating.
3. Vendor shall be responsible for the proper design and selection of valve, actuator, and accessories based on the information furnished
C1 in this specification. This Data Sheet shall refer to SNO-I-ES-013, Instrument Specification for Shutdown and Blowdown Valve
4. Actuator shall be sized based on valve manufacturer's required Torque values with 130% minimum safety margin to open or close the valve
against full ANSI rated differential pressure at minimum pneumatic supply pressure of 60 psig.
5. Vendor shall provide Torque table containing breaking, running and seating torques for valves and actuator along with Quotation.
Vendor shall provide the torque table and calculation for COMPANY approval.
6. Actuator and accessories shall be supplied fully assembled, tubed and tested ready for installation.
7. Solenoid valve coil shall be provided with reverse polarity protection diodes, integral outlet box and terminal strip for cable connection.
8. Three way valve shall be universal type. Solenoid Coil shall be Class H.
Air filter regulator shall be 316 SS Material and equipped with pressure gauge on inlet and outlet of air filter regulator.
C1 9. All SDV & BDV shall be designed & tested as per API 6D
C1 10. Valve Stem Shall be Anti-Blowout Type.

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 5 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
1 Tag No. Quantity SDV -0002G 1 (One)
2 Manufacturer Model VTA VTA
3 Contract No. Requisition Item No.
4 Location Central Processing Plant
GENERAL
5 P&ID No. SNO-R-PI-003
6 Service From Well Senoro Cluster-2 to Production and Test Manifold
7 Line No. 16"-HF-0077-15R
8 Area Classification Zone-2, Gr. IIB, T3
9 Valve Type Valve Code Trunnion Mounted Ball BA453
10 Body Size Body Form 16 in Ball
11 Body Material Port Size ASTM A182 F51 Full Bore
12 Connection Rating RTJ ASME 1500#
C1 13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
C 14 Packing Lubrication & Isolation Expanded Graphite VTA
15 Bonnet Bolt Bonnet Nuts UNS S31803 UNS S31803
16 Ball Material Stem Material ASTM A182 F51 ASTM A182 F51
C1 17 Leakage Rate Seat Material ISO 5028 Rate A PTFE OR NYLON
18 NACE Requirement Yes
C 19 Type Stroking Time Pneumatic Piston / Spring return 15 Seconds
C 20 Size Safety Factor VTA in 1.5
21 Actuator Orientation Actuator Form Horizontal Cylinder
22 Ingress Protection Electrical Protection IP65 Eex i
23 Instrument Air Supply 80-120 Psig
24 Action on Air Failure Action on Power Failure Closed Closed
ACTUATOR 25 Fireproofing No
26 Solenoid Valve Schematic Detail Yes Type-14
27 Limit Switch Closed Limit Swich Open Yes Yes
28 Mounting Position Solenoid Power Supply Top 24VDC
29 Manual Reset Yes
30 Mechanical Position Indicator Red Closed / Green Open
C 31 Partial Stroke Facility Yes
31 Signal Cable 1/2" NPT
ELECTRICAL 32 Control Cable -
CONNECTIONS 33 Solenoid Cable 3/4" NPT
34
35 Fluid
Fl id Hydrocarbon
H d b Fluid
Fl id
36 Phase Gas/Liquid/Aqueous
37 Operating Pressure 920 psig
38 Design Pressure 3200 psig
39 Operating Temperature 153 ºF
40 Design Temperature 250 ºF
PROCESS DATA
41 Max. Diff. Pressure for Actuator Size 3200 psig
42
43 Line Size and Sch. Inlet Outlet 16 in Sch. 100 16 in Sch. 100
44 Speed of Operation Design VTA
45 (Seconds) Actual VTA
46
Notes
1. VTA : Vendor to advice
2. Actuated ball valve and actuator shall be provided with 316 SS nameplate engraved or die stamped with Valve Tag No., Manufacturer's Name,
Model No., Valve Size & Rating.
3. Vendor shall be responsible for the proper design and selection of valve, actuator, and accessories based on the information furnished
C1 in this specification. This Data Sheet shall refer to SNO-I-ES-013, Instrument Specification for Shutdown and Blowdown Valve
4. Actuator shall be sized based on valve manufacturer's required Torque values with 130% minimum safety margin to open or close the valve
against full ANSI rated differential pressure at minimum pneumatic supply pressure of 60 psig.
5. Vendor shall provide Torque table containing breaking, running and seating torques for valves and actuator along with Quotation.
Vendor shall provide the torque table and calculation for COMPANY approval.
6. Actuator and accessories shall be supplied fully assembled, tubed and tested ready for installation.
7. Solenoid valve coil shall be provided with reverse polarity protection diodes, integral outlet box and terminal strip for cable connection.
8. Three way valve shall be universal type. Solenoid Coil shall be Class H.
Air filter regulator shall be 316 SS Material and equipped with pressure gauge on inlet and outlet of air filter regulator.
C1 9. All SDV & BDV shall be designed & tested as per API 6D
C1 10. Valve Stem Shall be Anti-Blowout Type.

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 6 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
1 Tag No. Quantity SDV -0030A 1 (One)
2 Manufacturer Model VTA VTA
3 Contract No. Requisition Item No.
4 Location Central Processing Plant
GENERAL
5 P&ID No. SNO-R-PI-003
6 Service Test Header From Senoro Cluster-2 to Test Manifold
7 Line No. 8"-HF-0090-15R
8 Area Classification Zone-2, Gr. IIB, T3
9 Valve Type Valve Code Trunnion Mounted Ball BA453
10 Body Size Body Form 8 in Ball
11 Body Material Port Size ASTM A182 F51 Full Bore
12 Connection Rating RTJ ASME 1500#
C1 13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
C 14 Packing Lubrication & Isolation Expanded Graphite VTA
15 Bonnet Bolt Bonnet Nuts UNS S31803 UNS S31803
16 Ball Material Stem Material ASTM A182 F51 ASTM A182 F51
C1 17 Leakage Rate Seat Material ISO 5028 Rate A PTFE OR NYLON
18 NACE Requirement Yes
C 19 Type Stroking Time Pneumatic Piston / Spring return 15 Seconds
20 Size Safety Factor VTA in 1.5
21 Actuator Orientation Actuator Form Horizontal Cylinder
22 Ingress Protection Electrical Protection IP65 Eex i
23 Instrument Air Supply 80-120 Psig
24 Action on Air Failure Action on Power Failure Closed Closed
ACTUATOR 25 Fireproofing No
26 Solenoid Valve Schematic Detail Yes Type-14
27 Limit Switch Closed Limit Swich Open Yes Yes
28 Mounting Position Solenoid Power Supply Top 24VDC
29 Manual Reset Yes
30 Mechanical Position Indicator Red Closed / Green Open
C 31 Partial Stroke Facility No
31 Signal Cable 1/2" NPT
ELECTRICAL 32 Control Cable -
CONNECTIONS 33 Solenoid Cable 3/4" NPT
34
35 Fluid
Fl id Hydrocarbon
H d b Fluid
Fl id
36 Phase Gas/Liquid/Aqueous
37 Operating Pressure 920 psig
38 Design Pressure 3200 psig
39 Operating Temperature 153 ºF
40 Design Temperature 250 ºF
PROCESS DATA
41 Max. Diff. Pressure for Actuator Size 3200 psig
42
43 Line Size and Sch. Inlet Outlet 8 in Sch. 100 8 in Sch. 100
44 Speed of Operation Design VTA
45 (Seconds) Actual VTA
46
Notes
1. VTA : Vendor to advice
2. Actuated ball valve and actuator shall be provided with 316 SS nameplate engraved or die stamped with Valve Tag No., Manufacturer's Name,
Model No., Valve Size & Rating.
3. Vendor shall be responsible for the proper design and selection of valve, actuator, and accessories based on the information furnished
C1 in this specification. This Data Sheet shall refer to SNO-I-ES-013, Instrument Specification for Shutdown and Blowdown Valve
4. Actuator shall be sized based on valve manufacturer's required Torque values with 130% minimum safety margin to open or close the valve
against full ANSI rated differential pressure at minimum pneumatic supply pressure of 60 psig.
5. Vendor shall provide Torque table containing breaking, running and seating torques for valves and actuator along with Quotation.
Vendor shall provide the torque table and calculation for COMPANY approval.
6. Actuator and accessories shall be supplied fully assembled, tubed and tested ready for installation.
7. Solenoid valve coil shall be provided with reverse polarity protection diodes, integral outlet box and terminal strip for cable connection.
8. Three way valve shall be universal type. Solenoid Coil shall be Class H.
Air filter regulator shall be 316 SS Material and equipped with pressure gauge on inlet and outlet of air filter regulator.
C1 9. All SDV & BDV shall be designed & tested as per API 6D
C1 10. Valve Stem Shall be Anti-Blowout Type.

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 7 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
C 1 Tag No. Quantity BDV-0001N 1 (One)
2 Manufacturer Model VTA VTA
3 Contract No. Requisition Item No.
4 Location Central Processing Plant
GENERAL
5 P&ID No. SNO-R-PI-003
6 Service From Production Manifold Header Train #1 to HP Flare
C 7 Line No. 2"-HF-0110-15R
8 Area Classification Zone-2, Gr. IIB, T3
9 Valve Type Valve Code Trunnion Mounted Ball BA451
10 Body Size Body Form 2 in Ball
11 Body Material Port Size ASTM A182 F51 Full Bore
12 Connection Rating RTJ ASME 1500#
C1 13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
C 14 Packing Lubrication & Isolation Expanded Graphite VTA
15 Bonnet Bolts Bonnet Nuts UNS S31803 UNS S31803
16 Ball Material Stem Material ASTM A182 F51 ASTM A182 F51
C1 17 Leakage Rate Seat Material ISO 5028 Rate A (TSO) PTFE OR NYLON
18 NACE Requirement Yes
C 19 Type Stroking Time Pneumatic Piston / Spring return 4 Seconds
20 Size Safety Factor VTA in 1.3
21 Actuator Orientation Actuator Form Horizontal Cylinder
22 Ingress Protection Electrical Protection IP65 Eex i
23 Instrument Air Supply 80-120 Psig
24 Action on Air Failure Action on Power Failure Open Open
ACTUATOR 25 Fireproofing No
26 Solenoid Valve Schematic Detail Yes Type-2
27 Limit Switch Closed Limit Swich Open Yes Yes
28 Mounting Position Solenoid Power Supply Top 24VDC
29 Manual Reset No
30 Mechanical Position Indicator Red Closed / Green Open
C 31 Partial Stroke Facility No
31 Signal Cable 1/2" NPT
ELECTRICAL 32 Control Cable -
CONNECTIONS 33 Solenoid Cable 3/4" NPT
34
35 Fluid
Fl id Hydrocarbon
H d b
36 Phase Gas / Liquid
37 Operating Pressure 905 psig
38 Design Pressure 3200 psig
39 Operating Temperature 180 ºF
40 Design Temperature 250 ºF
PROCESS DATA
41 Max. Diff. Pressure for Actuator Size 3200 psig
42
43 Line Size and Sch. Inlet Outlet 2 in Sch. 80S 2 in Sch. 80S
44 Speed of Operation Design VTA
45 (Seconds) Actual VTA
46
Notes
1. VTA : Vendor to advice
2. Actuated ball valve and actuator shall be provided with 316 SS nameplate engraved or die stamped with Valve Tag No., Manufacturer's Name,
Model No., Valve Size & Rating.
3. Vendor shall be responsible for the proper design and selection of valve, actuator, and accessories based on the information furnished
C1 in this specification. This Data Sheet shall refer to SNO-I-ES-013, Instrument Specification for Shutdown and Blowdown Valve
4. Actuator shall be sized based on valve manufacturer's required Torque values with 130% minimum safety margin to open or close the valve
against full ANSI rated differential pressure at minimum pneumatic supply pressure of 60 psig.
5. Vendor shall provide Torque table containing breaking, running and seating torques for valves and actuator along with Quotation.
Vendor shall provide the torque table and calculation for COMPANY approval.
6. Actuator and accessories shall be supplied fully assembled, tubed and tested ready for installation.
7. Solenoid valve coil shall be provided with reverse polarity protection diodes, integral outlet box and terminal strip for cable connection.
8. Three way valve shall be universal type. Solenoid Coil shall be Class H.
Air filter regulator shall be 316 SS Material and equipped with pressure gauge on inlet and outlet of air filter regulator.
C1 9. All SDV & BDV shall be designed & tested as per API 6D
C1 10. Valve Stem Shall be Anti-Blowout Type.

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 8 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
C 1 Tag No. Quantity BDV-0001P 1 (One)
2 Manufacturer Model VTA VTA
3 Contract No. Requisition Item No.
4 Location Central Processing Plant
GENERAL
5 P&ID No. SNO-R-PI-003
6 Service From Production Manifold Header Train #2 to HP Flare
C 7 Line No. 2"-HF-0111-15R
8 Area Classification Zone-2, Gr. IIB, T3
9 Valve Type Valve Code Trunnion Mounted Ball BA451
10 Body Size Body Form 2 in Ball
11 Body Material Port Size ASTM A182 F51 Full Bore
12 Connection Rating RTJ ASME 1500#
C1 13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
C 14 Packing Lubrication & Isolation Expanded Graphite VTA
15 Bonnet Bolts Bonnet Nuts UNS S31803 UNS S31803
16 Ball Material Stem Material ASTM A182 F51 ASTM A182 F51
C1 17 Leakage Rate Seat Material ISO 5028 Rate A (TSO) PTFE OR NYLON
18 NACE Requirement Yes
C 19 Type Stroking Time Pneumatic Piston / Spring return 4 Seconds
20 Size Safety Factor VTA in 1.5
21 Actuator Orientation Actuator Form Horizontal Cylinder
22 Ingress Protection Electrical Protection IP65 Eex i
23 Instrument Air Supply 80-120 Psig
24 Action on Air Failure Action on Power Failure Open Open
ACTUATOR 25 Fireproofing No
26 Solenoid Valve Schematic Detail Yes Type-2
27 Limit Switch Closed Limit Swich Open Yes Yes
28 Mounting Position Solenoid Power Supply Top 24VDC
29 Manual Reset No
30 Mechanical Position Indicator Red Closed / Green Open
C 31 Partial Stroke Facility No
31 Signal Cable 1/2" NPT
ELECTRICAL 32 Control Cable -
CONNECTIONS 33 Solenoid Cable 3/4" NPT
34
35 Fluid
Fl id Hydrocarbon
H d b
36 Phase Gas / Liquid
37 Operating Pressure 905 psig
38 Design Pressure 3200 psig
39 Operating Temperature 180 ºF
40 Design Temperature 250 ºF
PROCESS DATA
41 Max. Diff. Pressure for Actuator Size 3200 psig
42
43 Line Size and Sch. Inlet Outlet 2 in Sch. 80S 2 in Sch. 80S
44 Speed of Operation Design VTA
45 (Seconds) Actual VTA
46
Notes
1. VTA : Vendor to advice
2. Actuated ball valve and actuator shall be provided with 316 SS nameplate engraved or die stamped with Valve Tag No., Manufacturer's Name,
Model No., Valve Size & Rating.
3. Vendor shall be responsible for the proper design and selection of valve, actuator, and accessories based on the information furnished
C1 in this specification. This Data Sheet shall refer to SNO-I-ES-013, Instrument Specification for Shutdown and Blowdown Valve
4. Actuator shall be sized based on valve manufacturer's required Torque values with 130% minimum safety margin to open or close the valve
against full ANSI rated differential pressure at minimum pneumatic supply pressure of 60 psig.
5. Vendor shall provide Torque table containing breaking, running and seating torques for valves and actuator along with Quotation.
Vendor shall provide the torque table and calculation for COMPANY approval.
6. Actuator and accessories shall be supplied fully assembled, tubed and tested ready for installation.
7. Solenoid valve coil shall be provided with reverse polarity protection diodes, integral outlet box and terminal strip for cable connection.
8. Three way valve shall be universal type. Solenoid Coil shall be Class H.
Air filter regulator shall be 316 SS Material and equipped with pressure gauge on inlet and outlet of air filter regulator.
C1 9. All SDV & BDV shall be designed & tested as per API 6D
C1 10. Valve Stem Shall be Anti-Blowout Type.

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 9 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
C 1 Tag No. Quantity BDV-0001R 1 (One)
2 Manufacturer Model VTA VTA
3 Contract No. Requisition Item No.
4 Location Central Processing Plant
GENERAL
5 P&ID No. SNO-R-PI-003
6 Service From Test Manifold Header Train #1 to HP Flare
C1 7 Line No. 2"-HF-0112-15R
8 Area Classification Zone-2, Gr. IIB, T3
C1 9 Valve Type Valve Code Trunnion Mounted Ball BA451
C1 10 Body Size Body Form 2 in Ball
11 Body Material Port Size ASTM A182 F51 Full Bore
12 Connection Rating RTJ ASME 1500#
C1 13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
C 14 Packing Lubrication & Isolation Expanded Graphite VTA
15 Bonnet Bolts Bonnet Nuts UNS S31803 UNS S31803
16 Ball Material Stem Material ASTM A182 F51 ASTM A182 F51
C1 17 Leakage Rate Seat Material ISO 5028 Rate A (TSO) PTFE OR NYLON
18 NACE Requirement Yes
C 19 Type Stroking Time Pneumatic Piston / Spring return 2 Seconds
20 Size Safety Factor VTA in 1.3
21 Actuator Orientation Actuator Form Horizontal Cylinder
22 Ingress Protection Electrical Protection IP65 Eex i
23 Instrument Air Supply 80-120 Psig
24 Action on Air Failure Action on Power Failure Open Open
ACTUATOR 25 Fireproofing No
26 Solenoid Valve Schematic Detail Yes Type-2
27 Limit Switch Closed Limit Swich Open Yes Yes
28 Mounting Position Solenoid Power Supply Top 24VDC
29 Manual Reset No
30 Mechanical Position Indicator Red Closed / Green Open
C 31 Partial Stroke Facility No
31 Signal Cable 1/2" NPT
ELECTRICAL 32 Control Cable -
CONNECTIONS 33 Solenoid Cable 3/4" NPT
34
35 Fluid
Fl id Hydrocarbon
H d b
36 Phase Gas / Liquid
37 Operating Pressure 905 psig
38 Design Pressure 3200 psig
39 Operating Temperature 180 ºF
40 Design Temperature 250 ºF
PROCESS DATA
41 Max. Diff. Pressure for Actuator Size 3200 psig
42
C1 43 Line Size and Sch. Inlet Outlet 2 in Sch. 80S 2 in Sch. 80S
44 Speed of Operation Design VTA
45 (Seconds) Actual VTA
46
Notes
1. VTA : Vendor to advice
2. Actuated ball valve and actuator shall be provided with 316 SS nameplate engraved or die stamped with Valve Tag No., Manufacturer's Name,
Model No., Valve Size & Rating.
3. Vendor shall be responsible for the proper design and selection of valve, actuator, and accessories based on the information furnished
C1 in this specification. This Data Sheet shall refer to SNO-I-ES-013, Instrument Specification for Shutdown and Blowdown Valve
4. Actuator shall be sized based on valve manufacturer's required Torque values with 130% minimum safety margin to open or close the valve
against full ANSI rated differential pressure at minimum pneumatic supply pressure of 60 psig.
5. Vendor shall provide Torque table containing breaking, running and seating torques for valves and actuator along with Quotation.
Vendor shall provide the torque table and calculation for COMPANY approval.
6. Actuator and accessories shall be supplied fully assembled, tubed and tested ready for installation.
7. Solenoid valve coil shall be provided with reverse polarity protection diodes, integral outlet box and terminal strip for cable connection.
8. Three way valve shall be universal type. Solenoid Coil shall be Class H.
Air filter regulator shall be 316 SS Material and equipped with pressure gauge on inlet and outlet of air filter regulator.
C1 9. All SDV & BDV shall be designed & tested as per API 6D
C1 10. Valve Stem Shall be Anti-Blowout Type.

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 10 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
C 1 Tag No. Quantity BDV-0001T 1 (One)
2 Manufacturer Model VTA VTA
3 Contract No. Requisition Item No.
4 Location Central Processing Plant
GENERAL
5 P&ID No. SNO-R-PI-003
6 Service From Test Manifold Header Train #2 to HP Flare
C1 7 Line No. 2"-HF-0113-15R
8 Area Classification Zone-2, Gr. IIB, T3
C1 9 Valve Type Valve Code Trunnion Mounted Ball BA451
C1 10 Body Size Body Form 2 in Ball
11 Body Material Port Size ASTM A182 F51 Full Bore
12 Connection Rating RTJ ASME 1500#
C1 13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
C 14 Packing Lubrication & Isolation Expanded Graphite VTA
15 Bonnet Bolts Bonnet Nuts UNS S31803 UNS S31803
16 Ball Material Stem Material ASTM A182 F51 ASTM A182 F51
C1 17 Leakage Rate Seat Material ISO 5028 Rate A (TSO) PTFE OR NYLON
18 NACE Requirement Yes
C 19 Type Stroking Time Pneumatic Piston / Spring return 2 Seconds
20 Size Safety Factor VTA in 1.3
21 Actuator Orientation Actuator Form Horizontal Cylinder
22 Ingress Protection Electrical Protection IP65 Eex i
23 Instrument Air Supply 80-120 Psig
24 Action on Air Failure Action on Power Failure Open Open
ACTUATOR 25 Fireproofing No
26 Solenoid Valve Schematic Detail Yes Type-2
27 Limit Switch Closed Limit Swich Open Yes Yes
28 Mounting Position Solenoid Power Supply Top 24VDC
29 Manual Reset No
30 Mechanical Position Indicator Red Closed / Green Open
C 31 Partial Stroke Facility No
31 Signal Cable 1/2" NPT
ELECTRICAL 32 Control Cable -
CONNECTIONS 33 Solenoid Cable 3/4" NPT
34
35 Fluid
Fl id Hydrocarbon
H d b
36 Phase Gas / Liquid
37 Operating Pressure 905 psig
38 Design Pressure 3200 psig
39 Operating Temperature 180 ºF
40 Design Temperature 250 ºF
PROCESS DATA
41 Max. Diff. Pressure for Actuator Size 3200 psig
42
C1 43 Line Size and Sch. Inlet Outlet 2 in Sch. 80S 2 in Sch. 80S
44 Speed of Operation Design VTA
45 (Seconds) Actual VTA
46
Notes
1. VTA : Vendor to advice
2. Actuated ball valve and actuator shall be provided with 316 SS nameplate engraved or die stamped with Valve Tag No., Manufacturer's Name,
Model No., Valve Size & Rating.
3. Vendor shall be responsible for the proper design and selection of valve, actuator, and accessories based on the information furnished
C1 in this specification. This Data Sheet shall refer to SNO-I-ES-013, Instrument Specification for Shutdown and Blowdown Valve
4. Actuator shall be sized based on valve manufacturer's required Torque values with 130% minimum safety margin to open or close the valve
against full ANSI rated differential pressure at minimum pneumatic supply pressure of 60 psig.
5. Vendor shall provide Torque table containing breaking, running and seating torques for valves and actuator along with Quotation.
Vendor shall provide the torque table and calculation for COMPANY approval.
6. Actuator and accessories shall be supplied fully assembled, tubed and tested ready for installation.
7. Solenoid valve coil shall be provided with reverse polarity protection diodes, integral outlet box and terminal strip for cable connection.
8. Three way valve shall be universal type. Solenoid Coil shall be Class H.
Air filter regulator shall be 316 SS Material and equipped with pressure gauge on inlet and outlet of air filter regulator.
C1 9. All SDV & BDV shall be designed & tested as per API 6D
C1 10. Valve Stem Shall be Anti-Blowout Type.

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 11 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
1 Tag No. Quantity SDV-1101A 1 (One)
2 Manufacturer Model VTA VTA
3 Contract No. Requisition Item No.
4 Location Central Processing Plant
GENERAL
5 P&ID No. SNO-R-PI-003B
6 Service From Production Manifold (Train 1) to Production Cooler E-1101 (Train 1)
7 Line No. 16"-HF-1002-15R
8 Area Classification Zone-2, Gr. IIB, T3
9 Valve Type Valve Code Trunnion Mounted Ball BA453
10 Body Size Body Form 16 in Ball
11 Body Material Port Size ASTM A182 F51 Full Bore
12 Connection Rating RTJ ASME 1500#
C1 13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
C 14 Packing Lubrication & Isolation Expanded Graphite VTA
15 Bonnet Bolts Bonnet Nuts UNS S31803 UNS S31803
16 Ball Material Stem Material ASTM A182 F51 ASTM A182 F51
C1 17 Leakage Rate Seat Material ISO 5028 Rate A PTFE OR NYLON
18 NACE Requirement Yes
C 19 Type Stroking Time Pneumatic Piston / Spring return 15 Seconds
C 20 Size Safety Factor VTA in 1.5
21 Actuator Orientation Actuator Form Horizontal Cylinder
22 Ingress Protection Electrical Protection IP65 Eex i
23 Instrument Air Supply 80-120 Psig
24 Action on Air Failure Action on Power Failure Closed Closed
ACTUATOR 25 Fireproofing No
26 Solenoid Valve Schematic Detail Yes Type-1
27 Limit Switch Closed Limit Swich Open Yes Yes
28 Mounting Position Solenoid Power Supply Top 24VDC
29 Manual Reset No
30 Mechanical Position Indicator Red Closed / Green Open
C 31 Partial Stroke Facility Yes
31 Signal Cable 1/2" NPT
ELECTRICAL 32 Control Cable -
CONNECTIONS 33 Solenoid Cable 3/4" NPT
34
35 Fluid
Fl id Hydrocarbon
H d b Fluid
Fl id
C 36 Phase Gas/Liquid/Vapor
37 Operating Pressure 920 psig
38 Design Pressure 3200 psig
39 Operating Temperature 153 ºF
40 Design Temperature 250 ºF
PROCESS DATA
41 Max. Diff. Pressure for Actuator Size 3200 psig
42
43 Line Size and Sch. Inlet Outlet 16 in Sch. 100 16 in Sch 100
44 Speed of Operation Design VTA
45 (Seconds) Actual VTA
46
Notes
1. VTA : Vendor to advice
2. Actuated ball valve and actuator shall be provided with 316 SS nameplate engraved or die stamped with Valve Tag No., Manufacturer's Name,
Model No., Valve Size & Rating.
3. Vendor shall be responsible for the proper design and selection of valve, actuator, and accessories based on the information furnished
C1 in this specification. This Data Sheet shall refer to SNO-I-ES-013, Instrument Specification for Shutdown and Blowdown Valve
4. Actuator shall be sized based on valve manufacturer's required Torque values with 130% minimum safety margin to open or close the valve
against full ANSI rated differential pressure at minimum pneumatic supply pressure of 60 psig.
5. Vendor shall provide Torque table containing breaking, running and seating torques for valves and actuator along with Quotation.
Vendor shall provide the torque table and calculation for COMPANY approval.
6. Actuator and accessories shall be supplied fully assembled, tubed and tested ready for installation.
7. Solenoid valve coil shall be provided with reverse polarity protection diodes, integral outlet box and terminal strip for cable connection.
8. Three way valve shall be universal type. Solenoid Coil shall be Class H.
Air filter regulator shall be 316 SS Material and equipped with pressure gauge on inlet and outlet of air filter regulator.
C1 9. All SDV & BDV shall be designed & tested as per API 6D
C1 10. Valve Stem Shall be Anti-Blowout Type.

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 12 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
1 Tag No. Quantity SDV -1201A 1 (One)
2 Manufacturer Model VTA VTA
3 Contract No. Requisition Item No.
4 Location Central Processing Plant
GENERAL
5 P&ID No. SNO-R-PI-003B
6 Service From Production Manifold (Train 2) to Production Cooler E-1201 (Train 2)
7 Line No. 16"-HF-2002-15R
8 Area Classification Zone-2, Gr. IIB, T3
9 Valve Type Valve Code Trunnion Mounted Ball BA453
10 Body Size Body Form 16 in Ball
11 Body Material Port Size ASTM A182 F51 Full Bore
12 Connection Rating RTJ ASME 1500#
C1 13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
C 14 Packing Lubrication & Isolation Expanded Graphite VTA
15 Bonnet Bolts Bonnet Nuts UNS S31803 UNS S31803
16 Ball Material Stem Material ASTM A182 F51 ASTM A182 F51
C1 17 Leakage Rate Seat Material ISO 5028 Rate A PTFE OR NYLON
18 NACE Requirement Yes
C 19 Type Stroking Time Pneumatic Piston / Spring return 15 Seconds
C 20 Size Safety Factor VTA in 1.5
21 Actuator Orientation Actuator Form Horizontal Cylinder
22 Ingress Protection Electrical Protection IP65 Eex i
23 Instrument Air Supply 80-120 Psig
24 Action on Air Failure Action on Power Failure Closed Closed
ACTUATOR 25 Fireproofing No
26 Solenoid Valve Schematic Detail Yes Type-1
27 Limit Switch Closed Limit Swich Open Yes Yes
28 Mounting Position Solenoid Power Supply Top 24VDC
29 Manual Reset No
30 Mechanical Position Indicator Red Closed / Green Open
C 31 Partial Stroke Facility Yes
31 Signal Cable 1/2" NPT
ELECTRICAL 32 Control Cable -
CONNECTIONS 33 Solenoid Cable 3/4" NPT
34
35 Fluid
Fl id Hydrocarbon
H d b Fluid
Fl id
C 36 Phase Gas/Liquid/Vapor
37 Operating Pressure 920 psig
38 Design Pressure 3200 psig
39 Operating Temperature 153 ºF
40 Design Temperature 250 ºF
PROCESS DATA
41 Max. Diff. Pressure for Actuator Size 3200 psig
42
43 Line Size and Sch. Inlet Outlet 16 in Sch. 100 16 in Sch 100
44 Speed of Operation Design VTA
45 (Seconds) Actual VTA
46
Notes
1. VTA : Vendor to advice
2. Actuated ball valve and actuator shall be provided with 316 SS nameplate engraved or die stamped with Valve Tag No., Manufacturer's Name,
Model No., Valve Size & Rating.
3. Vendor shall be responsible for the proper design and selection of valve, actuator, and accessories based on the information furnished
C1 in this specification. This Data Sheet shall refer to SNO-I-ES-013, Instrument Specification for Shutdown and Blowdown Valve
4. Actuator shall be sized based on valve manufacturer's required Torque values with 130% minimum safety margin to open or close the valve
against full ANSI rated differential pressure at minimum pneumatic supply pressure of 60 psig.
5. Vendor shall provide Torque table containing breaking, running and seating torques for valves and actuator along with Quotation.
Vendor shall provide the torque table and calculation for COMPANY approval.
6. Actuator and accessories shall be supplied fully assembled, tubed and tested ready for installation.
7. Solenoid valve coil shall be provided with reverse polarity protection diodes, integral outlet box and terminal strip for cable connection.
8. Three way valve shall be universal type. Solenoid Coil shall be Class H.
Air filter regulator shall be 316 SS Material and equipped with pressure gauge on inlet and outlet of air filter regulator.
C1 9. All SDV & BDV shall be designed & tested as per API 6D
C1 10. Valve Stem Shall be Anti-Blowout Type.

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 13 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
1 Tag No. Quantity SDV -1103A/1203A 2 (Two)
2 Manufacturer Model VTA VTA
3 Contract No. Requisition Item No.
4 Location Central Processing Plant
GENERAL
5 P&ID No. SNO-R-PI-004 / SNO-R-PI-039
6 Service From Test Header to Test Separator Cooler
7 Line No. 8"-HF-1005-15R / 8"-HF-2005-15R
8 Area Classification Zone-2, Gr. IIB, T3
9 Valve Type Valve Code Trunnion Mounted Ball BA453
10 Body Size Body Form 8 in Ball
11 Body Material Port Size ASTM A182 F51 Full Bore
12 Connection Rating RTJ ASME 1500#
C1 13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
C 14 Packing Lubrication & Isolation Expanded Graphite VTA
15 Bonnet Bolts Bonnet Nuts UNS S31803 UNS S31803
16 Ball Material Stem Material ASTM A182 F51 ASTM A182 F51
C1 17 Leakage Rate Seat Material ISO 5028 Rate A PTFE OR NYLON
18 NACE Requirement Yes
C 19 Type Stroking Time Pneumatic Piston / Spring return 15 Seconds
20 Size Safety Factor VTA in 1.3
21 Actuator Orientation Actuator Form Horizontal Cylinder
22 Ingress Protection Electrical Protection IP65 Eex i
23 Instrument Air Supply 80-120 Psig
24 Action on Air Failure Action on Power Failure Closed Closed
ACTUATOR 25 Fireproofing No
26 Solenoid Valve Schematic Detail Yes Type-1
27 Limit Switch Closed Limit Swich Open Yes Yes
28 Mounting Position Solenoid Power Supply Top 24VDC
29 Manual Reset No
30 Mechanical Position Indicator Red Closed / Green Open
C 31 Partial Stroke Facility No
31 Signal Cable 1/2" NPT
ELECTRICAL 32 Control Cable -
CONNECTIONS 33 Solenoid Cable 3/4" NPT
34
35 Fluid
Fl id Hydrocarbon
H d b Fluid
Fl id
C 36 Phase Gas/Liquid/Vapor
37 Operating Pressure 920 psig
38 Design Pressure 3200 psig
39 Operating Temperature 153 ºF
40 Design Temperature 250 ºF
PROCESS DATA
41 Max. Diff. Pressure for Actuator Size 3200 psig
42
43 Line Size and Sch. Inlet Outlet 8 in Sch. 100 8 in Sch. 100
44 Speed of Operation Design VTA
45 (Seconds) Actual VTA
46
Notes
1. VTA : Vendor to advice
2. Actuated ball valve and actuator shall be provided with 316 SS nameplate engraved or die stamped with Valve Tag No., Manufacturer's Name,
Model No., Valve Size & Rating.
3. Vendor shall be responsible for the proper design and selection of valve, actuator, and accessories based on the information furnished
C1 in this specification. This Data Sheet shall refer to SNO-I-ES-013, Instrument Specification for Shutdown and Blowdown Valve
4. Actuator shall be sized based on valve manufacturer's required Torque values with 130% minimum safety margin to open or close the valve
against full ANSI rated differential pressure at minimum pneumatic supply pressure of 60 psig.
5. Vendor shall provide Torque table containing breaking, running and seating torques for valves and actuator along with Quotation.
Vendor shall provide the torque table and calculation for COMPANY approval.
6. Actuator and accessories shall be supplied fully assembled, tubed and tested ready for installation.
7. Solenoid valve coil shall be provided with reverse polarity protection diodes, integral outlet box and terminal strip for cable connection.
Three way valve shall be universal type. Solenoid Coil shall be Class H.
8. Air filter regulator shall be 316 SS Material and equipped with pressure gauge on inlet and outlet of air filter regulator.
C1 9. All SDV & BDV shall be designed & tested as per API 6D
C1 10. Valve Stem Shall be Anti-Blowout Type.

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 14 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
1 Tag No. Quantity SDV -1102A / 1202A 2 (Two)
2 Manufacturer Model VTA VTA
3 Contract No. Requisition Item No.
4 Location Central Processing Plant
GENERAL
5 P&ID No. SNO-R-PI-005 / SNO-R-PI-040
6 Service Production Separator Liquid Outlet To Hydro Cyclone
7 Line No. 4"-WW-1001-9N / 4"-WW-2001-9N
8 Area Classification Zone-2, Gr. IIB, T3
9 Valve Type Valve Code Trunnion Mounted Ball BA471
10 Body Size Body Form 4 in Ball
11 Body Material Port Size ASTM A351 CF8M Full Bore
12 Connection Rating RTJ ASME 900#
C1 13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
C 14 Packing Lubrication & Isolation Expanded Graphite VTA
15 Bonnet Bolts Bonnet Nuts ASTM A193 B8M CL2 ASTM A194 8M
C 16 Ball Material Stem Material 316SS 316SS
C1 17 Leakage Rate Seat Material ISO 5028 Rate A PTFE OR NYLON
18 NACE Requirement Yes
C 19 Type Stroking Time Pneumatic Piston / Spring return 8 Seconds
20 Size Safety Factor VTA in 1.3
21 Actuator Orientation Actuator Form Horizontal Cylinder
22 Ingress Protection Electrical Protection IP65 Eex i
23 Instrument Air Supply 80-120 Psig
24 Action on Air Failure Action on Power Failure Closed Closed
ACTUATOR 25 Fireproofing No
26 Solenoid Valve Schematic Detail Yes Type-1
27 Limit Switch Closed Limit Swich Open Yes Yes
28 Mounting Position Solenoid Power Supply Top 24VDC
29 Manual Reset No
30 Mechanical Position Indicator Red Closed / Green Open
C 31 Partial Stroke Facility No
31 Signal Cable 1/2" NPT
ELECTRICAL 32 Control Cable -
CONNECTIONS 33 Solenoid Cable 3/4" NPT
34
35 Fluid
Fl id Water
W t
36 Phase Liquid
37 Operating Pressure 905 psig
C 38 Design Pressure 1300 + F.V psig
39 Operating Temperature 120 ºF
40 Design Temperature 140 ºF
PROCESS DATA
41 Max. Diff. Pressure for Actuator Size 1300 psig
42
43 Line Size and Sch. Inlet Outlet 4 in Sch. 80S 4 in Sch. 80S
44 Speed of Operation Design VTA
45 (Seconds) Actual VTA
46
Notes
1. VTA : Vendor to advice
2. Actuated ball valve and actuator shall be provided with 316 SS nameplate engraved or die stamped with Valve Tag No., Manufacturer's Name,
Model No., Valve Size & Rating.
3. Vendor shall be responsible for the proper design and selection of valve, actuator, and accessories based on the information furnished
C1 in this specification. This Data Sheet shall refer to SNO-I-ES-013, Instrument Specification for Shutdown and Blowdown Valve
4. Actuator shall be sized based on valve manufacturer's required Torque values with 130% minimum safety margin to open or close the valve
against full ANSI rated differential pressure at minimum pneumatic supply pressure of 60 psig.
5. Vendor shall provide Torque table containing breaking, running and seating torques for valves and actuator along with Quotation.
Vendor shall provide the torque table and calculation for COMPANY approval.
6. Actuator and accessories shall be supplied fully assembled, tubed and tested ready for installation.
7. Solenoid valve coil shall be provided with reverse polarity protection diodes, integral outlet box and terminal strip for cable connection.
8. Three way valve shall be universal type. Solenoid Coil shall be Class H.
Air filter regulator shall be 316 SS Material and equipped with pressure gauge on inlet and outlet of air filter regulator.
C1 9. All SDV & BDV shall be designed & tested as per API 6D
C1 10. Valve Stem Shall be Anti-Blowout Type.

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 15 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
1 Tag No. Quantity SDV -1102B / 1202B 2 (Two)
2 Manufacturer Model VTA VTA
3 Contract No. Requisition Item No.
4 Location Central Processing Plant
GENERAL
5 P&ID No. SNO-R-PI-005 / SNO-R-PI-040
6 Service Production Separator Liquid Outlet To Condensate Surge Vessel
C 7 Line No. 4"-HL-1020-9N / 4"-HL-2003-9N
8 Area Classification Zone-2, Gr. IIB, T3
9 Valve Type Valve Code Trunnion Mounted Ball BA471
10 Body Size Body Form 4 in Ball
11 Body Material Port Size ASTM A351 CF8M Full Bore
12 Connection Rating RTJ ASME 900#
C1 13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
C 14 Packing Lubrication & Isolation Expanded Graphite VTA
15 Bonnet Bolts Bonnet Nuts ASTM A193 B8M CL2 ASTM A194 8M
C 16 Ball Material Stem Material 316SS 316SS
C1 17 Leakage Rate Seat Material ISO 5028 Rate A PTFE OR NYLON
18 NACE Requirement Yes
C 19 Type Stroking Time Pneumatic Piston / Spring return 8 Seconds
20 Size Safety Factor VTA in 1.3
21 Actuator Orientation Actuator Form Horizontal Cylinder
22 Ingress Protection Electrical Protection IP65 Eex i
23 Instrument Air Supply 80-120 Psig
24 Action on Air Failure Action on Power Failure Closed Closed
ACTUATOR 25 Fireproofing No
26 Solenoid Valve Schematic Detail Yes Type-1
27 Limit Switch Closed Limit Swich Open Yes Yes
28 Mounting Position Solenoid Power Supply Top 24VDC
29 Manual Reset No
30 Mechanical Position Indicator Red Closed / Green Open
C 31 Partial Stroke Facility No
31 Signal Cable 1/2" NPT
ELECTRICAL 32 Control Cable -
CONNECTIONS 33 Solenoid Cable 3/4" NPT
34
35 Fluid
Fl id Hydrocarbon
H d b Liquid
Li id
36 Phase Liquid
37 Operating Pressure 905 psig
C 38 Design Pressure 1300 + F.V psig
39 Operating Temperature 120 ºF
40 Design Temperature 140 ºF
PROCESS DATA
41 Max. Diff. Pressure for Actuator Size 1300 psig
42
43 Line Size and Sch. Inlet Outlet 4 in Sch. 80S 4 in Sch. 80S
44 Speed of Operation Design VTA
45 (Seconds) Actual VTA
46
Notes
1. VTA : Vendor to advice
2. Actuated ball valve and actuator shall be provided with 316 SS nameplate engraved or die stamped with Valve Tag No., Manufacturer's Name,
Model No., Valve Size & Rating.
3. Vendor shall be responsible for the proper design and selection of valve, actuator, and accessories based on the information furnished
C1 in this specification. This Data Sheet shall refer to SNO-I-ES-013, Instrument Specification for Shutdown and Blowdown Valve
4. Actuator shall be sized based on valve manufacturer's required Torque values with 130% minimum safety margin to open or close the valve
against full ANSI rated differential pressure at minimum pneumatic supply pressure of 60 psig.
5. Vendor shall provide Torque table containing breaking, running and seating torques for valves and actuator along with Quotation.
Vendor shall provide the torque table and calculation for COMPANY approval.
6. Actuator and accessories shall be supplied fully assembled, tubed and tested ready for installation.
7. Solenoid valve coil shall be provided with reverse polarity protection diodes, integral outlet box and terminal strip for cable connection.
8. Three way valve shall be universal type. Solenoid Coil shall be Class H.
Air filter regulator shall be 316 SS Material and equipped with pressure gauge on inlet and outlet of air filter regulator.
C1 9. All SDV & BDV shall be designed & tested as per API 6D
C1 10. Valve Stem Shall be Anti-Blowout Type.

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 16 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
1 Tag No. Quantity BDV -1102C / 1202C 2 (Two)
2 Manufacturer Model VTA VTA
3 Contract No. Requisition Item No.
4 Location Central Processing Plant
GENERAL
5 P&ID No. SNO-R-PI-005 / SNO-R-PI-040
6 Service Production Separator Gas Outlet To HP Flare Header
C1 7 Line No. 3"-HF-1105-9N / 3"-HF-2105-9N
8 Area Classification Zone-2, Gr. IIB, T3
9 Valve Type Valve Code Trunnion Mounted Ball BA471
C1 10 Body Size Body Form 3 in Ball
11 Body Material Port Size ASTM A351 CF8M Full Bore
12 Connection Rating RTJ ASME 900#
C1 13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
C 14 Packing Lubrication & Isolation Expanded Graphite VTA
15 Bonnet Bolts Bonnet Nuts ASTM A193 B8M CL2 ASTM A194 8M
C 16 Ball Material Stem Material 316SS 316SS
C1 17 Leakage Rate Seat Material ISO 5028 Rate A (TSO) PTFE OR NYLON
18 NACE Requirement Yes
C 19 Type Stroking Time Pneumatic Piston / Spring return 8 Seconds
20 Size Safety Factor VTA in 1.3
21 Actuator Orientation Actuator Form Horizontal Cylinder
22 Ingress Protection Electrical Protection IP65 Eex i
23 Instrument Air Supply 80-120 Psig
24 Action on Air Failure Action on Power Failure Open Open
ACTUATOR 25 Fireproofing No
26 Solenoid Valve Schematic Detail Yes Type-2
27 Limit Switch Closed Limit Swich Open Yes Yes
28 Mounting Position Solenoid Power Supply Top 24VDC
29 Manual Reset No
30 Mechanical Position Indicator Red Closed / Green Open
C 31 Partial Stroke Facility No
31 Signal Cable 1/2" NPT
ELECTRICAL 32 Control Cable -
CONNECTIONS 33 Solenoid Cable 3/4" NPT
34
35 Fluid
Fl id Hydrocarbon
H d b Gas
G
36 Phase Gas/Vapour
37 Operating Pressure 905 psig
38 Design Pressure 1300 + F.V. psig
39 Operating Temperature 120 ºF
40 Design Temperature 140 ºF
PROCESS DATA
41 Max. Diff. Pressure for Actuator Size 1300 psig
42
C1 43 Line Size and Sch. Inlet Outlet 3 in Sch. 80S 3 in Sch. 80S
44 Speed of Operation Design VTA
45 (Seconds) Actual VTA
46
Notes
1. VTA : Vendor to advice
2. Actuated ball valve and actuator shall be provided with 316 SS nameplate engraved or die stamped with Valve Tag No., Manufacturer's Name,
Model No., Valve Size & Rating.
3. Vendor shall be responsible for the proper design and selection of valve, actuator, and accessories based on the information furnished
C1 in this specification. This Data Sheet shall refer to SNO-I-ES-013, Instrument Specification for Shutdown and Blowdown Valve
4. Actuator shall be sized based on valve manufacturer's required Torque values with 130% minimum safety margin to open or close the valve
against full ANSI rated differential pressure at minimum pneumatic supply pressure of 60 psig.
5. Vendor shall provide Torque table containing breaking, running and seating torques for valves and actuator along with Quotation.
Vendor shall provide the torque table and calculation for COMPANY approval.
6. Actuator and accessories shall be supplied fully assembled, tubed and tested ready for installation.
7. Solenoid valve coil shall be provided with reverse polarity protection diodes, integral outlet box and terminal strip for cable connection.
8. Three way valve shall be universal type. Solenoid Coil shall be Class H.
Air filter regulator shall be 316 SS Material and equipped with pressure gauge on inlet and outlet of air filter regulator.
C1 9. All SDV & BDV shall be designed & tested as per API 6D
C1 10. Valve Stem Shall be Anti-Blowout Type.

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 17 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
1 Tag No. Quantity SDV -1104A / 1204A 2 (Two)
2 Manufacturer Model VTA VTA
3 Contract No. Requisition Item No.
4 Location Central Processing Plant
GENERAL
5 P&ID No. SNO-R-PI-006 / SNO-R-PI-041
6 Service Test Separator Gas Outlet To Degassing Coloumn
C 7 Line No. 3"-WW-1001-9N / 3"-WW-2041-9N
8 Area Classification Zone-2, Gr. IIB, T3
9 Valve Type Valve Code Trunnion Mounted Ball BA471
10 Body Size Body Form 3 in Ball
11 Body Material Port Size ASTM A351 CF8M Full Bore
12 Connection Rating RTJ ASME 900#
C1 13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
C 14 Packing Lubrication & Isolation Expanded Graphite VTA
15 Bonnet Bolts Bonnet Nuts ASTM A193 B8M CL2 ASTM A194 8M
C 16 Ball Material Stem Material 316SS 316SS
C1 17 Leakage Rate Seat Material ISO 5028 Rate A PTFE OR NYLON
18 NACE Requirement Yes
C 19 Type Stroking Time Pneumatic Piston / Spring return 6 Seconds
20 Size Safety Factor VTA in 1.3
21 Actuator Orientation Actuator Form Horizontal Cylinder
22 Ingress Protection Electrical Protection IP65 Eex i
23 Instrument Air Supply 80-120 Psig
24 Action on Air Failure Action on Power Failure Closed Closed
ACTUATOR 25 Fireproofing No
26 Solenoid Valve Schematic Detail Yes Type-1
27 Limit Switch Closed Limit Swich Open Yes Yes
28 Mounting Position Solenoid Power Supply Top 24VDC
29 Manual Reset No
30 Mechanical Position Indicator Red Closed / Green Open
C 31 Partial Stroke Facility No
31 Signal Cable 1/2" NPT
ELECTRICAL 32 Control Cable -
CONNECTIONS 33 Solenoid Cable 3/4" NPT
34
35 Fluid
Fl id Water
W t
36 Phase Liquid
37 Operating Pressure 905 psig
C 38 Design Pressure 1300 + F.V. psig
39 Operating Temperature 120 ºF
40 Design Temperature 140 ºF
PROCESS DATA
41 Max. Diff. Pressure for Actuator Size 1300 psig
42
43 Line Size and Sch. Inlet Outlet 3 in Sch. 80S 3 in Sch. 80S
44 Speed of Operation Design VTA
45 (Seconds) Actual VTA
46
Notes
1. VTA : Vendor to advice
2. Actuated ball valve and actuator shall be provided with 316 SS nameplate engraved or die stamped with Valve Tag No., Manufacturer's Name,
Model No., Valve Size & Rating.
3. Vendor shall be responsible for the proper design and selection of valve, actuator, and accessories based on the information furnished
C1 in this specification. This Data Sheet shall refer to SNO-I-ES-013, Instrument Specification for Shutdown and Blowdown Valve
4. Actuator shall be sized based on valve manufacturer's required Torque values with 130% minimum safety margin to open or close the valve
against full ANSI rated differential pressure at minimum pneumatic supply pressure of 60 psig.
5. Vendor shall provide Torque table containing breaking, running and seating torques for valves and actuator along with Quotation.
Vendor shall provide the torque table and calculation for COMPANY approval.
6. Actuator and accessories shall be supplied fully assembled, tubed and tested ready for installation.
7. Solenoid valve coil shall be provided with reverse polarity protection diodes, integral outlet box and terminal strip for cable connection.
8. Three way valve shall be universal type. Solenoid Coil shall be Class H.
Air filter regulator shall be 316 SS Material and equipped with pressure gauge on inlet and outlet of air filter regulator.
C1 9. All SDV & BDV shall be designed & tested as per API 6D
C1 10. Valve Stem Shall be Anti-Blowout Type.

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 18 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
1 Tag No. Quantity SDV -1104B / 1204B 2 (Two)
2 Manufacturer Model VTA VTA
3 Contract No. Requisition Item No.
4 Location Central Processing Plant
GENERAL
5 P&ID No. SNO-R-PI-006 / SNO-R-PI-041
6 Service Test Separator Gas Outlet To Condensate Surge Vessel
C 7 Line No. 3"-HL-1050-9N / 3"-HL-xxxx-9N
8 Area Classification Zone-2, Gr. IIB, T3
9 Valve Type Valve Code Trunnion Mounted Ball BA471
10 Body Size Body Form 3 in Ball
11 Body Material Port Size ASTM A351 CF8M Full Bore
12 Connection Rating RTJ ASME 900#
C1 13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
C 14 Packing Lubrication & Isolation Expanded Graphite VTA
15 Bonnet Bolts Bonnet Nuts ASTM A193 B8M CL2 ASTM A194 8M
C 16 Ball Material Stem Material 316SS 316SS
C1 17 Leakage Rate Seat Material ISO 5028 Rate A PTFE OR NYLON
18 NACE Requirement Yes
C 19 Type Stroking Time Pneumatic Piston / Spring return 6 Seconds
20 Size Safety Factor VTA in 1.3
21 Actuator Orientation Actuator Form Horizontal Cylinder
22 Ingress Protection Electrical Protection IP65 Eex i
23 Instrument Air Supply 80-120 Psig
24 Action on Air Failure Action on Power Failure Closed Closed
ACTUATOR 25 Fireproofing No
26 Solenoid Valve Schematic Detail Yes Type-1
27 Limit Switch Closed Limit Swich Open Yes Yes
28 Mounting Position Solenoid Power Supply Top 24VDC
29 Manual Reset No
30 Mechanical Position Indicator Red Closed / Green Open
C 31 Partial Stroke Facility No
31 Signal Cable 1/2" NPT
ELECTRICAL 32 Control Cable -
CONNECTIONS 33 Solenoid Cable 3/4" NPT
34
35 Fluid
Fl id Hydrocarbon
H d b Liquid
Li id
36 Phase Liquid
37 Operating Pressure 905 psig
C 38 Design Pressure 1300 + F.V. psig
39 Operating Temperature 120 ºF
40 Design Temperature 140 ºF
PROCESS DATA
41 Max. Diff. Pressure for Actuator Size 1300 psig
42
43 Line Size and Sch. Inlet Outlet 3 in Sch. 80S 3 in Sch. 80S
44 Speed of Operation Design VTA
45 (Seconds) Actual VTA
46
Notes
1. VTA : Vendor to advice
2. Actuated ball valve and actuator shall be provided with 316 SS nameplate engraved or die stamped with Valve Tag No., Manufacturer's Name,
Model No., Valve Size & Rating.
3. Vendor shall be responsible for the proper design and selection of valve, actuator, and accessories based on the information furnished
C1 in this specification. This Data Sheet shall refer to SNO-I-ES-013, Instrument Specification for Shutdown and Blowdown Valve
4. Actuator shall be sized based on valve manufacturer's required Torque values with 130% minimum safety margin to open or close the valve
against full ANSI rated differential pressure at minimum pneumatic supply pressure of 60 psig.
5. Vendor shall provide Torque table containing breaking, running and seating torques for valves and actuator along with Quotation.
Vendor shall provide the torque table and calculation for COMPANY approval.
6. Actuator and accessories shall be supplied fully assembled, tubed and tested ready for installation.
7. Solenoid valve coil shall be provided with reverse polarity protection diodes, integral outlet box and terminal strip for cable connection.
8. Three way valve shall be universal type. Solenoid Coil shall be Class H.
Air filter regulator shall be 316 SS Material and equipped with pressure gauge on inlet and outlet of air filter regulator.
C1 9. All SDV & BDV shall be designed & tested as per API 6D
C1 10. Valve Stem Shall be Anti-Blowout Type.

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 19 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
1 Tag No. Quantity SDV -1104C / 1204C 2 (Two)
2 Manufacturer Model VTA VTA
3 Contract No. Requisition Item No.
4 Location Central Processing Plant
GENERAL
5 P&ID No. SNO-R-PI-006 / SNO-R-PI-041
6 Service Production Separator Gas Outlet To Condensate Surge Vessel
7 Line No. 10"-HG-1006-9N / 10"-HG-2006-9N
8 Area Classification Zone-2, Gr. IIB, T3
9 Valve Type Valve Code Trunnion Mounted Ball BA472
10 Body Size Body Form 10 in Ball
11 Body Material Port Size ASTM A351 CF8M Full Bore
12 Connection Rating RTJ ASME 900#
C1 13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
C 14 Packing Lubrication & Isolation Expanded Graphite VTA
15 Bonnet Bolts Bonnet Nuts ASTM A193 B8M CL2 ASTM A194 8M
C 16 Ball Material Stem Material 316SS 316SS
C1 17 Leakage Rate Seat Material ISO 5028 Rate A PTFE OR NYLON
18 NACE Requirement Yes
C 19 Type Stroking Time Pneumatic Piston / Spring return 15 Seconds
20 Size Safety Factor VTA in 1.3
21 Actuator Orientation Actuator Form Horizontal Cylinder
22 Ingress Protection Electrical Protection IP65 Eex i
23 Instrument Air Supply 80-120 Psig
24 Action on Air Failure Action on Power Failure Closed Closed
ACTUATOR 25 Fireproofing No
26 Solenoid Valve Schematic Detail Yes Type-1
27 Limit Switch Closed Limit Swich Open Yes Yes
28 Mounting Position Solenoid Power Supply Top 24VDC
29 Manual Reset No
30 Mechanical Position Indicator Red Closed / Green Open
C 31 Partial Stroke Facility No
31 Signal Cable 1/2" NPT
ELECTRICAL 32 Control Cable -
CONNECTIONS 33 Solenoid Cable 3/4" NPT
34
35 Fluid
Fl id Hydrocarbon
H d b Gas
G
36 Phase Gas/Vapour
37 Operating Pressure 905 psig
C 38 Design Pressure 1300 + F.V. psig
39 Operating Temperature 120 ºF
40 Design Temperature 140 ºF
PROCESS DATA
41 Max. Diff. Pressure for Actuator Size 1300 psig
42
43 Line Size and Sch. Inlet Outlet 10 in Sch. 100 10 in Sch. 100
44 Speed of Operation Design VTA
45 (Seconds) Actual VTA
46
Notes
1. VTA : Vendor to advice
2. Actuated ball valve and actuator shall be provided with 316 SS nameplate engraved or die stamped with Valve Tag No., Manufacturer's Name,
Model No., Valve Size & Rating.
3. Vendor shall be responsible for the proper design and selection of valve, actuator, and accessories based on the information furnished
C1 in this specification. This Data Sheet shall refer to SNO-I-ES-013, Instrument Specification for Shutdown and Blowdown Valve
4. Actuator shall be sized based on valve manufacturer's required Torque values with 130% minimum safety margin to open or close the valve
against full ANSI rated differential pressure at minimum pneumatic supply pressure of 60 psig.
5. Vendor shall provide Torque table containing breaking, running and seating torques for valves and actuator along with Quotation.
Vendor shall provide the torque table and calculation for COMPANY approval.
6. Actuator and accessories shall be supplied fully assembled, tubed and tested ready for installation.
7. Solenoid valve coil shall be provided with reverse polarity protection diodes, integral outlet box and terminal strip for cable connection.
8. Three way valve shall be universal type. Solenoid Coil shall be Class H.
Air filter regulator shall be 316 SS Material and equipped with pressure gauge on inlet and outlet of air filter regulator.
C1 9. All SDV & BDV shall be designed & tested as per API 6D
C1 10. Valve Stem Shall be Anti-Blowout Type.

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 20 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
1 Tag No. Quantity BDV -1104D / 1204D 2 (Two)
2 Manufacturer Model VTA VTA
3 Contract No. Requisition Item No.
4 Location Central Processing Plant
GENERAL
5 P&ID No. SNO-R-PI-006 / SNO-R-PI-041
6 Service Production Separator Gas Outlet To HP Flare Header
C1 7 Line No. 2"-HG-1007-9N / 2"-HG-2007-9N
8 Area Classification Zone-2, Gr. IIB, T3
9 Valve Type Valve Code Trunnion Mounted Ball BA472
C1 10 Body Size Body Form 2 in Ball
C1 11 Body Material Port Size ASTM A182 F316L Full Bore
C 12 Connection Rating RTJ ASME 1500#
C1 13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
C 14 Packing Lubrication & Isolation Expanded Graphite VTA
15 Bonnet Bolts Bonnet Nuts ASTM A193 B8M CL2 ASTM A194 8M
C 16 Ball Material Stem Material 316 SS 316 SS
C1 17 Leakage Rate Seat Material ISO 5028 Rate A (TSO) PTFE OR NYLON
18 NACE Requirement Yes
C1 19 Type Stroking Time Pneumatic Piston / Spring return 4 Seconds
20 Size Safety Factor VTA in 1.3
21 Actuator Orientation Actuator Form Horizontal Cylinder
22 Ingress Protection Electrical Protection IP65 Eex i
23 Instrument Air Supply 80-120 Psig
24 Action on Air Failure Action on Power Failure Open Open
ACTUATOR 25 Fireproofing No
26 Solenoid Valve Schematic Detail Yes Type-2
27 Limit Switch Closed Limit Swich Open Yes Yes
28 Mounting Position Solenoid Power Supply Top 24VDC
29 Manual Reset No
30 Mechanical Position Indicator Red Closed / Green Open
C 31 Partial Stroke Facility No
31 Signal Cable 1/2" NPT
ELECTRICAL 32 Control Cable -
CONNECTIONS 33 Solenoid Cable 3/4" NPT
34
35 Fluid
Fl id Hydrocarbon
H d b Gas
G
36 Phase Gas/Vapour
37 Operating Pressure 905 psig
C 38 Design Pressure 1300 + F.V. psig
39 Operating Temperature 120 ºF
40 Design Temperature 140 ºF
PROCESS DATA
41 Max. Diff. Pressure for Actuator Size 1300 psig
42
C1 43 Line Size and Sch. Inlet Outlet 2 in Sch. 80S 2 in Sch. 80S
44 Speed of Operation Design VTA
45 (Seconds) Actual VTA
46
Notes
1. VTA : Vendor to advice
2. Actuated ball valve and actuator shall be provided with 316 SS nameplate engraved or die stamped with Valve Tag No., Manufacturer's Name,
Model No., Valve Size & Rating.
3. Vendor shall be responsible for the proper design and selection of valve, actuator, and accessories based on the information furnished
C1 in this specification. This Data Sheet shall refer to SNO-I-ES-013, Instrument Specification for Shutdown and Blowdown Valve
4. Actuator shall be sized based on valve manufacturer's required Torque values with 130% minimum safety margin to open or close the valve
against full ANSI rated differential pressure at minimum pneumatic supply pressure of 60 psig.
5. Vendor shall provide Torque table containing breaking, running and seating torques for valves and actuator along with Quotation.
Vendor shall provide the torque table and calculation for COMPANY approval.
6. Actuator and accessories shall be supplied fully assembled, tubed and tested ready for installation.
7. Solenoid valve coil shall be provided with reverse polarity protection diodes, integral outlet box and terminal strip for cable connection.
8. Three way valve shall be universal type. Solenoid Coil shall be Class H.
Air filter regulator shall be 316 SS Material and equipped with pressure gauge on inlet and outlet of air filter regulator.
C1 9. All SDV & BDV shall be designed & tested as per API 6D
C1 10. Valve Stem Shall be Anti-Blowout Type.

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 21 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
1 Tag No. Quantity SDV -1105A / 1205A 2 (Two)
2 Manufacturer Model VTA VTA
3 Contract No. Requisition Item No.
4 Location Central Processing Plant
GENERAL
5 P&ID No. SNO-R-PI-007 / SNO-R-PI-042
6 Service Production Filter Coalescer To Closed Drain Header
7 Line No. 2"-DC-1107-9N / 2"-DC-2107-9N
8 Area Classification Zone-2, Gr. IIB, T3
C1 9 Valve Type Valve Code Trunnion Mounted Ball BA466
10 Body Size Body Form 2 in Ball
11 Body Material Port Size ASTM A182 F316L Full Bore
C 12 Connection Rating RTJ ASME 1500#
C1 13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
C 14 Packing Lubrication & Isolation Expanded Graphite VTA
15 Bonnet Bolts Bonnet Nuts ASTM A193 B8M CL2 ASTM A194 8M
C 16 Ball Material Stem Material 316SS 316SS
C1 17 Leakage Rate Seat Material ISO 5028 Rate A (TSO) PTFE OR NYLON
18 NACE Requirement Yes
C 19 Type Stroking Time Pneumatic Piston / Spring return 4 Seconds
20 Size Safety Factor VTA in 1.3
21 Actuator Orientation Actuator Form Horizontal Cylinder
22 Ingress Protection Electrical Protection IP65 Eex i
23 Instrument Air Supply 80-120 Psig
24 Action on Air Failure Action on Power Failure Closed Closed
ACTUATOR 25 Fireproofing No
26 Solenoid Valve Schematic Detail Yes Type-1
27 Limit Switch Closed Limit Swich Open Yes Yes
28 Mounting Position Solenoid Power Supply Top 24VDC
29 Manual Reset No
30 Mechanical Position Indicator Red Closed / Green Open
C 31 Partial Stroke Facility No
31 Signal Cable 1/2" NPT
ELECTRICAL 32 Control Cable -
CONNECTIONS 33 Solenoid Cable 3/4" NPT
34
35 Fluid
Fl id Hydrocarbon
H d b
36 Phase Liquid
C 37 Operating Pressure 905 psig
38 Design Pressure 1300 psig
39 Operating Temperature 120 ºF
C 40 Design Temperature -20 / 150 ºF
PROCESS DATA
41 Max. Diff. Pressure for Actuator Size 1300 psig
42
43 Line Size and Sch. Inlet Outlet 2 in Sch. 80S 2 in Sch. 80S
44 Speed of Operation Design VTA
45 (Seconds) Actual VTA
46
Notes
1. VTA : Vendor to advice
2. Actuated ball valve and actuator shall be provided with 316 SS nameplate engraved or die stamped with Valve Tag No., Manufacturer's Name,
Model No., Valve Size & Rating.
3. Vendor shall be responsible for the proper design and selection of valve, actuator, and accessories based on the information furnished
C1 in this specification. This Data Sheet shall refer to SNO-I-ES-013, Instrument Specification for Shutdown and Blowdown Valve
4. Actuator shall be sized based on valve manufacturer's required Torque values with 130% minimum safety margin to open or close the valve
against full ANSI rated differential pressure at minimum pneumatic supply pressure of 60 psig.
5. Vendor shall provide Torque table containing breaking, running and seating torques for valves and actuator along with Quotation.
Vendor shall provide the torque table and calculation for COMPANY approval.
6. Actuator and accessories shall be supplied fully assembled, tubed and tested ready for installation.
7. Solenoid valve coil shall be provided with reverse polarity protection diodes, integral outlet box and terminal strip for cable connection.
8. Three way valve shall be universal type. Solenoid Coil shall be Class H.
Air filter regulator shall be 316 SS Material and equipped with pressure gauge on inlet and outlet of air filter regulator.
C1 9. All SDV & BDV shall be designed & tested as per API 6D
C1 10. Valve Stem Shall be Anti-Blowout Type.

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 22 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
1 Tag No. Quantity SDV -1105B / 1205B 2 (Two)
2 Manufacturer Model VTA VTA
3 Contract No. Requisition Item No.
4 Location Central Processing Plant
GENERAL
5 P&ID No. SNO-R-PI-007 / SNO-R-PI-042
6 Service Production Filter Coalescer To Amine Absorber
7 Line No. 12"-HG-1050-9N / 12"-HG-2050-9N
8 Area Classification Zone-2, Gr. IIB, T3
9 Valve Type Valve Code Trunnion Mounted Ball BA472
10 Body Size Body Form 12 in Ball
11 Body Material Port Size ASTM A351 CF8M Full Bore
12 Connection Rating RTJ ASME 900#
C1 13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
C 14 Packing Lubrication & Isolation Expanded Graphite VTA
15 Bonnet Bolts Bonnet Nuts ASTM A193 B8M CL2 ASTM A194 8M
C 16 Ball Material Stem Material 316 SS 316 SS
C1 17 Leakage Rate Seat Material ISO 5028 Rate A PTFE OR NYLON
18 NACE Requirement Yes
C 19 Type Stroking Time Pneumatic Piston / Spring return 15 Seconds
C 20 Size Safety Factor VTA in 1.5
21 Actuator Orientation Actuator Form Horizontal Cylinder
22 Ingress Protection Electrical Protection IP65 Eex i
23 Instrument Air Supply 80-120 Psig
24 Action on Air Failure Action on Power Failure Closed Closed
ACTUATOR 25 Fireproofing No
26 Solenoid Valve Schematic Detail Yes Type-1
27 Limit Switch Closed Limit Swich Open Yes Yes
28 Mounting Position Solenoid Power Supply Top 24VDC
29 Manual Reset No
30 Mechanical Position Indicator Red Closed / Green Open
C 31 Partial Stroke Facility Yes
31 Signal Cable 1/2" NPT
ELECTRICAL 32 Control Cable -
CONNECTIONS 33 Solenoid Cable 3/4" NPT
34
35 Fluid
Fl id Hydrocarbon
H d b GasG
36 Phase Gas/Vapour
C 37 Operating Pressure 905 psig
38 Design Pressure 1300 psig
39 Operating Temperature 120 ºF
C 40 Design Temperature -20 / 150 ºF
PROCESS DATA
41 Max. Diff. Pressure for Actuator Size 1300 psig
42
43 Line Size and Sch. Inlet Outlet 12 in Sch. 100 12 in Sch. 100
44 Speed of Operation Design VTA
45 (Seconds) Actual VTA
46
Notes
1. VTA : Vendor to advice
2. Actuated ball valve and actuator shall be provided with 316 SS nameplate engraved or die stamped with Valve Tag No., Manufacturer's Name,
Model No., Valve Size & Rating.
3. Vendor shall be responsible for the proper design and selection of valve, actuator, and accessories based on the information furnished
C1 in this specification. This Data Sheet shall refer to SNO-I-ES-013, Instrument Specification for Shutdown and Blowdown Valve
4. Actuator shall be sized based on valve manufacturer's required Torque values with 130% minimum safety margin to open or close the valve
against full ANSI rated differential pressure at minimum pneumatic supply pressure of 60 psig.
5. Vendor shall provide Torque table containing breaking, running and seating torques for valves and actuator along with Quotation.
Vendor shall provide the torque table and calculation for COMPANY approval.
6. Actuator and accessories shall be supplied fully assembled, tubed and tested ready for installation.
7. Solenoid valve coil shall be provided with reverse polarity protection diodes, integral outlet box and terminal strip for cable connection.
8. Three way valve shall be universal type. Solenoid Coil shall be Class H.
Air filter regulator shall be 316 SS Material and equipped with pressure gauge on inlet and outlet of air filter regulator.
C1 9. All SDV & BDV shall be designed & tested as per API 6D
C1 10. Valve Stem Shall be Anti-Blowout Type.

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 23 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
1 Tag No. Quantity BDV -1105C / 1205C 2 (Two)
2 Manufacturer Model VTA VTA
3 Contract No. Requisition Item No.
4 Location Central Processing Plant
GENERAL
5 P&ID No. SNO-R-PI-007 / SNO-R-PI-042
6 Service Production Filter Coalescer To HP Flare Header
C1 7 Line No. 2"-HG-1004-9N / 2"-HG-2004-9N
8 Area Classification Zone-2, Gr. IIB, T3
9 Valve Type Valve Code Trunnion Mounted Ball BA471
C1 10 Body Size Body Form 2 in Ball
C1 11 Body Material Port Size ASTM A182 F316L Full Bore
12 Connection Rating RTJ ASME 1500#
C1 13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
C 14 Packing Lubrication & Isolation Expanded Graphite VTA
15 Bonnet Bolts Bonnet Nuts ASTM A193 B8M CL2 ASTM A194 8M
C 16 Ball Material Stem Material 316 SS 316 SS
C1 17 Leakage Rate Seat Material ISO 5028 Rate A (TSO) PTFE OR NYLON
18 NACE Requirement Yes
C1 19 Type Stroking Time Pneumatic Piston / Spring return 4 Seconds
20 Size Safety Factor VTA in 1.3
21 Actuator Orientation Actuator Form Horizontal Cylinder
22 Ingress Protection Electrical Protection IP65 Eex i
23 Instrument Air Supply 80-120 Psig
24 Action on Air Failure Action on Power Failure Open Open
ACTUATOR 25 Fireproofing No
26 Solenoid Valve Schematic Detail Yes Type-2
27 Limit Switch Closed Limit Swich Open Yes Yes
28 Mounting Position Solenoid Power Supply Top 24VDC
29 Manual Reset No
30 Mechanical Position Indicator Red Closed / Green Open
C 31 Partial Stroke Facility No
31 Signal Cable 1/2" NPT
ELECTRICAL 32 Control Cable -
CONNECTIONS 33 Solenoid Cable 3/4" NPT
34
35 Fluid
Fl id Hydrocarbon
H d b Gas
G
36 Phase Gas/Vapour
C 37 Operating Pressure 905 psig
38 Design Pressure 1300 psig
39 Operating Temperature 120 ºF
C 40 Design Temperature -20 / 150 ºF
PROCESS DATA
41 Max. Diff. Pressure for Actuator Size 1300 psig
42
C1 43 Line Size and Sch. Inlet Outlet 2 in Sch. 80S 2 in Sch. 80S
44 Speed of Operation Design VTA
45 (Seconds) Actual VTA
46
Notes
1. VTA : Vendor to advice
2. Actuated ball valve and actuator shall be provided with 316 SS nameplate engraved or die stamped with Valve Tag No., Manufacturer's Name,
Model No., Valve Size & Rating.
3. Vendor shall be responsible for the proper design and selection of valve, actuator, and accessories based on the information furnished
C1 in this specification. This Data Sheet shall refer to SNO-I-ES-013, Instrument Specification for Shutdown and Blowdown Valve
4. Actuator shall be sized based on valve manufacturer's required Torque values with 130% minimum safety margin to open or close the valve
against full ANSI rated differential pressure at minimum pneumatic supply pressure of 60 psig.
5. Vendor shall provide Torque table containing breaking, running and seating torques for valves and actuator along with Quotation.
Vendor shall provide the torque table and calculation for COMPANY approval.
6. Actuator and accessories shall be supplied fully assembled, tubed and tested ready for installation.
7. Solenoid valve coil shall be provided with reverse polarity protection diodes, integral outlet box and terminal strip for cable connection.
Three way valve shall be universal type. Solenoid Coil shall be Class H.
8. Air filter regulator shall be 316 SS Material and equipped with pressure gauge on inlet and outlet of air filter regulator.
C1 9. All SDV & BDV shall be designed & tested as per API 6D
C1 10. Valve Stem Shall be Anti-Blowout Type.

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 24 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
1 Tag No. Quantity SDV -6101 / 6201 2 (Two)
2 Manufacturer Model VTA VTA
3 Contract No. Requisition Item No.
4 Location Central Processing Plant
GENERAL
5 P&ID No. SNO-R-PI-008 / SNO-R-PI-043
6 Service Condensate Surge Vessel To Condensate Coalescer
7 Line No. 4"-HL-1301-1N / 4"-HL-2301-1N
8 Area Classification Zone-2, Gr. IIB, T3
C1 9 Valve Type Valve Code Trunnion Mounted Ball BA098
10 Body Size Body Form 4 in Ball
11 Body Material Port Size ASTM A351 CF8M Full Bore
12 Connection Rating RF Flange ASME 150#
C1 13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
C 14 Packing Lubrication & Isolation Expanded Graphite VTA
15 Bonnet Bolts Bonnet Nuts ASTM A193 B8M CL2 ASTM A194 8M
C 16 Ball Material Stem Material 316 SS 316 SS
C1 17 Leakage Rate Seat Material ISO 5028 Rate A PTFE
18 NACE Requirement Yes
C 19 Type Stroking Time Pneumatic Piston / Spring return 8 Seconds
20 Size Safety Factor VTA in 1.3
21 Actuator Orientation Actuator Form Horizontal Cylinder
22 Ingress Protection Electrical Protection IP65 Eex i
23 Instrument Air Supply 80-120 Psig
24 Action on Air Failure Action on Power Failure Closed Closed
ACTUATOR 25 Fireproofing No
26 Solenoid Valve Schematic Detail Yes Type-1
27 Limit Switch Closed Limit Swich Open Yes Yes
28 Mounting Position Solenoid Power Supply Top 24VDC
29 Manual Reset No
30 Mechanical Position Indicator Red Closed / Green Open
C 31 Partial Stroke Facility No
31 Signal Cable 1/2" NPT
ELECTRICAL 32 Control Cable -
CONNECTIONS 33 Solenoid Cable 3/4" NPT
34
35 Fluid
Fl id Hydrocarbon
H d b
36 Phase Liquid
37 Operating Pressure 155 psig
38 Design Pressure 210 psig
39 Operating Temperature 102 ºF
40 Design Temperature 140 ºF
PROCESS DATA
41 Max. Diff. Pressure for Actuator Size 210 psig
42
43 Line Size and Sch. Inlet Outlet 4 in Sch. 10S 4 in Sch. 10S
44 Speed of Operation Design VTA
45 (Seconds) Actual VTA
46
Notes
1. VTA : Vendor to advice
2. Actuated ball valve and actuator shall be provided with 316 SS nameplate engraved or die stamped with Valve Tag No., Manufacturer's Name,
Model No., Valve Size & Rating.
3. Vendor shall be responsible for the proper design and selection of valve, actuator, and accessories based on the information furnished
C1 in this specification. This Data Sheet shall refer to SNO-I-ES-013, Instrument Specification for Shutdown and Blowdown Valve
4. Actuator shall be sized based on valve manufacturer's required Torque values with 130% minimum safety margin to open or close the valve
against full ANSI rated differential pressure at minimum pneumatic supply pressure of 60 psig.
5. Vendor shall provide Torque table containing breaking, running and seating torques for valves and actuator along with Quotation.
Vendor shall provide the torque table and calculation for COMPANY approval.
6. Actuator and accessories shall be supplied fully assembled, tubed and tested ready for installation.
7. Solenoid valve coil shall be provided with reverse polarity protection diodes, integral outlet box and terminal strip for cable connection.
8. Three way valve shall be universal type. Solenoid Coil shall be Class H.
Air filter regulator shall be 316 SS Material and equipped with pressure gauge on inlet and outlet of air filter regulator.
C1 9. All SDV & BDV shall be designed & tested as per API 6D
C1 10. Valve Stem Shall be Anti-Blowout Type.

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 25 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
1 Tag No. Quantity SDV -6101A / 6201A 2 (Two)
2 Manufacturer Model VTA VTA
3 Contract No. Requisition Item No.
4 Location Central Processing Plant
GENERAL
5 P&ID No. SNO-R-PI-008 / SNO-R-PI-043
6 Service Condensate Surge Vessel To Degassing Coloumn
C 7 Line No. 2"-WW-1085-1N / 2"-WW-2085-1N
8 Area Classification Zone-2, Gr. IIB, T3
C1 9 Valve Type Valve Code Trunnion Mounted Ball BA098
10 Body Size Body Form 2 in Ball
11 Body Material Port Size ASTM A351 CF8M Full Bore
C 12 Connection Rating RF Flange ASME 150#
C1 13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
C 14 Packing Lubrication & Isolation Expanded Graphite VTA
15 Bonnet Bolts Bonnet Nuts ASTM A193 B8M CL2 ASTM A194 8M
C 16 Ball Material Stem Material 316 SS 316 SS
C1 17 Leakage Rate Seat Material ISO 5028 Rate A PTFE OR NYLON
18 NACE Requirement Yes
C 19 Type Stroking Time Pneumatic Piston / Spring return 4 Seconds
20 Size Safety Factor VTA in 1.3
21 Actuator Orientation Actuator Form Horizontal Cylinder
22 Ingress Protection Electrical Protection IP65 Eex i
23 Instrument Air Supply 80-120 Psig
24 Action on Air Failure Action on Power Failure Closed Closed
ACTUATOR 25 Fireproofing No
26 Solenoid Valve Schematic Detail Yes Type-1
27 Limit Switch Closed Limit Swich Open Yes Yes
28 Mounting Position Solenoid Power Supply Top 24VDC
29 Manual Reset No
30 Mechanical Position Indicator Red Closed / Green Open
C 31 Partial Stroke Facility No
31 Signal Cable 1/2" NPT
ELECTRICAL 32 Control Cable -
CONNECTIONS 33 Solenoid Cable 3/4" NPT
34
35 Fluid
Fl id Water
W t
36 Phase Liquid
37 Operating Pressure 155 psig
38 Design Pressure 210 psig
39 Operating Temperature 102 ºF
40 Design Temperature 140 ºF
PROCESS DATA
41 Max. Diff. Pressure for Actuator Size 210 psig
42
43 Line Size and Sch. Inlet Outlet 2 in Sch. 10S 2 in Sch. 10S
44 Speed of Operation Design VTA
45 (Seconds) Actual VTA
46
Notes
1. VTA : Vendor to advice
2. Actuated ball valve and actuator shall be provided with 316 SS nameplate engraved or die stamped with Valve Tag No., Manufacturer's Name,
Model No., Valve Size & Rating.
3. Vendor shall be responsible for the proper design and selection of valve, actuator, and accessories based on the information furnished
C1 in this specification. This Data Sheet shall refer to SNO-I-ES-013, Instrument Specification for Shutdown and Blowdown Valve
4. Actuator shall be sized based on valve manufacturer's required Torque values with 130% minimum safety margin to open or close the valve
against full ANSI rated differential pressure at minimum pneumatic supply pressure of 60 psig.
5. Vendor shall provide Torque table containing breaking, running and seating torques for valves and actuator along with Quotation.
Vendor shall provide the torque table and calculation for COMPANY approval.
6. Actuator and accessories shall be supplied fully assembled, tubed and tested ready for installation.
7. Solenoid valve coil shall be provided with reverse polarity protection diodes, integral outlet box and terminal strip for cable connection.
8. Three way valve shall be universal type. Solenoid Coil shall be Class H.
Air filter regulator shall be 316 SS Material and equipped with pressure gauge on inlet and outlet of air filter regulator.
C1 9. All SDV & BDV shall be designed & tested as per API 6D
C1 10. Valve Stem Shall be Anti-Blowout Type.

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 26 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
1 Tag No. Quantity BDV -6101B/ 6201B 2 (Two)
2 Manufacturer Model VTA VTA
3 Contract No. Requisition Item No.
4 Location Central Processing Plant
GENERAL
5 P&ID No. SNO-R-PI-008 / SNO-R-PI-043
6 Service From Condensate Surge Vessel Gas Outlet To HP Flare Header
C1 7 Line No. 2"-HG-1010-1N / 2"-HG-2010-1N
8 Area Classification Zone-2, Gr. IIB, T3
C1 9 Valve Type Valve Code Trunnion Mounted Ball BA098
C1 10 Body Size Body Form 2 in Ball
11 Body Material Port Size ASTM A351 CF8M Full Bore
12 Connection Rating RF Flange ASME 150#
C1 13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
C 14 Packing Lubrication & Isolation Expanded Graphite VTA
15 Bonnet Bolts Bonnet Nuts ASTM A193 B8M CL2 ASTM A194 8M
C 16 Ball Material Stem Material 316 SS 316 SS
C1 17 Leakage Rate Seat Material ISO 5028 Rate A (TSO) PTFE
18 NACE Requirement Yes
C1 19 Type Stroking Time Pneumatic Piston / Spring return 4 Seconds
20 Size Safety Factor VTA in 1.3
21 Actuator Orientation Actuator Form Horizontal Cylinder
22 Ingress Protection Electrical Protection IP65 Eex i
23 Instrument Air Supply 80-120 Psig
24 Action on Air Failure Action on Power Failure Open Open
ACTUATOR 25 Fireproofing No
26 Solenoid Valve Schematic Detail Yes Type-2
27 Limit Switch Closed Limit Swich Open Yes Yes
28 Mounting Position Solenoid Power Supply Top 24VDC
29 Manual Reset No
30 Mechanical Position Indicator Red Closed / Green Open
C 31 Partial Stroke Facility No
31 Signal Cable 1/2" NPT
ELECTRICAL 32 Control Cable -
CONNECTIONS 33 Solenoid Cable 3/4" NPT
34
35 Fluid
Fl id Hydrocarbon
H d b Gas
G
36 Phase Gas/Vapour
37 Operating Pressure 155 psig
38 Design Pressure 210 psig
39 Operating Temperature 102 ºF
40 Design Temperature 140 ºF
PROCESS DATA
41 Max. Diff. Pressure for Actuator Size 210 psig
42
C1 43 Line Size and Sch. Inlet Outlet 2 in Sch. 10S 2 in Sch. 10S
44 Speed of Operation Design VTA
45 (Seconds) Actual VTA
46
Notes
1. VTA : Vendor to advice
2. Actuated ball valve and actuator shall be provided with 316 SS nameplate engraved or die stamped with Valve Tag No., Manufacturer's Name,
Model No., Valve Size & Rating.
3. Vendor shall be responsible for the proper design and selection of valve, actuator, and accessories based on the information furnished
C1 in this specification. This Data Sheet shall refer to SNO-I-ES-013, Instrument Specification for Shutdown and Blowdown Valve
4. Actuator shall be sized based on valve manufacturer's required Torque values with 130% minimum safety margin to open or close the valve
against full ANSI rated differential pressure at minimum pneumatic supply pressure of 60 psig.
5. Vendor shall provide Torque table containing breaking, running and seating torques for valves and actuator along with Quotation.
Vendor shall provide the torque table and calculation for COMPANY approval.
6. Actuator and accessories shall be supplied fully assembled, tubed and tested ready for installation.
7. Solenoid valve coil shall be provided with reverse polarity protection diodes, integral outlet box and terminal strip for cable connection.
8. Three way valve shall be universal type. Solenoid Coil shall be Class H.
Air filter regulator shall be 316 SS Material and equipped with pressure gauge on inlet and outlet of air filter regulator.
C1 9. All SDV & BDV shall be designed & tested as per API 6D
C1 10. Valve Stem Shall be Anti-Blowout Type.

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 27 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
1 Tag No. Quantity SDV -6101C / 6201C 2 (Two)
2 Manufacturer Model VTA VTA
3 Contract No. Requisition Item No.
4 Location Central Processing Plant
GENERAL
5 P&ID No. SNO-R-PI-008 / SNO-R-PI-043
6 Service Condensate Surge Vessel To LP Fuel Gas Treatment
7 Line No. 3"-HG-1009-1N / 3"-HG-2009-1N
8 Area Classification Zone-2, Gr. IIB, T3
C1 9 Valve Type Valve Code Trunnion Mounted Ball BA098
10 Body Size Body Form 3 in Ball
11 Body Material Port Size ASTM A351 CF8M Full Bore
12 Connection Rating RF Flange ASME 150#
C1 13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
C 14 Packing Lubrication & Isolation Expanded Graphite VTA
15 Bonnet Bolts Bonnet Nuts ASTM A193 B8M CL2 ASTM A194 8M
C 16 Ball Material Stem Material 316 SS 316 SS
C1 17 Leakage Rate Seat Material ISO 5028 Rate A PTFE
18 NACE Requirement Yes
C 19 Type Stroking Time Pneumatic Piston / Spring return 6 Seconds
20 Size Safety Factor VTA in 1.3
21 Actuator Orientation Actuator Form Horizontal Cylinder
22 Ingress Protection Electrical Protection IP65 Eex i
23 Instrument Air Supply 80-120 Psig
24 Action on Air Failure Action on Power Failure Closed Closed
ACTUATOR 25 Fireproofing No
26 Solenoid Valve Schematic Detail Yes Type-1
27 Limit Switch Closed Limit Swich Open Yes Yes
28 Mounting Position Solenoid Power Supply Top 24VDC
29 Manual Reset No
30 Mechanical Position Indicator Red Closed / Green Open
C 31 Partial Stroke Facility No
31 Signal Cable 1/2" NPT
ELECTRICAL 32 Control Cable -
CONNECTIONS 33 Solenoid Cable 3/4" NPT
34
35 Fluid
Fl id Hydrocarbon
H d b GasG
36 Phase Gas/Vapour
37 Operating Pressure 155 psig
38 Design Pressure 210 psig
39 Operating Temperature 102 ºF
40 Design Temperature 140 ºF
PROCESS DATA
41 Max. Diff. Pressure for Actuator Size 210 psig
42
43 Line Size and Sch. Inlet Outlet 3 in Sch. 10S 3 in Sch. 10S
44 Speed of Operation Design VTA
45 (Seconds) Actual VTA
46
Notes
1. VTA : Vendor to advice
2. Actuated ball valve and actuator shall be provided with 316 SS nameplate engraved or die stamped with Valve Tag No., Manufacturer's Name,
Model No., Valve Size & Rating.
3. Vendor shall be responsible for the proper design and selection of valve, actuator, and accessories based on the information furnished
C1 in this specification. This Data Sheet shall refer to SNO-I-ES-013, Instrument Specification for Shutdown and Blowdown Valve
4. Actuator shall be sized based on valve manufacturer's required Torque values with 130% minimum safety margin to open or close the valve
against full ANSI rated differential pressure at minimum pneumatic supply pressure of 60 psig.
5. Vendor shall provide Torque table containing breaking, running and seating torques for valves and actuator along with Quotation.
Vendor shall provide the torque table and calculation for COMPANY approval.
6. Actuator and accessories shall be supplied fully assembled, tubed and tested ready for installation.
7. Solenoid valve coil shall be provided with reverse polarity protection diodes, integral outlet box and terminal strip for cable connection.
Three way valve shall be universal type. Solenoid Coil shall be Class H.
8. Air filter regulator shall be 316 SS Material and equipped with pressure gauge on inlet and outlet of air filter regulator.
C1 9. All SDV & BDV shall be designed & tested as per API 6D
C1 10. Valve Stem Shall be Anti-Blowout Type.

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 28 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
1 Tag No. Quantity SDV -4101A 1 (One)
2 Manufacturer Model VTA VTA
3 Contract No. Requisition Item No.
4 Location Central Processing Plant
GENERAL
5 P&ID No. SNO-R-PI-010
6 Service Acid Gas Compression
7 Line No. 3"-FG-0065-1B
8 Area Classification Zone-2, Gr. IIB, T3
9 Valve Type Valve Code Trunnion Mounted Ball BA032
10 Body Size Body Form 3 in Ball
11 Body Material Port Size ASTM A216 WCB Full Bore
12 Connection Rating RF Flange ASME 150#
13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
14 Packing Lubrication & Isolation Expanded Graphite VTA
15 Bonnet Bolts Bonnet Nuts ASTM A193 B7M ASTM A194 2HM
16 Ball Material Stem Material 316 SS 316 SS
17 Leakage Rate Seat Material ISO 5028 Rate A PTFE
18 NACE Requirement Yes
19 Type Stroking Time Pneumatic Piston / Spring return 6 Seconds
20 Size Safety Factor VTA in 1.3
21 Actuator Orientation Actuator Form Horizontal Cylinder
22 Ingress Protection Electrical Protection IP65 Eex i
23 Instrument Air Supply 80-120 Psig
24 Action on Air Failure Action on Power Failure Closed Closed
ACTUATOR 25 Fireproofing No
26 Solenoid Valve Schematic Detail Yes Type-1
27 Limit Switch Closed Limit Swich Open Yes Yes
28 Mounting Position Solenoid Power Supply Top 24VDC
29 Manual Reset No
30 Mechanical Position Indicator Red Closed / Green Open
31 Partial Stroke Facility Yes
31 Signal Cable 1/2" NPT
ELECTRICAL 32 Control Cable -
CONNECTIONS 33 Solenoid Cable 3/4" NPT
34
35 Fluid
Fl id LP Fuel
F l Gas
G
36 Phase Gas
37 Operating Pressure 100 psig
38 Design Pressure 150 psig
39 Operating Temperature 107 ºF
40 Design Temperature 200 ºF
PROCESS DATA
41 Max. Diff. Pressure for Actuator Size 150 psig
42
43 Line Size and Sch. Inlet Outlet 3 in Sch. 80 3 in Sch. 80
44 Speed of Operation Design VTA
45 (Seconds) Actual VTA
46
Notes
C1 1. SDV-4101 is deleted because of deletion of SNO-R-PI-010

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 29 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
1 Tag No. Quantity SDV -4101B 1 (One)
2 Manufacturer Model VTA VTA
3 Contract No. Requisition Item No.
4 Location Central Processing Plant
GENERAL
5 P&ID No. SNO-R-PI-010
6 Service Acid Gas to Acid Gas Conversion Unit
7 Line No. 24"-GA-1001-1N
8 Area Classification Zone-2, Gr. IIB, T3
9 Valve Type Valve Code Trunnion Mounted Ball BA100
10 Body Size Body Form 24 in Ball
11 Body Material Port Size ASTM A351 CF8M Full Bore
12 Connection Rating RF Flange ASME 150#
13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
14 Packing Lubrication & Isolation Expanded Graphite VTA
15 Bonnet Bolts Bonnet Nuts ASTM A193 B8M CL2 ASTM A194 8M
16 Ball Material Stem Material 316 SS 316 SS
17 Leakage Rate Seat Material ISO 5028 Rate A PTFE
18 NACE Requirement Yes
19 Type Stroking Time Pneumatic Piston / Spring return VTA
20 Size Safety Factor VTA in 1.3
21 Actuator Orientation Actuator Form Horizontal Cylinder
22 Ingress Protection Electrical Protection IP65 Eex i
23 Instrument Air Supply 80-120 Psig
24 Action on Air Failure Action on Power Failure Closed Closed
ACTUATOR 25 Fireproofing No
26 Solenoid Valve Schematic Detail Yes Type-1
27 Limit Switch Closed Limit Swich Open Yes Yes
28 Mounting Position Solenoid Power Supply Top 24VDC
29 Manual Reset No
30 Mechanical Position Indicator Red Closed / Green Open
31 Partial Stroke Facility Yes
31 Signal Cable 1/2" NPT
ELECTRICAL 32 Control Cable -
CONNECTIONS 33 Solenoid Cable 3/4" NPT
34
35 Fluid
Fl id A id G
Acid Gas
36 Phase Gas
37 Operating Pressure 17 psig
38 Design Pressure 100 psig
39 Operating Temperature 120 ºF
40 Design Temperature 250 ºF
PROCESS DATA
41 Max. Diff. Pressure for Actuator Size 100 psig
42
43 Line Size and Sch. Inlet Outlet 24 in Sch. 10 24 in Sch. 10
44 Speed of Operation Design VTA
45 (Seconds) Actual VTA
46
Notes
C1 1. SDV-4101B is deleted because of deletion of SNO-R-PI-010

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 30 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
1 Tag No. Quantity SDV -6073A 1 (One)
2 Manufacturer Model VTA VTA
3 Contract No. Requisition Item No.
4 Location Central Processing Plant
GENERAL
5 P&ID No. SNO-R-PI-010D
6 Service From Acid Gas Metering to Loading Arm
7 Line No. 16"-SA-0011-1B
8 Area Classification Zone-2, Gr. IIB, T3
9 Valve Type Valve Code Trunnion Mounted Ball BA034
10 Body Size Body Form 16 in Ball
11 Body Material Port Size A105 Full Bore
12 Connection Rating RF Flange ASME 150#
13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
14 Packing Lubrication & Isolation Expanded Graphite VTA
15 Bonnet Bolts Bonnet Nuts A193 B7M A194 2HM
16 Ball Material Stem Material 316 SS 316 SS
17 Leakage Rate Seat Material ISO 5028 Rate A PTFE
18 NACE Requirement Yes
19 Type Stroking Time Pneumatic Piston / Spring return 15 Seconds
20 Size Safety Factor VTA in 1.3
21 Actuator Orientation Actuator Form Horizontal Cylinder
22 Ingress Protection Electrical Protection IP65 Eex i
23 Instrument Air Supply 80-120 Psig
24 Action on Air Failure Action on Power Failure Closed Closed
ACTUATOR 25 Fireproofing No
26 Solenoid Valve Schematic Detail Yes Type-1
27 Limit Switch Closed Limit Swich Open Yes Yes
28 Mounting Position Solenoid Power Supply Top 24VDC
29 Manual Reset No
30 Mechanical Position Indicator Red Closed / Green Open
31 Partial Stroke Facility No
31 Signal Cable 1/2" NPT
ELECTRICAL 32 Control Cable -
CONNECTIONS 33 Solenoid Cable 3/4" NPT
34
35 Fl
Fluid
id S
Sulphuric
l h i AAcid
id
36 Phase Liquid
37 Operating Pressure 144 psig
38 Design Pressure 210 psig
39 Operating Temperature AMB ºF
40 Design Temperature 150 ºF
PROCESS DATA
41 Max. Diff. Pressure for Actuator Size 200 psig
42
43 Line Size and Sch. Inlet Outlet 16 in Sch. 20 16 in Sch. 20
44 Speed of Operation Design VTA
45 (Seconds) Actual VTA
46
Notes
C1 1. SDV-6073A is supplied by Construction Company of Sulphuric Acid Jetty

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 31 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
1 Tag No. Quantity XV -6073E 1 (One)
2 Manufacturer Model VTA VTA
3 Contract No. Requisition Item No.
4 Location Central Processing Plant
GENERAL
5 P&ID No. SNO-R-PI-010D
6 Service From N2 Bottle to Sulphuric Acid Jetty Loading Arm Package
7 Line No. 2"-NI-xxxx-1G
8 Area Classification Zone-2, Gr. IIB, T3
9 Valve Type Valve Code Trunnion Mounted Ball BA084
10 Body Size Body Form 2 in Ball
11 Body Material Port Size ASTM A216 WCB Full Bore
12 Connection Rating RF Flange ASME 150#
13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
14 Packing Lubrication & Isolation Expanded Graphite VTA
15 Bonnet Bolts Bonnet Nuts ASTM A193 B7(GALV.) ASTM A194 2H(GALV.)
16 Ball Material Stem Material A105 + ENP 76µm A105 + ENP 76µm
17 Leakage Rate Seat Material ISO 5028 Rate A RTFE
18 NACE Requirement No
19 Type Stroking Time Pneumatic Piston / Spring return 4 Seconds
20 Size Safety Factor VTA in 1.3
21 Actuator Orientation Actuator Form Horizontal Cylinder
22 Ingress Protection Electrical Protection IP65 Eex i
23 Instrument Air Supply 80-120 Psig
24 Action on Air Failure Action on Power Failure Closed Closed
ACTUATOR 25 Fireproofing No
26 Solenoid Valve Schematic Detail Yes Type-6
27 Limit Switch Closed Limit Swich Open Yes Yes
28 Mounting Position Solenoid Power Supply Top 24VDC
29 Manual Reset No
30 Mechanical Position Indicator Red Closed / Green Open
31 Partial Stroke Facility No
31 Signal Cable 1/2" NPT
ELECTRICAL 32 Control Cable -
CONNECTIONS 33 Solenoid Cable 3/4" NPT
34
35 Fluid
Fl id Nitrogen
Nit
36 Phase Gas
37 Operating Pressure 110 (HOL psig
38 Design Pressure 150 psig
39 Operating Temperature 85 ºF
40 Design Temperature 100 ºF
PROCESS DATA
41 Max. Diff. Pressure for Actuator Size 150 psig
42
43 Line Size and Sch. Inlet Outlet 2 in Sch. 40 2 in Sch. 40
44 Speed of Operation Design VTA
45 (Seconds) Actual VTA
46
Notes
C1 1. XV-6073E is supplied by Loading Arm Package Supplier

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 32 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
1 Tag No. Quantity SDV -6105B / 6205B 2 (Two)
2 Manufacturer Model VTA VTA
3 Contract No. Requisition Item No.
4 Location Central Processing Plant
GENERAL
5 P&ID No. SNO-R-PI-013 / SNO-R-PI-048
6 Service Hot Oil Supply to Stabilizer Reboiler
7 Line No. 6"-OH-1130-3A / 6"-OH-2130-3A
8 Area Classification Zone-2, Gr. IIB, T3
9 Valve Type Valve Code Trunnion Mounted Ball BA010
10 Body Size Body Form 6 in Ball
11 Body Material Port Size ASTM A216 WCB Full Bore
12 Connection Rating RF Flange ASME 300#
C1 13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
C 14 Packing Lubrication & Isolation Expanded Graphite VTA
C 15 Bonnet Bolts Bonnet Nuts A193 B7 A194 2H
C 16 Ball Material Stem Material 316 SS CS+ENP 76μm
C1 17 Leakage Rate Seat Material ISO 5028 Rate A PTFE
18 NACE Requirement No
C 19 Type Stroking Time Pneumatic Piston / Spring return 12 Seconds
20 Size Safety Factor VTA in 1.3
21 Actuator Orientation Actuator Form Horizontal Cylinder
22 Ingress Protection Electrical Protection IP65 Eex i
23 Instrument Air Supply 80-120 Psig
24 Action on Air Failure Action on Power Failure Closed Closed
ACTUATOR 25 Fireproofing No
26 Solenoid Valve Schematic Detail Yes Type-1
27 Limit Switch Closed Limit Swich Open Yes Yes
28 Mounting Position Solenoid Power Supply Top 24VDC
29 Manual Reset No
30 Mechanical Position Indicator Red Closed / Green Open
C 31 Partial Stroke Facility No
31 Signal Cable 1/2" NPT
ELECTRICAL 32 Control Cable -
CONNECTIONS 33 Solenoid Cable 3/4" NPT
34
35 Fluid
Fl id Hot
H t Oil
C 36 Phase Liquid
37 Operating Pressure 65 psig
38 Design Pressure 210 psig
39 Operating Temperature 450 ºF
40 Design Temperature 500 ºF
PROCESS DATA
41 Max. Diff. Pressure for Actuator Size 210 psig
42
43 Line Size and Sch. Inlet Outlet 6 in Sch. 40 6 in Sch. 40
44 Speed of Operation Design VTA
45 (Seconds) Actual VTA
46
Notes
1. VTA : Vendor to advice
2. Actuated ball valve and actuator shall be provided with 316 SS nameplate engraved or die stamped with Valve Tag No., Manufacturer's Name,
Model No., Valve Size & Rating.
3. Vendor shall be responsible for the proper design and selection of valve, actuator, and accessories based on the information furnished
C1 in this specification. This Data Sheet shall refer to SNO-I-ES-013, Instrument Specification for Shutdown and Blowdown Valve
4. Actuator shall be sized based on valve manufacturer's required Torque values with 130% minimum safety margin to open or close the valve
against full ANSI rated differential pressure at minimum pneumatic supply pressure of 60 psig.
5. Vendor shall provide Torque table containing breaking, running and seating torques for valves and actuator along with Quotation.
Vendor shall provide the torque table and calculation for COMPANY approval.
6. Actuator and accessories shall be supplied fully assembled, tubed and tested ready for installation.
7. Solenoid valve coil shall be provided with reverse polarity protection diodes, integral outlet box and terminal strip for cable connection.
Three way valve shall be universal type. Solenoid Coil shall be Class H.
8. Air filter regulator shall be 316 SS Material and equipped with pressure gauge on inlet and outlet of air filter regulator.
C1 9. All SDV & BDV shall be designed & tested as per API 6D
C1 10. Valve Stem Shall be Anti-Blowout Type.

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 33 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
1 Tag No. Quantity SDV -6107B / 6207B 2 (Two)
2 Manufacturer Model VTA VTA
3 Contract No. Requisition Item No.
4 Location Central Processing Plant
GENERAL
5 P&ID No. SNO-R-PI-014 / SNO-R-PI-049
6 Service Stabilizer Reflux Drum to Close Drain Header
C 7 Line No. 2"-HL-1171-3N / 2"-HL-2171-3N
8 Area Classification Zone-2, Gr. IIB, T3
C1 9 Valve Type Valve Code Trunnion Mounted Ball BA146
10 Body Size Body Form 2 in Ball
11 Body Material Port Size ASTM A351 CF8M Full Bore
C 12 Connection Rating RF Flange ASME 300#
C1 13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
C 14 Packing Lubrication & Isolation Expanded Graphite VTA
15 Bonnet Bolts Bonnet Nuts ASTM A193 B8M CL2 ASTM A194 8M
C 16 Ball Material Stem Material 316 SS 316 SS
C1 17 Leakage Rate Seat Material ISO 5028 Rate A (TSO) PTFE
18 NACE Requirement Yes
C 19 Type Stroking Time Pneumatic Piston / Spring return 4 Seconds
20 Size Safety Factor VTA in 1.3
21 Actuator Orientation Actuator Form Horizontal Cylinder
22 Ingress Protection Electrical Protection IP65 Eex i
23 Instrument Air Supply 80-120 Psig
24 Action on Air Failure Action on Power Failure Closed Closed
ACTUATOR 25 Fireproofing No
26 Solenoid Valve Schematic Detail Yes Type-1
27 Limit Switch Closed Limit Swich Open Yes Yes
28 Mounting Position Solenoid Power Supply Top 24VDC
29 Manual Reset No
30 Mechanical Position Indicator Red Closed / Green Open
C 31 Partial Stroke Facility No
31 Signal Cable 1/2" NPT
ELECTRICAL 32 Control Cable -
CONNECTIONS 33 Solenoid Cable 3/4" NPT
34
35 Fluid
Fl id Hydrocarbon
H d b
36 Phase Liquid
37 Operating Pressure 120 psig
C 38 Design Pressure 210 + F.V. psig
39 Operating Temperature 120 ºF
40 Design Temperature 220 ºF
PROCESS DATA
41 Max. Diff. Pressure for Actuator Size 210 psig
42
C 43 Line Size and Sch. Inlet Outlet 2 in Sch. 40S 2 in Sch. 40S
44 Speed of Operation Design VTA
45 (Seconds) Actual VTA
46
Notes
1. VTA : Vendor to advice
2. Actuated ball valve and actuator shall be provided with 316 SS nameplate engraved or die stamped with Valve Tag No., Manufacturer's Name,
Model No., Valve Size & Rating.
3. Vendor shall be responsible for the proper design and selection of valve, actuator, and accessories based on the information furnished
C1 in this specification. This Data Sheet shall refer to SNO-I-ES-013, Instrument Specification for Shutdown and Blowdown Valve
4. Actuator shall be sized based on valve manufacturer's required Torque values with 130% minimum safety margin to open or close the valve
against full ANSI rated differential pressure at minimum pneumatic supply pressure of 60 psig.
5. Vendor shall provide Torque table containing breaking, running and seating torques for valves and actuator along with Quotation.
Vendor shall provide the torque table and calculation for COMPANY approval.
6. Actuator and accessories shall be supplied fully assembled, tubed and tested ready for installation.
7. Solenoid valve coil shall be provided with reverse polarity protection diodes, integral outlet box and terminal strip for cable connection.
8. Three way valve shall be universal type. Solenoid Coil shall be Class H.
Air filter regulator shall be 316 SS Material and equipped with pressure gauge on inlet and outlet of air filter regulator.
C1 9. All SDV & BDV shall be designed & tested as per API 6D
C1 10. Valve Stem Shall be Anti-Blowout Type.

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 34 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
1 Tag No. Quantity SDV -6107D / 6207D 2 (Two)
2 Manufacturer Model VTA VTA
3 Contract No. Requisition Item No.
4 Location Central Processing Plant
GENERAL
5 P&ID No. SNO-R-PI-014 / SNO-R-PI-049
6 Service Stabilizer Reflux Drum to LP Fuel Gas Treatment
C 7 Line No. 4"-HG-1017-3N / 4"-HG-2017-3N
8 Area Classification Zone-2, Gr. IIB, T3
C1 9 Valve Type Valve Code Trunnion Mounted Ball BA146
10 Body Size Body Form 4 in Ball
11 Body Material Port Size ASTM A351 CF8M Full Bore
C 12 Connection Rating RF Flange ASME 300#
C1 13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
C 14 Packing Lubrication & Isolation Expanded Graphite VTA
15 Bonnet Bolts Bonnet Nuts ASTM A193 B8M CL2 ASTM A194 8M
C 16 Ball Material Stem Material 316 SS 316 SS
C1 17 Leakage Rate Seat Material ISO 5028 Rate A PTFE
18 NACE Requirement Yes
C 19 Type Stroking Time Pneumatic Piston / Spring return 8 Seconds
20 Size Safety Factor VTA in 1.3
21 Actuator Orientation Actuator Form Horizontal Cylinder
22 Ingress Protection Electrical Protection IP65 Eex i
23 Instrument Air Supply 80-120 Psig
24 Action on Air Failure Action on Power Failure Closed Closed
ACTUATOR 25 Fireproofing No
26 Solenoid Valve Schematic Detail Yes Type-1
27 Limit Switch Closed Limit Swich Open Yes Yes
28 Mounting Position Solenoid Power Supply Top 24VDC
29 Manual Reset No
30 Mechanical Position Indicator Red Closed / Green Open
C 31 Partial Stroke Facility No
31 Signal Cable 1/2" NPT
ELECTRICAL 32 Control Cable -
CONNECTIONS 33 Solenoid Cable 3/4" NPT
34
35 Fluid
Fl id Hydrocarbon
H d b
36 Phase Gas
37 Operating Pressure 120 psig
C 38 Design Pressure 210 + F.V. psig
39 Operating Temperature 120 ºF
40 Design Temperature 220 ºF
PROCESS DATA
41 Max. Diff. Pressure for Actuator Size 210 psig
42
C 43 Line Size and Sch. Inlet Outlet 4 in Sch. 40S 4 in Sch. 40S
44 Speed of Operation Design VTA
45 (Seconds) Actual VTA
46
Notes
1. VTA : Vendor to advice
2. Actuated ball valve and actuator shall be provided with 316 SS nameplate engraved or die stamped with Valve Tag No., Manufacturer's Name,
Model No., Valve Size & Rating.
3. Vendor shall be responsible for the proper design and selection of valve, actuator, and accessories based on the information furnished
C1 in this specification. This Data Sheet shall refer to SNO-I-ES-013, Instrument Specification for Shutdown and Blowdown Valve
4. Actuator shall be sized based on valve manufacturer's required Torque values with 130% minimum safety margin to open or close the valve
against full ANSI rated differential pressure at minimum pneumatic supply pressure of 60 psig.
5. Vendor shall provide Torque table containing breaking, running and seating torques for valves and actuator along with Quotation.
Vendor shall provide the torque table and calculation for COMPANY approval.
6. Actuator and accessories shall be supplied fully assembled, tubed and tested ready for installation.
7. Solenoid valve coil shall be provided with reverse polarity protection diodes, integral outlet box and terminal strip for cable connection.
Three way valve shall be universal type. Solenoid Coil shall be Class H.
8. Air filter regulator shall be 316 SS Material and equipped with pressure gauge on inlet and outlet of air filter regulator.
C1 9. All SDV & BDV shall be designed & tested as per API 6D
C1 10. Valve Stem Shall be Anti-Blowout Type.

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 35 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
1 Tag No. Quantity BDV -6106A / 6206A 2 (Two)
2 Manufacturer Model VTA VTA
3 Contract No. Requisition Item No.
4 Location Central Processing Plant
GENERAL
5 P&ID No. SNO-R-PI-014 / SNO-R-PI-049
6 Service From Stabilizer Overhead Condenser to HP Flare Header
C1 7 Line No. 2"-HF-1006-3N / 2"-HF-2006-3N
8 Area Classification Zone-2, Gr. IIB, T3
C1 9 Valve Type Valve Code Trunnion Mounted Ball BA146
C1 10 Body Size Body Form 2 in Ball
11 Body Material Port Size ASTM A351 CF8M Full Bore
12 Connection Rating RF Flange ASME 300#
C1 13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
C 14 Packing Lubrication & Isolation Expanded Graphite VTA
15 Bonnet Bolts Bonnet Nuts ASTM A193 B8M CL2 ASTM A194 8M
C 16 Ball Material Stem Material 316 SS 316 SS
C1 17 Leakage Rate Seat Material ISO 5028 Rate A (TSO) PTFE
18 NACE Requirement Yes
C 19 Type Stroking Time Pneumatic Piston / Spring return 4 Seconds
20 Size Safety Factor VTA in 1.3
21 Actuator Orientation Actuator Form Horizontal Cylinder
22 Ingress Protection Electrical Protection IP65 Eex i
23 Instrument Air Supply 80-120 Psig
24 Action on Air Failure Action on Power Failure Open Open
ACTUATOR 25 Fireproofing No
26 Solenoid Valve Schematic Detail Yes Type-2
27 Limit Switch Closed Limit Swich Open Yes Yes
28 Mounting Position Solenoid Power Supply Top 24VDC
29 Manual Reset No
30 Mechanical Position Indicator Red Closed / Green Open
C 31 Partial Stroke Facility No
31 Signal Cable 1/2" NPT
ELECTRICAL 32 Control Cable -
CONNECTIONS 33 Solenoid Cable 3/4" NPT
34
35 Fluid
Fl id Hydrocarbon
H d b
36 Phase Gas
37 Operating Pressure 120 psig
C 38 Design Pressure 210 + F.V. psig
39 Operating Temperature 120 ºF
40 Design Temperature 220 ºF
PROCESS DATA
41 Max. Diff. Pressure for Actuator Size 210 psig
42
C1 43 Line Size and Sch. Inlet Outlet 2 in Sch. 40S 2 in Sch. 40S
44 Speed of Operation Design VTA
45 (Seconds) Actual VTA
46
Notes
1. VTA : Vendor to advice
2. Actuated ball valve and actuator shall be provided with 316 SS nameplate engraved or die stamped with Valve Tag No., Manufacturer's Name,
Model No., Valve Size & Rating.
3. Vendor shall be responsible for the proper design and selection of valve, actuator, and accessories based on the information furnished
C1 in this specification. This Data Sheet shall refer to SNO-I-ES-013, Instrument Specification for Shutdown and Blowdown Valve
4. Actuator shall be sized based on valve manufacturer's required Torque values with 130% minimum safety margin to open or close the valve
against full ANSI rated differential pressure at minimum pneumatic supply pressure of 60 psig.
5. Vendor shall provide Torque table containing breaking, running and seating torques for valves and actuator along with Quotation.
Vendor shall provide the torque table and calculation for COMPANY approval.
6. Actuator and accessories shall be supplied fully assembled, tubed and tested ready for installation.
7. Solenoid valve coil shall be provided with reverse polarity protection diodes, integral outlet box and terminal strip for cable connection.
Three way valve shall be universal type. Solenoid Coil shall be Class H.
8. Air filter regulator shall be 316 SS Material and equipped with pressure gauge on inlet and outlet of air filter regulator.
C1 9. All SDV & BDV shall be designed & tested as per API 6D
C1 10. Valve Stem Shall be Anti-Blowout Type.

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 36 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
1 Tag No. Quantity SDV -6040B 1 (One)
2 Manufacturer Model VTA VTA
3 Contract No. Requisition Item No.
4 Location Central Processing Plant
GENERAL
5 P&ID No. SNO-R-PI-015
6 Service Stabilizer Overhead Filter Coalescer to Close Drain Header
C 7 Line No. 2"-HL-1014-3N
8 Area Classification Zone-2, Gr. IIB, T3
C1 9 Valve Type Valve Code Trunnion Mounted Ball BA146
10 Body Size Body Form 2 in Ball
11 Body Material Port Size ASTM A351 CF8M Full Bore
C 12 Connection Rating RF Flange ASME 300#
C1 13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
C 14 Packing Lubrication & Isolation Expanded Graphite VTA
15 Bonnet Bolts Bonnet Nuts ASTM A193 B8M CL2 ASTM A194 8M
C 16 Ball Material Stem Material 316 SS 316 SS
C1 17 Leakage Rate Seat Material ISO 5028 Rate A (TSO) PTFE
18 NACE Requirement Yes
C 19 Type Stroking Time Pneumatic Piston / Spring return 4 Seconds
20 Size Safety Factor VTA in 1.3
21 Actuator Orientation Actuator Form Horizontal Cylinder
22 Ingress Protection Electrical Protection IP65 Eex i
23 Instrument Air Supply 80-120 Psig
24 Action on Air Failure Action on Power Failure Closed Closed
ACTUATOR 25 Fireproofing No
26 Solenoid Valve Schematic Detail Yes Type-1
27 Limit Switch Closed Limit Swich Open Yes Yes
28 Mounting Position Solenoid Power Supply Top 24VDC
29 Manual Reset No
30 Mechanical Position Indicator Red Closed / Green Open
C 31 Partial Stroke Facility No
31 Signal Cable 1/2" NPT
ELECTRICAL 32 Control Cable -
CONNECTIONS 33 Solenoid Cable 3/4" NPT
34
35 Fluid
Fl id Hydrocarbon
H d b
36 Phase Liquid
C 37 Operating Pressure 114 psig
38 Design Pressure 210 psig
C 39 Operating Temperature 109 ºF
C 40 Design Temperature -20 / 200 ºF
PROCESS DATA
41 Max. Diff. Pressure for Actuator Size 210 psig
42
C 43 Line Size and Sch. Inlet Outlet 2 in Sch. 40S 2 in Sch. 40S
44 Speed of Operation Design VTA
45 (Seconds) Actual VTA
46
Notes
1. VTA : Vendor to advice
2. Actuated ball valve and actuator shall be provided with 316 SS nameplate engraved or die stamped with Valve Tag No., Manufacturer's Name,
Model No., Valve Size & Rating.
3. Vendor shall be responsible for the proper design and selection of valve, actuator, and accessories based on the information furnished
C1 in this specification. This Data Sheet shall refer to SNO-I-ES-013, Instrument Specification for Shutdown and Blowdown Valve
4. Actuator shall be sized based on valve manufacturer's required Torque values with 130% minimum safety margin to open or close the valve
against full ANSI rated differential pressure at minimum pneumatic supply pressure of 60 psig.
5. Vendor shall provide Torque table containing breaking, running and seating torques for valves and actuator along with Quotation.
Vendor shall provide the torque table and calculation for COMPANY approval.
6. Actuator and accessories shall be supplied fully assembled, tubed and tested ready for installation.
7. Solenoid valve coil shall be provided with reverse polarity protection diodes, integral outlet box and terminal strip for cable connection.
8. Three way valve shall be universal type. Solenoid Coil shall be Class H.
Air filter regulator shall be 316 SS Material and equipped with pressure gauge on inlet and outlet of air filter regulator.
C1 9. All SDV & BDV shall be designed & tested as per API 6D
C1 10. Valve Stem Shall be Anti-Blowout Type.

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 37 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
1 Tag No. Quantity BDV -5102A / 5202A 2 (Two)
2 Manufacturer Model VTA VTA
3 Contract No. Requisition Item No.
4 Location Central Processing Plant
GENERAL
5 P&ID No. SNO-R-PI-017 SNO-R-PI-071
6 Service Gas/Gas Exchanger Outlet to HP Flare Header
C1 7 Line No. 3"-HG-1616-6A / 3"-HG-2616-6A
8 Area Classification Zone-2, Gr. IIB, T3
C1 9 Valve Type Valve Code Trunnion Mounted Ball BA013
C1 10 Body Size Body Form 3 in Ball
C 11 Body Material Port Size A216 WCB Full Bore
12 Connection Rating RF Flange ASME 600#
C1 13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
C 14 Packing Lubrication & Isolation Expanded Graphite VTA
C 15 Bonnet Bolts Bonnet Nuts A193 B7 A194 2H
C 16 Ball Material Stem Material CS+ENP 76μm A564 630, H1150M+ENP 76 μm
C1 17 Leakage Rate Seat Material ISO 5028 Rate A (TSO) PTFE OR NYLON
18 NACE Requirement No
C 19 Type Stroking Time Pneumatic Piston / Spring return 6 Seconds
20 Size Safety Factor VTA in 1.3
21 Actuator Orientation Actuator Form Horizontal Cylinder
22 Ingress Protection Electrical Protection IP65 Eex i
23 Instrument Air Supply 80-120 Psig
24 Action on Air Failure Action on Power Failure Open Open
ACTUATOR 25 Fireproofing No
26 Solenoid Valve Schematic Detail Yes Type-2
27 Limit Switch Closed Limit Swich Open Yes Yes
28 Mounting Position Solenoid Power Supply Top 24VDC
29 Manual Reset No
30 Mechanical Position Indicator Red Closed / Green Open
C 31 Partial Stroke Facility No
31 Signal Cable 1/2" NPT
ELECTRICAL 32 Control Cable -
CONNECTIONS 33 Solenoid Cable 3/4" NPT
34
35 Fluid
Fl id Hydrocarbon
H d b Gas
G
36 Phase Gas/Vapour
C 37 Operating Pressure 852 psig
38 Design Pressure 1300 psig
39 Operating Temperature 100 ºF
C 40 Design Temperature -40 / 150 ºF
PROCESS DATA
41 Max. Diff. Pressure for Actuator Size 1300 psig
42
C1 43 Line Size and Sch. Inlet Outlet 3 in Sch. 120 3 in Sch. 120
44 Speed of Operation Design VTA
45 (Seconds) Actual VTA
46
Notes
1. VTA : Vendor to advice
2. Actuated ball valve and actuator shall be provided with 316 SS nameplate engraved or die stamped with Valve Tag No., Manufacturer's Name,
Model No., Valve Size & Rating.
3. Vendor shall be responsible for the proper design and selection of valve, actuator, and accessories based on the information furnished
C1 in this specification. This Data Sheet shall refer to SNO-I-ES-013, Instrument Specification for Shutdown and Blowdown Valve
4. Actuator shall be sized based on valve manufacturer's required Torque values with 130% minimum safety margin to open or close the valve
against full ANSI rated differential pressure at minimum pneumatic supply pressure of 60 psig.
5. Vendor shall provide Torque table containing breaking, running and seating torques for valves and actuator along with Quotation.
Vendor shall provide the torque table and calculation for COMPANY approval.
6. Actuator and accessories shall be supplied fully assembled, tubed and tested ready for installation.
7. Solenoid valve coil shall be provided with reverse polarity protection diodes, integral outlet box and terminal strip for cable connection.
8. Three way valve shall be universal type. Solenoid Coil shall be Class H.
Air filter regulator shall be 316 SS Material and equipped with pressure gauge on inlet and outlet of air filter regulator.
C1 9. All SDV & BDV shall be designed & tested as per API 6D
C1 10. Valve Stem Shall be Anti-Blowout Type.

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 38 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
1 Tag No. Quantity SDV -5102B / 5202B 2 (Two)
2 Manufacturer Model VTA VTA
3 Contract No. Requisition Item No.
4 Location Central Processing Plant
GENERAL
5 P&ID No. SNO-R-PI-017 SNO-R-PI-071
6 Service Gas/Gas Exchanger Outlet to CPP Gas Metering
7 Line No. 12"-HG-1022-6A / 12"-HG-2022-6A
8 Area Classification Zone-2, Gr. IIB, T3
C1 9 Valve Type Valve Code Trunnion Mounted Ball BA015
10 Body Size Body Form 12 in Ball
C 11 Body Material Port Size A105 Full Bore
12 Connection Rating RF Flange ASME 600#
C1 13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
C 14 Packing Lubrication & Isolation Expanded Graphite VTA
C 15 Bonnet Bolts Bonnet Nuts A193 B7 A194 2H
C 16 Ball Material Stem Material CS+ENP 76μm A564 630, H1150M+ENP 76 μm
C1 17 Leakage Rate Seat Material ISO 5028 Rate A PTFE OR NYLON
18 NACE Requirement No
C 19 Type Stroking Time Pneumatic Piston / Spring return 15 Seconds
C 20 Size Safety Factor VTA in 1.5
21 Actuator Orientation Actuator Form Horizontal Cylinder
22 Ingress Protection Electrical Protection IP65 Eex i
23 Instrument Air Supply 80-120 Psig
24 Action on Air Failure Action on Power Failure Closed Closed
ACTUATOR 25 Fireproofing No
26 Solenoid Valve Schematic Detail Yes Type-1
27 Limit Switch Closed Limit Swich Open Yes Yes
28 Mounting Position Solenoid Power Supply Top 24VDC
29 Manual Reset No
30 Mechanical Position Indicator Red Closed / Green Open
C 31 Partial Stroke Facility Yes
31 Signal Cable 1/2" NPT
ELECTRICAL 32 Control Cable -
CONNECTIONS 33 Solenoid Cable 3/4" NPT
34
35 Fluid
Fl id Hydrocarbon
H d b GasG
36 Phase Gas/Vapour
C 37 Operating Pressure 852 psig
38 Design Pressure 1300 psig
39 Operating Temperature 100 ºF
C 40 Design Temperature -40 / 150 ºF
PROCESS DATA
41 Max. Diff. Pressure for Actuator Size 1300 psig
42
43 Line Size and Sch. Inlet Outlet 12 in Sch. 100 12 in Sch. 100
44 Speed of Operation Design VTA
45 (Seconds) Actual VTA
46
Notes
1. VTA : Vendor to advice
2. Actuated ball valve and actuator shall be provided with 316 SS nameplate engraved or die stamped with Valve Tag No., Manufacturer's Name,
Model No., Valve Size & Rating.
3. Vendor shall be responsible for the proper design and selection of valve, actuator, and accessories based on the information furnished
C1 in this specification. This Data Sheet shall refer to SNO-I-ES-013, Instrument Specification for Shutdown and Blowdown Valve
4. Actuator shall be sized based on valve manufacturer's required Torque values with 130% minimum safety margin to open or close the valve
against full ANSI rated differential pressure at minimum pneumatic supply pressure of 60 psig.
5. Vendor shall provide Torque table containing breaking, running and seating torques for valves and actuator along with Quotation.
Vendor shall provide the torque table and calculation for COMPANY approval.
6. Actuator and accessories shall be supplied fully assembled, tubed and tested ready for installation.
7. Solenoid valve coil shall be provided with reverse polarity protection diodes, integral outlet box and terminal strip for cable connection.
8. Three way valve shall be universal type. Solenoid Coil shall be Class H.
Air filter regulator shall be 316 SS Material and equipped with pressure gauge on inlet and outlet of air filter regulator.
C1 9. All SDV & BDV shall be designed & tested as per API 6D
C1 10. Valve Stem Shall be Anti-Blowout Type.

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 39 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
1 Tag No. Quantity SDV -5104A / 5204A 2 (Two)
2 Manufacturer Model VTA VTA
3 Contract No. Requisition Item No.
4 Location Central Processing Plant
GENERAL
5 P&ID No. SNO-R-PI-018 / SNO-R-PI-072
6 Service Outlet to Low Temperature Separator to Condensate Surge Vessel
C 7 Line No. 2"-HL-1022-9N / 2"-HL-2020-9N
8 Area Classification Zone-2, Gr. IIB, T3
C1 9 Valve Type Valve Code Trunnion Mounted Ball BA466
10 Body Size Body Form 2 in Ball
11 Body Material Port Size ASTM A182 F316L Full Bore
C 12 Connection Rating RTJ ASME 1500#
C1 13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
C 14 Packing Lubrication & Isolation Expanded Graphite VTA
15 Bonnet Bolts Bonnet Nuts ASTM A193 B8M ASTM A194 8M
C 16 Ball Material Stem Material 316 SS 316 SS
C1 17 Leakage Rate Seat Material ISO 5028 Rate A PTFE OR NYLON
18 NACE Requirement Yes
C 19 Type Stroking Time Pneumatic Piston / Spring return 4 Seconds
20 Size Safety Factor VTA in 1.3
21 Actuator Orientation Actuator Form Horizontal Cylinder
22 Ingress Protection Electrical Protection IP65 Eex i
23 Instrument Air Supply 80-120 Psig
24 Action on Air Failure Action on Power Failure Closed Closed
ACTUATOR 25 Fireproofing No
26 Solenoid Valve Schematic Detail Yes Type-1
27 Limit Switch Closed Limit Swich Open Yes Yes
28 Mounting Position Solenoid Power Supply Top 24VDC
29 Manual Reset No
30 Mechanical Position Indicator Red Closed / Green Open
C 31 Partial Stroke Facility No
31 Signal Cable 1/2" NPT
ELECTRICAL 32 Control Cable -
CONNECTIONS 33 Solenoid Cable 3/4" NPT
34
35 Fluid
Fl id Hydrocarbon
H d b
36 Phase Liquid
C 37 Operating Pressure 852 psig
38 Design Pressure 1300 psig
39 Operating Temperature 60 ºF
40 Design Temperature 130 ºF
PROCESS DATA
41 Max. Diff. Pressure for Actuator Size 1300 psig
42
43 Line Size and Sch. Inlet Outlet 2 in Sch. 80S 2 in Sch. 80S
44 Speed of Operation Design VTA
45 (Seconds) Actual VTA
46
Notes
1. VTA : Vendor to advice
2. Actuated ball valve and actuator shall be provided with 316 SS nameplate engraved or die stamped with Valve Tag No., Manufacturer's Name,
Model No., Valve Size & Rating.
3. Vendor shall be responsible for the proper design and selection of valve, actuator, and accessories based on the information furnished
C1 in this specification. This Data Sheet shall refer to SNO-I-ES-013, Instrument Specification for Shutdown and Blowdown Valve
4. Actuator shall be sized based on valve manufacturer's required Torque values with 130% minimum safety margin to open or close the valve
against full ANSI rated differential pressure at minimum pneumatic supply pressure of 60 psig.
5. Vendor shall provide Torque table containing breaking, running and seating torques for valves and actuator along with Quotation.
Vendor shall provide the torque table and calculation for COMPANY approval.
6. Actuator and accessories shall be supplied fully assembled, tubed and tested ready for installation.
7. Solenoid valve coil shall be provided with reverse polarity protection diodes, integral outlet box and terminal strip for cable connection.
8. Three way valve shall be universal type. Solenoid Coil shall be Class H.
Air filter regulator shall be 316 SS Material and equipped with pressure gauge on inlet and outlet of air filter regulator.
C1 9. All SDV & BDV shall be designed & tested as per API 6D
C1 10. Valve Stem Shall be Anti-Blowout Type.

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 40 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
1 Tag No. Quantity SDV -6104A / 6204A 2 (Two)
2 Manufacturer Model VTA VTA
3 Contract No. Requisition Item No.
4 Location Central Processing Plant
GENERAL
5 P&ID No. SNO-R-PI-019 / SNO-R-PI-054
6 Service Stabilizer Condensate Cooler to Condensate Storage Tank
C 7 Line No. 4"-HL-1120-3A / 4"-HL-2120-3A
8 Area Classification Zone-2, Gr. IIB, T3
C1 9 Valve Type Valve Code Trunnion Mounted Ball BA008
10 Body Size Body Form 4 in Ball
11 Body Material Port Size ASTM A216 WCB Full Bore
12 Connection Rating RF Flange ASME 300#
C1 13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
C 14 Packing Lubrication & Isolation Expanded Graphite VTA
C 15 Bonnet Bolts Bonnet Nuts ASTM A193 B7 ASTM A194 2H
C 16 Ball Material Stem Material 316 SS CS+ENP 76μm
C1 17 Leakage Rate Seat Material ISO 5028 Rate A PTFE
18 NACE Requirement No
C 19 Type Stroking Time Pneumatic Piston / Spring return 8 Seconds
20 Size Safety Factor VTA in 1.3
21 Actuator Orientation Actuator Form Horizontal Cylinder
22 Ingress Protection Electrical Protection IP65 Eex i
23 Instrument Air Supply 80-120 Psig
24 Action on Air Failure Action on Power Failure Closed Closed
ACTUATOR 25 Fireproofing No
26 Solenoid Valve Schematic Detail Yes Type-1
27 Limit Switch Closed Limit Swich Open Yes Yes
28 Mounting Position Solenoid Power Supply Top 24VDC
29 Manual Reset No
30 Mechanical Position Indicator Red Closed / Green Open
C 31 Partial Stroke Facility No
31 Signal Cable 1/2" NPT
ELECTRICAL 32 Control Cable -
CONNECTIONS 33 Solenoid Cable 3/4" NPT
34
35 Fluid
Fl id Hydrocarbon
H d b
36 Phase Liquid
C 37 Operating Pressure 122 psig
38 Design Pressure 210 psig
39 Operating Temperature 120 ºF
40 Design Temperature 150 ºF
PROCESS DATA
41 Max. Diff. Pressure for Actuator Size 210 psig
42
43 Line Size and Sch. Inlet Outlet 4 in Sch. 40 4 in Sch. 40
44 Speed of Operation Design VTA
45 (Seconds) Actual VTA
46
Notes
1. VTA : Vendor to advice
2. Actuated ball valve and actuator shall be provided with 316 SS nameplate engraved or die stamped with Valve Tag No., Manufacturer's Name,
Model No., Valve Size & Rating.
3. Vendor shall be responsible for the proper design and selection of valve, actuator, and accessories based on the information furnished
C1 in this specification. This Data Sheet shall refer to SNO-I-ES-013, Instrument Specification for Shutdown and Blowdown Valve
4. Actuator shall be sized based on valve manufacturer's required Torque values with 130% minimum safety margin to open or close the valve
against full ANSI rated differential pressure at minimum pneumatic supply pressure of 60 psig.
5. Vendor shall provide Torque table containing breaking, running and seating torques for valves and actuator along with Quotation.
Vendor shall provide the torque table and calculation for COMPANY approval.
6. Actuator and accessories shall be supplied fully assembled, tubed and tested ready for installation.
7. Solenoid valve coil shall be provided with reverse polarity protection diodes, integral outlet box and terminal strip for cable connection.
8. Three way valve shall be universal type. Solenoid Coil shall be Class H.
Air filter regulator shall be 316 SS Material and equipped with pressure gauge on inlet and outlet of air filter regulator.
C1 9. All SDV & BDV shall be designed & tested as per API 6D
C1 10. Valve Stem Shall be Anti-Blowout Type.

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 41 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
1 Tag No. Quantity XV -6005A 1 (One)
2 Manufacturer Model VTA VTA
3 Contract No. Requisition Item No.
4 Location Central Processing Plant
GENERAL
5 P&ID No. SNO-R-PI-020
6 Service Condensate Storage Tank SN0-T-6001 Inlet
7 Line No. 6"-HL-1015-3A
8 Area Classification Zone-2, Gr. IIB, T3
9 Valve Type Valve Code Trunnion Mounted Ball BA010
10 Body Size Body Form 6 in Ball
11 Body Material Port Size ASTM A216 WCB Full Bore
12 Connection Rating RF Flange ASME 300#
C 13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
C 14 Packing Lubrication & Isolation Expanded Graphite VTA
C 15 Bonnet Bolts Bonnet Nuts ASTM A193 B7 ASTM A194 2H
C 16 Ball Material Stem Material 316 SS CS+ENP 76μm
C 17 Leakage Rate Seat Material ISO 5028 Rate A PTFE
18 NACE Requirement No
C 19 Type Stroking Time Pneumatic Piston / Spring return 12 Seconds
20 Size Safety Factor VTA in 1.3
21 Actuator Orientation Actuator Form Horizontal Cylinder
22 Ingress Protection Electrical Protection IP65 Eex i
23 Instrument Air Supply 80-120 Psig
24 Action on Air Failure Action on Power Failure Closed Closed
ACTUATOR 25 Fireproofing No
26 Solenoid Valve Schematic Detail Yes (Note 10) Type-10
27 Limit Switch Closed Limit Swich Open Yes Yes
28 Mounting Position Solenoid Power Supply Top 24VDC
29 Manual Reset No
30 Mechanical Position Indicator Red Closed / Green Open
C 31 Partial Stroke Facility No
31 Signal Cable 1/2" NPT
ELECTRICAL 32 Control Cable -
CONNECTIONS 33 Solenoid Cable 3/4" NPT
34
35 Fluid
Fl id Hydrocarbon
H d b
36 Phase Liquid
C 37 Operating Pressure 0.25 psig
38 Design Pressure 210 psig
39 Operating Temperature 120 ºF
40 Design Temperature 200 ºF
PROCESS DATA
41 Max. Diff. Pressure for Actuator Size 210 psig
42
43 Line Size and Sch. Inlet Outlet 6 in Sch. 40 6 in Sch. 40
44 Speed of Operation Design VTA
45 (Seconds) Actual VTA
46
Notes
1. VTA : Vendor to advice
2. Actuated ball valve and actuator shall be provided with 316 SS nameplate engraved or die stamped with Valve Tag No., Manufacturer's Name,
Model No., Valve Size & Rating.
3. Vendor shall be responsible for the proper design and selection of valve, actuator, and accessories based on the information furnished
C1 in this specification. This Data Sheet shall refer to SNO-I-ES-013, Instrument Specification for Shutdown and Blowdown Valve
4. Actuator shall be sized based on valve manufacturer's required Torque values with 130% minimum safety margin to open or close the valve
against full ANSI rated differential pressure at minimum pneumatic supply pressure of 60 psig.
5. Vendor shall provide Torque table containing breaking, running and seating torques for valves and actuator along with Quotation.
Vendor shall provide the torque table and calculation for COMPANY approval.
6. Actuator and accessories shall be supplied fully assembled, tubed and tested ready for installation.
7. Solenoid valve coil shall be provided with reverse polarity protection diodes, integral outlet box and terminal strip for cable connection.
Three way valve shall be universal type. Solenoid Coil shall be Class H.
8. Air filter regulator shall be 316 SS Material and equipped with pressure gauge on inlet and outlet of air filter regulator.
C1 9. All SDV & BDV shall be designed & tested as per API 6D
C1 10. Valve Stem Shall be Anti-Blowout Type.

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 42 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
1 Tag No. Quantity XV -6001A 1 (One)
2 Manufacturer Model VTA VTA
3 Contract No. Requisition Item No.
4 Location Central Processing Plant
GENERAL
5 P&ID No. SNO-R-PI-020
6 Service Condensate Storage Tank SN0-T-6001 Outlet to Condensate Transfer Pump
7 Line No. 12"-HL-0003-1A
8 Area Classification Zone-2, Gr. IIB, T3
9 Valve Type Valve Code Trunnion Mounted Ball BA005
10 Body Size Body Form 12 in Ball
11 Body Material Port Size ASTM A216 WCB Full Bore
12 Connection Rating RF Flange ASME 150#
C1 13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
C 14 Packing Lubrication & Isolation Expanded Graphite VTA
C 15 Bonnet Bolts Bonnet Nuts ASTM A193 B7 ASTM A194 2H
C 16 Ball Material Stem Material CS+ENP 76μm CS+ENP 76μm
C1 17 Leakage Rate Seat Material ISO 5028 Rate A PTFE
18 NACE Requirement No
C 19 Type Stroking Time Pneumatic Piston / Spring return 15 Seconds
20 Size Safety Factor VTA in 1.3
21 Actuator Orientation Actuator Form Horizontal Cylinder
22 Ingress Protection Electrical Protection IP65 Eex i
23 Instrument Air Supply 80-120 Psig
24 Action on Air Failure Action on Power Failure Closed Closed
ACTUATOR 25 Fireproofing No
26 Solenoid Valve Schematic Detail Yes (Note 10) Type-10
27 Limit Switch Closed Limit Swich Open Yes Yes
28 Mounting Position Solenoid Power Supply Top 24VDC
29 Manual Reset No
30 Mechanical Position Indicator Red Closed / Green Open
C 31 Partial Stroke Facility No
31 Signal Cable 1/2" NPT
ELECTRICAL 32 Control Cable -
CONNECTIONS 33 Solenoid Cable 3/4" NPT
34
35 Fluid
Fl id Hydrocarbon
H d b
36 Phase Liquid
37 Operating Pressure 8 psig
C 38 Design Pressure 50 psig
39 Operating Temperature 120 ºF
40 Design Temperature 200 ºF
PROCESS DATA
C 41 Max. Diff. Pressure for Actuator Size 50 psig
42
43 Line Size and Sch. Inlet Outlet 12 in Sch. 20 12 in Sch. 20
44 Speed of Operation Design VTA
45 (Seconds) Actual VTA
46
Notes
1. VTA : Vendor to advice
2. Actuated ball valve and actuator shall be provided with 316 SS nameplate engraved or die stamped with Valve Tag No., Manufacturer's Name,
Model No., Valve Size & Rating.
3. Vendor shall be responsible for the proper design and selection of valve, actuator, and accessories based on the information furnished
C1 in this specification. This Data Sheet shall refer to SNO-I-ES-013, Instrument Specification for Shutdown and Blowdown Valve
4. Actuator shall be sized based on valve manufacturer's required Torque values with 130% minimum safety margin to open or close the valve
against full ANSI rated differential pressure at minimum pneumatic supply pressure of 60 psig.
5. Vendor shall provide Torque table containing breaking, running and seating torques for valves and actuator along with Quotation.
Vendor shall provide the torque table and calculation for COMPANY approval.
6. Actuator and accessories shall be supplied fully assembled, tubed and tested ready for installation.
7. Solenoid valve coil shall be provided with reverse polarity protection diodes, integral outlet box and terminal strip for cable connection.
Three way valve shall be universal type. Solenoid Coil shall be Class H.
8. Air filter regulator shall be 316 SS Material and equipped with pressure gauge on inlet and outlet of air filter regulator.
C1 9. All SDV & BDV shall be designed & tested as per API 6D
C1 10. Valve Stem Shall be Anti-Blowout Type.

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 43 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
C 1 Tag No. Quantity XV -6001B 1 (One)
2 Manufacturer Model VTA VTA
3 Contract No. Requisition Item No.
4 Location Central Processing Plant
GENERAL
5 P&ID No. SNO-R-PI-021
6 Service Condensate Storage Tank SN0-T-6002 Outlet to Condensate Transfer Pump
7 Line No. 12"-HL-0004-1A
8 Area Classification Zone-2, Gr. IIB, T3
9 Valve Type Valve Code Trunnion Mounted Ball BA005
10 Body Size Body Form 12 in Ball
11 Body Material Port Size ASTM A216 WCB Full Bore
12 Connection Rating RF Flange ASME 150#
C1 13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
C 14 Packing Lubrication & Isolation Expanded Graphite VTA
C 15 Bonnet Bolts Bonnet Nuts ASTM A193 B7 ASTM A194 2H
C 16 Ball Material Stem Material CS+ENP 76μm CS+ENP 76μm
C1 17 Leakage Rate Seat Material ISO 5028 Rate A PTFE
18 NACE Requirement No
C 19 Type Stroking Time Pneumatic Piston / Spring return 15 Seconds
20 Size Safety Factor VTA in 1.3
21 Actuator Orientation Actuator Form Horizontal Cylinder
22 Ingress Protection Electrical Protection IP65 Eex i
23 Instrument Air Supply 80-120 Psig
24 Action on Air Failure Action on Power Failure Closed Closed
ACTUATOR 25 Fireproofing No
26 Solenoid Valve Schematic Detail Yes (Note 10) Type-10
27 Limit Switch Closed Limit Swich Open Yes Yes
28 Mounting Position Solenoid Power Supply Top 24VDC
29 Manual Reset No
30 Mechanical Position Indicator Red Closed / Green Open
C 31 Partial Stroke Facility No
31 Signal Cable 1/2" NPT
ELECTRICAL 32 Control Cable -
CONNECTIONS 33 Solenoid Cable 3/4" NPT
34
35 Fluid
Fl id Hydrocarbon
H d b
36 Phase Liquid
37 Operating Pressure 8 psig
C 38 Design Pressure 50 psig
39 Operating Temperature 120 ºF
40 Design Temperature 200 ºF
PROCESS DATA
C 41 Max. Diff. Pressure for Actuator Size 50 psig
42
43 Line Size and Sch. Inlet Outlet 12 in Sch. 20 12 in Sch. 20
44 Speed of Operation Design VTA
45 (Seconds) Actual VTA
46
Notes
1. VTA : Vendor to advice
2. Actuated ball valve and actuator shall be provided with 316 SS nameplate engraved or die stamped with Valve Tag No., Manufacturer's Name,
Model No., Valve Size & Rating.
3. Vendor shall be responsible for the proper design and selection of valve, actuator, and accessories based on the information furnished
C1 in this specification. This Data Sheet shall refer to SNO-I-ES-013, Instrument Specification for Shutdown and Blowdown Valve
4. Actuator shall be sized based on valve manufacturer's required Torque values with 130% minimum safety margin to open or close the valve
against full ANSI rated differential pressure at minimum pneumatic supply pressure of 60 psig.
5. Vendor shall provide Torque table containing breaking, running and seating torques for valves and actuator along with Quotation.
Vendor shall provide the torque table and calculation for COMPANY approval.
6. Actuator and accessories shall be supplied fully assembled, tubed and tested ready for installation.
7. Solenoid valve coil shall be provided with reverse polarity protection diodes, integral outlet box and terminal strip for cable connection.
Three way valve shall be universal type. Solenoid Coil shall be Class H.
8. Air filter regulator shall be 316 SS Material and equipped with pressure gauge on inlet and outlet of air filter regulator.
C1 9. All SDV & BDV shall be designed & tested as per API 6D
C1 10. Valve Stem Shall be Anti-Blowout Type.

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 44 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
1 Tag No. Quantity XV -6005B 1 (One)
2 Manufacturer Model VTA VTA
3 Contract No. Requisition Item No.
4 Location Central Processing Plant
GENERAL
5 P&ID No. SNO-R-PI-021
6 Service Condensate Degassing Coloumn Inlet
C 7 Line No. 6"-HL-0001-3A
8 Area Classification Zone-2, Gr. IIB, T3
9 Valve Type Valve Code Trunnion Mounted Ball BA010
10 Body Size Body Form 6 in Ball
11 Body Material Port Size ASTM A216 WCB Full Bore
12 Connection Rating RF Flange ASME 300#
C1 13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
C 14 Packing Lubrication & Isolation Expanded Graphite VTA
C 15 Bonnet Bolts Bonnet Nuts ASTM A193 B7 ASTM A194 2H
C 16 Ball Material Stem Material 316 SS CS+ENP 76μm
C1 17 Leakage Rate Seat Material ISO 5028 Rate A PTFE
18 NACE Requirement No
C 19 Type Stroking Time Pneumatic Piston / Spring return 12 Seconds
20 Size Safety Factor VTA in 1.3
21 Actuator Orientation Actuator Form Horizontal Cylinder
22 Ingress Protection Electrical Protection IP65 Eex i
23 Instrument Air Supply 80-120 Psig
24 Action on Air Failure Action on Power Failure Closed Closed
ACTUATOR 25 Fireproofing No
26 Solenoid Valve Schematic Detail Yes (Note 10) Type-10
27 Limit Switch Closed Limit Swich Open Yes Yes
28 Mounting Position Solenoid Power Supply Top 24VDC
29 Manual Reset No
30 Mechanical Position Indicator Red Closed / Green Open
C 31 Partial Stroke Facility No
31 Signal Cable 1/2" NPT
ELECTRICAL 32 Control Cable -
CONNECTIONS 33 Solenoid Cable 3/4" NPT
34
35 Fluid
Fl id Hydrocarbon
H d b
36 Phase Liquid
C 37 Operating Pressure 0.25 psig
38 Design Pressure 210 psig
39 Operating Temperature 120 ºF
40 Design Temperature 200 ºF
PROCESS DATA
41 Max. Diff. Pressure for Actuator Size 210 psig
42
43 Line Size and Sch. Inlet Outlet 6 in Sch. 40 6 in Sch. 40
44 Speed of Operation Design VTA
45 (Seconds) Actual VTA
46
Notes
1. VTA : Vendor to advice
2. Actuated ball valve and actuator shall be provided with 316 SS nameplate engraved or die stamped with Valve Tag No., Manufacturer's Name,
Model No., Valve Size & Rating.
3. Vendor shall be responsible for the proper design and selection of valve, actuator, and accessories based on the information furnished
C1 in this specification. This Data Sheet shall refer to SNO-I-ES-013, Instrument Specification for Shutdown and Blowdown Valve
4. Actuator shall be sized based on valve manufacturer's required Torque values with 130% minimum safety margin to open or close the valve
against full ANSI rated differential pressure at minimum pneumatic supply pressure of 60 psig.
5. Vendor shall provide Torque table containing breaking, running and seating torques for valves and actuator along with Quotation.
Vendor shall provide the torque table and calculation for COMPANY approval.
6. Actuator and accessories shall be supplied fully assembled, tubed and tested ready for installation.
7. Solenoid valve coil shall be provided with reverse polarity protection diodes, integral outlet box and terminal strip for cable connection.
Three way valve shall be universal type. Solenoid Coil shall be Class H.
8. Air filter regulator shall be 316 SS Material and equipped with pressure gauge on inlet and outlet of air filter regulator.
C1 9. All SDV & BDV shall be designed & tested as per API 6D
C1 10. Valve Stem Shall be Anti-Blowout Type.

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 45 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
C 1 Tag No. Quantity BDV-5108A / 5208A 2 (Two)
2 Manufacturer Model VTA VTA
3 Contract No. Requisition Item No.
4 Location Central Processing Plant
GENERAL
C 5 P&ID No. SNO-R-PI-023 / 055
6 Service From Propane Refrigerant Package to HP Flare Header
C1 7 Line No. 4"-HD-1052-3A / 4"-HD-2052-3A
8 Area Classification Zone-2, Gr. IIB, T3
C1 9 Valve Type Valve Code Trunnion Mounted Ball BA008
C1 10 Body Size Body Form 4 in Ball
11 Body Material Port Size ASTM A216 WCB Full Bore
12 Connection Rating RF Flange ASME 300#
C1 13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
C 14 Packing Lubrication & Isolation Expanded Graphite VTA
C 15 Bonnet Bolts Bonnet Nuts ASTM A193 B7 ASTM A194 2H
C 16 Ball Material Stem Material 316 SS CS+ENP 76μm
C1 17 Leakage Rate Seat Material ISO 5028 Rate A (TSO) PTFE
18 NACE Requirement No
C 19 Type Stroking Time Pneumatic Piston / Spring return 8 Seconds
20 Size Safety Factor VTA in 1.3
21 Actuator Orientation Actuator Form Horizontal Cylinder
22 Ingress Protection Electrical Protection IP65 Eex i
23 Instrument Air Supply 80-120 Psig
24 Action on Air Failure Action on Power Failure Open Open
ACTUATOR 25 Fireproofing No
26 Solenoid Valve Schematic Detail Yes Type-2
27 Limit Switch Closed Limit Swich Open Yes Yes
28 Mounting Position Solenoid Power Supply Top 24VDC
29 Manual Reset No
30 Mechanical Position Indicator Red Closed / Green Open
C 31 Partial Stroke Facility No
31 Signal Cable 1/2" NPT
ELECTRICAL 32 Control Cable -
CONNECTIONS 33 Solenoid Cable 3/4" NPT
34
35 Fluid
Fl id Hydrocarbon
H d b
36 Phase Gas
C 37 Operating Pressure 215 psig
C 38 Design Pressure 275 psig
C 39 Operating Temperature 115 ºF
C 40 Design Temperature 200 ºF
PROCESS DATA
C 41 Max. Diff. Pressure for Actuator Size 275 psig
42
C1 43 Line Size and Sch. Inlet Outlet 4 in Sch. 40 4 in Sch. 40
44 Speed of Operation Design VTA
45 (Seconds) Actual VTA
46
Notes
1. VTA : Vendor to advice
2. Actuated ball valve and actuator shall be provided with 316 SS nameplate engraved or die stamped with Valve Tag No., Manufacturer's Name,
Model No., Valve Size & Rating.
3. Vendor shall be responsible for the proper design and selection of valve, actuator, and accessories based on the information furnished
C1 in this specification. This Data Sheet shall refer to SNO-I-ES-013, Instrument Specification for Shutdown and Blowdown Valve
4. Actuator shall be sized based on valve manufacturer's required Torque values with 130% minimum safety margin to open or close the valve
against full ANSI rated differential pressure at minimum pneumatic supply pressure of 60 psig.
5. Vendor shall provide Torque table containing breaking, running and seating torques for valves and actuator along with Quotation.
Vendor shall provide the torque table and calculation for COMPANY approval.
6. Actuator and accessories shall be supplied fully assembled, tubed and tested ready for installation.
7. Solenoid valve coil shall be provided with reverse polarity protection diodes, integral outlet box and terminal strip for cable connection.
Three way valve shall be universal type. Solenoid Coil shall be Class H.
8. Air filter regulator shall be 316 SS Material and equipped with pressure gauge on inlet and outlet of air filter regulator.
C1 9. All SDV & BDV shall be designed & tested as per API 6D
C1 10. Valve Stem Shall be Anti-Blowout Type.

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 46 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
1 Tag No. Quantity BDV -5020A 1 (One)
2 Manufacturer Model VTA VTA
3 Contract No. Requisition Item No.
4 Location Central Processing Plant
GENERAL
5 P&ID No. SNO-R-PI-024
6 Service Sales Gas Export Launcher to HP Flare Header
7 Line No. 2"-HG-0021-6A
8 Area Classification Zone-2, Gr. IIB, T3
C1 9 Valve Type Valve Code Trunnion Mounted Ball BA013
10 Body Size Body Form 2 in Ball
C 11 Body Material Port Size A216 WCB Full Bore
12 Connection Rating RF Flange ASME 600#
C1 13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
C 14 Packing Lubrication & Isolation Expanded Graphite VTA
C 15 Bonnet Bolts Bonnet Nuts ASTM A193 B7 ASTM A194 2H
C 16 Ball Material Stem Material CS+ENP 76μm A564 630, H1150M+ENP 76 μm
C1 17 Leakage Rate Seat Material ISO 5028 Rate A (TSO) PTFE OR NYLON
18 NACE Requirement No
C 19 Type Stroking Time Pneumatic Piston / Spring return 4 Seconds
20 Size Safety Factor VTA in 1.3
21 Actuator Orientation Actuator Form Horizontal Cylinder
22 Ingress Protection Electrical Protection IP65 Eex i
23 Instrument Air Supply 80-120 Psig
24 Action on Air Failure Action on Power Failure Open Open
ACTUATOR 25 Fireproofing No
26 Solenoid Valve Schematic Detail Yes Type 2
27 Limit Switch Closed Limit Swich Open Yes Yes
28 Mounting Position Solenoid Power Supply Top 24VDC
29 Manual Reset No
30 Mechanical Position Indicator Red Closed / Green Open
C 31 Partial Stroke Facility No
31 Signal Cable 1/2" NPT
ELECTRICAL 32 Control Cable -
CONNECTIONS 33 Solenoid Cable 3/4" NPT
34
35 Fluid
Fl id Hydrocarbon
H d b
36 Phase Gas
C 37 Operating Pressure 825 psig
38 Design Pressure 1100 psig
39 Operating Temperature 100 ºF
40 Design Temperature 150 ºF
PROCESS DATA
41 Max. Diff. Pressure for Actuator Size 1100 psig
42
43 Line Size and Sch. Inlet Outlet 2 in Sch. 160 2 in Sch. 160
44 Speed of Operation Design VTA
45 (Seconds) Actual VTA
46
Notes
1. VTA : Vendor to advice
2. Actuated ball valve and actuator shall be provided with 316 SS nameplate engraved or die stamped with Valve Tag No., Manufacturer's Name,
Model No., Valve Size & Rating.
3. Vendor shall be responsible for the proper design and selection of valve, actuator, and accessories based on the information furnished
C1 in this specification. This Data Sheet shall refer to SNO-I-ES-013, Instrument Specification for Shutdown and Blowdown Valve
4. Actuator shall be sized based on valve manufacturer's required Torque values with 130% minimum safety margin to open or close the valve
against full ANSI rated differential pressure at minimum pneumatic supply pressure of 60 psig.
5. Vendor shall provide Torque table containing breaking, running and seating torques for valves and actuator along with Quotation.
Vendor shall provide the torque table and calculation for COMPANY approval.
6. Actuator and accessories shall be supplied fully assembled, tubed and tested ready for installation.
7. Solenoid valve coil shall be provided with reverse polarity protection diodes, integral outlet box and terminal strip for cable connection.
8. Three way valve shall be universal type. Solenoid Coil shall be Class H.
Air filter regulator shall be 316 SS Material and equipped with pressure gauge on inlet and outlet of air filter regulator.
C1 9. All SDV & BDV shall be designed & tested as per API 6D
C1 10. Valve Stem Shall be Anti-Blowout Type.

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 47 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
1 Tag No. Quantity SDV -5020C 1 (One)
2 Manufacturer Model VTA VTA
3 Contract No. Requisition Item No.
4 Location Central Processing Plant
GENERAL
5 P&ID No. SNO-R-PI-024
6 Service Sales Gas Export Launcher Outlet
C 7 Line No. 30"-HG-xxxx-6A
8 Area Classification Zone-2, Gr. IIB, T3
9 Valve Type Valve Code Trunnion Mounted Ball BA015
10 Body Size Body Form 30 in Ball
C 11 Body Material Port Size A105 Full Bore
12 Connection Rating RF Flange ASME 600#
C1 13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
C 14 Packing Lubrication & Isolation Expanded Graphite VTA
C 15 Bonnet Bolts Bonnet Nuts A193 B7 A194 2H
C 16 Ball Material Stem Material CS+ENP 76μm A564 630, H1150M+ENP 76 μm
C1 17 Leakage Rate Seat Material ISO 5028 Rate A PTFE OR NYLON
18 NACE Requirement No
C 19 Type Stroking Time Pneumatic Piston / Spring return 30 Seconds
C 20 Size Safety Factor VTA in 1.5
21 Actuator Orientation Actuator Form Horizontal Cylinder
22 Ingress Protection Electrical Protection IP65 Eex i
23 Instrument Air Supply 80-120 Psig
24 Action on Air Failure Action on Power Failure Closed Closed
ACTUATOR 25 Fireproofing No
26 Solenoid Valve Schematic Detail Yes Type 1
27 Limit Switch Closed Limit Swich Open Yes Yes
28 Mounting Position Solenoid Power Supply Top 24VDC
29 Manual Reset No
30 Mechanical Position Indicator Red Closed / Green Open
C 31 Partial Stroke Facility Yes
31 Signal Cable 1/2" NPT
ELECTRICAL 32 Control Cable -
CONNECTIONS 33 Solenoid Cable 3/4" NPT
34
35 Fluid
Fl id Hydrocarbon
H d b
36 Phase Gas
C 37 Operating Pressure 825 psig
38 Design Pressure 1100 psig
39 Operating Temperature 100 ºF
40 Design Temperature 150 ºF
PROCESS DATA
41 Max. Diff. Pressure for Actuator Size 1100 psig
42
43 Line Size and Sch. Inlet Outlet 30 in Sch. Note 30 in Sch. Note 10
44 Speed of Operation Design VTA
45 (Seconds) Actual VTA
46
Notes
1. VTA : Vendor to advice
2. Actuated ball valve and actuator shall be provided with 316 SS nameplate engraved or die stamped with Valve Tag No., Manufacturer's Name,
Model No., Valve Size & Rating.
3. Vendor shall be responsible for the proper design and selection of valve, actuator, and accessories based on the information furnished
C1 in this specification. This Data Sheet shall refer to SNO-I-ES-013, Instrument Specification for Shutdown and Blowdown Valve
4. Actuator shall be sized based on valve manufacturer's required Torque values with 130% minimum safety margin to open or close the valve
against full ANSI rated differential pressure at minimum pneumatic supply pressure of 60 psig.
5. Vendor shall provide Torque table containing breaking, running and seating torques for valves and actuator along with Quotation.
Vendor shall provide the torque table and calculation for COMPANY approval.
6. Actuator and accessories shall be supplied fully assembled, tubed and tested ready for installation.
7. Solenoid valve coil shall be provided with reverse polarity protection diodes, integral outlet box and terminal strip for cable connection.
8. Three way valve shall be universal type. Solenoid Coil shall be Class H.
Air filter regulator shall be 316 SS Material and equipped with pressure gauge on inlet and outlet of air filter regulator.
C1 9. All SDV & BDV shall be designed & tested as per API 6D
C1 10. Valve Stem Shall be Anti-Blowout Type.

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 48 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
1 Tag No. Quantity XV -5020A 1 (One)
2 Manufacturer Model VTA VTA
3 Contract No. Requisition Item No.
4 Location Central Processing Plant
GENERAL
5 P&ID No. SNO-R-PI-024
6 Service Sales Gas Export Launcher Outlet
C1 7 Line No. 2"-HG-0351-6A
8 Area Classification Zone-2, Gr. IIB, T3
9 Valve Type Valve Code Trunnion Mounted Ball BA013
10 Body Size Body Form Hold in Ball
C 11 Body Material Port Size A216 WCB Full Bore
12 Connection Rating RF Flange ASME 600#
C1 13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
C 14 Packing Lubrication & Isolation Expanded Graphite VTA
C 15 Bonnet Bolts Bonnet Nuts ASTM A193 B7 ASTM A194 2H
C 16 Ball Material Stem Material CS+ENP 76μm A564 630, H1150M+ENP 76 μm
C1 17 Leakage Rate Seat Material ISO 5028 Rate A PTFE OR NYLON
18 NACE Requirement No
C 19 Type Stroking Time Pneumatic Piston / Spring return 4 Seconds
20 Size Safety Factor VTA in 1.3
21 Actuator Orientation Actuator Form Horizontal Cylinder
22 Ingress Protection Electrical Protection IP65 Eex i
23 Instrument Air Supply 80-120 Psig
24 Action on Air Failure Action on Power Failure Closed Closed
ACTUATOR 25 Fireproofing No
26 Solenoid Valve Schematic Detail Yes (Note 10) Type 10
27 Limit Switch Closed Limit Swich Open Yes Yes
28 Mounting Position Solenoid Power Supply Top 24VDC
29 Manual Reset No
30 Mechanical Position Indicator Red Closed / Green Open
C 31 Partial Stroke Facility No
31 Signal Cable 1/2" NPT
ELECTRICAL 32 Control Cable -
CONNECTIONS 33 Solenoid Cable 3/4" NPT
34
35 Fluid
Fl id Hydrocarbon
H d b
36 Phase Gas
C 37 Operating Pressure 825 psig
38 Design Pressure 1100 psig
39 Operating Temperature 100 ºF
40 Design Temperature 150 ºF
PROCESS DATA
41 Max. Diff. Pressure for Actuator Size 1100 psig
42
43 Line Size and Sch. Inlet Outlet 2 in Sch. 160 2 in Sch. 160
44 Speed of Operation Design VTA
45 (Seconds) Actual VTA
46
Notes
1. VTA : Vendor to advice
2. Actuated ball valve and actuator shall be provided with 316 SS nameplate engraved or die stamped with Valve Tag No., Manufacturer's Name,
Model No., Valve Size & Rating.
3. Vendor shall be responsible for the proper design and selection of valve, actuator, and accessories based on the information furnished
C1 in this specification. This Data Sheet shall refer to SNO-I-ES-013, Instrument Specification for Shutdown and Blowdown Valve
4. Actuator shall be sized based on valve manufacturer's required Torque values with 130% minimum safety margin to open or close the valve
against full ANSI rated differential pressure at minimum pneumatic supply pressure of 60 psig.
5. Vendor shall provide Torque table containing breaking, running and seating torques for valves and actuator along with Quotation.
Vendor shall provide the torque table and calculation for COMPANY approval.
6. Actuator and accessories shall be supplied fully assembled, tubed and tested ready for installation.
7. Solenoid valve coil shall be provided with reverse polarity protection diodes, integral outlet box and terminal strip for cable connection.
Three way valve shall be universal type. Solenoid Coil shall be Class H.
8. Air filter regulator shall be 316 SS Material and equipped with pressure gauge on inlet and outlet of air filter regulator.
C1 9. All SDV & BDV shall be designed & tested as per API 6D
C1 10. Valve Stem Shall be Anti-Blowout Type.

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 49 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
1 Tag No. Quantity SDV -6040A 1 (One)
2 Manufacturer Model VTA VTA
3 Contract No. Requisition Item No.
4 Location Central Processing Plant
GENERAL
5 P&ID No. SNO-R-PI-025
6 Service Condensate Export Flowline to Jetty
C 7 Line No. 8"-HL-0211-1A
8 Area Classification Zone-2, Gr. IIB, T3
9 Valve Type Valve Code Trunnion Mounted Ball BA005
10 Body Size Body Form 8 in Ball
11 Body Material Port Size ASTM A216 WCB Full Bore
12 Connection Rating RF Flange ASME 150#
C1 13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
C 14 Packing Lubrication & Isolation Expanded Graphite VTA
C 15 Bonnet Bolts Bonnet Nuts ASTM A193 B7 ASTM A194 2H
C 16 Ball Material Stem Material CS+ENP 76μm CS+ENP 76μm
C1 17 Leakage Rate Seat Material ISO 5028 Rate A PTFE
18 NACE Requirement No
C 19 Type Stroking Time Pneumatic Piston / Spring return 15 Seconds
20 Size Safety Factor VTA in 1.3
21 Actuator Orientation Actuator Form Horizontal Cylinder
22 Ingress Protection Electrical Protection IP65 Eex i
23 Instrument Air Supply 80-120 Psig
24 Action on Air Failure Action on Power Failure Closed Closed
ACTUATOR 25 Fireproofing No
26 Solenoid Valve Schematic Detail Yes Type-1
27 Limit Switch Closed Limit Swich Open Yes Yes
28 Mounting Position Solenoid Power Supply Top 24VDC
29 Manual Reset No
30 Mechanical Position Indicator Red Closed / Green Open
C 31 Partial Stroke Facility No
31 Signal Cable 1/2" NPT
ELECTRICAL 32 Control Cable -
CONNECTIONS 33 Solenoid Cable 3/4" NPT
34
35 Fluid
Fl id Hydrocarbon
H d b
36 Phase Liquid
C 37 Operating Pressure 149 psig
C 38 Design Pressure 225 psig
C 39 Operating Temperature AMB ºF
C 40 Design Temperature 200 ºF
PROCESS DATA
C 41 Max. Diff. Pressure for Actuator Size 225 psig
42
43 Line Size and Sch. Inlet Outlet 8 in Sch. 20 8 in Sch. 20
44 Speed of Operation Design VTA
45 (Seconds) Actual VTA
46
Notes
1. VTA : Vendor to advice
2. Actuated ball valve and actuator shall be provided with 316 SS nameplate engraved or die stamped with Valve Tag No., Manufacturer's Name,
Model No., Valve Size & Rating.
3. Vendor shall be responsible for the proper design and selection of valve, actuator, and accessories based on the information furnished
C1 in this specification. This Data Sheet shall refer to SNO-I-ES-013, Instrument Specification for Shutdown and Blowdown Valve
4. Actuator shall be sized based on valve manufacturer's required Torque values with 130% minimum safety margin to open or close the valve
against full ANSI rated differential pressure at minimum pneumatic supply pressure of 60 psig.
5. Vendor shall provide Torque table containing breaking, running and seating torques for valves and actuator along with Quotation.
Vendor shall provide the torque table and calculation for COMPANY approval.
6. Actuator and accessories shall be supplied fully assembled, tubed and tested ready for installation.
7. Solenoid valve coil shall be provided with reverse polarity protection diodes, integral outlet box and terminal strip for cable connection.
8. Three way valve shall be universal type. Solenoid Coil shall be Class H.
Air filter regulator shall be 316 SS Material and equipped with pressure gauge on inlet and outlet of air filter regulator.
C1 9. All SDV & BDV shall be designed & tested as per API 6D
C1 10. Valve Stem Shall be Anti-Blowout Type.

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 50 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
1 Tag No. Quantity SDV -5030A 1 (One)
2 Manufacturer Model VTA VTA
3 Contract No. Requisition Item No.
4 Location Central Processing Plant
GENERAL
5 P&ID No. SNO-R-PI-027
6 Service Sales Gas Pig Receiver Inlet
C1 7 Line No. 30"-HG-0010-6H
8 Area Classification Zone-2, Gr. IIB, T3
9 Valve Type Valve Code Trunnion Mounted Ball BA015
10 Body Size Body Form 30 in Ball
C 11 Body Material Port Size A105 Full Bore
12 Connection Rating RF Flange ASME 600#
C1 13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
C 14 Packing Lubrication & Isolation Expanded Graphite VTA
15 Bonnet Bolts Bonnet Nuts ASTM A193 B7 ASTM A194 2H
C 16 Ball Material Stem Material CS+ENP 76μm A564 630, H1150M+ENP 76 μm
C1 17 Leakage Rate Seat Material ISO 5028 Rate A PTFE OR NYLON
18 NACE Requirement No
C 19 Type Stroking Time Pneumatic Piston / Spring return 30 Seconds
C 20 Size Safety Factor VTA in 1.5
21 Actuator Orientation Actuator Form Horizontal Cylinder
22 Ingress Protection Electrical Protection IP65 Eex i
23 Instrument Air Supply 80-120 Psig
24 Action on Air Failure Action on Power Failure Closed Closed
ACTUATOR 25 Fireproofing No
26 Solenoid Valve Schematic Detail Yes Type 1
27 Limit Switch Closed Limit Swich Open Yes Yes
28 Mounting Position Solenoid Power Supply Top 24VDC
29 Manual Reset No
30 Mechanical Position Indicator Red Closed / Green Open
C 31 Partial Stroke Facility Yes
31 Signal Cable 1/2" NPT
ELECTRICAL 32 Control Cable -
CONNECTIONS 33 Solenoid Cable 3/4" NPT
34
35 Fluid
Fl id Hydrocarbon
H d b
36 Phase Gas
C 37 Operating Pressure 779 psig
38 Design Pressure 1100 psig
39 Operating Temperature 100 ºF
40 Design Temperature 150 ºF
PROCESS DATA
41 Max. Diff. Pressure for Actuator Size 1100 psig
42
43 Line Size and Sch. Inlet Outlet 30 in Sch. Note 30 in Sch. Note 10
44 Speed of Operation Design VTA
45 (Seconds) Actual VTA
46
Notes
1. VTA : Vendor to advice
2. Actuated ball valve and actuator shall be provided with 316 SS nameplate engraved or die stamped with Valve Tag No., Manufacturer's Name,
Model No., Valve Size & Rating.
3. Vendor shall be responsible for the proper design and selection of valve, actuator, and accessories based on the information furnished
C1 in this specification. This Data Sheet shall refer to SNO-I-ES-013, Instrument Specification for Shutdown and Blowdown Valve
4. Actuator shall be sized based on valve manufacturer's required Torque values with 130% minimum safety margin to open or close the valve
against full ANSI rated differential pressure at minimum pneumatic supply pressure of 60 psig.
5. Vendor shall provide Torque table containing breaking, running and seating torques for valves and actuator along with Quotation.
Vendor shall provide the torque table and calculation for COMPANY approval.
6. Actuator and accessories shall be supplied fully assembled, tubed and tested ready for installation.
7. Solenoid valve coil shall be provided with reverse polarity protection diodes, integral outlet box and terminal strip for cable connection.
8. Three way valve shall be universal type. Solenoid Coil shall be Class H.
Air filter regulator shall be 316 SS Material and equipped with pressure gauge on inlet and outlet of air filter regulator.
C1 9. All SDV & BDV shall be designed & tested as per API 6D
C1 10. Valve Stem Shall be Anti-Blowout Type.

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 1 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
1 Tag No. Quantity SDV-6050A 1 (One)
2 Manufacturer Model VTA VTA
3 Contract No. Requisition Item No.
4 Location Central Processing Plant
GENERAL
5 P&ID No. SNO-R-PI-028
6 Service Condensate Export Flowline to Jetty
C 7 Line No. 8"-HL-0211-1A
8 Area Classification Zone-2, Gr. IIB, T3
9 Valve Type Valve Code Trunnion Mounted Ball BA005
10 Body Size Body Form 8 in Ball
11 Body Material Port Size ASTM A216 WCB Full Bore
12 Connection Rating RF Flange ASME 150#
C1 13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
C 14 Packing Lubrication & Isolation Expanded Graphite VTA
C 15 Bonnet Bolts Bonnet Nuts ASTM A193 B7 ASTM A194 2H
C 16 Ball Material Stem Material CS+ENP 76μm CS+ENP 76μm
C1 17 Leakage Rate Seat Material ISO 5028 Rate A PTFE
18 NACE Requirement No
C 19 Type Stroking Time Pneumatic Piston / Spring return 15 Seconds
20 Size Safety Factor VTA in 1.3
21 Actuator Orientation Actuator Form Horizontal Cylinder
22 Ingress Protection Electrical Protection IP65 Eex i
23 Instrument Air Supply 80-120 Psig
24 Action on Air Failure Action on Power Failure Closed Closed
ACTUATOR 25 Fireproofing No
26 Solenoid Valve Schematic Detail Yes Type-1
27 Limit Switch Closed Limit Swich Open Yes Yes
28 Mounting Position Solenoid Power Supply Top 24VDC
29 Manual Reset No
30 Mechanical Position Indicator Red Closed / Green Open
C 31 Partial Stroke Facility No
31 Signal Cable 1/2" NPT
ELECTRICAL 32 Control Cable -
CONNECTIONS 33 Solenoid Cable 3/4" NPT
34
35 Fluid
Fl id Hydrocarbon
H d b
36 Phase Liquid
C 37 Operating Pressure 149 psig
C 38 Design Pressure 225 psig
C 39 Operating Temperature AMB ºF
C 40 Design Temperature 200 ºF
PROCESS DATA
C 41 Max. Diff. Pressure for Actuator Size 225 psig
42
43 Line Size and Sch. Inlet Outlet 8 in Sch. 20 8 in Sch. 20
44 Speed of Operation Design VTA
45 (Seconds) Actual VTA
46
Notes
1. VTA : Vendor to advice
2. Actuated ball valve and actuator shall be provided with 316 SS nameplate engraved or die stamped with Valve Tag No., Manufacturer's Name,
Model No., Valve Size & Rating.
3. Vendor shall be responsible for the proper design and selection of valve, actuator, and accessories based on the information furnished
C1 in this specification. This Data Sheet shall refer to SNO-I-ES-013, Instrument Specification for Shutdown and Blowdown Valve
4. Actuator shall be sized based on valve manufacturer's required Torque values with 130% minimum safety margin to open or close the valve
against full ANSI rated differential pressure at minimum pneumatic supply pressure of 60 psig.
5. Vendor shall provide Torque table containing breaking, running and seating torques for valves and actuator along with Quotation.
Vendor shall provide the torque table and calculation for COMPANY approval.
6. Actuator and accessories shall be supplied fully assembled, tubed and tested ready for installation.
7. Solenoid valve coil shall be provided with reverse polarity protection diodes, integral outlet box and terminal strip for cable connection.
8. Three way valve shall be universal type. Solenoid Coil shall be Class H.
Air filter regulator shall be 316 SS Material and equipped with pressure gauge on inlet and outlet of air filter regulator.
C1 9. All SDV & BDV shall be designed & tested as per API 6D
C1 10. Valve Stem Shall be Anti-Blowout Type.

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 52 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
1 Tag No. Quantity XV -7002B 1 (One)
2 Manufacturer Model VTA VTA
3 Contract No. Requisition Item No.
4 Location Central Processing Plant
GENERAL
5 P&ID No. SNO-R-PI-031
6 Service Produced Water Tank SNO-T-7002 To Water Injection Pump
7 Line No. 4"-WW-0003-1N
8 Area Classification Zone-2, Gr. IIB, T3
C1 9 Valve Type Valve Code Trunnion Mounted Ball BA098
10 Body Size Body Form 4 in Ball
11 Body Material Port Size ASTM A351 CF8M Full Bore
12 Connection Rating RF Flange ASME 150#
C1 13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
C 14 Packing Lubrication & Isolation Expanded Graphite VTA
15 Bonnet Bolts Bonnet Nuts ASTM A193 B8M CL2 ASTM A194 8M
C 16 Ball Material Stem Material 316 SS 316 SS
C1 17 Leakage Rate Seat Material ISO 5028 Rate A PTFE
18 NACE Requirement Yes
C 19 Type Stroking Time Pneumatic Piston / Spring return 8 Seconds
20 Size Safety Factor VTA in 1.3
21 Actuator Orientation Actuator Form Horizontal Cylinder
22 Ingress Protection Electrical Protection IP65 Eex i
23 Instrument Air Supply 80-120 Psig
24 Action on Air Failure Action on Power Failure Closed Closed
ACTUATOR 25 Fireproofing No
26 Solenoid Valve Schematic Detail Yes (Note 10) Type 10
27 Limit Switch Closed Limit Swich Open Yes Yes
28 Mounting Position Solenoid Power Supply Top 24VDC
29 Manual Reset No
30 Mechanical Position Indicator Red Closed / Green Open
C 31 Partial Stroke Facility No
31 Signal Cable 1/2" NPT
ELECTRICAL 32 Control Cable -
CONNECTIONS 33 Solenoid Cable 3/4" NPT
34
35 Fluid
Fl id Water
W t
36 Phase Liquid
C 37 Operating Pressure 0.1 psig
C 38 Design Pressure 50 psig
39 Operating Temperature 100 ºF
40 Design Temperature 150 ºF
PROCESS DATA
C 41 Max. Diff. Pressure for Actuator Size 50 psig
42
43 Line Size and Sch. Inlet Outlet 4 in Sch. 10S 4 in Sch. 10S
44 Speed of Operation Design VTA
45 (Seconds) Actual VTA
46
Notes
1. VTA : Vendor to advice
2. Actuated ball valve and actuator shall be provided with 316 SS nameplate engraved or die stamped with Valve Tag No., Manufacturer's Name,
Model No., Valve Size & Rating.
3. Vendor shall be responsible for the proper design and selection of valve, actuator, and accessories based on the information furnished
C1 in this specification. This Data Sheet shall refer to SNO-I-ES-013, Instrument Specification for Shutdown and Blowdown Valve
4. Actuator shall be sized based on valve manufacturer's required Torque values with 130% minimum safety margin to open or close the valve
against full ANSI rated differential pressure at minimum pneumatic supply pressure of 60 psig.
5. Vendor shall provide Torque table containing breaking, running and seating torques for valves and actuator along with Quotation.
Vendor shall provide the torque table and calculation for COMPANY approval.
6. Actuator and accessories shall be supplied fully assembled, tubed and tested ready for installation.
7. Solenoid valve coil shall be provided with reverse polarity protection diodes, integral outlet box and terminal strip for cable connection.
8. Three way valve shall be universal type. Solenoid Coil shall be Class H.
Air filter regulator shall be 316 SS Material and equipped with pressure gauge on inlet and outlet of air filter regulator.
C1 9. All SDV & BDV shall be designed & tested as per API 6D
C1 10. Valve Stem Shall be Anti-Blowout Type.

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 53 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
1 Tag No. Quantity SDV -7010A 1 (One)
2 Manufacturer Model VTA VTA
3 Contract No. Requisition Item No.
4 Location Central Processing Plant
GENERAL
5 P&ID No. SNO-R-PI-032
6 Service Produced Water to Re-Injection Well No.4
C 7 Line No. 4"-WW-0024-15N
8 Area Classification Zone-2, Gr. IIB, T3
9 Valve Type Valve Code Trunnion Mounted Ball BA487
10 Body Size Body Form 4 in Ball
11 Body Material Port Size ASTM A351 CF8M Full Bore
12 Connection Rating RTJ ASME 1500#
C1 13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
C 14 Packing Lubrication & Isolation Expanded Graphite VTA
15 Bonnet Bolts Bonnet Nuts ASTM A193 B8M CL2 ASTM A194 8M
C 16 Ball Material Stem Material 316 SS 316 SS
C1 17 Leakage Rate Seat Material ISO 5028 Rate A PTFE OR NYLON
18 NACE Requirement Yes
C 19 Type Stroking Time Pneumatic Piston / Spring return 8 Seconds
20 Size Safety Factor VTA in 1.3
21 Actuator Orientation Actuator Form Horizontal Cylinder
22 Ingress Protection Electrical Protection IP65 Eex i
23 Instrument Air Supply 80-120 Psig
24 Action on Air Failure Action on Power Failure Closed Closed
ACTUATOR 25 Fireproofing No
26 Solenoid Valve Schematic Detail Yes Type-1
27 Limit Switch Closed Limit Swich Open Yes Yes
28 Mounting Position Solenoid Power Supply Top 24VDC
29 Manual Reset No
30 Mechanical Position Indicator Red Closed / Green Open
C 31 Partial Stroke Facility No
31 Signal Cable 1/2" NPT
ELECTRICAL 32 Control Cable -
CONNECTIONS 33 Solenoid Cable 3/4" NPT
34
35 Fluid
Fl id Water
W t
36 Phase Liquid
C 37 Operating Pressure 1580 psig
C 38 Design Pressure 1800 psig
C 39 Operating Temperature 120 ºF
C 40 Design Temperature 140 ºF
PROCESS DATA
C 41 Max. Diff. Pressure for Actuator Size 1800 psig
42
43 Line Size and Sch. Inlet Outlet 4 in Sch. 160 4 in Sch. 160
44 Speed of Operation Design VTA
45 (Seconds) Actual VTA
46
Notes
1. VTA : Vendor to advice
2. Actuated ball valve and actuator shall be provided with 316 SS nameplate engraved or die stamped with Valve Tag No., Manufacturer's Name,
Model No., Valve Size & Rating.
3. Vendor shall be responsible for the proper design and selection of valve, actuator, and accessories based on the information furnished
C1 in this specification. This Data Sheet shall refer to SNO-I-ES-013, Instrument Specification for Shutdown and Blowdown Valve
4. Actuator shall be sized based on valve manufacturer's required Torque values with 130% minimum safety margin to open or close the valve
against full ANSI rated differential pressure at minimum pneumatic supply pressure of 60 psig.
5. Vendor shall provide Torque table containing breaking, running and seating torques for valves and actuator along with Quotation.
Vendor shall provide the torque table and calculation for COMPANY approval.
6. Actuator and accessories shall be supplied fully assembled, tubed and tested ready for installation.
7. Solenoid valve coil shall be provided with reverse polarity protection diodes, integral outlet box and terminal strip for cable connection.
Three way valve shall be universal type. Solenoid Coil shall be Class H.
8. Air filter regulator shall be 316 SS Material and equipped with pressure gauge on inlet and outlet of air filter regulator.
C1 9. All SDV & BDV shall be designed & tested as per API 6D
C1 10. Valve Stem Shall be Anti-Blowout Type.

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 54 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
1 Tag No. Quantity SDV -5010C 1 (One)
2 Manufacturer Model VTA VTA
3 Contract No. Requisition Item No.
4 Location Central Processing Plant
GENERAL
5 P&ID No. SNO-R-PI-033
6 Service Sales Gas Pig Receiver Inlet
7 Line No. 20"-HG-0008-6A
8 Area Classification Zone-2, Gr. IIB, T3
9 Valve Type Valve Code Trunnion Mounted Ball BA015
10 Body Size Body Form 20 in Ball
C 11 Body Material Port Size A105 Full Bore
12 Connection Rating RF Flange ASME 600#
C1 13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
C 14 Packing Lubrication & Isolation Expanded Graphite VTA
15 Bonnet Bolts Bonnet Nuts ASTM A193 B7 ASTM A194 2H
C 16 Ball Material Stem Material CS+ENP 76μm A564 630, H1150M+ENP 76 μm
C1 17 Leakage Rate Seat Material ISO 5028 Rate A PTFE OR NYLON
18 NACE Requirement No
C 19 Type Stroking Time Pneumatic Piston / Spring return 15 Seconds
C 20 Size Safety Factor VTA in 1.5
21 Actuator Orientation Actuator Form Horizontal Cylinder
22 Ingress Protection Electrical Protection IP65 Eex i
23 Instrument Air Supply 80-120 Psig
24 Action on Air Failure Action on Power Failure Closed Closed
ACTUATOR 25 Fireproofing No
26 Solenoid Valve Schematic Detail Yes Type 1
27 Limit Switch Closed Limit Swich Open Yes Yes
28 Mounting Position Solenoid Power Supply Top 24VDC
29 Manual Reset No
30 Mechanical Position Indicator Red Closed / Green Open
C 31 Partial Stroke Facility Yes
31 Signal Cable 1/2" NPT
ELECTRICAL 32 Control Cable -
CONNECTIONS 33 Solenoid Cable 3/4" NPT
34
35 Fluid
Fl id Hydrocarbon
H d b
36 Phase Gas
C 37 Operating Pressure 775 psig
38 Design Pressure 1100 psig
39 Operating Temperature 95 ºF
40 Design Temperature 150 ºF
PROCESS DATA
41 Max. Diff. Pressure for Actuator Size 1100 psig
42
43 Line Size and Sch. Inlet Outlet 20 in Sch. 80 20 in Sch. 80
44 Speed of Operation Design VTA
45 (Seconds) Actual VTA
46
Notes
1. VTA : Vendor to advice
2. Actuated ball valve and actuator shall be provided with 316 SS nameplate engraved or die stamped with Valve Tag No., Manufacturer's Name,
Model No., Valve Size & Rating.
3. Vendor shall be responsible for the proper design and selection of valve, actuator, and accessories based on the information furnished
C1 in this specification. This Data Sheet shall refer to SNO-I-ES-013, Instrument Specification for Shutdown and Blowdown Valve
4. Actuator shall be sized based on valve manufacturer's required Torque values with 130% minimum safety margin to open or close the valve
against full ANSI rated differential pressure at minimum pneumatic supply pressure of 60 psig.
5. Vendor shall provide Torque table containing breaking, running and seating torques for valves and actuator along with Quotation.
Vendor shall provide the torque table and calculation for COMPANY approval.
6. Actuator and accessories shall be supplied fully assembled, tubed and tested ready for installation.
7. Solenoid valve coil shall be provided with reverse polarity protection diodes, integral outlet box and terminal strip for cable connection.
8. Three way valve shall be universal type. Solenoid Coil shall be Class H.
Air filter regulator shall be 316 SS Material and equipped with pressure gauge on inlet and outlet of air filter regulator.
C1 9. All SDV & BDV shall be designed & tested as per API 6D
C1 10. Valve Stem Shall be Anti-Blowout Type.

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 55 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
1 Tag No. Quantity XV -6010A 1 (One)
2 Manufacturer Model VTA VTA
3 Contract No. Requisition Item No.
4 Location Central Processing Plant
GENERAL
5 P&ID No. SNO-R-PI-034
6 Service Condensate Loading Tank SN0-T-6010A Inlet
C 7 Line No. 8"-HL-0014-1A
8 Area Classification Zone-2, Gr. IIB, T3
9 Valve Type Valve Code Trunnion Mounted Ball BA005
10 Body Size Body Form 8 in Ball
11 Body Material Port Size ASTM A216-WCB Full Bore
12 Connection Rating RF Flange ASME 150#
C1 13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
C 14 Packing Lubrication & Isolation Expanded Graphite VTA
C 15 Bonnet Bolts Bonnet Nuts ASTM A193 B7 ASTM A194 2H
C 16 Ball Material Stem Material CS+ENP 76μm CS+ENP 76μm
C1 17 Leakage Rate Seat Material ISO 5028 Rate A PTFE
18 NACE Requirement No
C 19 Type Stroking Time Pneumatic Piston / Spring return 15 Seconds
C 20 Size Safety Factor VTA in 1.5
21 Actuator Orientation Actuator Form Horizontal Cylinder
22 Ingress Protection Electrical Protection IP65 Eex i
23 Instrument Air Supply 80-120 Psig
24 Action on Air Failure Action on Power Failure Closed Closed
ACTUATOR 25 Fireproofing No
26 Solenoid Valve Schematic Detail Yes (Note 10) Type-10
27 Limit Switch Closed Limit Swich Open Yes Yes
28 Mounting Position Solenoid Power Supply Top 24VDC
29 Manual Reset No
30 Mechanical Position Indicator Red Closed / Green Open
C1 31 Partial Stroke Facility No
31 Signal Cable 1/2" NPT
ELECTRICAL 32 Control Cable -
CONNECTIONS 33 Solenoid Cable 3/4" NPT
34
35 Fluid
Fl id Hydrocarbon
H d b
36 Phase Liquid
C 37 Operating Pressure 149 psig
C 38 Design Pressure 225 psig
C 39 Operating Temperature AMB ºF
C 40 Design Temperature 200 ºF
PROCESS DATA
C 41 Max. Diff. Pressure for Actuator Size 225 psig
42
43 Line Size and Sch. Inlet Outlet 8 in Sch. 20 8 in Sch. 20
44 Speed of Operation Design VTA
45 (Seconds) Actual VTA
46
Notes
1. VTA : Vendor to advice
2. Actuated ball valve and actuator shall be provided with 316 SS nameplate engraved or die stamped with Valve Tag No., Manufacturer's Name,
Model No., Valve Size & Rating.
3. Vendor shall be responsible for the proper design and selection of valve, actuator, and accessories based on the information furnished
C1 in this specification. This Data Sheet shall refer to SNO-I-ES-013, Instrument Specification for Shutdown and Blowdown Valve
4. Actuator shall be sized based on valve manufacturer's required Torque values with 130% minimum safety margin to open or close the valve
against full ANSI rated differential pressure at minimum pneumatic supply pressure of 60 psig.
5. Vendor shall provide Torque table containing breaking, running and seating torques for valves and actuator along with Quotation.
Vendor shall provide the torque table and calculation for COMPANY approval.
6. Actuator and accessories shall be supplied fully assembled, tubed and tested ready for installation.
7. Solenoid valve coil shall be provided with reverse polarity protection diodes, integral outlet box and terminal strip for cable connection.
8. Three way valve shall be universal type. Solenoid Coil shall be Class H.
Air filter regulator shall be 316 SS Material and equipped with pressure gauge on inlet and outlet of air filter regulator.
C1 9. All SDV & BDV shall be designed & tested as per API 6D
C1 10. Valve Stem Shall be Anti-Blowout Type.

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 56 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
1 Tag No. Quantity XV -6010B 1 (One)
2 Manufacturer Model VTA VTA
3 Contract No. Requisition Item No.
4 Location Central Processing Plant
GENERAL
5 P&ID No. SNO-R-PI-034
6 Service Condensate Storage Tank SN0-T-6010A Outlet To Condensate Loading Pump
7 Line No. 24"-HL-0016-1A
8 Area Classification Zone-2, Gr. IIB, T3
9 Valve Type Valve Code Trunnion Mounted Ball BA005
10 Body Size Body Form 24 in Ball
11 Body Material Port Size ASTM A216-WCB Full Bore
12 Connection Rating RF Flange ASME 150#
C1 13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
C 14 Packing Lubrication & Isolation Expanded Graphite VTA
C 15 Bonnet Bolts Bonnet Nuts ASTM A193 B7 ASTM A194 2H
C 16 Ball Material Stem Material CS+ENP 76μm CS+ENP 76μm
C1 17 Leakage Rate Seat Material ISO 5028 Rate A PTFE
18 NACE Requirement No
C 19 Type Stroking Time Pneumatic Piston / Spring return 24 Seconds
20 Size Safety Factor VTA in 1.3
21 Actuator Orientation Actuator Form Horizontal Cylinder
22 Ingress Protection Electrical Protection IP65 Eex i
23 Instrument Air Supply 80-120 Psig
24 Action on Air Failure Action on Power Failure Closed Closed
ACTUATOR 25 Fireproofing No
26 Solenoid Valve Schematic Detail Yes (Note 10) Type-10
27 Limit Switch Closed Limit Swich Open Yes Yes
28 Mounting Position Solenoid Power Supply Top 24VDC
29 Manual Reset No
30 Mechanical Position Indicator Red Closed / Green Open
C 31 Partial Stroke Facility No
31 Signal Cable 1/2" NPT
ELECTRICAL 32 Control Cable -
CONNECTIONS 33 Solenoid Cable 3/4" NPT
34
35 Fluid
Fl id Hydrocarbon
H d b
36 Phase Liquid
C 37 Operating Pressure ATM psig
C 38 Design Pressure 50 psig
C 39 Operating Temperature 120 ºF
C 40 Design Temperature 150 ºF
PROCESS DATA
C 41 Max. Diff. Pressure for Actuator Size 50 psig
42
43 Line Size and Sch. Inlet Outlet 24 in Sch. 20 24 in Sch. 20
44 Speed of Operation Design VTA
45 (Seconds) Actual VTA
46
Notes
1. VTA : Vendor to advice
2. Actuated ball valve and actuator shall be provided with 316 SS nameplate engraved or die stamped with Valve Tag No., Manufacturer's Name,
Model No., Valve Size & Rating.
3. Vendor shall be responsible for the proper design and selection of valve, actuator, and accessories based on the information furnished
C1 in this specification. This Data Sheet shall refer to SNO-I-ES-013, Instrument Specification for Shutdown and Blowdown Valve
4. Actuator shall be sized based on valve manufacturer's required Torque values with 130% minimum safety margin to open or close the valve
against full ANSI rated differential pressure at minimum pneumatic supply pressure of 60 psig.
5. Vendor shall provide Torque table containing breaking, running and seating torques for valves and actuator along with Quotation.
Vendor shall provide the torque table and calculation for COMPANY approval.
6. Actuator and accessories shall be supplied fully assembled, tubed and tested ready for installation.
7. Solenoid valve coil shall be provided with reverse polarity protection diodes, integral outlet box and terminal strip for cable connection.
8. Three way valve shall be universal type. Solenoid Coil shall be Class H.
Air filter regulator shall be 316 SS Material and equipped with pressure gauge on inlet and outlet of air filter regulator.
C1 9. All SDV & BDV shall be designed & tested as per API 6D
C1 10. Valve Stem Shall be Anti-Blowout Type.

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 57 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
1 Tag No. Quantity XV -6010C 1 (One)
2 Manufacturer Model VTA VTA
3 Contract No. Requisition Item No.
4 Location Central Processing Plant
GENERAL
5 P&ID No. SNO-R-PI-034
6 Service Condensate Loading Tank SN0-T-6010B Inlet
7 Line No. 8"-HL-0015-1A
8 Area Classification Zone-2, Gr. IIB, T3
9 Valve Type Valve Code Trunnion Mounted Ball BA005
10 Body Size Body Form 8 in Ball
11 Body Material Port Size ASTM A216-WCB Full Bore
12 Connection Rating RF Flange ASME 150#
C1 13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
C 14 Packing Lubrication & Isolation Expanded Graphite VTA
C 15 Bonnet Bolts Bonnet Nuts ASTM A193 B7 ASTM A194 2H
C 16 Ball Material Stem Material CS+ENP 76μm CS+ENP 76μm
C1 17 Leakage Rate Seat Material ISO 5028 Rate A PTFE
18 NACE Requirement No
C 19 Type Stroking Time Pneumatic Piston / Spring return 15 Seconds
20 Size Safety Factor VTA in 1.3
21 Actuator Orientation Actuator Form Horizontal Cylinder
22 Ingress Protection Electrical Protection IP65 Eex i
23 Instrument Air Supply 80-120 Psig
24 Action on Air Failure Action on Power Failure Closed Closed
ACTUATOR 25 Fireproofing No
26 Solenoid Valve Schematic Detail Yes (Note 10) Type-10
27 Limit Switch Closed Limit Swich Open Yes Yes
28 Mounting Position Solenoid Power Supply Top 24VDC
29 Manual Reset No
30 Mechanical Position Indicator Red Closed / Green Open
C 31 Partial Stroke Facility No
31 Signal Cable 1/2" NPT
ELECTRICAL 32 Control Cable -
CONNECTIONS 33 Solenoid Cable 3/4" NPT
34
35 Fluid
Fl id Hydrocarbon
H d b
36 Phase Liquid
C 37 Operating Pressure 149 psig
C 38 Design Pressure 225 psig
C 39 Operating Temperature AMB ºF
C 40 Design Temperature 200 ºF
PROCESS DATA
C 41 Max. Diff. Pressure for Actuator Size 225 psig
42
43 Line Size and Sch. Inlet Outlet 8 in Sch. 20 8 in Sch. 20
44 Speed of Operation Design VTA
45 (Seconds) Actual VTA
46
Notes
1. VTA : Vendor to advice
2. Actuated ball valve and actuator shall be provided with 316 SS nameplate engraved or die stamped with Valve Tag No., Manufacturer's Name,
Model No., Valve Size & Rating.
3. Vendor shall be responsible for the proper design and selection of valve, actuator, and accessories based on the information furnished
C1 in this specification. This Data Sheet shall refer to SNO-I-ES-013, Instrument Specification for Shutdown and Blowdown Valve
4. Actuator shall be sized based on valve manufacturer's required Torque values with 130% minimum safety margin to open or close the valve
against full ANSI rated differential pressure at minimum pneumatic supply pressure of 60 psig.
5. Vendor shall provide Torque table containing breaking, running and seating torques for valves and actuator along with Quotation.
Vendor shall provide the torque table and calculation for COMPANY approval.
6. Actuator and accessories shall be supplied fully assembled, tubed and tested ready for installation.
7. Solenoid valve coil shall be provided with reverse polarity protection diodes, integral outlet box and terminal strip for cable connection.
8. Three way valve shall be universal type. Solenoid Coil shall be Class H.
Air filter regulator shall be 316 SS Material and equipped with pressure gauge on inlet and outlet of air filter regulator.
C1 9. All SDV & BDV shall be designed & tested as per API 6D
C1 10. Valve Stem Shall be Anti-Blowout Type.

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 58 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
1 Tag No. Quantity XV -6010D 1 (One)
2 Manufacturer Model VTA VTA
3 Contract No. Requisition Item No.
4 Location Central Processing Plant
GENERAL
5 P&ID No. SNO-R-PI-034
6 Service Condensate Loading Tank SN0-T-6010B Outlet To Condensate Loading Pump
7 Line No. 24"-HL-0017-1A
8 Area Classification Zone-2, Gr. IIB, T3
9 Valve Type Valve Code Trunnion Mounted Ball BA005
10 Body Size Body Form 24 in Ball
11 Body Material Port Size ASTM A216-WCB Full Bore
12 Connection Rating RF Flange ASME 150#
C1 13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
C 14 Packing Lubrication & Isolation Expanded Graphite VTA
C 15 Bonnet Bolts Bonnet Nuts ASTM A193 B7 ASTM A194 2H
C 16 Ball Material Stem Material CS+ENP 76μm CS+ENP 76μm
C1 17 Leakage Rate Seat Material ISO 5028 Rate A PTFE
18 NACE Requirement No
C 19 Type Stroking Time Pneumatic Piston / Spring return VTA
20 Size Safety Factor VTA in 1.3
21 Actuator Orientation Actuator Form Horizontal Cylinder
22 Ingress Protection Electrical Protection IP65 Eex i
23 Instrument Air Supply 80-120 Psig
24 Action on Air Failure Action on Power Failure Closed Closed
ACTUATOR 25 Fireproofing No
26 Solenoid Valve Schematic Detail Yes (Note 10) Type-10
27 Limit Switch Closed Limit Swich Open Yes Yes
28 Mounting Position Solenoid Power Supply Top 24VDC
29 Manual Reset No
30 Mechanical Position Indicator Red Closed / Green Open
C 31 Partial Stroke Facility No
31 Signal Cable 1/2" NPT
ELECTRICAL 32 Control Cable -
CONNECTIONS 33 Solenoid Cable 3/4" NPT
34
35 Fluid
Fl id Hydrocarbon
H d b
36 Phase Liquid
C 37 Operating Pressure ATM psig
C 38 Design Pressure 50 psig
39 Operating Temperature 120 ºF
40 Design Temperature 150 ºF
PROCESS DATA
C 41 Max. Diff. Pressure for Actuator Size 50 psig
42
43 Line Size and Sch. Inlet Outlet 24 in Sch. 20 24 in Sch. 20
44 Speed of Operation Design VTA
45 (Seconds) Actual VTA
46
Notes
1. VTA : Vendor to advice
2. Actuated ball valve and actuator shall be provided with 316 SS nameplate engraved or die stamped with Valve Tag No., Manufacturer's Name,
Model No., Valve Size & Rating.
3. Vendor shall be responsible for the proper design and selection of valve, actuator, and accessories based on the information furnished
C1 in this specification. This Data Sheet shall refer to SNO-I-ES-013, Instrument Specification for Shutdown and Blowdown Valve
4. Actuator shall be sized based on valve manufacturer's required Torque values with 130% minimum safety margin to open or close the valve
against full ANSI rated differential pressure at minimum pneumatic supply pressure of 60 psig.
5. Vendor shall provide Torque table containing breaking, running and seating torques for valves and actuator along with Quotation.
Vendor shall provide the torque table and calculation for COMPANY approval.
6. Actuator and accessories shall be supplied fully assembled, tubed and tested ready for installation.
7. Solenoid valve coil shall be provided with reverse polarity protection diodes, integral outlet box and terminal strip for cable connection.
8. Three way valve shall be universal type. Solenoid Coil shall be Class H.
Air filter regulator shall be 316 SS Material and equipped with pressure gauge on inlet and outlet of air filter regulator.
C1 9. All SDV & BDV shall be designed & tested as per API 6D
C1 10. Valve Stem Shall be Anti-Blowout Type.

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 59 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
1 Tag No. Quantity SDV -6030A 1 (One)
2 Manufacturer Model VTA VTA
3 Contract No. Requisition Item No.
4 Location Central Processing Plant
GENERAL
5 P&ID No. SNO-R-PI-037
6 Service Condensate Metering to Loading Arm Package
7 Line No. 20"-HL-0050-1A
8 Area Classification Zone-2, Gr. IIB, T3
9 Valve Type Valve Code Trunnion Mounted Ball BA005
10 Body Size Body Form 20 in Ball
11 Body Material Port Size ASTM A216-WCB Full Bore
12 Connection Rating RF Flange ASME 150#
13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
14 Packing Lubrication & Isolation Expanded Graphite VTA
15 Bonnet Bolts Bonnet Nuts ASTM A193 B7 ASTM A194 2H
16 Ball Material Stem Material CS+ENP 76μm CS+ENP 76μm
17 Leakage Rate Seat Material ISO 5028 Rate A PTFE
18 NACE Requirement No
19 Type Stroking Time Pneumatic Piston / Spring return 15 Seconds
20 Size Safety Factor VTA in 1.3
21 Actuator Orientation Actuator Form Horizontal Cylinder
22 Ingress Protection Electrical Protection IP65 Eex i
23 Instrument Air Supply 80-120 Psig
24 Action on Air Failure Action on Power Failure Closed Closed
ACTUATOR 25 Fireproofing No
26 Solenoid Valve Schematic Detail Yes Type-1
27 Limit Switch Closed Limit Swich Open Yes Yes
28 Mounting Position Solenoid Power Supply Top 24VDC
29 Manual Reset No
30 Mechanical Position Indicator Red Closed / Green Open
31 Partial Stroke Facility No
31 Signal Cable 1/2" NPT
ELECTRICAL 32 Control Cable -
CONNECTIONS 33 Solenoid Cable 3/4" NPT
34
35 Fluid
Fl id Hydrocarbon
H d b
36 Phase Liquid
37 Operating Pressure 97 psig
38 Design Pressure 170 psig
39 Operating Temperature AMB ºF
40 Design Temperature 150 ºF
PROCESS DATA
41 Max. Diff. Pressure for Actuator Size 170 psig
42
43 Line Size and Sch. Inlet Outlet 20 in Sch. 20 20 in Sch. 20
44 Speed of Operation Design VTA
45 (Seconds) Actual VTA
46
Notes
C1 1. SDV-6030A is supplied by Construction Company of Condensate Jetty

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 60 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
1 Tag No. Quantity XV-6030E 1 (One)
2 Manufacturer Model VTA VTA
3 Contract No. Requisition Item No.
4 Location Central Processing Plant
GENERAL
5 P&ID No. SNO-R-PI-037
6 Service From N2 Bottle to Jetty Loading Arm Package
7 Line No. 2"-NI-0306-9A
8 Area Classification Zone-2, Gr. IIB, T3
9 Valve Type Valve Code Trunnion Mounted Ball BA084
10 Body Size Body Form 2 in Ball
11 Body Material Port Size ASTM A216 WCB Full Bore
12 Connection Rating RF Flange ASME 150#
13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
14 Packing Lubrication & Isolation Expanded Graphite VTA
15 Bonnet Bolts Bonnet Nuts ASTM A193 B7(GALV.) ASTM A194 2H(GALV.)
16 Ball Material Stem Material A105 + ENP 76µm A105 + ENP 76µm
17 Leakage Rate Seat Material ISO 5028 Rate A RTFE
18 NACE Requirement No
19 Type Stroking Time Pneumatic Piston / Spring return 4 Seconds
20 Size Safety Factor VTA in 1.3
21 Actuator Orientation Actuator Form Horizontal Cylinder
22 Ingress Protection Electrical Protection IP65 Eex i
23 Instrument Air Supply 80-120 Psig
24 Action on Air Failure Action on Power Failure Closed Closed
ACTUATOR 25 Fireproofing No
26 Solenoid Valve Schematic Detail Yes Type-1
27 Limit Switch Closed Limit Swich Open Yes Yes
28 Mounting Position Solenoid Power Supply Top 24VDC
29 Manual Reset No
30 Mechanical Position Indicator Red Closed / Green Open
31 Partial Stroke Facility No
31 Signal Cable 1/2" NPT
ELECTRICAL 32 Control Cable -
CONNECTIONS 33 Solenoid Cable 3/4" NPT
34
35 Fluid
Fl id Nitrogen
Nit
36 Phase Gas
37 Operating Pressure 110 (HOL psig
38 Design Pressure 150 psig
39 Operating Temperature 85 ºF
40 Design Temperature 100 ºF
PROCESS DATA
41 Max. Diff. Pressure for Actuator Size 150 psig
42
43 Line Size and Sch. Inlet Outlet 2 in Sch. 40 2 in Sch. 40
44 Speed of Operation Design VTA
45 (Seconds) Actual VTA
46
Notes
C1 1. XV-xxxx is supplied by Jetty Loading Arm Supplier

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 61 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
C1 1 Tag No. Quantity BDV -5041 1 (One)
2 Manufacturer Model VTA VTA
3 Contract No. Requisition Item No.
4 Location Central Processing Plant
GENERAL
5 P&ID No. SNO-R-PI-057
6 Service Sales Gas Filter Coalescer to Buyer's Flare System
C1 7 Line No. 4"-HG-0015-6A
8 Area Classification Zone-2, Gr. IIB, T3
C1 9 Valve Type Valve Code Trunnion Mounted Ball BA013
C1 10 Body Size Body Form 4 in Ball
C 11 Body Material Port Size A216 WCB Full Bore
12 Connection Rating RF Flange ASME 600#
C1 13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
C 14 Packing Lubrication & Isolation Expanded Graphite VTA
C 15 Bonnet Bolts Bonnet Nuts ASTM A193 B7 ASTM A194 2H
C 16 Ball Material Stem Material CS+ENP 76μm A564 630, H1150M+ENP 76 μm
C1 17 Leakage Rate Seat Material ISO 5028 Rate A PTFE OR NYLON
18 NACE Requirement No
C 19 Type Stroking Time Pneumatic Piston / Spring return 8 Seconds
20 Size Safety Factor VTA in 1.3
21 Actuator Orientation Actuator Form Horizontal Cylinder
22 Ingress Protection Electrical Protection IP65 Eex i
23 Instrument Air Supply 80-120 Psig
24 Action on Air Failure Action on Power Failure Open Open
ACTUATOR 25 Fireproofing No
26 Solenoid Valve Schematic Detail Yes Type-2
27 Limit Switch Closed Limit Swich Open Yes Yes
28 Mounting Position Solenoid Power Supply Top 24VDC
C 29 Manual Reset No
30 Mechanical Position Indicator Red Closed / Green Open
C 31 Partial Stroke Facility No
31 Signal Cable 1/2" NPT
ELECTRICAL 32 Control Cable -
CONNECTIONS 33 Solenoid Cable 3/4" NPT
34
35 Fluid
Fl id Hydrocarbon
H d b
36 Phase Gas
37 Operating Pressure 740 psig
38 Design Pressure 1100 psig
39 Operating Temperature 95 ºF
40 Design Temperature 150 ºF
PROCESS DATA
41 Max. Diff. Pressure for Actuator Size 1100 psig
42
C1 43 Line Size and Sch. Inlet Outlet 4 in Sch. 120 4 in Sch. 120
44 Speed of Operation Design VTA
45 (Seconds) Actual VTA
46
Notes
1. VTA : Vendor to advice
2. Actuated ball valve and actuator shall be provided with 316 SS nameplate engraved or die stamped with Valve Tag No., Manufacturer's Name,
Model No., Valve Size & Rating.
3. Vendor shall be responsible for the proper design and selection of valve, actuator, and accessories based on the information furnished
C1 in this specification. This Data Sheet shall refer to SNO-I-ES-013, Instrument Specification for Shutdown and Blowdown Valve
4. Actuator shall be sized based on valve manufacturer's required Torque values with 130% minimum safety margin to open or close the valve
against full ANSI rated differential pressure at minimum pneumatic supply pressure of 60 psig.
5. Vendor shall provide Torque table containing breaking, running and seating torques for valves and actuator along with Quotation.
Vendor shall provide the torque table and calculation for COMPANY approval.
6. Actuator and accessories shall be supplied fully assembled, tubed and tested ready for installation.
7. Solenoid valve coil shall be provided with reverse polarity protection diodes, integral outlet box and terminal strip for cable connection.
Three way valve shall be universal type. Solenoid Coil shall be Class H.
8. Air filter regulator shall be 316 SS Material and equipped with pressure gauge on inlet and outlet of air filter regulator.
C1 9. All SDV & BDV shall be designed & tested as per API 6D
C1 10. Valve Stem Shall be Anti-Blowout Type.

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 62 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
1 Tag No. Quantity SDV-6007 1 (One)
2 Manufacturer Model VTA VTA
3 Contract No. Requisition Item No.
4 Location Central Processing Plant
GENERAL
5 P&ID No. SNO-R-PI-059
6 Service Off Spec Condensate Pumps Outlet
7 Line No. 3"-HL-0060-1A
8 Area Classification Zone-2, Gr. IIB, T3
C1 9 Valve Type Valve Code Trunnion Mounted Ball BA003
10 Body Size Body Form 3 in Ball
11 Body Material Port Size ASTM A216-WCB Full Bore
12 Connection Rating RF Flange ASME 150#
C1 13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
C 14 Packing Lubrication & Isolation Expanded Graphite VTA
C 15 Bonnet Bolts Bonnet Nuts ASTM A193 B7 ASTM A194 2H
C 16 Ball Material Stem Material CS+ENP 76μm CS+ENP 76μm
C1 17 Leakage Rate Seat Material ISO 5028 Rate A PTFE
18 NACE Requirement No
C 19 Type Stroking Time Pneumatic Piston / Spring return 6 Seconds
20 Size Safety Factor VTA in 1.3
21 Actuator Orientation Actuator Form Horizontal Cylinder
22 Ingress Protection Electrical Protection IP65 Eex i
23 Instrument Air Supply 80-120 Psig
24 Action on Air Failure Action on Power Failure Closed Closed
ACTUATOR 25 Fireproofing No
26 Solenoid Valve Schematic Detail Yes Type-1
27 Limit Switch Closed Limit Swich Open Yes Yes
28 Mounting Position Solenoid Power Supply Top 24VDC
29 Manual Reset No
30 Mechanical Position Indicator Red Closed / Green Open
C 31 Partial Stroke Facility No
31 Signal Cable 1/2" NPT
ELECTRICAL 32 Control Cable -
CONNECTIONS 33 Solenoid Cable 3/4" NPT
34
35 Fluid
Fl id Hydrocarbon
H d b
36 Phase Liquid
C 37 Operating Pressure 182 psig
C 38 Design Pressure 250 psig
C 39 Operating Temperature AMB ºF
40 Design Temperature 200 ºF
PROCESS DATA
C 41 Max. Diff. Pressure for Actuator Size 250 psig
42
43 Line Size and Sch. Inlet Outlet 3 in Sch. 80 3 in Sch. 80
44 Speed of Operation Design VTA
45 (Seconds) Actual VTA
46
Notes
1. VTA : Vendor to advice
2. Actuated ball valve and actuator shall be provided with 316 SS nameplate engraved or die stamped with Valve Tag No., Manufacturer's Name,
Model No., Valve Size & Rating.
3. Vendor shall be responsible for the proper design and selection of valve, actuator, and accessories based on the information furnished
C1 in this specification. This Data Sheet shall refer to SNO-I-ES-013, Instrument Specification for Shutdown and Blowdown Valve
4. Actuator shall be sized based on valve manufacturer's required Torque values with 130% minimum safety margin to open or close the valve
against full ANSI rated differential pressure at minimum pneumatic supply pressure of 60 psig.
5. Vendor shall provide Torque table containing breaking, running and seating torques for valves and actuator along with Quotation.
Vendor shall provide the torque table and calculation for COMPANY approval.
6. Actuator and accessories shall be supplied fully assembled, tubed and tested ready for installation.
7. Solenoid valve coil shall be provided with reverse polarity protection diodes, integral outlet box and terminal strip for cable connection.
Three way valve shall be universal type. Solenoid Coil shall be Class H.
8. Air filter regulator shall be 316 SS Material and equipped with pressure gauge on inlet and outlet of air filter regulator.
C1 9. All SDV & BDV shall be designed & tested as per API 6D
C1 10. Valve Stem Shall be Anti-Blowout Type.

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 63 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
1 Tag No. Quantity SDV-8065A 1 (One)
2 Manufacturer Model VTA VTA
3 Contract No. Requisition Item No.
4 Location Central Processing Plant
GENERAL
5 P&ID No. SNO-R-PI-101
6 Service HP Fuel Gas Scrubber SNO-V-8065 To Closed Drain Header
7 Line No. 2"-DC-0010-3B
8 Area Classification Zone-2, Gr. IIB, T3
C1 9 Valve Type Valve Code Trunnion Mounted Ball BA122
10 Body Size Body Form 2 in Ball
C 11 Body Material Port Size A105 Full Bore
12 Connection Rating RF Flange ASME 300#
C1 13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
C 14 Packing Lubrication & Isolation Expanded Graphite VTA
15 Bonnet Bolts Bonnet Nuts ASTM A193 B7M ASTM A194 2HM
C 16 Ball Material Stem Material CS+ENP 76μm 316 SS
C1 17 Leakage Rate Seat Material ISO 5028 Rate A (TSO) PTFE
18 NACE Requirement Yes
C 19 Type Stroking Time Pneumatic Piston / Spring return 4 Seconds
20 Size Safety Factor VTA in 1.3
21 Actuator Orientation Actuator Form Horizontal Cylinder
22 Ingress Protection Electrical Protection IP65 Eex i
23 Instrument Air Supply 80-120 Psig
24 Action on Air Failure Action on Power Failure Closed Closed
ACTUATOR 25 Fireproofing No
26 Solenoid Valve Schematic Detail Yes Type-1
27 Limit Switch Closed Limit Swich Open Yes Yes
28 Mounting Position Solenoid Power Supply Top 24VDC
29 Manual Reset No
30 Mechanical Position Indicator Red Closed / Green Open
C 31 Partial Stroke Facility No
31 Signal Cable 1/2" NPT
ELECTRICAL 32 Control Cable -
CONNECTIONS 33 Solenoid Cable 3/4" NPT
34
35 Fluid
Fl id Hydrocarbon
H d b
36 Phase Liquid
37 Operating Pressure 300 psig
38 Design Pressure 350 psig
39 Operating Temperature 69 ºF
40 Design Temperature 200 ºF
PROCESS DATA
41 Max. Diff. Pressure for Actuator Size 350 psig
42
43 Line Size and Sch. Inlet Outlet 2 in Sch. 80 2 in Sch. 80
44 Speed of Operation Design VTA
45 (Seconds) Actual VTA
46
Notes
1. VTA : Vendor to advice
2. Actuated ball valve and actuator shall be provided with 316 SS nameplate engraved or die stamped with Valve Tag No., Manufacturer's Name,
Model No., Valve Size & Rating.
3. Vendor shall be responsible for the proper design and selection of valve, actuator, and accessories based on the information furnished
C1 in this specification. This Data Sheet shall refer to SNO-I-ES-013, Instrument Specification for Shutdown and Blowdown Valve
4. Actuator shall be sized based on valve manufacturer's required Torque values with 130% minimum safety margin to open or close the valve
against full ANSI rated differential pressure at minimum pneumatic supply pressure of 60 psig.
5. Vendor shall provide Torque table containing breaking, running and seating torques for valves and actuator along with Quotation.
Vendor shall provide the torque table and calculation for COMPANY approval.
6. Actuator and accessories shall be supplied fully assembled, tubed and tested ready for installation.
7. Solenoid valve coil shall be provided with reverse polarity protection diodes, integral outlet box and terminal strip for cable connection.
8. Three way valve shall be universal type. Solenoid Coil shall be Class H.
Air filter regulator shall be 316 SS Material and equipped with pressure gauge on inlet and outlet of air filter regulator.
C1 9. All SDV & BDV shall be designed & tested as per API 6D
C1 10. Valve Stem Shall be Anti-Blowout Type.

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 64 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
1 Tag No. Quantity SDV -8065B 1 (One)
2 Manufacturer Model VTA VTA
3 Contract No. Requisition Item No.
4 Location Central Processing Plant
GENERAL
5 P&ID No. SNO-R-PI-101
6 Service HP Fuel Gas Scrubber SNO-V-8065 Inlet
7 Line No. 6"-FG-0008-6B
8 Area Classification Zone-2, Gr. IIB, T3
9 Valve Type Valve Code Trunnion Mounted Ball BA045
10 Body Size Body Form 6 in Ball
11 Body Material Port Size ASTM A216-WCB Full Bore
12 Connection Rating RF Flange ASME 600#
C1 13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
C 14 Packing Lubrication & Isolation Expanded Graphite VTA
15 Bonnet Bolts Bonnet Nuts ASTM A193 B7M ASTM A194 2HM
C 16 Ball Material Stem Material CS+ENP 76μm A564 630, H1150M+ENP 76 μm
C1 17 Leakage Rate Seat Material ISO 5028 Rate A PTFE OR NYLON
18 NACE Requirement Yes
C 19 Type Stroking Time Pneumatic Piston / Spring return 12 Seconds
C 20 Size Safety Factor VTA in 1.5
21 Actuator Orientation Actuator Form Horizontal Cylinder
22 Ingress Protection Electrical Protection IP65 Eex i
23 Instrument Air Supply 80-120 Psig
24 Action on Air Failure Action on Power Failure Closed Closed
ACTUATOR 25 Fireproofing No
26 Solenoid Valve Schematic Detail Yes Type-1
27 Limit Switch Closed Limit Swich Open Yes Yes
28 Mounting Position Solenoid Power Supply Top 24VDC
29 Manual Reset No
30 Mechanical Position Indicator Red Closed / Green Open
C 31 Partial Stroke Facility Yes
31 Signal Cable 1/2" NPT
ELECTRICAL 32 Control Cable -
CONNECTIONS 33 Solenoid Cable 3/4" NPT
34
35 Fluid
Fl id Fuel
F l Gas
G
36 Phase Gas
C 37 Operating Pressure 852 psig
38 Design Pressure 1300 psig
39 Operating Temperature 100 ºF
40 Design Temperature 150 ºF
PROCESS DATA
41 Max. Diff. Pressure for Actuator Size 1300 psig
42
43 Line Size and Sch. Inlet Outlet 6 in Sch. 120 6 in Sch. 120
44 Speed of Operation Design VTA
45 (Seconds) Actual VTA
46
Notes
1. VTA : Vendor to advice
2. Actuated ball valve and actuator shall be provided with 316 SS nameplate engraved or die stamped with Valve Tag No., Manufacturer's Name,
Model No., Valve Size & Rating.
3. Vendor shall be responsible for the proper design and selection of valve, actuator, and accessories based on the information furnished
C1 in this specification. This Data Sheet shall refer to SNO-I-ES-013, Instrument Specification for Shutdown and Blowdown Valve
4. Actuator shall be sized based on valve manufacturer's required Torque values with 130% minimum safety margin to open or close the valve
against full ANSI rated differential pressure at minimum pneumatic supply pressure of 60 psig.
5. Vendor shall provide Torque table containing breaking, running and seating torques for valves and actuator along with Quotation.
Vendor shall provide the torque table and calculation for COMPANY approval.
6. Actuator and accessories shall be supplied fully assembled, tubed and tested ready for installation.
7. Solenoid valve coil shall be provided with reverse polarity protection diodes, integral outlet box and terminal strip for cable connection.
8. Three way valve shall be universal type. Solenoid Coil shall be Class H.
Air filter regulator shall be 316 SS Material and equipped with pressure gauge on inlet and outlet of air filter regulator.
C1 9. All SDV & BDV shall be designed & tested as per API 6D
C1 10. Valve Stem Shall be Anti-Blowout Type.

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 65 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
1 Tag No. Quantity BDV -8065B 1 (One)
2 Manufacturer Model VTA VTA
3 Contract No. Requisition Item No.
4 Location Central Processing Plant
GENERAL
5 P&ID No. SNO-R-PI-101
6 Service From Fuel Gas Scrubber to Flare Header
C1 7 Line No. 3"-FG-0032-6B
8 Area Classification Zone-2, Gr. IIB, T3
C1 9 Valve Type Valve Code Trunnion Mounted Ball BA044
C1 10 Body Size Body Form 3 in Ball
11 Body Material Port Size ASTM A216-WCB Full Bore
12 Connection Rating RF Flange ASME 600#
C1 13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
C 14 Packing Lubrication & Isolation Expanded Graphite VTA
15 Bonnet Bolts Bonnet Nuts ASTM A193 B7M ASTM A194 2HM
C 16 Ball Material Stem Material CS+ENP 76μm A564 630, H1150M+ENP 76 μm
C1 17 Leakage Rate Seat Material ISO 5028 Rate A (TSO) PTFE OR NYLON
18 NACE Requirement Yes
C 19 Type Stroking Time Pneumatic Piston / Spring return 6 Seconds
20 Size Safety Factor VTA in 1.3
21 Actuator Orientation Actuator Form Horizontal Cylinder
22 Ingress Protection Electrical Protection IP65 Eex i
23 Instrument Air Supply 80-120 Psig
24 Action on Air Failure Action on Power Failure Open Open
ACTUATOR 25 Fireproofing No
26 Solenoid Valve Schematic Detail Yes Type-2
27 Limit Switch Closed Limit Swich Open Yes Yes
28 Mounting Position Solenoid Power Supply Top 24VDC
29 Manual Reset No
30 Mechanical Position Indicator Red Closed / Green Open
C 31 Partial Stroke Facility No
31 Signal Cable 1/2" NPT
ELECTRICAL 32 Control Cable -
CONNECTIONS 33 Solenoid Cable 3/4" NPT
34
35 Fluid
Fl id Fuel
F l Gas
G
36 Phase Gas
C 37 Operating Pressure 852 psig
38 Design Pressure 1300 psig
39 Operating Temperature 100 ºF
C 40 Design Temperature 200 ºF
PROCESS DATA
41 Max. Diff. Pressure for Actuator Size 1300 psig
42
C1 43 Line Size and Sch. Inlet Outlet 3 in Sch. 160 3 in Sch. 160
44 Speed of Operation Design VTA
45 (Seconds) Actual VTA
46
Notes
1. VTA : Vendor to advice
2. Actuated ball valve and actuator shall be provided with 316 SS nameplate engraved or die stamped with Valve Tag No., Manufacturer's Name,
Model No., Valve Size & Rating.
3. Vendor shall be responsible for the proper design and selection of valve, actuator, and accessories based on the information furnished
C1 in this specification. This Data Sheet shall refer to SNO-I-ES-013, Instrument Specification for Shutdown and Blowdown Valve
4. Actuator shall be sized based on valve manufacturer's required Torque values with 130% minimum safety margin to open or close the valve
against full ANSI rated differential pressure at minimum pneumatic supply pressure of 60 psig.
5. Vendor shall provide Torque table containing breaking, running and seating torques for valves and actuator along with Quotation.
Vendor shall provide the torque table and calculation for COMPANY approval.
6. Actuator and accessories shall be supplied fully assembled, tubed and tested ready for installation.
7. Solenoid valve coil shall be provided with reverse polarity protection diodes, integral outlet box and terminal strip for cable connection.
8. Three way valve shall be universal type. Solenoid Coil shall be Class H.
Air filter regulator shall be 316 SS Material and equipped with pressure gauge on inlet and outlet of air filter regulator.
C1 9. All SDV & BDV shall be designed & tested as per API 6D
C1 10. Valve Stem Shall be Anti-Blowout Type.

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 66 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
1 Tag No. Quantity BDV -8066A 1 (One)
2 Manufacturer Model VTA VTA
3 Contract No. Requisition Item No.
4 Location Central Processing Plant
GENERAL
5 P&ID No. SNO-R-PI-102
6 Service From Fuel Gas Scrubber to Flare Header
7 Line No. 2"-FG-0015-3B
8 Area Classification Zone-2, Gr. IIB, T3
C1 9 Valve Type Valve Code Trunnion Mounted Ball BA122
10 Body Size Body Form 2 in Ball
C 11 Body Material Port Size A105 Full Bore
12 Connection Rating RF Flange ASME 300#
C1 13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
C 14 Packing Lubrication & Isolation Expanded Graphite VTA
15 Bonnet Bolts Bonnet Nuts ASTM A193 B7M ASTM A194 2HM
C 16 Ball Material Stem Material CS+ENP 76μm 316 SS
C1 17 Leakage Rate Seat Material ISO 5028 Rate A (TSO) PTFE
18 NACE Requirement Yes
C 19 Type Stroking Time Pneumatic Piston / Spring return 4 Seconds
20 Size Safety Factor VTA in 1.3
21 Actuator Orientation Actuator Form Horizontal Cylinder
22 Ingress Protection Electrical Protection IP65 Eex i
23 Instrument Air Supply 80-120 Psig
24 Action on Air Failure Action on Power Failure Open Open
ACTUATOR 25 Fireproofing No
26 Solenoid Valve Schematic Detail Yes Type-2
27 Limit Switch Closed Limit Swich Open Yes Yes
28 Mounting Position Solenoid Power Supply Top 24VDC
29 Manual Reset No
30 Mechanical Position Indicator Red Closed / Green Open
C 31 Partial Stroke Facility No
31 Signal Cable 1/2" NPT
ELECTRICAL 32 Control Cable -
CONNECTIONS 33 Solenoid Cable 3/4" NPT
34
35 Fluid
Fl id Fuel
F l Gas
G
36 Phase Gas
37 Operating Pressure 300 psig
38 Design Pressure 350 psig
39 Operating Temperature 70 ºF
40 Design Temperature 200 ºF
PROCESS DATA
41 Max. Diff. Pressure for Actuator Size 350 psig
42
43 Line Size and Sch. Inlet Outlet 2 in Sch. 80 2 in Sch. 80
44 Speed of Operation Design VTA
45 (Seconds) Actual VTA
46
Notes
1. VTA : Vendor to advice
2. Actuated ball valve and actuator shall be provided with 316 SS nameplate engraved or die stamped with Valve Tag No., Manufacturer's Name,
Model No., Valve Size & Rating.
3. Vendor shall be responsible for the proper design and selection of valve, actuator, and accessories based on the information furnished
C1 in this specification. This Data Sheet shall refer to SNO-I-ES-013, Instrument Specification for Shutdown and Blowdown Valve
4. Actuator shall be sized based on valve manufacturer's required Torque values with 130% minimum safety margin to open or close the valve
against full ANSI rated differential pressure at minimum pneumatic supply pressure of 60 psig.
5. Vendor shall provide Torque table containing breaking, running and seating torques for valves and actuator along with Quotation.
Vendor shall provide the torque table and calculation for COMPANY approval.
6. Actuator and accessories shall be supplied fully assembled, tubed and tested ready for installation.
7. Solenoid valve coil shall be provided with reverse polarity protection diodes, integral outlet box and terminal strip for cable connection.
8. Three way valve shall be universal type. Solenoid Coil shall be Class H.
Air filter regulator shall be 316 SS Material and equipped with pressure gauge on inlet and outlet of air filter regulator.
C1 9. All SDV & BDV shall be designed & tested as per API 6D
C1 10. Valve Stem Shall be Anti-Blowout Type.

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 67 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
1 Tag No. Quantity SDV -8145A / 8245A 2 (Two)
2 Manufacturer Model VTA VTA
3 Contract No. Requisition Item No.
4 Location Central Processing Plant
GENERAL
C 5 P&ID No. SNO-R-PI-105 / 134
C 6 Service Hot Oil Circulation Pump P-8043A/8043B to Hot Oil Heater
C1 7 Line No. 10"-OH-1002-3A / 10"-OH-2002-3A
8 Area Classification Zone-2, Gr. IIB, T3
9 Valve Type Valve Code Trunnion Mounted Ball BA010
C1 10 Body Size Body Form 10 in Ball
11 Body Material Port Size ASTM A216-WCB Full Bore
12 Connection Rating RF Flange ASME 300#
C1 13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
C 14 Packing Lubrication & Isolation Expanded Graphite VTA
C 15 Bonnet Bolts Bonnet Nuts ASTM A193 B7 ASTM A194 2H
C 16 Ball Material Stem Material 316 SS CS+ENP 76μm
C1 17 Leakage Rate Seat Material ISO 5028 Rate D Metal
18 NACE Requirement No
C 19 Type Stroking Time Pneumatic Piston / Spring return 15 Seconds
C 20 Size Safety Factor VTA in 1.5
21 Actuator Orientation Actuator Form Horizontal Cylinder
22 Ingress Protection Electrical Protection IP65 Eex i
23 Instrument Air Supply 80-120 Psig
24 Action on Air Failure Action on Power Failure Closed Closed
ACTUATOR 25 Fireproofing No
26 Solenoid Valve Schematic Detail Yes Type-1
27 Limit Switch Closed Limit Swich Open Yes Yes
28 Mounting Position Solenoid Power Supply Top 24VDC
29 Manual Reset No
30 Mechanical Position Indicator Red Closed / Green Open
C 31 Partial Stroke Facility Yes
31 Signal Cable 1/2" NPT
ELECTRICAL 32 Control Cable -
CONNECTIONS 33 Solenoid Cable 3/4" NPT
34
35 Fl id
Fluid H t Oil
Hot
36 Phase Liquid
C 37 Operating Pressure 125 psig
C 38 Design Pressure 275 psig
C 39 Operating Temperature 301 ºF
C 40 Design Temperature 550 ºF
PROCESS DATA
C 41 Max. Diff. Pressure for Actuator Size 275 psig
42
C1 43 Line Size and Sch. Inlet Outlet 10 in Sch. 40 10 in Sch. 40
44 Speed of Operation Design VTA
45 (Seconds) Actual VTA
46
Notes
1. VTA : Vendor to advice
2. Actuated ball valve and actuator shall be provided with 316 SS nameplate engraved or die stamped with Valve Tag No., Manufacturer's Name,
Model No., Valve Size & Rating.
3. Vendor shall be responsible for the proper design and selection of valve, actuator, and accessories based on the information furnished
C1 in this specification. This Data Sheet shall refer to SNO-I-ES-013, Instrument Specification for Shutdown and Blowdown Valve
4. Actuator shall be sized based on valve manufacturer's required Torque values with 130% minimum safety margin to open or close the valve
against full ANSI rated differential pressure at minimum pneumatic supply pressure of 60 psig.
5. Vendor shall provide Torque table containing breaking, running and seating torques for valves and actuator along with Quotation.
Vendor shall provide the torque table and calculation for COMPANY approval.
6. Actuator and accessories shall be supplied fully assembled, tubed and tested ready for installation.
7. Solenoid valve coil shall be provided with reverse polarity protection diodes, integral outlet box and terminal strip for cable connection.
8. Three way valve shall be universal type. Solenoid Coil shall be Class H.
Air filter regulator shall be 316 SS Material and equipped with pressure gauge on inlet and outlet of air filter regulator.
C1 9. All SDV & BDV shall be designed & tested as per API 6D
C1 10. Valve Stem Shall be Anti-Blowout Type.

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 68 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
1 Tag No. Quantity SDV -8145I / 8245I 2 (Two)
2 Manufacturer Model VTA VTA
3 Contract No. Requisition Item No.
4 Location Central Processing Plant
GENERAL
C 5 P&ID No. SNO-R-PI-105 / 134
C 6 Service Hot Oil Heater - Train 1 / Train2 Outlet
C 7 Line No. 10"-OH-1017-3A / 10"OH-2017-3A
8 Area Classification Zone-2, Gr. IIB, T3
9 Valve Type Valve Code Trunnion Mounted Ball BA010
10 Body Size Body Form 10 in Ball
11 Body Material Port Size ASTM A216-WCB Full Bore
12 Connection Rating RF Flange ASME 300#
C1 13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
C 14 Packing Lubrication & Isolation Expanded Graphite VTA
C 15 Bonnet Bolts Bonnet Nuts ASTM A193 B7 ASTM A194 2H
C 16 Ball Material Stem Material 316 SS CS+ENP 76μm
C1 17 Leakage Rate Seat Material ISO 5028 Rate D Metal
18 NACE Requirement No
C 19 Type Stroking Time Pneumatic Piston / Spring return 15 Seconds
20 Size Safety Factor VTA in 1.3
21 Actuator Orientation Actuator Form Horizontal Cylinder
22 Ingress Protection Electrical Protection IP65 Eex i
23 Instrument Air Supply 80-120 Psig
24 Action on Air Failure Action on Power Failure Closed Closed
ACTUATOR 25 Fireproofing No
26 Solenoid Valve Schematic Detail Yes Type-1
27 Limit Switch Closed Limit Swich Open Yes Yes
28 Mounting Position Solenoid Power Supply Top 24VDC
29 Manual Reset No
30 Mechanical Position Indicator Red Closed / Green Open
C 31 Partial Stroke Facility No
31 Signal Cable 1/2" NPT
ELECTRICAL 32 Control Cable -
CONNECTIONS 33 Solenoid Cable 3/4" NPT
34
Fl id
35 Fluid H t Oil
Hot
36 Phase Liquid
C 37 Operating Pressure 125 psig
C 38 Design Pressure 275 psig
39 Operating Temperature 450 ºF
40 Design Temperature 550 ºF
PROCESS DATA
C 41 Max. Diff. Pressure for Actuator Size 275 psig
42
43 Line Size and Sch. Inlet Outlet 10 in Sch. 40 10 in Sch. 40
44 Speed of Operation Design VTA
45 (Seconds) Actual VTA
46
Notes
1. VTA : Vendor to advice
2. Actuated ball valve and actuator shall be provided with 316 SS nameplate engraved or die stamped with Valve Tag No., Manufacturer's Name,
Model No., Valve Size & Rating.
3. Vendor shall be responsible for the proper design and selection of valve, actuator, and accessories based on the information furnished
C1 in this specification. This Data Sheet shall refer to SNO-I-ES-013, Instrument Specification for Shutdown and Blowdown Valve
4. Actuator shall be sized based on valve manufacturer's required Torque values with 130% minimum safety margin to open or close the valve
against full ANSI rated differential pressure at minimum pneumatic supply pressure of 60 psig.
5. Vendor shall provide Torque table containing breaking, running and seating torques for valves and actuator along with Quotation.
Vendor shall provide the torque table and calculation for COMPANY approval.
6. Actuator and accessories shall be supplied fully assembled, tubed and tested ready for installation.
7. Solenoid valve coil shall be provided with reverse polarity protection diodes, integral outlet box and terminal strip for cable connection.
8. Three way valve shall be universal type. Solenoid Coil shall be Class H.
Air filter regulator shall be 316 SS Material and equipped with pressure gauge on inlet and outlet of air filter regulator.
C1 9. All SDV & BDV shall be designed & tested as per API 6D
C1 10. Valve Stem Shall be Anti-Blowout Type.

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 69 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
1 Tag No. Quantity SDV -8026 1 (One)
2 Manufacturer Model VTA VTA
3 Contract No. Requisition Item No.
4 Location Central Processing Plant
GENERAL
5 P&ID No. SNO-R-PI-130
6 Service Liquid Recovery Pumps Outlet
7 Line No. 4"-FL-0020-9N
8 Area Classification Zone-2, Gr. IIB, T3
9 Valve Type Valve Code Trunnion Mounted Ball BA471
10 Body Size Body Form 4 in Ball
11 Body Material Port Size ASTM A351 CF8M Full Bore
12 Connection Rating RTJ Flange ASME 900#
C1 13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
C 14 Packing Lubrication & Isolation Expanded Graphite VTA
15 Bonnet Bolts Bonnet Nuts ASTM A193 B8M CL 2 ASTM A194 8M
C 16 Ball Material Stem Material 316 SS 316 SS
C1 17 Leakage Rate Seat Material ISO 5028 Rate A PTFE OR NYLON
18 NACE Requirement Yes
C 19 Type Stroking Time Pneumatic Piston / Spring return 8 Seconds
20 Size Safety Factor VTA in 1.3
21 Actuator Orientation Actuator Form Horizontal Cylinder
22 Ingress Protection Electrical Protection IP65 Eex i
23 Instrument Air Supply 80-120 Psig
24 Action on Air Failure Action on Power Failure Closed Closed
ACTUATOR 25 Fireproofing No
26 Solenoid Valve Schematic Detail Yes Type-1
27 Limit Switch Closed Limit Swich Open Yes Yes
28 Mounting Position Solenoid Power Supply Top 24VDC
29 Manual Reset No
30 Mechanical Position Indicator Red Closed / Green Open
C 31 Partial Stroke Facility No
31 Signal Cable 1/2" NPT
ELECTRICAL 32 Control Cable -
CONNECTIONS 33 Solenoid Cable 3/4" NPT
34
Fl id
35 Fluid H d b Liquid
Hydrocarbon Li id
36 Phase Liquid
C 37 Operating Pressure 968 psig
C 38 Design Pressure 1300 psig
39 Operating Temperature AMB ºF
40 Design Temperature 200 ºF
PROCESS DATA
C 41 Max. Diff. Pressure for Actuator Size 1300 psig
42
43 Line Size and Sch. Inlet Outlet 4 in Sch. 80S 4 in Sch. 80S
44 Speed of Operation Design VTA
45 (Seconds) Actual VTA
46
Notes
1. VTA : Vendor to advice
2. Actuated ball valve and actuator shall be provided with 316 SS nameplate engraved or die stamped with Valve Tag No., Manufacturer's Name,
Model No., Valve Size & Rating.
3. Vendor shall be responsible for the proper design and selection of valve, actuator, and accessories based on the information furnished
C1 in this specification. This Data Sheet shall refer to SNO-I-ES-013, Instrument Specification for Shutdown and Blowdown Valve
4. Actuator shall be sized based on valve manufacturer's required Torque values with 130% minimum safety margin to open or close the valve
against full ANSI rated differential pressure at minimum pneumatic supply pressure of 60 psig.
5. Vendor shall provide Torque table containing breaking, running and seating torques for valves and actuator along with Quotation.
Vendor shall provide the torque table and calculation for COMPANY approval.
6. Actuator and accessories shall be supplied fully assembled, tubed and tested ready for installation.
7. Solenoid valve coil shall be provided with reverse polarity protection diodes, integral outlet box and terminal strip for cable connection.
Three way valve shall be universal type. Solenoid Coil shall be Class H.
8. Air filter regulator shall be 316 SS Material and equipped with pressure gauge on inlet and outlet of air filter regulator.
C1 9. All SDV & BDV shall be designed & tested as per API 6D
C1 10. Valve Stem Shall be Anti-Blowout Type.

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 70 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
1 Tag No. Quantity SDV -8607B 1 (One)
2 Manufacturer Model VTA VTA
3 Contract No. Requisition Item No.
4 Location Central Processing Plant
GENERAL
5 P&ID No. SNO-R-PI-131
6 Service From HP Fuel Gas to LP Fuel Gas Scrubber
7 Line No. 4"-FG-0035-3B
8 Area Classification Zone-2, Gr. IIB, T3
C1 9 Valve Type Valve Code Trunnion Mounted Ball BA122
10 Body Size Body Form 4 in Ball
C 11 Body Material Port Size A105 Full Bore
12 Connection Rating RF Flange ASME 300#
C1 13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
C 14 Packing Lubrication & Isolation Expanded Graphite VTA
15 Bonnet Bolts Bonnet Nuts ASTM A193 B7M ASTM A194 2HM
C 16 Ball Material Stem Material CS+ENP 76μm 316SS
C1 17 Leakage Rate Seat Material ISO 5028 Rate A PTFE
18 NACE Requirement Yes
C 19 Type Stroking Time Pneumatic Piston / Spring return 8 Seconds
C 20 Size Safety Factor VTA in 1.5
21 Actuator Orientation Actuator Form Horizontal Cylinder
22 Ingress Protection Electrical Protection IP65 Eex i
23 Instrument Air Supply 80-120 Psig
24 Action on Air Failure Action on Power Failure Closed Closed
ACTUATOR 25 Fireproofing No
26 Solenoid Valve Schematic Detail Yes Type-1
27 Limit Switch Closed Limit Swich Open Yes Yes
28 Mounting Position Solenoid Power Supply Top 24VDC
C 29 Manual Reset No
30 Mechanical Position Indicator Red Closed / Green Open
C 31 Partial Stroke Facility Yes
31 Signal Cable 1/2" NPT
ELECTRICAL 32 Control Cable -
CONNECTIONS 33 Solenoid Cable 3/4" NPT
34
Fl id
35 Fluid F l Gas
Fuel G
36 Phase Gas
C 37 Operating Pressure 302 psig
38 Design Pressure 350 psig
C 39 Operating Temperature 110 ºF
40 Design Temperature 200 ºF
PROCESS DATA
41 Max. Diff. Pressure for Actuator Size 350 psig
42
43 Line Size and Sch. Inlet Outlet 4 in Sch. 40 4 in Sch. 40
44 Speed of Operation Design VTA
45 (Seconds) Actual VTA
46
Notes
1. VTA : Vendor to advice
2. Actuated ball valve and actuator shall be provided with 316 SS nameplate engraved or die stamped with Valve Tag No., Manufacturer's Name,
Model No., Valve Size & Rating.
3. Vendor shall be responsible for the proper design and selection of valve, actuator, and accessories based on the information furnished
C1 in this specification. This Data Sheet shall refer to SNO-I-ES-013, Instrument Specification for Shutdown and Blowdown Valve
4. Actuator shall be sized based on valve manufacturer's required Torque values with 130% minimum safety margin to open or close the valve
against full ANSI rated differential pressure at minimum pneumatic supply pressure of 60 psig.
5. Vendor shall provide Torque table containing breaking, running and seating torques for valves and actuator along with Quotation.
Vendor shall provide the torque table and calculation for COMPANY approval.
6. Actuator and accessories shall be supplied fully assembled, tubed and tested ready for installation.
7. Solenoid valve coil shall be provided with reverse polarity protection diodes, integral outlet box and terminal strip for cable connection.
8. Three way valve shall be universal type. Solenoid Coil shall be Class H.
Air filter regulator shall be 316 SS Material and equipped with pressure gauge on inlet and outlet of air filter regulator.
C1 9. All SDV & BDV shall be designed & tested as per API 6D
C1 10. Valve Stem Shall be Anti-Blowout Type.

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 71 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
1 Tag No. Quantity SDV -8607C 1 (One)
2 Manufacturer Model VTA VTA
3 Contract No. Requisition Item No.
4 Location Central Processing Plant
GENERAL
5 P&ID No. SNO-R-PI-131
6 Service LP Fuel Gas Scrubber to Closed Drain Header
7 Line No. 2"-DC-0012-1B
8 Area Classification Zone-2, Gr. IIB, T3
C1 9 Valve Type Valve Code Trunnion Mounted Ball BA032
10 Body Size Body Form 2 in Ball
11 Body Material Port Size ASTM A216-WCB Full Bore
12 Connection Rating RF Flange ASME 150#
C1 13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
C 14 Packing Lubrication & Isolation Expanded Graphite VTA
15 Bonnet Bolts Bonnet Nuts ASTM A193 B7M ASTM A194 2HM
16 Ball Material Stem Material 316 SS 316 SS
C1 17 Leakage Rate Seat Material ISO 5028 Rate A (TSO) PTFE
18 NACE Requirement Yes
C 19 Type Stroking Time Pneumatic Piston / Spring return 4 Seconds
20 Size Safety Factor VTA in 1.3
21 Actuator Orientation Actuator Form Horizontal Cylinder
22 Ingress Protection Electrical Protection IP65 Eex i
23 Instrument Air Supply 80-120 Psig
24 Action on Air Failure Action on Power Failure Closed Closed
ACTUATOR 25 Fireproofing No
26 Solenoid Valve Schematic Detail Yes Type-1
27 Limit Switch Closed Limit Swich Open Yes Yes
28 Mounting Position Solenoid Power Supply Top 24VDC
29 Manual Reset No
30 Mechanical Position Indicator Red Closed / Green Open
C 31 Partial Stroke Facility No
31 Signal Cable 1/2" NPT
ELECTRICAL 32 Control Cable -
CONNECTIONS 33 Solenoid Cable 3/4" NPT
34
Fl id
35 Fluid H d b
Hydrocarbon
36 Phase Liquid
C 37 Operating Pressure 102 psig
C 38 Design Pressure 152 psig
C 39 Operating Temperature 92 ºF
40 Design Temperature 200 ºF
PROCESS DATA
C 41 Max. Diff. Pressure for Actuator Size 152 psig
42
43 Line Size and Sch. Inlet Outlet 2 in Sch. 80 2 in Sch. 80
44 Speed of Operation Design VTA
45 (Seconds) Actual VTA
46
Notes
1. VTA : Vendor to advice
2. Actuated ball valve and actuator shall be provided with 316 SS nameplate engraved or die stamped with Valve Tag No., Manufacturer's Name,
Model No., Valve Size & Rating.
3. Vendor shall be responsible for the proper design and selection of valve, actuator, and accessories based on the information furnished
C1 in this specification. This Data Sheet shall refer to SNO-I-ES-013, Instrument Specification for Shutdown and Blowdown Valve
4. Actuator shall be sized based on valve manufacturer's required Torque values with 130% minimum safety margin to open or close the valve
against full ANSI rated differential pressure at minimum pneumatic supply pressure of 60 psig.
5. Vendor shall provide Torque table containing breaking, running and seating torques for valves and actuator along with Quotation.
Vendor shall provide the torque table and calculation for COMPANY approval.
6. Actuator and accessories shall be supplied fully assembled, tubed and tested ready for installation.
7. Solenoid valve coil shall be provided with reverse polarity protection diodes, integral outlet box and terminal strip for cable connection.
8. Three way valve shall be universal type. Solenoid Coil shall be Class H.
Air filter regulator shall be 316 SS Material and equipped with pressure gauge on inlet and outlet of air filter regulator.
C1 9. All SDV & BDV shall be designed & tested as per API 6D
C1 10. Valve Stem Shall be Anti-Blowout Type.

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 72 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
1 Tag No. Quantity SDV-6071A 1 (One)
2 Manufacturer Model VTA VTA
3 Contract No. Requisition Item No.
4 Location Central Processing Plant
GENERAL
5 P&ID No. SNO-R-PI-150
6 Service SN0-V-6071 to Elec. Heater E-6079
7 Line No. 3"-HL-0207-9N
8 Area Classification Zone-2, Gr. IIB, T3
9 Valve Type Valve Code Trunnion Mounted Ball BA471
10 Body Size Body Form 3 in Ball
11 Body Material Port Size ASTM A351 CF8M Full Bore
12 Connection Rating RTJ ASME 900#
C1 13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
C 14 Packing Lubrication & Isolation Expanded Graphite VTA
15 Bonnet Bolts Bonnet Nuts ASTM A193 B8M CL2 ASTM A194 8M
C 16 Ball Material Stem Material 316 SS 316 SS
C1 17 Leakage Rate Seat Material ISO 5028 Rate A PTFE OR NYLON
18 NACE Requirement Yes
C 19 Type Stroking Time Pneumatic Piston / Spring return 6 Seconds
20 Size Safety Factor VTA in 1.3
21 Actuator Orientation Actuator Form Horizontal Cylinder
22 Ingress Protection Electrical Protection IP65 Eex i
23 Instrument Air Supply 80-120 Psig
24 Action on Air Failure Action on Power Failure Closed Closed
ACTUATOR 25 Fireproofing No
26 Solenoid Valve Schematic Detail Yes Type-1
27 Limit Switch Closed Limit Swich Open Yes Yes
28 Mounting Position Solenoid Power Supply Top 24VDC
29 Manual Reset No
30 Mechanical Position Indicator Red Closed / Green Open
C 31 Partial Stroke Facility No
31 Signal Cable 1/2" NPT
ELECTRICAL 32 Control Cable -
CONNECTIONS 33 Solenoid Cable 3/4" NPT
34
Fl id
35 Fluid H d b Fluid
Hydrocarbon Fl id
36 Phase Liquid
37 Operating Pressure 1002 psig
38 Design Pressure 1300 psig
39 Operating Temperature 120 ºF
40 Design Temperature 140 ºF
PROCESS DATA
41 Max. Diff. Pressure for Actuator Size 1300 psig
42
43 Line Size and Sch. Inlet Outlet 3 in Sch. 80S 3 in Sch. 80S
44 Speed of Operation Design VTA
45 (Seconds) Actual VTA
46
Notes
1. VTA : Vendor to advice
2. Actuated ball valve and actuator shall be provided with 316 SS nameplate engraved or die stamped with Valve Tag No., Manufacturer's Name,
Model No., Valve Size & Rating.
3. Vendor shall be responsible for the proper design and selection of valve, actuator, and accessories based on the information furnished
C1 in this specification. This Data Sheet shall refer to SNO-I-ES-013, Instrument Specification for Shutdown and Blowdown Valve
4. Actuator shall be sized based on valve manufacturer's required Torque values with 130% minimum safety margin to open or close the valve
against full ANSI rated differential pressure at minimum pneumatic supply pressure of 60 psig.
5. Vendor shall provide Torque table containing breaking, running and seating torques for valves and actuator along with Quotation.
Vendor shall provide the torque table and calculation for COMPANY approval.
6. Actuator and accessories shall be supplied fully assembled, tubed and tested ready for installation.
7. Solenoid valve coil shall be provided with reverse polarity protection diodes, integral outlet box and terminal strip for cable connection.
8. Three way valve shall be universal type. Solenoid Coil shall be Class H.
Air filter regulator shall be 316 SS Material and equipped with pressure gauge on inlet and outlet of air filter regulator.
C1 9. All SDV & BDV shall be designed & tested as per API 6D
C1 10. Valve Stem Shall be Anti-Blowout Type.

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 73 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
1 Tag No. Quantity SDV -6078A 1 (One)
2 Manufacturer Model VTA VTA
3 Contract No. Requisition Item No.
4 Location Central Processing Plant
GENERAL
5 P&ID No. SNO-R-PI-150
6 Service Cluster #5 to Gas/Liquid Heat Exchanger (SNO-E-6078 A/B/C)
C 7 Line No. 6"-HF-XXXX-15R
8 Area Classification Zone-2, Gr. IIB, T3
9 Valve Type Valve Code Trunnion Mounted Ball BA453
10 Body Size Body Form 6 in Ball
11 Body Material Port Size ASTM A182 F51 Full Bore
12 Connection Rating RTJ ASME 1500#
C1 13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
C 14 Packing Lubrication & Isolation Expanded Graphite VTA
15 Bonnet Bolts Bonnet Nuts UNS S31803 UNS S31803
16 Ball Material Stem Material ASTM A182 F51 ASTM A182 F51
C1 17 Leakage Rate Seat Material ISO 5028 Rate A (TSO) PTFE OR NYLON
18 NACE Requirement Yes
C 19 Type Stroking Time Pneumatic Piston / Spring return 12 Seconds
20 Size Safety Factor VTA in 1.3
21 Actuator Orientation Actuator Form Horizontal Cylinder
22 Ingress Protection Electrical Protection IP65 Eex i
23 Instrument Air Supply 80-120 Psig
24 Action on Air Failure Action on Power Failure Closed Closed
ACTUATOR 25 Fireproofing No
26 Solenoid Valve Schematic Detail Yes Type-16
27 Limit Switch Closed Limit Swich Open Yes Yes
28 Mounting Position Solenoid Power Supply Top 24VDC
29 Manual Reset Yes
30 Mechanical Position Indicator Red Closed / Green Open
C 31 Partial Stroke Facility No
31 Signal Cable 1/2" NPT
ELECTRICAL 32 Control Cable -
CONNECTIONS 33 Solenoid Cable 3/4" NPT
34
Fl id
C 35 Fluid W ll Fluid
Well Fl id
36 Phase Gas / Liquid
37 Operating Pressure 1022 psig
38 Design Pressure 1300 psig
39 Operating Temperature 146 ºF
C 40 Design Temperature 250 ºF
PROCESS DATA
41 Max. Diff. Pressure for Actuator Size 1300 psig
42
43 Line Size and Sch. Inlet Outlet 6 in Sch. 80S 6 in Sch. 80S
44 Speed of Operation Design VTA
45 (Seconds) Actual VTA
46
Notes
1. VTA : Vendor to advice
2. Actuated ball valve and actuator shall be provided with 316 SS nameplate engraved or die stamped with Valve Tag No., Manufacturer's Name,
Model No., Valve Size & Rating.
3. Vendor shall be responsible for the proper design and selection of valve, actuator, and accessories based on the information furnished
C1 in this specification. This Data Sheet shall refer to SNO-I-ES-013, Instrument Specification for Shutdown and Blowdown Valve
4. Actuator shall be sized based on valve manufacturer's required Torque values with 130% minimum safety margin to open or close the valve
against full ANSI rated differential pressure at minimum pneumatic supply pressure of 60 psig.
5. Vendor shall provide Torque table containing breaking, running and seating torques for valves and actuator along with Quotation.
Vendor shall provide the torque table and calculation for COMPANY approval.
6. Actuator and accessories shall be supplied fully assembled, tubed and tested ready for installation.
7. Solenoid valve coil shall be provided with reverse polarity protection diodes, integral outlet box and terminal strip for cable connection.
8. Three way valve shall be universal type. Solenoid Coil shall be Class H.
Air filter regulator shall be 316 SS Material and equipped with pressure gauge on inlet and outlet of air filter regulator.
C1 9. All SDV & BDV shall be designed & tested as per API 6D
C1 10. Valve Stem Shall be Anti-Blowout Type.

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 74 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
1 Tag No. Quantity BDV-6071E 1 (One)
2 Manufacturer Model VTA VTA
3 Contract No. Requisition Item No.
4 Location Central Processing Plant
GENERAL
5 P&ID No. SNO-R-PI-150
6 Service SNO-V-6071 to HP Flare Header
C1 7 Line No. 3"-HG-0214-9N
8 Area Classification Zone-2, Gr. IIB, T3
C1 9 Valve Type Valve Code Trunnion Mounted Ball BA466
C1 10 Body Size Body Form 3 in Ball
C1 11 Body Material Port Size ASTM A351 CF8M Full Bore
C 12 Connection Rating RTJ ASME 900#
C1 13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
C 14 Packing Lubrication & Isolation Expanded Graphite VTA
15 Bonnet Bolts Bonnet Nuts ASTM A193 B8M CL2 ASTM A194 8M
C 16 Ball Material Stem Material 316SS 316SS
C1 17 Leakage Rate Seat Material ISO 5028 Rate A PTFE OR NYLON
18 NACE Requirement Yes
C1 19 Type Stroking Time Pneumatic Piston / Spring return 6 Seconds
20 Size Safety Factor VTA in 1.3
21 Actuator Orientation Actuator Form Horizontal Cylinder
22 Ingress Protection Electrical Protection IP65 Eex i
23 Instrument Air Supply 80-120 Psig
24 Action on Air Failure Action on Power Failure Open Open
ACTUATOR 25 Fireproofing No
26 Solenoid Valve Schematic Detail Yes Type-2
27 Limit Switch Closed Limit Swich Open Yes Yes
28 Mounting Position Solenoid Power Supply Top 24VDC
29 Manual Reset No
30 Mechanical Position Indicator Red Closed / Green Open
C 31 Partial Stroke Facility No
31 Signal Cable 1/2" NPT
ELECTRICAL 32 Control Cable -
CONNECTIONS 33 Solenoid Cable 3/4" NPT
34
35 Fl id
Fluid H d b Fluid
Hydrocarbon Fl id
36 Phase Gas
37 Operating Pressure 1002 psig
38 Design Pressure 1300 psig
39 Operating Temperature 120 ºF
40 Design Temperature 140 ºF
PROCESS DATA
41 Max. Diff. Pressure for Actuator Size 1300 psig
42
C1 43 Line Size and Sch. Inlet Outlet 3 in Sch. 80S 3 in Sch. 80S
44 Speed of Operation Design VTA
45 (Seconds) Actual VTA
46
Notes
1. VTA : Vendor to advice
2. Actuated ball valve and actuator shall be provided with 316 SS nameplate engraved or die stamped with Valve Tag No., Manufacturer's Name,
Model No., Valve Size & Rating.
3. Vendor shall be responsible for the proper design and selection of valve, actuator, and accessories based on the information furnished
C1 in this specification. This Data Sheet shall refer to SNO-I-ES-013, Instrument Specification for Shutdown and Blowdown Valve
4. Actuator shall be sized based on valve manufacturer's required Torque values with 130% minimum safety margin to open or close the valve
against full ANSI rated differential pressure at minimum pneumatic supply pressure of 60 psig.
5. Vendor shall provide Torque table containing breaking, running and seating torques for valves and actuator along with Quotation.
Vendor shall provide the torque table and calculation for COMPANY approval.
6. Actuator and accessories shall be supplied fully assembled, tubed and tested ready for installation.
7. Solenoid valve coil shall be provided with reverse polarity protection diodes, integral outlet box and terminal strip for cable connection.
8. Three way valve shall be universal type. Solenoid Coil shall be Class H.
Air filter regulator shall be 316 SS Material and equipped with pressure gauge on inlet and outlet of air filter regulator.
C1 9. All SDV & BDV shall be designed & tested as per API 6D
C1 10. Valve Stem Shall be Anti-Blowout Type.

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 75 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
1 Tag No. Quantity SDV -6075A 1 (One)
2 Manufacturer Model VTA VTA
3 Contract No. Requisition Item No.
4 Location Central Processing Plant
GENERAL
5 P&ID No. SNO-R-PI-152
6 Service SN0-V-6075 to Gas Liquid Heat Exchager E-6078
7 Line No. 2"-HL-0206-9N
8 Area Classification Zone-2, Gr. IIB, T3
C1 9 Valve Type Valve Code Trunnion Mounted Ball BA466
10 Body Size Body Form 2 in Ball
11 Body Material Port Size ASTM A182 F316L Full Bore
C 12 Connection Rating RTJ ASME 1500#
C1 13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
C 14 Packing Lubrication & Isolation Expanded Graphite VTA
15 Bonnet Bolts Bonnet Nuts ASTM A193 B8M CL2 ASTM A194 8M
C 16 Ball Material Stem Material 316 SS 316 SS
C1 17 Leakage Rate Seat Material ISO 5028 Rate A PTFE OR NYLON
18 NACE Requirement Yes
C 19 Type Stroking Time Pneumatic Piston / Spring return 4 Seconds
20 Size Safety Factor VTA in 1.3
21 Actuator Orientation Actuator Form Horizontal Cylinder
22 Ingress Protection Electrical Protection IP65 Eex i
23 Instrument Air Supply 80-120 Psig
24 Action on Air Failure Action on Power Failure Closed Closed
ACTUATOR 25 Fireproofing No
26 Solenoid Valve Schematic Detail Yes Type-1
27 Limit Switch Closed Limit Swich Open Yes Yes
28 Mounting Position Solenoid Power Supply Top 24VDC
29 Manual Reset No
30 Mechanical Position Indicator Red Closed / Green Open
C 31 Partial Stroke Facility No
31 Signal Cable 1/2" NPT
ELECTRICAL 32 Control Cable -
CONNECTIONS 33 Solenoid Cable 3/4" NPT
34
Fl id
35 Fluid H d b Fluid
Hydrocarbon Fl id
36 Phase Liquid
37 Operating Pressure 630 psig
38 Design Pressure 725 psig
C 39 Operating Temperature 65 ºF
C 40 Design Temperature 130 ºF
PROCESS DATA
41 Max. Diff. Pressure for Actuator Size 725 psig
42
43 Line Size and Sch. Inlet Outlet 2 in Sch. 80S 2 in Sch. 80S
44 Speed of Operation Design VTA
45 (Seconds) Actual VTA
46
Notes
1. VTA : Vendor to advice
2. Actuated ball valve and actuator shall be provided with 316 SS nameplate engraved or die stamped with Valve Tag No., Manufacturer's Name,
Model No., Valve Size & Rating.
3. Vendor shall be responsible for the proper design and selection of valve, actuator, and accessories based on the information furnished
C1 in this specification. This Data Sheet shall refer to SNO-I-ES-013, Instrument Specification for Shutdown and Blowdown Valve
4. Actuator shall be sized based on valve manufacturer's required Torque values with 130% minimum safety margin to open or close the valve
against full ANSI rated differential pressure at minimum pneumatic supply pressure of 60 psig.
5. Vendor shall provide Torque table containing breaking, running and seating torques for valves and actuator along with Quotation.
Vendor shall provide the torque table and calculation for COMPANY approval.
6. Actuator and accessories shall be supplied fully assembled, tubed and tested ready for installation.
7. Solenoid valve coil shall be provided with reverse polarity protection diodes, integral outlet box and terminal strip for cable connection.
8. Three way valve shall be universal type. Solenoid Coil shall be Class H.
Air filter regulator shall be 316 SS Material and equipped with pressure gauge on inlet and outlet of air filter regulator.
C1 9. All SDV & BDV shall be designed & tested as per API 6D
C1 10. Valve Stem Shall be Anti-Blowout Type.

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 76 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
1 Tag No. Quantity SDV-6073 1 (One)
2 Manufacturer Model VTA VTA
3 Contract No. Requisition Item No.
4 Location Central Processing Plant
GENERAL
5 P&ID No. SNO-R-PI-152
6 Service SNO-E-6073 to Export Gas
C 7 Line No. 4"-HL-0211-6A
8 Area Classification Zone-2, Gr. IIB, T3
C1 9 Valve Type Valve Code Trunnion Mounted Ball BA013
10 Body Size Body Form 4 in Ball
C 11 Body Material Port Size ASTM A216 WCB Full Bore
12 Connection Rating RF Flange ASME 600#
C1 13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
C 14 Packing Lubrication & Isolation Expanded Graphite VTA
C 15 Bonnet Bolts Bonnet Nuts ASTM A193 B7 ASTM A194 2H
C 16 Ball Material Stem Material CS+ENP 76μm A564 630, H1150M+ENP 76 μm
C1 17 Leakage Rate Seat Material ISO 5028 Rate A PTFE OR NYLON
18 NACE Requirement No
C 19 Type Stroking Time Pneumatic Piston / Spring return 8 Seconds
20 Size Safety Factor VTA in 1.3
21 Actuator Orientation Actuator Form Horizontal Cylinder
22 Ingress Protection Electrical Protection IP65 Eex i
23 Instrument Air Supply 80-120 Psig
24 Action on Air Failure Action on Power Failure Closed Closed
ACTUATOR 25 Fireproofing No
C 26 Solenoid Valve Schematic Detail Yes Type-16
27 Limit Switch Closed Limit Swich Open Yes Yes
28 Mounting Position Solenoid Power Supply Top 24VDC
29 Manual Reset No
30 Mechanical Position Indicator Red Closed / Green Open
C 31 Partial Stroke Facility No
31 Signal Cable 1/2" NPT
ELECTRICAL 32 Control Cable -
CONNECTIONS 33 Solenoid Cable 3/4" NPT
34
Fl id
35 Fluid H d b Fluid
Hydrocarbon Fl id
36 Phase Gas
C 37 Operating Pressure 630 psig
38 Design Pressure 725 psig
C 39 Operating Temperature 65 ºF
40 Design Temperature 130 ºF
PROCESS DATA
41 Max. Diff. Pressure for Actuator Size 725 psig
42
43 Line Size and Sch. Inlet Outlet 4 in Sch. 40S 4 in Sch. 40S
44 Speed of Operation Design VTA
45 (Seconds) Actual VTA
46
Notes
1. VTA : Vendor to advice
2. Actuated ball valve and actuator shall be provided with 316 SS nameplate engraved or die stamped with Valve Tag No., Manufacturer's Name,
Model No., Valve Size & Rating.
3. Vendor shall be responsible for the proper design and selection of valve, actuator, and accessories based on the information furnished
C1 in this specification. This Data Sheet shall refer to SNO-I-ES-013, Instrument Specification for Shutdown and Blowdown Valve
4. Actuator shall be sized based on valve manufacturer's required Torque values with 130% minimum safety margin to open or close the valve
against full ANSI rated differential pressure at minimum pneumatic supply pressure of 60 psig.
5. Vendor shall provide Torque table containing breaking, running and seating torques for valves and actuator along with Quotation.
Vendor shall provide the torque table and calculation for COMPANY approval.
6. Actuator and accessories shall be supplied fully assembled, tubed and tested ready for installation.
7. Solenoid valve coil shall be provided with reverse polarity protection diodes, integral outlet box and terminal strip for cable connection.
8. Three way valve shall be universal type. Solenoid Coil shall be Class H.
Air filter regulator shall be 316 SS Material and equipped with pressure gauge on inlet and outlet of air filter regulator.
C1 9. All SDV & BDV shall be designed & tested as per API 6D
C1 10. Valve Stem Shall be Anti-Blowout Type.

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 77 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
1 Tag No. Quantity SDV -2102A / 2202A 2 (Two)
2 Manufacturer Model VTA VTA
3 Contract No. Requisition Item No.
4 Location Central Processing Plant
GENERAL
5 P&ID No. SNO-R-PI-301 / SNO-R-PI-311
6 Service Amine Contactor to Amine Flash Drum
7 Line No. 12"-CA-1500-9N / 12"-CA-2500-9N
8 Area Classification Zone-2, Gr. IIB, T3
9 Valve Type Valve Code Trunnion Mounted Ball BA472
10 Body Size Body Form 12 in Ball
11 Body Material Port Size ASTM A351 CF8M Full Bore
12 Connection Rating RTJ ASME 900#
C1 13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
C 14 Packing Lubrication & Isolation Expanded Graphite VTA
15 Bonnet Bolts Bonnet Nuts ASTM A193 B8M CL2 ASTM A194 8M
C 16 Ball Material Stem Material 316 SS 316 SS
C1 17 Leakage Rate Seat Material ISO 5028 Rate A PTFE OR NYLON
18 NACE Requirement Yes
C 19 Type Stroking Time Pneumatic Piston / Spring return 15 Seconds
20 Size Safety Factor VTA in 1.3
21 Actuator Orientation Actuator Form Horizontal Cylinder
22 Ingress Protection Electrical Protection IP65 Eex i
23 Instrument Air Supply 80-120 Psig
C 24 Action on Air Failure Action on Power Failure Closed Closed
ACTUATOR 25 Fireproofing No
26 Solenoid Valve Schematic Detail Yes Type-1
27 Limit Switch Closed Limit Swich Open Yes Yes
28 Mounting Position Solenoid Power Supply Top 24VDC
29 Manual Reset No
30 Mechanical Position Indicator Red Closed / Green Open
C 31 Partial Stroke Facility No
31 Signal Cable 1/2" NPT
ELECTRICAL 32 Control Cable -
CONNECTIONS 33 Solenoid Cable 3/4" NPT
34
Fl id
35 Fluid A i
Amine
36 Phase Liquid
37 Operating Pressure 900 psig
38 Design Pressure 1300 psig
39 Operating Temperature 163 ºF
40 Design Temperature 185 ºF
PROCESS DATA
41 Max. Diff. Pressure for Actuator Size 1300 psig
42
43 Line Size and Sch. Inlet Outlet 12 in Sch. 100 12 in Sch. 100
44 Speed of Operation Design VTA
45 (Seconds) Actual VTA
46
Notes
1. VTA : Vendor to advice
2. Actuated ball valve and actuator shall be provided with 316 SS nameplate engraved or die stamped with Valve Tag No., Manufacturer's Name,
Model No., Valve Size & Rating.
3. Vendor shall be responsible for the proper design and selection of valve, actuator, and accessories based on the information furnished
C1 in this specification. This Data Sheet shall refer to SNO-I-ES-013, Instrument Specification for Shutdown and Blowdown Valve
4. Actuator shall be sized based on valve manufacturer's required Torque values with 130% minimum safety margin to open or close the valve
against full ANSI rated differential pressure at minimum pneumatic supply pressure of 60 psig.
5. Vendor shall provide Torque table containing breaking, running and seating torques for valves and actuator along with Quotation.
Vendor shall provide the torque table and calculation for COMPANY approval.
6. Actuator and accessories shall be supplied fully assembled, tubed and tested ready for installation.
7. Solenoid valve coil shall be provided with reverse polarity protection diodes, integral outlet box and terminal strip for cable connection.
8. Three way valve shall be universal type. Solenoid Coil shall be Class H.
Air filter regulator shall be 316 SS Material and equipped with pressure gauge on inlet and outlet of air filter regulator.
C1 9. All SDV & BDV shall be designed & tested as per API 6D
C1 10. Valve Stem Shall be Anti-Blowout Type.

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 78 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
1 Tag No. Quantity SDV -2102B / 2202B 2 (Two)
2 Manufacturer Model VTA VTA
3 Contract No. Requisition Item No.
4 Location Central Processing Plant
GENERAL
5 P&ID No. SNO-R-PI-301 / SNO-R-PI-311
6 Service From Lean Amine Circulation Pump to Amine Contactor
7 Line No. 12"-CA-1527-6B / 12"-CA-2527-6B
8 Area Classification Zone-2, Gr. IIB, T3
9 Valve Type Valve Code Trunnion Mounted Ball BA045
10 Body Size Body Form 12 in Ball
C 11 Body Material Port Size A216 WCB Full Bore
12 Connection Rating RF Flange ASME 600#
C1 13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
C 14 Packing Lubrication & Isolation Expanded Graphite VTA
15 Bonnet Bolts Bonnet Nuts ASTM A193 B7M ASTM A194 2HM
C 16 Ball Material Stem Material CS+ENP 76μm A564 630, H1150M+ENP 76 μm
C1 17 Leakage Rate Seat Material ISO 5028 Rate A PTFE OR NYLON
18 NACE Requirement Yes
C 19 Type Stroking Time Pneumatic Piston / Spring return 15 Seconds
20 Size Safety Factor VTA in 1.3
21 Actuator Orientation Actuator Form Horizontal Cylinder
22 Ingress Protection Electrical Protection IP65 Eex i
23 Instrument Air Supply 80-120 Psig
C 24 Action on Air Failure Action on Power Failure Closed Closed
ACTUATOR 25 Fireproofing No
26 Solenoid Valve Schematic Detail Yes Type-1
27 Limit Switch Closed Limit Swich Open Yes Yes
28 Mounting Position Solenoid Power Supply Top 24VDC
29 Manual Reset No
30 Mechanical Position Indicator Red Closed / Green Open
C 31 Partial Stroke Facility No
31 Signal Cable 1/2" NPT
ELECTRICAL 32 Control Cable -
CONNECTIONS 33 Solenoid Cable 3/4" NPT
34
Fl id
35 Fluid A i
Amine
36 Phase Liquid
C 37 Operating Pressure 900 psig
C 38 Design Pressure 1300 psig
C 39 Operating Temperature 132 ºF
C 40 Design Temperature 185 ºF
PROCESS DATA
C 41 Max. Diff. Pressure for Actuator Size 1300 psig
42
43 Line Size and Sch. Inlet Outlet 12 in Sch. 100 12 in Sch. 100
44 Speed of Operation Design VTA
45 (Seconds) Actual VTA
46
Notes
1. VTA : Vendor to advice
2. Actuated ball valve and actuator shall be provided with 316 SS nameplate engraved or die stamped with Valve Tag No., Manufacturer's Name,
Model No., Valve Size & Rating.
3. Vendor shall be responsible for the proper design and selection of valve, actuator, and accessories based on the information furnished
C1 in this specification. This Data Sheet shall refer to SNO-I-ES-013, Instrument Specification for Shutdown and Blowdown Valve
4. Actuator shall be sized based on valve manufacturer's required Torque values with 130% minimum safety margin to open or close the valve
against full ANSI rated differential pressure at minimum pneumatic supply pressure of 60 psig.
5. Vendor shall provide Torque table containing breaking, running and seating torques for valves and actuator along with Quotation.
Vendor shall provide the torque table and calculation for COMPANY approval.
6. Actuator and accessories shall be supplied fully assembled, tubed and tested ready for installation.
7. Solenoid valve coil shall be provided with reverse polarity protection diodes, integral outlet box and terminal strip for cable connection.
8. Three way valve shall be universal type. Solenoid Coil shall be Class H.
Air filter regulator shall be 316 SS Material and equipped with pressure gauge on inlet and outlet of air filter regulator.
C1 9. All SDV & BDV shall be designed & tested as per API 6D
C1 10. Valve Stem Shall be Anti-Blowout Type.

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 79 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
C 1 Tag No. Quantity SDV -2104D/ 2204D 2 (Two)
2 Manufacturer Model VTA VTA
3 Contract No. Requisition Item No.
4 Location Central Processing Plant
GENERAL
5 P&ID No. SNO-R-PI-302 / SNO-R-PI-312
6 Service Amine Flash Drum to Lean / Rich Exchanger
7 Line No. 12"-CA-1505-1N / 12"-CA-2505-1N
8 Area Classification Zone-2, Gr. IIB, T3
9 Valve Type Valve Code Trunnion Mounted Ball BA100
10 Body Size Body Form 12 in Ball
11 Body Material Port Size ASTM A351 CF8M Full Bore
12 Connection Rating RF Flange ASME 150#
C1 13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
C 14 Packing Lubrication & Isolation Expanded Graphite VTA
15 Bonnet Bolts Bonnet Nuts ASTM A193 B8M CL2 ASTM A194 8M
C 16 Ball Material Stem Material 316 SS 316 SS
C1 17 Leakage Rate Seat Material ISO 5028 Rate A PTFE
18 NACE Requirement Yes
C 19 Type Stroking Time Pneumatic Piston / Spring return 15 Seconds
20 Size Safety Factor VTA in 1.3
21 Actuator Orientation Actuator Form Horizontal Cylinder
22 Ingress Protection Electrical Protection IP65 Eex i
23 Instrument Air Supply 80-120 Psig
24 Action on Air Failure Action on Power Failure Closed Closed
ACTUATOR 25 Fireproofing No
26 Solenoid Valve Schematic Detail Yes Type 1
27 Limit Switch Closed Limit Swich Open Yes Yes
28 Mounting Position Solenoid Power Supply Top 24VDC
29 Manual Reset No
30 Mechanical Position Indicator Red Closed / Green Open
C 31 Partial Stroke Facility No
31 Signal Cable 1/2" NPT
ELECTRICAL 32 Control Cable -
CONNECTIONS 33 Solenoid Cable 3/4" NPT
34
Fl id
35 Fluid Ri h Amine
Rich A i
36 Phase Liquid
37 Operating Pressure 105 psig
38 Design Pressure 155 psig
39 Operating Temperature 163 ºF
C 40 Design Temperature 185 ºF
PROCESS DATA
41 Max. Diff. Pressure for Actuator Size 155 psig
42
43 Line Size and Sch. Inlet Outlet 12 in Sch. 10S 12 in Sch. 10S
44 Speed of Operation Design VTA
45 (Seconds) Actual VTA
46
Notes
1. VTA : Vendor to advice
2. Actuated ball valve and actuator shall be provided with 316 SS nameplate engraved or die stamped with Valve Tag No., Manufacturer's Name,
Model No., Valve Size & Rating.
3. Vendor shall be responsible for the proper design and selection of valve, actuator, and accessories based on the information furnished
C1 in this specification. This Data Sheet shall refer to SNO-I-ES-013, Instrument Specification for Shutdown and Blowdown Valve
4. Actuator shall be sized based on valve manufacturer's required Torque values with 130% minimum safety margin to open or close the valve
against full ANSI rated differential pressure at minimum pneumatic supply pressure of 60 psig.
5. Vendor shall provide Torque table containing breaking, running and seating torques for valves and actuator along with Quotation.
Vendor shall provide the torque table and calculation for COMPANY approval.
6. Actuator and accessories shall be supplied fully assembled, tubed and tested ready for installation.
7. Solenoid valve coil shall be provided with reverse polarity protection diodes, integral outlet box and terminal strip for cable connection.
8. Three way valve shall be universal type. Solenoid Coil shall be Class H.
Air filter regulator shall be 316 SS Material and equipped with pressure gauge on inlet and outlet of air filter regulator.
C1 9. All SDV & BDV shall be designed & tested as per API 6D
C1 10. Valve Stem Shall be Anti-Blowout Type.

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 80 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
C 1 Tag No. Quantity SDV-2104C / 2204C 2 (Two)
2 Manufacturer Model VTA VTA
3 Contract No. Requisition Item No.
4 Location Central Processing Plant
GENERAL
5 P&ID No. SNO-R-PI-302 / SNO-R-PI-312
6 Service Amine Flash Drum to Amine regen OVHD Condenser
7 Line No. 2"-GA-1500-1N / 2"-GA-2500-1N
8 Area Classification Zone-2, Gr. IIB, T3
C1 9 Valve Type Valve Code Trunnion Mounted Ball BA098
10 Body Size Body Form 2 in Ball
11 Body Material Port Size ASTM A351 CF8M Full Bore
12 Connection Rating RF Flange ASME 150#
C1 13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
C 14 Packing Lubrication & Isolation Expanded Graphite VTA
15 Bonnet Bolts Bonnet Nuts ASTM A193 B8M CL2 ASTM A194 8M
C 16 Ball Material Stem Material 316 SS 316 SS
C1 17 Leakage Rate Seat Material ISO 5028 Rate A PTFE
18 NACE Requirement Yes
C 19 Type Stroking Time Pneumatic Piston / Spring return 4 Seconds
20 Size Safety Factor VTA in 1.3
21 Actuator Orientation Actuator Form Horizontal Cylinder
22 Ingress Protection Electrical Protection IP65 Eex i
23 Instrument Air Supply 80-120 Psig
24 Action on Air Failure Action on Power Failure Closed Closed
ACTUATOR 25 Fireproofing No
26 Solenoid Valve Schematic Detail Yes Type 1
27 Limit Switch Closed Limit Swich Open Yes Yes
28 Mounting Position Solenoid Power Supply Top 24VDC
29 Manual Reset No
30 Mechanical Position Indicator Red Closed / Green Open
C 31 Partial Stroke Facility No
31 Signal Cable 1/2" NPT
ELECTRICAL 32 Control Cable -
CONNECTIONS 33 Solenoid Cable 3/4" NPT
34
Fl id
C 35 Fluid Ri h Amine
Rich A i
36 Phase Liquid
37 Operating Pressure 105 psig
38 Design Pressure 155 psig
39 Operating Temperature 163 ºF
C 40 Design Temperature 185 ºF
PROCESS DATA
41 Max. Diff. Pressure for Actuator Size 155 psig
42
43 Line Size and Sch. Inlet Outlet 2 in Sch. 10S 2 in Sch. 10S
44 Speed of Operation Design VTA
45 (Seconds) Actual VTA
46
Notes
1. VTA : Vendor to advice
2. Actuated ball valve and actuator shall be provided with 316 SS nameplate engraved or die stamped with Valve Tag No., Manufacturer's Name,
Model No., Valve Size & Rating.
3. Vendor shall be responsible for the proper design and selection of valve, actuator, and accessories based on the information furnished
C1 in this specification. This Data Sheet shall refer to SNO-I-ES-013, Instrument Specification for Shutdown and Blowdown Valve
4. Actuator shall be sized based on valve manufacturer's required Torque values with 130% minimum safety margin to open or close the valve
against full ANSI rated differential pressure at minimum pneumatic supply pressure of 60 psig.
5. Vendor shall provide Torque table containing breaking, running and seating torques for valves and actuator along with Quotation.
Vendor shall provide the torque table and calculation for COMPANY approval.
6. Actuator and accessories shall be supplied fully assembled, tubed and tested ready for installation.
7. Solenoid valve coil shall be provided with reverse polarity protection diodes, integral outlet box and terminal strip for cable connection.
8. Three way valve shall be universal type. Solenoid Coil shall be Class H.
Air filter regulator shall be 316 SS Material and equipped with pressure gauge on inlet and outlet of air filter regulator.
C1 9. All SDV & BDV shall be designed & tested as per API 6D
C1 10. Valve Stem Shall be Anti-Blowout Type.

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 81 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
C 1 Tag No. Quantity SDV-2106B / 2206B 2 (Two)
2 Manufacturer Model VTA VTA
3 Contract No. Requisition Item No.
4 Location Central Processing Plant
GENERAL
C 5 P&ID No. SNO-R-PI-304 / 314
6 Service From Hot Oil Distribution to Amine Reboiler SNO-E-2106A / 2206A
C 7 Line No. 12"-OH-1137-3A / 12"-OH-2137-3A
8 Area Classification Zone-2, Gr. IIB, T3
9 Valve Type Valve Code Trunnion Mounted Ball BA010
10 Body Size Body Form 12 in Ball
11 Body Material Port Size ASTM A216 WCB Full Bore
12 Connection Rating RF Flange ASME 300#
C1 13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
C 14 Packing Lubrication & Isolation Expanded Graphite VTA
C 15 Bonnet Bolts Bonnet Nuts ASTM A193 B7 ASTM A194 2H
C 16 Ball Material Stem Material 316 SS CS+ENP 76μm
C1 17 Leakage Rate Seat Material ISO 5028 Rate D Metal
18 NACE Requirement No
C 19 Type Stroking Time Pneumatic Piston / Spring return 15 Seconds
C 20 Size Safety Factor VTA in 1.5
21 Actuator Orientation Actuator Form Horizontal Cylinder
22 Ingress Protection Electrical Protection IP65 Eex i
23 Instrument Air Supply 80-120 Psig
24 Action on Air Failure Action on Power Failure Closed Closed
ACTUATOR 25 Fireproofing No
26 Solenoid Valve Schematic Detail Yes Type 1
27 Limit Switch Closed Limit Swich Open Yes Yes
28 Mounting Position Solenoid Power Supply Top 24VDC
29 Manual Reset No
30 Mechanical Position Indicator Red Closed / Green Open
C 31 Partial Stroke Facility Yes
31 Signal Cable 1/2" NPT
ELECTRICAL 32 Control Cable -
CONNECTIONS 33 Solenoid Cable 3/4" NPT
34
Fl id
35 Fluid H t Oil
Hot
36 Phase Liquid
37 Operating Pressure 65 psig
38 Design Pressure 210 psig
39 Operating Temperature 350 ºF
40 Design Temperature 450 ºF
PROCESS DATA
41 Max. Diff. Pressure for Actuator Size 210 psig
42
43 Line Size and Sch. Inlet Outlet 12 in Sch. 40 12 in Sch. 40
44 Speed of Operation Design VTA
45 (Seconds) Actual VTA
46
Notes
1. VTA : Vendor to advice
2. Actuated ball valve and actuator shall be provided with 316 SS nameplate engraved or die stamped with Valve Tag No., Manufacturer's Name,
Model No., Valve Size & Rating.
3. Vendor shall be responsible for the proper design and selection of valve, actuator, and accessories based on the information furnished
C1 in this specification. This Data Sheet shall refer to SNO-I-ES-013, Instrument Specification for Shutdown and Blowdown Valve
4. Actuator shall be sized based on valve manufacturer's required Torque values with 130% minimum safety margin to open or close the valve
against full ANSI rated differential pressure at minimum pneumatic supply pressure of 60 psig.
5. Vendor shall provide Torque table containing breaking, running and seating torques for valves and actuator along with Quotation.
Vendor shall provide the torque table and calculation for COMPANY approval.
6. Actuator and accessories shall be supplied fully assembled, tubed and tested ready for installation.
7. Solenoid valve coil shall be provided with reverse polarity protection diodes, integral outlet box and terminal strip for cable connection.
8. Three way valve shall be universal type. Solenoid Coil shall be Class H.
Air filter regulator shall be 316 SS Material and equipped with pressure gauge on inlet and outlet of air filter regulator.
C1 9. All SDV & BDV shall be designed & tested as per API 6D
C1 10. Valve Stem Shall be Anti-Blowout Type.

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 82 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
C 1 Tag No. Quantity SDV -2106A / 2206A 2 (Two)
2 Manufacturer Model VTA VTA
3 Contract No. Requisition Item No.
4 Location Central Processing Plant
GENERAL
5 P&ID No. SNO-R-PI-304 / SNO-R-PI-314
6 Service From Hot Oil Distribution to Amine Reboiler SNO-E-2106B / E-2206B
7 Line No. 12"-OH-1139-3A / 12"-OH-2139-3A
8 Area Classification Zone-2, Gr. IIB, T3
9 Valve Type Valve Code Trunnion Mounted Ball BA010
10 Body Size Body Form 12 in Ball
11 Body Material Port Size ASTM A216 WCB Full Bore
12 Connection Rating RF Flange ASME 300#
C1 13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
C 14 Packing Lubrication & Isolation Expanded Graphite VTA
C 15 Bonnet Bolts Bonnet Nuts ASTM A193 B7 ASTM A194 2H
C 16 Ball Material Stem Material 316 SS CS+ENP 76μm
C1 17 Leakage Rate Seat Material ISO 5028 Rate D Metal
18 NACE Requirement No
C 19 Type Stroking Time Pneumatic Piston / Spring return 15 Seconds
C 20 Size Safety Factor VTA in 1.5
21 Actuator Orientation Actuator Form Horizontal Cylinder
22 Ingress Protection Electrical Protection IP65 Eex i
23 Instrument Air Supply 80-120 Psig
24 Action on Air Failure Action on Power Failure Closed Closed
ACTUATOR 25 Fireproofing No
26 Solenoid Valve Schematic Detail Yes Type 1
27 Limit Switch Closed Limit Swich Open Yes Yes
28 Mounting Position Solenoid Power Supply Top 24VDC
29 Manual Reset No
30 Mechanical Position Indicator Red Closed / Green Open
C 31 Partial Stroke Facility Yes
31 Signal Cable 1/2" NPT
ELECTRICAL 32 Control Cable -
CONNECTIONS 33 Solenoid Cable 3/4" NPT
34
Fl id
35 Fluid H t Oil
Hot
36 Phase Liquid
37 Operating Pressure 65 psig
38 Design Pressure 210 psig
39 Operating Temperature 350 ºF
40 Design Temperature 450 ºF
PROCESS DATA
41 Max. Diff. Pressure for Actuator Size 210 psig
42
43 Line Size and Sch. Inlet Outlet 12 in Sch. 40 12 in Sch. 40
44 Speed of Operation Design VTA
45 (Seconds) Actual VTA
46
Notes
1. VTA : Vendor to advice
2. Actuated ball valve and actuator shall be provided with 316 SS nameplate engraved or die stamped with Valve Tag No., Manufacturer's Name,
Model No., Valve Size & Rating.
3. Vendor shall be responsible for the proper design and selection of valve, actuator, and accessories based on the information furnished
C1 in this specification. This Data Sheet shall refer to SNO-I-ES-013, Instrument Specification for Shutdown and Blowdown Valve
4. Actuator shall be sized based on valve manufacturer's required Torque values with 130% minimum safety margin to open or close the valve
against full ANSI rated differential pressure at minimum pneumatic supply pressure of 60 psig.
5. Vendor shall provide Torque table containing breaking, running and seating torques for valves and actuator along with Quotation.
Vendor shall provide the torque table and calculation for COMPANY approval.
6. Actuator and accessories shall be supplied fully assembled, tubed and tested ready for installation.
7. Solenoid valve coil shall be provided with reverse polarity protection diodes, integral outlet box and terminal strip for cable connection.
Three way valve shall be universal type. Solenoid Coil shall be Class H.
8. Air filter regulator shall be 316 SS Material and equipped with pressure gauge on inlet and outlet of air filter regulator.
C1 9. All SDV & BDV shall be designed & tested as per API 6D
C1 10. Valve Stem Shall be Anti-Blowout Type.

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 83 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
1 Tag No. Quantity SDV -2105A / 2205A 2 (Two)
2 Manufacturer Model VTA VTA
3 Contract No. Requisition Item No.
4 Location Central Processing Plant
GENERAL
5 P&ID No. SNO-R-PI-305 / SNO-R-PI-315
6 Service Amine Reflux Drum to Acid Gas Compresion
7 Line No. 16"-GA-1516-1N / 16"-GA-2516-1N
8 Area Classification Zone-2, Gr. IIB, T3
9 Valve Type Valve Code Trunnion Mounted Ball BA100
10 Body Size Body Form 16 in Ball
11 Body Material Port Size ASTM A351 CF8M Full Bore
12 Connection Rating RF Flange ASME 150#
C1 13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
C 14 Packing Lubrication & Isolation Expanded Graphite VTA
15 Bonnet Bolts Bonnet Nuts ASTM A193 B8M CL2 ASTM A194 8M
C 16 Ball Material Stem Material 316 SS 316 SS
C1 17 Leakage Rate Seat Material ISO 5028 Rate A PTFE
18 NACE Requirement Yes
C 19 Type Stroking Time Pneumatic Piston / Spring return 15 Seconds
20 Size Safety Factor VTA in 1.3
21 Actuator Orientation Actuator Form Horizontal Cylinder
22 Ingress Protection Electrical Protection IP65 Eex i
23 Instrument Air Supply 80-120 Psig
24 Action on Air Failure Action on Power Failure Closed Closed
ACTUATOR 25 Fireproofing No
26 Solenoid Valve Schematic Detail Yes Type 1
27 Limit Switch Closed Limit Swich Open Yes Yes
28 Mounting Position Solenoid Power Supply Top 24VDC
29 Manual Reset No
30 Mechanical Position Indicator Red Closed / Green Open
C 31 Partial Stroke Facility No
31 Signal Cable 1/2" NPT
ELECTRICAL 32 Control Cable -
CONNECTIONS 33 Solenoid Cable 3/4" NPT
34
Fl id
35 Fluid Hf b
Hrfrocarbon
36 Phase Gas
37 Operating Pressure 17 psig
38 Design Pressure 100 psig
39 Operating Temperature 120 ºF
40 Design Temperature 250 ºF
PROCESS DATA
41 Max. Diff. Pressure for Actuator Size 100 psig
42
43 Line Size and Sch. Inlet Outlet 16 in Sch. 10 16 in Sch. 10
44 Speed of Operation Design VTA
45 (Seconds) Actual VTA
46
Notes
1. VTA : Vendor to advice
2. Actuated ball valve and actuator shall be provided with 316 SS nameplate engraved or die stamped with Valve Tag No., Manufacturer's Name,
Model No., Valve Size & Rating.
3. Vendor shall be responsible for the proper design and selection of valve, actuator, and accessories based on the information furnished
C1 in this specification. This Data Sheet shall refer to SNO-I-ES-013, Instrument Specification for Shutdown and Blowdown Valve
4. Actuator shall be sized based on valve manufacturer's required Torque values with 130% minimum safety margin to open or close the valve
against full ANSI rated differential pressure at minimum pneumatic supply pressure of 60 psig.
5. Vendor shall provide Torque table containing breaking, running and seating torques for valves and actuator along with Quotation.
Vendor shall provide the torque table and calculation for COMPANY approval.
6. Actuator and accessories shall be supplied fully assembled, tubed and tested ready for installation.
7. Solenoid valve coil shall be provided with reverse polarity protection diodes, integral outlet box and terminal strip for cable connection.
8. Three way valve shall be universal type. Solenoid Coil shall be Class H.
Air filter regulator shall be 316 SS Material and equipped with pressure gauge on inlet and outlet of air filter regulator.
C1 9. All SDV & BDV shall be designed & tested as per API 6D
C1 10. Valve Stem Shall be Anti-Blowout Type.

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 84 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
1 Tag No. Quantity SDV -2105B / 2205B 2 (Two)
2 Manufacturer Model VTA VTA
3 Contract No. Requisition Item No.
4 Location Central Processing Plant
GENERAL
5 P&ID No. SNO-R-PI-305 / SNO-R-PI-315
6 Service Amine Reflux Drum to Amine Reflux Pumps
C 7 Line No. 3"-CA-1508-1N / 3"-CA-2508-1N
8 Area Classification Zone-2, Gr. IIB, T3
C1 9 Valve Type Valve Code Trunnion Mounted Ball BA098
10 Body Size Body Form 3 in Ball
11 Body Material Port Size ASTM A351 CF8M Full Bore
12 Connection Rating RF Flange ASME 150#
C1 13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
C 14 Packing Lubrication & Isolation Expanded Graphite VTA
15 Bonnet Bolts Bonnet Nuts ASTM A193 B8M CL2 ASTM A194 8M
C 16 Ball Material Stem Material 316 SS 316 SS
C1 17 Leakage Rate Seat Material ISO 5028 Rate A PTFE
18 NACE Requirement Yes
C 19 Type Stroking Time Pneumatic Piston / Spring return 6 Seconds
20 Size Safety Factor VTA in 1.3
21 Actuator Orientation Actuator Form Horizontal Cylinder
22 Ingress Protection Electrical Protection IP65 Eex i
23 Instrument Air Supply 80-120 Psig
24 Action on Air Failure Action on Power Failure Closed Closed
ACTUATOR 25 Fireproofing No
26 Solenoid Valve Schematic Detail Yes Type 1
27 Limit Switch Closed Limit Swich Open Yes Yes
28 Mounting Position Solenoid Power Supply Top 24VDC
29 Manual Reset No
30 Mechanical Position Indicator Red Closed / Green Open
C 31 Partial Stroke Facility No
31 Signal Cable 1/2" NPT
ELECTRICAL 32 Control Cable -
CONNECTIONS 33 Solenoid Cable 3/4" NPT
34
Fl id
35 Fluid A i
Amine
C 36 Phase Liquid
C 37 Operating Pressure 75 psig
C 38 Design Pressure 175 psig
39 Operating Temperature 120 ºF
40 Design Temperature 250 ºF
PROCESS DATA
C 41 Max. Diff. Pressure for Actuator Size 175 psig
42
43 Line Size and Sch. Inlet Outlet 3 in Sch. 10S 3 in Sch. 10S
44 Speed of Operation Design VTA
45 (Seconds) Actual VTA
46
Notes
1. VTA : Vendor to advice
2. Actuated ball valve and actuator shall be provided with 316 SS nameplate engraved or die stamped with Valve Tag No., Manufacturer's Name,
Model No., Valve Size & Rating.
3. Vendor shall be responsible for the proper design and selection of valve, actuator, and accessories based on the information furnished
C1 in this specification. This Data Sheet shall refer to SNO-I-ES-013, Instrument Specification for Shutdown and Blowdown Valve
4. Actuator shall be sized based on valve manufacturer's required Torque values with 130% minimum safety margin to open or close the valve
against full ANSI rated differential pressure at minimum pneumatic supply pressure of 60 psig.
5. Vendor shall provide Torque table containing breaking, running and seating torques for valves and actuator along with Quotation.
Vendor shall provide the torque table and calculation for COMPANY approval.
6. Actuator and accessories shall be supplied fully assembled, tubed and tested ready for installation.
7. Solenoid valve coil shall be provided with reverse polarity protection diodes, integral outlet box and terminal strip for cable connection.
8. Three way valve shall be universal type. Solenoid Coil shall be Class H.
Air filter regulator shall be 316 SS Material and equipped with pressure gauge on inlet and outlet of air filter regulator.
C1 9. All SDV & BDV shall be designed & tested as per API 6D
C1 10. Valve Stem Shall be Anti-Blowout Type.

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 85 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
1 Tag No. Quantity SDV -2123F / 2223F 2 (Two)
2 Manufacturer Model VTA VTA
3 Contract No. Requisition Item No.
4 Location Central Processing Plant
GENERAL
5 P&ID No. SNO-R-PI-306 / SNO-R-PI-316
6 Service Sweet Gas KO Drum to Amine Flash Drum
C 7 Line No. 2"-CA-1521-9N / 2"-CA-2521-9N
8 Area Classification Zone-2, Gr. IIB, T3
C1 9 Valve Type Valve Code Trunnion Mounted Ball BA466
10 Body Size Body Form 2 in Ball
C 11 Body Material Port Size A182 F316L Full Bore
C 12 Connection Rating RTJ ASME 1500#
C1 13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
C 14 Packing Lubrication & Isolation Expanded Graphite VTA
15 Bonnet Bolts Bonnet Nuts ASTM A193 B8M CL2 ASTM A194 8M
C 16 Ball Material Stem Material 316 SS 316 SS
C1 17 Leakage Rate Seat Material ISO 5028 Rate A PTFE OR NYLON
18 NACE Requirement Yes
C 19 Type Stroking Time Pneumatic Piston / Spring return 4 Seconds
20 Size Safety Factor VTA in 1.3
21 Actuator Orientation Actuator Form Horizontal Cylinder
22 Ingress Protection Electrical Protection IP65 Eex i
23 Instrument Air Supply 80-120 Psig
24 Action on Air Failure Action on Power Failure Closed Closed
ACTUATOR 25 Fireproofing No
26 Solenoid Valve Schematic Detail Yes Type-1
27 Limit Switch Closed Limit Swich Open Yes Yes
28 Mounting Position Solenoid Power Supply Top 24VDC
29 Manual Reset No
30 Mechanical Position Indicator Red Closed / Green Open
C 31 Partial Stroke Facility No
31 Signal Cable 1/2" NPT
ELECTRICAL 32 Control Cable -
CONNECTIONS 33 Solenoid Cable 3/4" NPT
34
Fl id
35 Fluid Ri h Amine
Rich A i
36 Phase Liquid
37 Operating Pressure 889 psig
38 Design Pressure 1300 psig
39 Operating Temperature 120 ºF
40 Design Temperature 150 ºF
PROCESS DATA
41 Max. Diff. Pressure for Actuator Size 1300 psig
42
43 Line Size and Sch. Inlet Outlet 2 in Sch. 80S 2 in Sch. 80S
44 Speed of Operation Design VTA
45 (Seconds) Actual VTA
46
Notes
1. VTA : Vendor to advice
2. Actuated ball valve and actuator shall be provided with 316 SS nameplate engraved or die stamped with Valve Tag No., Manufacturer's Name,
Model No., Valve Size & Rating.
3. Vendor shall be responsible for the proper design and selection of valve, actuator, and accessories based on the information furnished
C1 in this specification. This Data Sheet shall refer to SNO-I-ES-013, Instrument Specification for Shutdown and Blowdown Valve
4. Actuator shall be sized based on valve manufacturer's required Torque values with 130% minimum safety margin to open or close the valve
against full ANSI rated differential pressure at minimum pneumatic supply pressure of 60 psig.
5. Vendor shall provide Torque table containing breaking, running and seating torques for valves and actuator along with Quotation.
Vendor shall provide the torque table and calculation for COMPANY approval.
6. Actuator and accessories shall be supplied fully assembled, tubed and tested ready for installation.
7. Solenoid valve coil shall be provided with reverse polarity protection diodes, integral outlet box and terminal strip for cable connection.
Three way valve shall be universal type. Solenoid Coil shall be Class H.
8. Air filter regulator shall be 316 SS Material and equipped with pressure gauge on inlet and outlet of air filter regulator.
C1 9. All SDV & BDV shall be designed & tested as per API 6D
C1 10. Valve Stem Shall be Anti-Blowout Type.

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 86 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
1 Tag No. Quantity SDV -2123G / 2223G 2 (Two)
2 Manufacturer Model VTA VTA
3 Contract No. Requisition Item No.
4 Location Central Processing Plant
GENERAL
5 P&ID No. SNO-R-PI-306 / SNO-R-PI-316
6 Service Sweet Gas KO Drum to TEG Contractor V-3102
7 Line No. 12"-HG-1505-6A / 12"-HG-2505-6A
8 Area Classification Zone-2, Gr. IIB, T3
9 Valve Type Valve Code Trunnion Mounted Ball BA015
10 Body Size Body Form 12 in Ball
C 11 Body Material Port Size A105 Full Bore
12 Connection Rating RF Flange ASME 600#
C1 13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
C 14 Packing Lubrication & Isolation Expanded Graphite VTA
C 15 Bonnet Bolts Bonnet Nuts ASTM A193 B7 ASTM A194 2H
C 16 Ball Material Stem Material CS+ENP 76μm A564 630, H1150M+ENP 76 μm
C1 17 Leakage Rate Seat Material ISO 5028 Rate A PTFE OR NYLON
18 NACE Requirement No
C 19 Type Stroking Time Pneumatic Piston / Spring return 15 Seconds
C 20 Size Safety Factor VTA in 1.5
21 Actuator Orientation Actuator Form Horizontal Cylinder
22 Ingress Protection Electrical Protection IP65 Eex i
23 Instrument Air Supply 80-120 Psig
24 Action on Air Failure Action on Power Failure Closed Closed
ACTUATOR 25 Fireproofing No
26 Solenoid Valve Schematic Detail Yes Type-1
27 Limit Switch Closed Limit Swich Open Yes Yes
28 Mounting Position Solenoid Power Supply Top 24VDC
29 Manual Reset No
30 Mechanical Position Indicator Red Closed / Green Open
C 31 Partial Stroke Facility Yes
31 Signal Cable 1/2" NPT
ELECTRICAL 32 Control Cable -
CONNECTIONS 33 Solenoid Cable 3/4" NPT
34
Fl id
35 Fluid H d b Gas
Hydrocarbon G
36 Phase Gas / Vapour
37 Operating Pressure 889 psig
38 Design Pressure 1300 psig
39 Operating Temperature 120 ºF
40 Design Temperature 150 ºF
PROCESS DATA
41 Max. Diff. Pressure for Actuator Size 1300 psig
42
43 Line Size and Sch. Inlet Outlet 12 in Sch. 100 12 in Sch. 100
44 Speed of Operation Design VTA
45 (Seconds) Actual VTA
46
Notes
1. VTA : Vendor to advice
2. Actuated ball valve and actuator shall be provided with 316 SS nameplate engraved or die stamped with Valve Tag No., Manufacturer's Name,
Model No., Valve Size & Rating.
3. Vendor shall be responsible for the proper design and selection of valve, actuator, and accessories based on the information furnished
C1 in this specification. This Data Sheet shall refer to SNO-I-ES-013, Instrument Specification for Shutdown and Blowdown Valve
4. Actuator shall be sized based on valve manufacturer's required Torque values with 130% minimum safety margin to open or close the valve
against full ANSI rated differential pressure at minimum pneumatic supply pressure of 60 psig.
5. Vendor shall provide Torque table containing breaking, running and seating torques for valves and actuator along with Quotation.
Vendor shall provide the torque table and calculation for COMPANY approval.
6. Actuator and accessories shall be supplied fully assembled, tubed and tested ready for installation.
7. Solenoid valve coil shall be provided with reverse polarity protection diodes, integral outlet box and terminal strip for cable connection.
8. Three way valve shall be universal type. Solenoid Coil shall be Class H.
Air filter regulator shall be 316 SS Material and equipped with pressure gauge on inlet and outlet of air filter regulator.
C1 9. All SDV & BDV shall be designed & tested as per API 6D
C1 10. Valve Stem Shall be Anti-Blowout Type.

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 87 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
1 Tag No. Quantity BDV -2123G / 2223G 2 (Two)
2 Manufacturer Model VTA VTA
3 Contract No. Requisition Item No.
4 Location Central Processing Plant
GENERAL
5 P&ID No. SNO-R-PI-306 / SNO-R-PI-316
6 Service Sweet Gas KO Drum to HP Flare Header
C 7 Line No. 6"-HG-1506-6A / 6"-HG-2506-6A
8 Area Classification Zone-2, Gr. IIB, T3
9 Valve Type Valve Code Trunnion Mounted Ball BA015
10 Body Size Body Form 6 in Ball
C 11 Body Material Port Size A105 Full Bore
12 Connection Rating RF Flange ASME 600#
C1 13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
C 14 Packing Lubrication & Isolation Expanded Graphite VTA
C 15 Bonnet Bolts Bonnet Nuts A193 B7 A194 2H
C 16 Ball Material Stem Material CS+ENP 76μm A564 630, H1150M+ENP 76 μm
C1 17 Leakage Rate Seat Material ISO 5028 Rate A (TSO) PTFE OR NYLON
C 18 NACE Requirement No
C 19 Type Stroking Time Pneumatic Piston / Spring return 12 Seconds
20 Size Safety Factor VTA in 1.3
21 Actuator Orientation Actuator Form Horizontal Cylinder
22 Ingress Protection Electrical Protection IP65 Eex i
23 Instrument Air Supply 80-120 Psig
24 Action on Air Failure Action on Power Failure Open Open
ACTUATOR 25 Fireproofing No
26 Solenoid Valve Schematic Detail Yes Type-2
27 Limit Switch Closed Limit Swich Open Yes Yes
28 Mounting Position Solenoid Power Supply Top 24VDC
29 Manual Reset No
30 Mechanical Position Indicator Red Closed / Green Open
C 31 Partial Stroke Facility No
31 Signal Cable 1/2" NPT
ELECTRICAL 32 Control Cable -
CONNECTIONS 33 Solenoid Cable 3/4" NPT
34
Fl id
35 Fluid H d b Gas
Hydrocarbon G
36 Phase Gas / Vapour
37 Operating Pressure 889 psig
38 Design Pressure 1300 psig
39 Operating Temperature 120 ºF
40 Design Temperature 150 ºF
PROCESS DATA
41 Max. Diff. Pressure for Actuator Size 1300 psig
42
43 Line Size and Sch. Inlet Outlet 6 in Sch. 40S 6 in Sch. 40S
44 Speed of Operation Design VTA
45 (Seconds) Actual VTA
46
Notes
1. VTA : Vendor to advice
2. Actuated ball valve and actuator shall be provided with 316 SS nameplate engraved or die stamped with Valve Tag No., Manufacturer's Name,
Model No., Valve Size & Rating.
3. Vendor shall be responsible for the proper design and selection of valve, actuator, and accessories based on the information furnished
C1 in this specification. This Data Sheet shall refer to SNO-I-ES-013, Instrument Specification for Shutdown and Blowdown Valve
4. Actuator shall be sized based on valve manufacturer's required Torque values with 130% minimum safety margin to open or close the valve
against full ANSI rated differential pressure at minimum pneumatic supply pressure of 60 psig.
5. Vendor shall provide Torque table containing breaking, running and seating torques for valves and actuator along with Quotation.
Vendor shall provide the torque table and calculation for COMPANY approval.
6. Actuator and accessories shall be supplied fully assembled, tubed and tested ready for installation.
7. Solenoid valve coil shall be provided with reverse polarity protection diodes, integral outlet box and terminal strip for cable connection.
8. Three way valve shall be universal type. Solenoid Coil shall be Class H.
Air filter regulator shall be 316 SS Material and equipped with pressure gauge on inlet and outlet of air filter regulator.
C1 9. All SDV & BDV shall be designed & tested as per API 6D
C1 10. Valve Stem Shall be Anti-Blowout Type.

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 88 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
1 Tag No. Quantity SDV -3102A / 3202A 2 (Two)
2 Manufacturer Model VTA VTA
3 Contract No. Requisition Item No.
4 Location Central Processing Plant
GENERAL
5 P&ID No. SNO-R-PI-401 / SNO-R-PI-411
C 6 Service SNO-V-3102 to Closed Drain / SNO-V-3202 to Closed Drain
C 7 Line No. 2"-DC-1601-6A / 2"-DC-2601-6A
8 Area Classification Zone-2, Gr. IIB, T3
9 Valve Type Valve Code Trunnion Mounted Ball BA013
10 Body Size Body Form 2 in Ball
C 11 Body Material Port Size ASTM A216 WCB Full Bore
12 Connection Rating RF Flange ASME 600#
C1 13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
C 14 Packing Lubrication & Isolation Expanded Graphite VTA
C 15 Bonnet Bolts Bonnet Nuts ASTM A193 B7 ASTM A194 2H
C 16 Ball Material Stem Material CS+ENP 76μm A564 630, H1150M+ENP 76 μm
C1 17 Leakage Rate Seat Material ISO 5028 Rate A (TSO) PTFE OR NYLON
18 NACE Requirement No
C 19 Type Stroking Time Pneumatic Piston / Spring return 4 Seconds
20 Size Safety Factor VTA in 1.3
21 Actuator Orientation Actuator Form Horizontal Cylinder
22 Ingress Protection Electrical Protection IP65 Eex i
23 Instrument Air Supply 80-120 Psig
24 Action on Air Failure Action on Power Failure Closed Closed
ACTUATOR 25 Fireproofing No
26 Solenoid Valve Schematic Detail Yes Type-1
27 Limit Switch Closed Limit Swich Open Yes Yes
28 Mounting Position Solenoid Power Supply Top 24VDC
C 29 Manual Reset No
30 Mechanical Position Indicator Red Closed / Green Open
C 31 Partial Stroke Facility No
31 Signal Cable 1/2" NPT
ELECTRICAL 32 Control Cable -
CONNECTIONS 33 Solenoid Cable 3/4" NPT
34
Fl id
35 Fluid H d b Fluid
Hydrocarbon Fl id
36 Phase Liquid
37 Operating Pressure 875 psig
38 Design Pressure 1300 psig
C 39 Operating Temperature 123 ºF
C 40 Design Temperature 150 ºF
PROCESS DATA
41 Max. Diff. Pressure for Actuator Size 1300 psig
42
43 Line Size and Sch. Inlet Outlet 2 in Sch. 160 2 in Sch 160
44 Speed of Operation Design VTA
45 (Seconds) Actual VTA
46
Notes
1. VTA : Vendor to advice
2. Actuated ball valve and actuator shall be provided with 316 SS nameplate engraved or die stamped with Valve Tag No., Manufacturer's Name,
Model No., Valve Size & Rating.
3. Vendor shall be responsible for the proper design and selection of valve, actuator, and accessories based on the information furnished
C1 in this specification. This Data Sheet shall refer to SNO-I-ES-013, Instrument Specification for Shutdown and Blowdown Valve
4. Actuator shall be sized based on valve manufacturer's required Torque values with 130% minimum safety margin to open or close the valve
against full ANSI rated differential pressure at minimum pneumatic supply pressure of 60 psig.
5. Vendor shall provide Torque table containing breaking, running and seating torques for valves and actuator along with Quotation.
Vendor shall provide the torque table and calculation for COMPANY approval.
6. Actuator and accessories shall be supplied fully assembled, tubed and tested ready for installation.
7. Solenoid valve coil shall be provided with reverse polarity protection diodes, integral outlet box and terminal strip for cable connection.
8. Three way valve shall be universal type. Solenoid Coil shall be Class H.
Air filter regulator shall be 316 SS Material and equipped with pressure gauge on inlet and outlet of air filter regulator.
C1 9. All SDV & BDV shall be designed & tested as per API 6D
C1 10. Valve Stem Shall be Anti-Blowout Type.

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 89 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
1 Tag No. Quantity SDV -3102F / 3202F 2 (Two)
2 Manufacturer Model VTA VTA
3 Contract No. Requisition Item No.
4 Location Central Processing Plant
GENERAL
5 P&ID No. SNO-R-PI-401 / SNO-R-PI-411
C 6 Service SNO-V-3102 to TEG Regeration Train 1 / V-3202 to TEG Regeration Train2
7 Line No. 3"-G-1601-6A / 3"-G-2601-6A
8 Area Classification Zone-2, Gr. IIB, T3
C1 9 Valve Type Valve Code Trunnion Mounted Ball BA013
10 Body Size Body Form 3 in Ball
C 11 Body Material Port Size ASTM A216 WCB Full Bore
12 Connection Rating RF Flange ASME 600#
C1 13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
C 14 Packing Lubrication & Isolation Expanded Graphite VTA
C 15 Bonnet Bolts Bonnet Nuts ASTM A193 B7 ASTM A194 2H
C 16 Ball Material Stem Material CS+ENP 76μm A564 630, H1150M+ENP 76 μm
C1 17 Leakage Rate Seat Material ISO 5028 Rate A PTFE OR NYLON
18 NACE Requirement No
C 19 Type Stroking Time Pneumatic Piston / Spring return 6 Seconds
20 Size Safety Factor VTA in 1.3
21 Actuator Orientation Actuator Form Horizontal Cylinder
22 Ingress Protection Electrical Protection IP65 Eex i
23 Instrument Air Supply 80-120 Psig
24 Action on Air Failure Action on Power Failure Closed Closed
ACTUATOR 25 Fireproofing No
26 Solenoid Valve Schematic Detail Yes Type-1
27 Limit Switch Closed Limit Swich Open Yes Yes
28 Mounting Position Solenoid Power Supply Top 24VDC
C 29 Manual Reset No
30 Mechanical Position Indicator Red Closed / Green Open
C 31 Partial Stroke Facility No
31 Signal Cable 1/2" NPT
ELECTRICAL 32 Control Cable -
CONNECTIONS 33 Solenoid Cable 3/4" NPT
34
Fl id
35 Fluid Ri h TEG
Rich
36 Phase Liquid
37 Operating Pressure 875 psig
38 Design Pressure 1300 psig
C 39 Operating Temperature 124 ºF
C 40 Design Temperature 150 ºF
PROCESS DATA
41 Max. Diff. Pressure for Actuator Size 1300 psig
42
43 Line Size and Sch. Inlet Outlet 3 in Sch. 160 3 in Sch 160
44 Speed of Operation Design VTA
45 (Seconds) Actual VTA
46
Notes
1. VTA : Vendor to advice
2. Actuated ball valve and actuator shall be provided with 316 SS nameplate engraved or die stamped with Valve Tag No., Manufacturer's Name,
Model No., Valve Size & Rating.
3. Vendor shall be responsible for the proper design and selection of valve, actuator, and accessories based on the information furnished
C1 in this specification. This Data Sheet shall refer to SNO-I-ES-013, Instrument Specification for Shutdown and Blowdown Valve
4. Actuator shall be sized based on valve manufacturer's required Torque values with 130% minimum safety margin to open or close the valve
against full ANSI rated differential pressure at minimum pneumatic supply pressure of 60 psig.
5. Vendor shall provide Torque table containing breaking, running and seating torques for valves and actuator along with Quotation.
Vendor shall provide the torque table and calculation for COMPANY approval.
6. Actuator and accessories shall be supplied fully assembled, tubed and tested ready for installation.
7. Solenoid valve coil shall be provided with reverse polarity protection diodes, integral outlet box and terminal strip for cable connection.
8. Three way valve shall be universal type. Solenoid Coil shall be Class H.
Air filter regulator shall be 316 SS Material and equipped with pressure gauge on inlet and outlet of air filter regulator.
C1 9. All SDV & BDV shall be designed & tested as per API 6D
C1 10. Valve Stem Shall be Anti-Blowout Type.

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 90 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
1 Tag No. Quantity SDV-3116A / 3216A 2 (Two)
2 Manufacturer Model VTA VTA
3 Contract No. Requisition Item No.
4 Location Central Processing Plant
GENERAL
5 P&ID No. SNO-R-PI-402A / SNO-R-PI-412A
C 6 Service SNO-F-3116A to TEG Flash Vessel SNO-V-3110 / F-3116A to V-3110
C 7 Line No. 2"-G-1612-6A / 2"-G-2612-6A
8 Area Classification Zone-2, Gr. IIB, T3
C1 9 Valve Type Valve Code Trunnion Mounted Ball BA013
C 10 Body Size Body Form 2 in Ball
C 11 Body Material Port Size ASTM A216 WCB Full Bore
12 Connection Rating RF Flange ASME 600#
C1 13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
C 14 Packing Lubrication & Isolation Expanded Graphite VTA
C 15 Bonnet Bolts Bonnet Nuts ASTM A193 B7 ASTM A194 2H
C 16 Ball Material Stem Material CS+ENP 76μm A564 630, H1150M+ENP 76 μm
C1 17 Leakage Rate Seat Material ISO 5028 Rate A PTFE OR NYLON
18 NACE Requirement No
C 19 Type Stroking Time Pneumatic Piston / Spring return 4 Seconds
20 Size Safety Factor VTA in 1.3
21 Actuator Orientation Actuator Form Horizontal Cylinder
22 Ingress Protection Electrical Protection IP65 Eex i
23 Instrument Air Supply 80-120 Psig
24 Action on Air Failure Action on Power Failure Closed Closed
ACTUATOR 25 Fireproofing No
26 Solenoid Valve Schematic Detail Yes Type-1
27 Limit Switch Closed Limit Swich Open Yes Yes
28 Mounting Position Solenoid Power Supply Top 24VDC
C 29 Manual Reset No
30 Mechanical Position Indicator Red Closed / Green Open
C 31 Partial Stroke Facility No
31 Signal Cable 1/2" NPT
ELECTRICAL 32 Control Cable -
CONNECTIONS 33 Solenoid Cable 3/4" NPT
34
Fl id
35 Fluid TEG
36 Phase Liquid
C 37 Operating Pressure 872 psig
38 Design Pressure 1300 psig
C 39 Operating Temperature 124 ºF
40 Design Temperature 150 ºF
PROCESS DATA
41 Max. Diff. Pressure for Actuator Size 1300 psig
42
C 43 Line Size and Sch. Inlet Outlet 2 in Sch. 160 2 in Sch 160
44 Speed of Operation Design VTA
45 (Seconds) Actual VTA
46
Notes
1. VTA : Vendor to advice
2. Actuated ball valve and actuator shall be provided with 316 SS nameplate engraved or die stamped with Valve Tag No., Manufacturer's Name,
Model No., Valve Size & Rating.
3. Vendor shall be responsible for the proper design and selection of valve, actuator, and accessories based on the information furnished
C1 in this specification. This Data Sheet shall refer to SNO-I-ES-013, Instrument Specification for Shutdown and Blowdown Valve
4. Actuator shall be sized based on valve manufacturer's required Torque values with 130% minimum safety margin to open or close the valve
against full ANSI rated differential pressure at minimum pneumatic supply pressure of 60 psig.
5. Vendor shall provide Torque table containing breaking, running and seating torques for valves and actuator along with Quotation.
Vendor shall provide the torque table and calculation for COMPANY approval.
6. Actuator and accessories shall be supplied fully assembled, tubed and tested ready for installation.
7. Solenoid valve coil shall be provided with reverse polarity protection diodes, integral outlet box and terminal strip for cable connection.
8. Three way valve shall be universal type. Solenoid Coil shall be Class H.
Air filter regulator shall be 316 SS Material and equipped with pressure gauge on inlet and outlet of air filter regulator.
C1 9. All SDV & BDV shall be designed & tested as per API 6D
C1 10. Valve Stem Shall be Anti-Blowout Type.

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 91 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
1 Tag No. Quantity SDV -3116J/3216J 2 (Two)
2 Manufacturer Model VTA VTA
3 Contract No. Requisition Item No.
4 Location Central Processing Plant
GENERAL
5 P&ID No. SNO-R-PI-402A / SNO-R-PI-412A
C 6 Service SNO-F-3116A to Gas/Gas Exchanger SNO-E-5102 / F-3216A to E-5202
7 Line No. 12"-HG-1614-6A / 12"-HG-2614-6A
8 Area Classification Zone-2, Gr. IIB, T3
9 Valve Type Valve Code Trunnion Mounted Ball BA015
10 Body Size Body Form 12 in Ball
C 11 Body Material Port Size A105 Full Bore
12 Connection Rating RF Flange ASME 600#
C1 13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
C 14 Packing Lubrication & Isolation Expanded Graphite VTA
C 15 Bonnet Bolts Bonnet Nuts ASTM A193 B7 ASTM A194 2H
C 16 Ball Material Stem Material CS+ENP 76μm A564 630, H1150M+ENP 76 μm
C1 17 Leakage Rate Seat Material ISO 5028 Rate A PTFE OR NYLON
18 NACE Requirement No
C 19 Type Stroking Time Pneumatic Piston / Spring return 15 Seconds
C 20 Size Safety Factor VTA in 1.5
21 Actuator Orientation Actuator Form Horizontal Cylinder
22 Ingress Protection Electrical Protection IP65 Eex i
23 Instrument Air Supply 80-120 Psig
24 Action on Air Failure Action on Power Failure Closed Closed
ACTUATOR 25 Fireproofing No
26 Solenoid Valve Schematic Detail Yes Type-1
27 Limit Switch Closed Limit Swich Open Yes Yes
28 Mounting Position Solenoid Power Supply Top 24VDC
29 Manual Reset No
30 Mechanical Position Indicator Red Closed / Green Open
C 31 Partial Stroke Facility Yes
31 Signal Cable 1/2" NPT
ELECTRICAL 32 Control Cable -
CONNECTIONS 33 Solenoid Cable 3/4" NPT
34
Fl id
35 Fluid H d b Gas
Hydrocarbon G
36 Phase Gas / Vapour
37 Operating Pressure 872 psig
38 Design Pressure 1300 psig
39 Operating Temperature 124 ºF
40 Design Temperature 150 ºF
PROCESS DATA
41 Max. Diff. Pressure for Actuator Size 1300 psig
42
43 Line Size and Sch. Inlet Outlet 12 in Sch. 100 12 in Sch. 100
44 Speed of Operation Design VTA
45 (Seconds) Actual VTA
46
Notes
1. VTA : Vendor to advice
2. Actuated ball valve and actuator shall be provided with 316 SS nameplate engraved or die stamped with Valve Tag No., Manufacturer's Name,
Model No., Valve Size & Rating.
3. Vendor shall be responsible for the proper design and selection of valve, actuator, and accessories based on the information furnished
C1 in this specification. This Data Sheet shall refer to SNO-I-ES-013, Instrument Specification for Shutdown and Blowdown Valve
4. Actuator shall be sized based on valve manufacturer's required Torque values with 130% minimum safety margin to open or close the valve
against full ANSI rated differential pressure at minimum pneumatic supply pressure of 60 psig.
5. Vendor shall provide Torque table containing breaking, running and seating torques for valves and actuator along with Quotation.
Vendor shall provide the torque table and calculation for COMPANY approval.
6. Actuator and accessories shall be supplied fully assembled, tubed and tested ready for installation.
7. Solenoid valve coil shall be provided with reverse polarity protection diodes, integral outlet box and terminal strip for cable connection.
8. Three way valve shall be universal type. Solenoid Coil shall be Class H.
Air filter regulator shall be 316 SS Material and equipped with pressure gauge on inlet and outlet of air filter regulator.
C1 9. All SDV & BDV shall be designed & tested as per API 6D
C1 10. Valve Stem Shall be Anti-Blowout Type.

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 92 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
1 Tag No. Quantity BDV -3116K / 3216K 2 (Two)
2 Manufacturer Model VTA VTA
3 Contract No. Requisition Item No.
4 Location Central Processing Plant
GENERAL
5 P&ID No. SNO-R-PI-402A / SNO-R-PI-412A
C 6 Service SNO-F-3116A to Gas Exchanger SNO-E-5102 / F-3216A to E-5202
C 7 Line No. 3"-HG-1618-6A / 3"-HG-2618-6A
8 Area Classification Zone-2, Gr. IIB, T3
C1 9 Valve Type Valve Code Trunnion Mounted Ball BA013
C 10 Body Size Body Form 3 in Ball
C 11 Body Material Port Size ASTM A216 WCB Full Bore
12 Connection Rating RF Flange ASME 600#
C1 13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
C 14 Packing Lubrication & Isolation Expanded Graphite VTA
C 15 Bonnet Bolts Bonnet Nuts ASTM A193 B7 ASTM A194 2H
C 16 Ball Material Stem Material CS+ENP 76μm A564 630, H1150M+ENP 76 μm
C1 17 Leakage Rate Seat Material ISO 5028 Rate A PTFE OR NYLON
18 NACE Requirement No
C 19 Type Stroking Time Pneumatic Piston / Spring return 6 Seconds
20 Size Safety Factor VTA in 1.3
21 Actuator Orientation Actuator Form Horizontal Cylinder
22 Ingress Protection Electrical Protection IP65 Eex i
23 Instrument Air Supply 80-120 Psig
24 Action on Air Failure Action on Power Failure Open Open
ACTUATOR 25 Fireproofing No
26 Solenoid Valve Schematic Detail Yes Type-2
27 Limit Switch Closed Limit Swich Open Yes Yes
28 Mounting Position Solenoid Power Supply Top 24VDC
29 Manual Reset No
30 Mechanical Position Indicator Red Closed / Green Open
C 31 Partial Stroke Facility No
31 Signal Cable 1/2" NPT
ELECTRICAL 32 Control Cable -
CONNECTIONS 33 Solenoid Cable 3/4" NPT
34
Fl id
35 Fluid H d b Fluid
Hydrocarbon Fl id
36 Phase Gas
C 37 Operating Pressure 872 psig
38 Design Pressure 1300 psig
C 39 Operating Temperature 124 ºF
40 Design Temperature 150 ºF
PROCESS DATA
41 Max. Diff. Pressure for Actuator Size 1300 psig
42
C 43 Line Size and Sch. Inlet Outlet 3 in Sch. 160 3 in Sch. 160
44 Speed of Operation Design VTA
45 (Seconds) Actual VTA
46
Notes
1. VTA : Vendor to advice
2. Actuated ball valve and actuator shall be provided with 316 SS nameplate engraved or die stamped with Valve Tag No., Manufacturer's Name,
Model No., Valve Size & Rating.
3. Vendor shall be responsible for the proper design and selection of valve, actuator, and accessories based on the information furnished
C1 in this specification. This Data Sheet shall refer to SNO-I-ES-013, Instrument Specification for Shutdown and Blowdown Valve
4. Actuator shall be sized based on valve manufacturer's required Torque values with 130% minimum safety margin to open or close the valve
against full ANSI rated differential pressure at minimum pneumatic supply pressure of 60 psig.
5. Vendor shall provide Torque table containing breaking, running and seating torques for valves and actuator along with Quotation.
Vendor shall provide the torque table and calculation for COMPANY approval.
6. Actuator and accessories shall be supplied fully assembled, tubed and tested ready for installation.
7. Solenoid valve coil shall be provided with reverse polarity protection diodes, integral outlet box and terminal strip for cable connection.
8. Three way valve shall be universal type. Solenoid Coil shall be Class H.
Air filter regulator shall be 316 SS Material and equipped with pressure gauge on inlet and outlet of air filter regulator.
C1 9. All SDV & BDV shall be designed & tested as per API 6D
C1 10. Valve Stem Shall be Anti-Blowout Type.

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 93 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
1 Tag No. Quantity SDV -3104A / 3204A 2 (Two)
2 Manufacturer Model VTA VTA
3 Contract No. Requisition Item No.
4 Location Central Processing Plant
GENERAL
5 P&ID No. SNO-R-PI-403 / SNO-R-PI-413
C 6 Service From Hot Oil Distribution to SNO-E-3104 / to SNO-E-3204
7 Line No. 6"-OH-1132-3A / 6"-OH-2132-3A
8 Area Classification Zone-2, Gr. IIB, T3
9 Valve Type Valve Code Trunnion Mounted Ball BA010
10 Body Size Body Form 6 in Ball
11 Body Material Port Size ASTM A216-WCB Full Bore
12 Connection Rating RF Flange ASME 300#
C1 13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
C 14 Packing Lubrication & Isolation Expanded Graphite VTA
C 15 Bonnet Bolts Bonnet Nuts ASTM A193 B7 ASTM A194 2H
C 16 Ball Material Stem Material 316 SS CS+ENP 76μm
C1 17 Leakage Rate Seat Material ISO 5028 Rate D Metal
18 NACE Requirement No
C 19 Type Stroking Time Pneumatic Piston / Spring return 12 Seconds
20 Size Safety Factor VTA in 1.3
21 Actuator Orientation Actuator Form Horizontal Cylinder
22 Ingress Protection Electrical Protection IP65 Eex i
23 Instrument Air Supply 80-120 Psig
24 Action on Air Failure Action on Power Failure Closed Closed
ACTUATOR 25 Fireproofing No
26 Solenoid Valve Schematic Detail Yes Type-1
27 Limit Switch Closed Limit Swich Open Yes Yes
28 Mounting Position Solenoid Power Supply Top 24VDC
29 Manual Reset No
30 Mechanical Position Indicator Red Closed / Green Open
C 31 Partial Stroke Facility No
31 Signal Cable 1/2" NPT
ELECTRICAL 32 Control Cable -
CONNECTIONS 33 Solenoid Cable 3/4" NPT
34
Fl id
35 Fluid H t Oil
Hot
36 Phase Liquid
37 Operating Pressure 65 psig
38 Design Pressure 210 psig
39 Operating Temperature 450 ºF
40 Design Temperature 500 ºF
PROCESS DATA
41 Max. Diff. Pressure for Actuator Size 210 psig
42
43 Line Size and Sch. Inlet Outlet 6 in Sch. 40 6 in Sch. 40
44 Speed of Operation Design VTA
45 (Seconds) Actual VTA
46
Notes
1. VTA : Vendor to advice
2. Actuated ball valve and actuator shall be provided with 316 SS nameplate engraved or die stamped with Valve Tag No., Manufacturer's Name,
Model No., Valve Size & Rating.
3. Vendor shall be responsible for the proper design and selection of valve, actuator, and accessories based on the information furnished
C1 in this specification. This Data Sheet shall refer to SNO-I-ES-013, Instrument Specification for Shutdown and Blowdown Valve
4. Actuator shall be sized based on valve manufacturer's required Torque values with 130% minimum safety margin to open or close the valve
against full ANSI rated differential pressure at minimum pneumatic supply pressure of 60 psig.
5. Vendor shall provide Torque table containing breaking, running and seating torques for valves and actuator along with Quotation.
Vendor shall provide the torque table and calculation for COMPANY approval.
6. Actuator and accessories shall be supplied fully assembled, tubed and tested ready for installation.
7. Solenoid valve coil shall be provided with reverse polarity protection diodes, integral outlet box and terminal strip for cable connection.
8. Three way valve shall be universal type. Solenoid Coil shall be Class H.
Air filter regulator shall be 316 SS Material and equipped with pressure gauge on inlet and outlet of air filter regulator.
C1 9. All SDV & BDV shall be designed & tested as per API 6D
C1 10. Valve Stem Shall be Anti-Blowout Type.

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 94 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
1 Tag No. Quantity SDV -3104B / 3204B 2 (Two)
2 Manufacturer Model VTA VTA
3 Contract No. Requisition Item No.
4 Location Central Processing Plant
GENERAL
5 P&ID No. SNO-R-PI-403 / SNO-R-PI-413
C 6 Service Fuel Gas Stripping to SNO-E-3104 / to SNO-E-3204
C 7 Line No. 2"-FG-0012-1B / 2"-FG-0041-1B
8 Area Classification Zone-2, Gr. IIB, T3
C1 9 Valve Type Valve Code Trunnion Mounted Ball BA032
10 Body Size Body Form 2 in Ball
11 Body Material Port Size ASTM A216-WCB Full Bore
12 Connection Rating RF Flange ASME 150#
C1 13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
C 14 Packing Lubrication & Isolation Expanded Graphite VTA
15 Bonnet Bolts Bonnet Nuts ASTM A193 B7M ASTM A194 2HM
16 Ball Material Stem Material 316 SS 316 SS
C1 17 Leakage Rate Seat Material ISO 5028 Rate A PTFE
18 NACE Requirement Yes
C 19 Type Stroking Time Pneumatic Piston / Spring return 4 Seconds
20 Size Safety Factor VTA in 1.3
21 Actuator Orientation Actuator Form Horizontal Cylinder
22 Ingress Protection Electrical Protection IP65 Eex i
23 Instrument Air Supply 80-120 Psig
24 Action on Air Failure Action on Power Failure Closed Closed
ACTUATOR 25 Fireproofing No
26 Solenoid Valve Schematic Detail Yes Type-1
27 Limit Switch Closed Limit Swich Open Yes Yes
28 Mounting Position Solenoid Power Supply Top 24VDC
29 Manual Reset No
30 Mechanical Position Indicator Red Closed / Green Open
C 31 Partial Stroke Facility No
31 Signal Cable 1/2" NPT
ELECTRICAL 32 Control Cable -
CONNECTIONS 33 Solenoid Cable 3/4" NPT
34
Fl id
35 Fluid F l Gas
Fuel G
36 Phase Gas
C 37 Operating Pressure 100 psig
C 38 Design Pressure 200 psig
C 39 Operating Temperature 310 ºF
C 40 Design Temperature 450 ºF
PROCESS DATA
C 41 Max. Diff. Pressure for Actuator Size 200 psig
42
43 Line Size and Sch. Inlet Outlet 2 in Sch. 80 2 in Sch. 80
44 Speed of Operation Design VTA
45 (Seconds) Actual VTA
46
Notes
1. VTA : Vendor to advice
2. Actuated ball valve and actuator shall be provided with 316 SS nameplate engraved or die stamped with Valve Tag No., Manufacturer's Name,
Model No., Valve Size & Rating.
3. Vendor shall be responsible for the proper design and selection of valve, actuator, and accessories based on the information furnished
C1 in this specification. This Data Sheet shall refer to SNO-I-ES-013, Instrument Specification for Shutdown and Blowdown Valve
4. Actuator shall be sized based on valve manufacturer's required Torque values with 130% minimum safety margin to open or close the valve
against full ANSI rated differential pressure at minimum pneumatic supply pressure of 60 psig.
5. Vendor shall provide Torque table containing breaking, running and seating torques for valves and actuator along with Quotation.
Vendor shall provide the torque table and calculation for COMPANY approval.
6. Actuator and accessories shall be supplied fully assembled, tubed and tested ready for installation.
7. Solenoid valve coil shall be provided with reverse polarity protection diodes, integral outlet box and terminal strip for cable connection.
8. Three way valve shall be universal type. Solenoid Coil shall be Class H.
Air filter regulator shall be 316 SS Material and equipped with pressure gauge on inlet and outlet of air filter regulator.
C1 9. All SDV & BDV shall be designed & tested as per API 6D
C1 10. Valve Stem Shall be Anti-Blowout Type.

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 95 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
1 Tag No. Quantity SDV -3110A / 3210A 2 (Two)
2 Manufacturer Model VTA VTA
3 Contract No. Requisition Item No.
4 Location Central Processing Plant
GENERAL
5 P&ID No. SNO-R-PI-404 / SNO-R-PI-414
6 Service SNO-V-3110 to SNO-F-3107
7 Line No. 3"-G-1610-1A / 3"-G-2610-1A
8 Area Classification Zone-2, Gr. IIB, T3
C1 9 Valve Type Valve Code Trunnion Mounted Ball BA003
10 Body Size Body Form 3 in Ball
11 Body Material Port Size ASTM A216-WCB Full Bore
12 Connection Rating RF Flange ASME 150#
C1 13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
C 14 Packing Lubrication & Isolation Expanded Graphite VTA
C 15 Bonnet Bolts Bonnet Nuts ASTM A193 B7 ASTM A194 2H
C 16 Ball Material Stem Material CS+ENP 76μm CS+ENP 76μm
C1 17 Leakage Rate Seat Material ISO 5028 Rate A PTFE
18 NACE Requirement No
C 19 Type Stroking Time Pneumatic Piston / Spring return 6 Seconds
20 Size Safety Factor VTA in 1.3
21 Actuator Orientation Actuator Form Horizontal Cylinder
22 Ingress Protection Electrical Protection IP65 Eex i
23 Instrument Air Supply 80-120 Psig
24 Action on Air Failure Action on Power Failure Closed Closed
ACTUATOR 25 Fireproofing No
26 Solenoid Valve Schematic Detail Yes Type-1
27 Limit Switch Closed Limit Swich Open Yes Yes
28 Mounting Position Solenoid Power Supply Top 24VDC
29 Manual Reset No
30 Mechanical Position Indicator Red Closed / Green Open
C 31 Partial Stroke Facility No
31 Signal Cable 1/2" NPT
ELECTRICAL 32 Control Cable -
CONNECTIONS 33 Solenoid Cable 3/4" NPT
34
Fl id
35 Fluid Ri h TEG
Rich
36 Phase Liquid
37 Operating Pressure 80 psig
C 38 Design Pressure 130 psig
39 Operating Temperature 149 ºF
40 Design Temperature 175 ºF
PROCESS DATA
C 41 Max. Diff. Pressure for Actuator Size 130 psig
42
43 Line Size and Sch. Inlet Outlet 3 in Sch. 80 3 in Sch. 80
44 Speed of Operation Design VTA
45 (Seconds) Actual VTA
46
Notes
1. VTA : Vendor to advice
2. Actuated ball valve and actuator shall be provided with 316 SS nameplate engraved or die stamped with Valve Tag No., Manufacturer's Name,
Model No., Valve Size & Rating.
3. Vendor shall be responsible for the proper design and selection of valve, actuator, and accessories based on the information furnished
C1 in this specification. This Data Sheet shall refer to SNO-I-ES-013, Instrument Specification for Shutdown and Blowdown Valve
4. Actuator shall be sized based on valve manufacturer's required Torque values with 130% minimum safety margin to open or close the valve
against full ANSI rated differential pressure at minimum pneumatic supply pressure of 60 psig.
5. Vendor shall provide Torque table containing breaking, running and seating torques for valves and actuator along with Quotation.
Vendor shall provide the torque table and calculation for COMPANY approval.
6. Actuator and accessories shall be supplied fully assembled, tubed and tested ready for installation.
7. Solenoid valve coil shall be provided with reverse polarity protection diodes, integral outlet box and terminal strip for cable connection.
8. Three way valve shall be universal type. Solenoid Coil shall be Class H.
Air filter regulator shall be 316 SS Material and equipped with pressure gauge on inlet and outlet of air filter regulator.
C1 9. All SDV & BDV shall be designed & tested as per API 6D
C1 10. Valve Stem Shall be Anti-Blowout Type.

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 96 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
1 Tag No. Quantity SDV -6051A 1 (One)
2 Manufacturer Model VTA VTA
3 Contract No. Requisition Item No.
4 Location Central Processing Plant
GENERAL
5 P&ID No. SNO-R-PI-602
6 Service From SNO-C-6051 to Lean/rich Exchanger E-6057
C 7 Line No. 6"-CA-6500-1N
8 Area Classification Zone-2, Gr. IIB, T3
9 Valve Type Valve Code Trunnion Mounted Ball BA100
10 Body Size Body Form 6 in Ball
11 Body Material Port Size ASTM A351 CF8M Full Bore
12 Connection Rating RF Flange ASME 150#
C1 13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
C 14 Packing Lubrication & Isolation Expanded Graphite VTA
15 Bonnet Bolts Bonnet Nuts ASTM A193 B8M CL2 ASTM A194 8M
C 16 Ball Material Stem Material 316 SS 316 SS
C1 17 Leakage Rate Seat Material ISO 5028 Rate A PTFE
18 NACE Requirement Yes
C 19 Type Stroking Time Pneumatic Piston / Spring return 12 Seconds
20 Size Safety Factor VTA in 1.3
21 Actuator Orientation Actuator Form Horizontal Cylinder
22 Ingress Protection Electrical Protection IP65 Eex i
23 Instrument Air Supply 80-120 Psig
24 Action on Air Failure Action on Power Failure Closed Closed
ACTUATOR 25 Fireproofing No
C 26 Solenoid Valve Schematic Detail Yes Type-1
27 Limit Switch Closed Limit Swich Open Yes Yes
28 Mounting Position Solenoid Power Supply Top 24VDC
29 Manual Reset Yes
30 Mechanical Position Indicator Red Closed / Green Open
C 31 Partial Stroke Facility No
31 Signal Cable 1/2" NPT
ELECTRICAL 32 Control Cable -
CONNECTIONS 33 Solenoid Cable 3/4" NPT
34
Fl id
35 Fluid Ri h Amine
Rich A i
36 Phase Liquid
37 Operating Pressure 115 psig
C 38 Design Pressure 165 psig
39 Operating Temperature 148 ºF
C 40 Design Temperature 170 ºF
PROCESS DATA
C 41 Max. Diff. Pressure for Actuator Size 165 psig
42
43 Line Size and Sch. Inlet Outlet 6 in Sch. 10S 6 in Sch 10S
44 Speed of Operation Design VTA
45 (Seconds) Actual VTA
46
Notes
1. VTA : Vendor to advice
2. Actuated ball valve and actuator shall be provided with 316 SS nameplate engraved or die stamped with Valve Tag No., Manufacturer's Name,
Model No., Valve Size & Rating.
3. Vendor shall be responsible for the proper design and selection of valve, actuator, and accessories based on the information furnished
C1 in this specification. This Data Sheet shall refer to SNO-I-ES-013, Instrument Specification for Shutdown and Blowdown Valve
4. Actuator shall be sized based on valve manufacturer's required Torque values with 130% minimum safety margin to open or close the valve
against full ANSI rated differential pressure at minimum pneumatic supply pressure of 60 psig.
5. Vendor shall provide Torque table containing breaking, running and seating torques for valves and actuator along with Quotation.
Vendor shall provide the torque table and calculation for COMPANY approval.
6. Actuator and accessories shall be supplied fully assembled, tubed and tested ready for installation.
7. Solenoid valve coil shall be provided with reverse polarity protection diodes, integral outlet box and terminal strip for cable connection.
8. Three way valve shall be universal type. Solenoid Coil shall be Class H.
Air filter regulator shall be 316 SS Material and equipped with pressure gauge on inlet and outlet of air filter regulator.
C1 9. All SDV & BDV shall be designed & tested as per API 6D
C1 10. Valve Stem Shall be Anti-Blowout Type.

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 97 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
1 Tag No. Quantity SDV-6051B 1 (One)
2 Manufacturer Model VTA VTA
3 Contract No. Requisition Item No.
4 Location Central Processing Plant
GENERAL
5 P&ID No. SNO-R-PI-602
6 Service From Lean Amine Cooler E-6056 to SNO-C-6051
C 7 Line No. 4"-CA-6503-3B
8 Area Classification Zone-2, Gr. IIB, T3
C1 9 Valve Type Valve Code Trunnion Mounted Ball BA122
10 Body Size Body Form 4 in Ball
C 11 Body Material Port Size A105 Full Bore
C 12 Connection Rating RF Flange ASME 300#
C1 13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
C 14 Packing Lubrication & Isolation Expanded Graphite VTA
C 15 Bonnet Bolts Bonnet Nuts ASTM A193 B7 ASTM A194 2H
C 16 Ball Material Stem Material CS+ENP 76μm 316SS
C1 17 Leakage Rate Seat Material ISO 5028 Rate A PTFE
C 18 NACE Requirement Yes
C 19 Type Stroking Time Pneumatic Piston / Spring return 8 Seconds
20 Size Safety Factor VTA in 1.3
21 Actuator Orientation Actuator Form Horizontal Cylinder
22 Ingress Protection Electrical Protection IP65 Eex i
23 Instrument Air Supply 80-120 Psig
24 Action on Air Failure Action on Power Failure Closed Closed
ACTUATOR 25 Fireproofing No
26 Solenoid Valve Schematic Detail Yes Type-1
27 Limit Switch Closed Limit Swich Open Yes Yes
28 Mounting Position Solenoid Power Supply Top 24VDC
29 Manual Reset No
30 Mechanical Position Indicator Red Closed / Green Open
C 31 Partial Stroke Facility No
31 Signal Cable 1/2" NPT
ELECTRICAL 32 Control Cable -
CONNECTIONS 33 Solenoid Cable 3/4" NPT
34
Fl id
35 Fluid Ri h Amine
Rich A i
36 Phase Liquid
C 37 Operating Pressure 190 psig
38 Design Pressure 305 psig
39 Operating Temperature 130 ºF
C 40 Design Temperature 200 ºF
PROCESS DATA
41 Max. Diff. Pressure for Actuator Size 305 psig
42
43 Line Size and Sch. Inlet Outlet 4 in Sch. 40 4 in Sch. 40
44 Speed of Operation Design VTA
45 (Seconds) Actual VTA
46
Notes
1. VTA : Vendor to advice
2. Actuated ball valve and actuator shall be provided with 316 SS nameplate engraved or die stamped with Valve Tag No., Manufacturer's Name,
Model No., Valve Size & Rating.
3. Vendor shall be responsible for the proper design and selection of valve, actuator, and accessories based on the information furnished
C1 in this specification. This Data Sheet shall refer to SNO-I-ES-013, Instrument Specification for Shutdown and Blowdown Valve
4. Actuator shall be sized based on valve manufacturer's required Torque values with 130% minimum safety margin to open or close the valve
against full ANSI rated differential pressure at minimum pneumatic supply pressure of 60 psig.
5. Vendor shall provide Torque table containing breaking, running and seating torques for valves and actuator along with Quotation.
Vendor shall provide the torque table and calculation for COMPANY approval.
6. Actuator and accessories shall be supplied fully assembled, tubed and tested ready for installation.
7. Solenoid valve coil shall be provided with reverse polarity protection diodes, integral outlet box and terminal strip for cable connection.
8. Three way valve shall be universal type. Solenoid Coil shall be Class H.
Air filter regulator shall be 316 SS Material and equipped with pressure gauge on inlet and outlet of air filter regulator.
C1 9. All SDV & BDV shall be designed & tested as per API 6D
C1 10. Valve Stem Shall be Anti-Blowout Type.

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 98 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
C 1 Tag No. Quantity SDV-6060A 1 (One)
2 Manufacturer Model VTA VTA
3 Contract No. Requisition Item No.
4 Location Central Processing Plant
GENERAL
5 P&ID No. SNO-R-PI-604
6 Service From Hot Oil Distribution to SNO-E-6060
C 7 Line No. 6"-OH-1007-3A
8 Area Classification Zone-2, Gr. IIB, T3
9 Valve Type Valve Code Trunnion Mounted Ball BA010
10 Body Size Body Form 6 in Ball
11 Body Material Port Size ASTM A216-WCB Full Bore
12 Connection Rating RF Flange ASME 300#
C1 13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
C 14 Packing Lubrication & Isolation Expanded Graphite VTA
C 15 Bonnet Bolts Bonnet Nuts ASTM A193 B7 ASTM A194 2H
C 16 Ball Material Stem Material 316 SS CS+ENP 76μm
C1 17 Leakage Rate Seat Material ISO 5028 Rate D Metal
18 NACE Requirement No
C 19 Type Stroking Time Pneumatic Piston / Spring return 12 Seconds
20 Size Safety Factor VTA in 1.3
21 Actuator Orientation Actuator Form Horizontal Cylinder
22 Ingress Protection Electrical Protection IP65 Eex i
23 Instrument Air Supply 80-120 Psig
24 Action on Air Failure Action on Power Failure Closed Closed
ACTUATOR 25 Fireproofing No
26 Solenoid Valve Schematic Detail Yes Type-1
27 Limit Switch Closed Limit Swich Open Yes Yes
28 Mounting Position Solenoid Power Supply Top 24VDC
29 Manual Reset No
30 Mechanical Position Indicator Red Closed / Green Open
C 31 Partial Stroke Facility No
31 Signal Cable 1/2" NPT
ELECTRICAL 32 Control Cable -
CONNECTIONS 33 Solenoid Cable 3/4" NPT
34
Fl id
35 Fluid H t Oil
Hot
36 Phase Liquid
37 Operating Pressure 65 psig
38 Design Pressure 210 psig
39 Operating Temperature 350 ºF
40 Design Temperature 450 ºF
PROCESS DATA
41 Max. Diff. Pressure for Actuator Size 210 psig
42
43 Line Size and Sch. Inlet Outlet 6 in Sch. 40 6 in Sch. 40
44 Speed of Operation Design VTA
45 (Seconds) Actual VTA
46
Notes
1. VTA : Vendor to advice
2. Actuated ball valve and actuator shall be provided with 316 SS nameplate engraved or die stamped with Valve Tag No., Manufacturer's Name,
Model No., Valve Size & Rating.
3. Vendor shall be responsible for the proper design and selection of valve, actuator, and accessories based on the information furnished
C1 in this specification. This Data Sheet shall refer to SNO-I-ES-013, Instrument Specification for Shutdown and Blowdown Valve
4. Actuator shall be sized based on valve manufacturer's required Torque values with 130% minimum safety margin to open or close the valve
against full ANSI rated differential pressure at minimum pneumatic supply pressure of 60 psig.
5. Vendor shall provide Torque table containing breaking, running and seating torques for valves and actuator along with Quotation.
Vendor shall provide the torque table and calculation for COMPANY approval.
6. Actuator and accessories shall be supplied fully assembled, tubed and tested ready for installation.
7. Solenoid valve coil shall be provided with reverse polarity protection diodes, integral outlet box and terminal strip for cable connection.
8. Three way valve shall be universal type. Solenoid Coil shall be Class H.
Air filter regulator shall be 316 SS Material and equipped with pressure gauge on inlet and outlet of air filter regulator.
C1 9. All SDV & BDV shall be designed & tested as per API 6D
C1 10. Valve Stem Shall be Anti-Blowout Type.

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 99 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
C 1 Tag No. Quantity SDV-6054A 1 (One)
2 Manufacturer Model VTA VTA
3 Contract No. Requisition Item No.
4 Location Central Processing Plant
GENERAL
5 P&ID No. SNO-R-PI-605
6 Service From Amine Reflux to Acid Gas Conversion Unit
C 7 Line No. 4"-GA-6516-1N
8 Area Classification Zone-2, Gr. IIB, T3
9 Valve Type Valve Code Trunnion Mounted Ball BA098
10 Body Size Body Form 4 in Ball
11 Body Material Port Size ASTM A351 CF8M Full Bore
12 Connection Rating RF Flange ASME 150#
C1 13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
C 14 Packing Lubrication & Isolation Expanded Graphite VTA
15 Bonnet Bolts Bonnet Nuts ASTM A193 B8M CL2 ASTM A194 8M
C 16 Ball Material Stem Material 316 SS 316 SS
C1 17 Leakage Rate Seat Material ISO 5028 Rate A PTFE
C 18 NACE Requirement Yes
C 19 Type Stroking Time Pneumatic Piston / Spring return 8 Seconds
20 Size Safety Factor VTA in 1.3
21 Actuator Orientation Actuator Form Horizontal Cylinder
22 Ingress Protection Electrical Protection IP65 Eex i
23 Instrument Air Supply 80-120 Psig
24 Action on Air Failure Action on Power Failure Closed Closed
ACTUATOR 25 Fireproofing No
26 Solenoid Valve Schematic Detail Yes Type-1
27 Limit Switch Closed Limit Swich Open Yes Yes
28 Mounting Position Solenoid Power Supply Top 24VDC
29 Manual Reset No
30 Mechanical Position Indicator Red Closed / Green Open
C 31 Partial Stroke Facility No
31 Signal Cable 1/2" NPT
ELECTRICAL 32 Control Cable -
CONNECTIONS 33 Solenoid Cable 3/4" NPT
34
Fl id
35 Fluid A id Gas
Acid G
36 Phase Gas
37 Operating Pressure 19 psig
38 Design Pressure 70 psig
39 Operating Temperature 120 ºF
40 Design Temperature 150 ºF
PROCESS DATA
41 Max. Diff. Pressure for Actuator Size 70 psig
42
43 Line Size and Sch. Inlet Outlet 4 in Sch. 10S 4 in Sch. 10S
44 Speed of Operation Design VTA
45 (Seconds) Actual VTA
46
Notes
1. VTA : Vendor to advice
2. Actuated ball valve and actuator shall be provided with 316 SS nameplate engraved or die stamped with Valve Tag No., Manufacturer's Name,
Model No., Valve Size & Rating.
3. Vendor shall be responsible for the proper design and selection of valve, actuator, and accessories based on the information furnished
C1 in this specification. This Data Sheet shall refer to SNO-I-ES-013, Instrument Specification for Shutdown and Blowdown Valve
4. Actuator shall be sized based on valve manufacturer's required Torque values with 130% minimum safety margin to open or close the valve
against full ANSI rated differential pressure at minimum pneumatic supply pressure of 60 psig.
5. Vendor shall provide Torque table containing breaking, running and seating torques for valves and actuator along with Quotation.
Vendor shall provide the torque table and calculation for COMPANY approval.
6. Actuator and accessories shall be supplied fully assembled, tubed and tested ready for installation.
7. Solenoid valve coil shall be provided with reverse polarity protection diodes, integral outlet box and terminal strip for cable connection.
8. Three way valve shall be universal type. Solenoid Coil shall be Class H.
Air filter regulator shall be 316 SS Material and equipped with pressure gauge on inlet and outlet of air filter regulator.
C1 9. All SDV & BDV shall be designed & tested as per API 6D
C1 10. Valve Stem Shall be Anti-Blowout Type.

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 100 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
C 1 Tag No. Quantity SDV-6054B 1 (One)
2 Manufacturer Model VTA VTA
3 Contract No. Requisition Item No.
4 Location Central Processing Plant
GENERAL
5 P&ID No. SNO-R-PI-605
6 Service SNO-V-6054 to SNO-P-6061A/B
C 7 Line No. 2"-CA-1508-1N
8 Area Classification Zone-2, Gr. IIB, T3
9 Valve Type Valve Code Trunnion Mounted Ball BA098
10 Body Size Body Form 2 in Ball
11 Body Material Port Size ASTM A351 CF8M Full Bore
12 Connection Rating RF Flange ASME 150#
C1 13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
C 14 Packing Lubrication & Isolation Expanded Graphite VTA
15 Bonnet Bolts Bonnet Nuts ASTM A193 B8M CL2 ASTM A194 8M
C 16 Ball Material Stem Material 316 SS 316 SS
C1 17 Leakage Rate Seat Material ISO 5028 Rate A PTFE
18 NACE Requirement Yes
C 19 Type Stroking Time Pneumatic Piston / Spring return 4 Seconds
20 Size Safety Factor VTA in 1.3
21 Actuator Orientation Actuator Form Horizontal Cylinder
22 Ingress Protection Electrical Protection IP65 Eex i
23 Instrument Air Supply 80-120 Psig
24 Action on Air Failure Action on Power Failure Closed Closed
ACTUATOR 25 Fireproofing No
26 Solenoid Valve Schematic Detail Yes Type-1
27 Limit Switch Closed Limit Swich Open Yes Yes
28 Mounting Position Solenoid Power Supply Top 24VDC
29 Manual Reset No
30 Mechanical Position Indicator Red Closed / Green Open
C 31 Partial Stroke Facility No
31 Signal Cable 1/2" NPT
ELECTRICAL 32 Control Cable -
CONNECTIONS 33 Solenoid Cable 3/4" NPT
34
Fl id
C 35 Fluid W t (H2S,
Water (H2S CO2 dissolved)
di l d)
36 Phase Liquid
C 37 Operating Pressure 74 psig
C 38 Design Pressure 150 psig
39 Operating Temperature 120 ºF
40 Design Temperature 150 ºF
PROCESS DATA
C 41 Max. Diff. Pressure for Actuator Size 150 psig
42
43 Line Size and Sch. Inlet Outlet 2 in Sch. 10S 2 in Sch. 10S
44 Speed of Operation Design VTA
45 (Seconds) Actual VTA
46
Notes
1. VTA : Vendor to advice
2. Actuated ball valve and actuator shall be provided with 316 SS nameplate engraved or die stamped with Valve Tag No., Manufacturer's Name,
Model No., Valve Size & Rating.
3. Vendor shall be responsible for the proper design and selection of valve, actuator, and accessories based on the information furnished
C1 in this specification. This Data Sheet shall refer to SNO-I-ES-013, Instrument Specification for Shutdown and Blowdown Valve
4. Actuator shall be sized based on valve manufacturer's required Torque values with 130% minimum safety margin to open or close the valve
against full ANSI rated differential pressure at minimum pneumatic supply pressure of 60 psig.
5. Vendor shall provide Torque table containing breaking, running and seating torques for valves and actuator along with Quotation.
Vendor shall provide the torque table and calculation for COMPANY approval.
6. Actuator and accessories shall be supplied fully assembled, tubed and tested ready for installation.
7. Solenoid valve coil shall be provided with reverse polarity protection diodes, integral outlet box and terminal strip for cable connection.
8. Three way valve shall be universal type. Solenoid Coil shall be Class H.
Air filter regulator shall be 316 SS Material and equipped with pressure gauge on inlet and outlet of air filter regulator.
C1 9. All SDV & BDV shall be designed & tested as per API 6D
C1 10. Valve Stem Shall be Anti-Blowout Type.

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 101 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
C 1 Tag No. Quantity SDV-6053F 1 (One)
2 Manufacturer Model VTA VTA
3 Contract No. Requisition Item No.
4 Location Central Processing Plant
GENERAL
5 P&ID No. SNO-R-PI-606
6 Service SNO-V-6053 to Rich/Lean Amine Exchanger SNO-E-6057
C 7 Line No. 2"-CA-6521-1N
8 Area Classification Zone-2, Gr. IIB, T3
C1 9 Valve Type Valve Code Trunnion Mounted Ball BA098
10 Body Size Body Form 2 in Ball
11 Body Material Port Size ASTM A351 CF8M Full Bore
12 Connection Rating RF Flange ASME 150#
C1 13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
C 14 Packing Lubrication & Isolation Expanded Graphite VTA
15 Bonnet Bolts Bonnet Nuts ASTM A193 B8M CL2 ASTM A194 8M
C 16 Ball Material Stem Material 316 SS 316 SS
C1 17 Leakage Rate Seat Material ISO 5028 Rate A PTFE
18 NACE Requirement Yes
C 19 Type Stroking Time Pneumatic Piston / Spring return 4 Seconds
20 Size Safety Factor VTA in 1.3
21 Actuator Orientation Actuator Form Horizontal Cylinder
22 Ingress Protection Electrical Protection IP65 Eex i
23 Instrument Air Supply 80-120 Psig
24 Action on Air Failure Action on Power Failure Closed Closed
ACTUATOR 25 Fireproofing No
26 Solenoid Valve Schematic Detail Yes Type-1
27 Limit Switch Closed Limit Swich Open Yes Yes
28 Mounting Position Solenoid Power Supply Top 24VDC
29 Manual Reset No
30 Mechanical Position Indicator Red Closed / Green Open
C 31 Partial Stroke Facility No
31 Signal Cable 1/2" NPT
ELECTRICAL 32 Control Cable -
CONNECTIONS 33 Solenoid Cable 3/4" NPT
34
Fl id
35 Fluid A i
Amine
36 Phase Liquid
37 Operating Pressure 104 psig
C 38 Design Pressure 165 psig
39 Operating Temperature 120 ºF
40 Design Temperature 150 ºF
PROCESS DATA
C 41 Max. Diff. Pressure for Actuator Size 165 psig
42
43 Line Size and Sch. Inlet Outlet 2 in Sch. 10S 2 in Sch. 10S
44 Speed of Operation Design VTA
45 (Seconds) Actual VTA
46
Notes
1. VTA : Vendor to advice
2. Actuated ball valve and actuator shall be provided with 316 SS nameplate engraved or die stamped with Valve Tag No., Manufacturer's Name,
Model No., Valve Size & Rating.
3. Vendor shall be responsible for the proper design and selection of valve, actuator, and accessories based on the information furnished
C1 in this specification. This Data Sheet shall refer to SNO-I-ES-013, Instrument Specification for Shutdown and Blowdown Valve
4. Actuator shall be sized based on valve manufacturer's required Torque values with 130% minimum safety margin to open or close the valve
against full ANSI rated differential pressure at minimum pneumatic supply pressure of 60 psig.
5. Vendor shall provide Torque table containing breaking, running and seating torques for valves and actuator along with Quotation.
Vendor shall provide the torque table and calculation for COMPANY approval.
6. Actuator and accessories shall be supplied fully assembled, tubed and tested ready for installation.
7. Solenoid valve coil shall be provided with reverse polarity protection diodes, integral outlet box and terminal strip for cable connection.
8. Three way valve shall be universal type. Solenoid Coil shall be Class H.
Air filter regulator shall be 316 SS Material and equipped with pressure gauge on inlet and outlet of air filter regulator.
C1 9. All SDV & BDV shall be designed & tested as per API 6D
C1 10. Valve Stem Shall be Anti-Blowout Type.

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 102 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
C 1 Tag No. Quantity SDV-6053G 1 (One)
2 Manufacturer Model VTA VTA
3 Contract No. Requisition Item No.
4 Location Central Processing Plant
GENERAL
5 P&ID No. SNO-R-PI-606
6 Service SNO-V-6053 to LP Fuel Gas Scrubber
C 7 Line No. 6"-HG-6603-1B
8 Area Classification Zone-2, Gr. IIB, T3
9 Valve Type Valve Code Trunnion Mounted Ball BA034
10 Body Size Body Form 6 in Ball
C 11 Body Material Port Size A105 Full Bore
12 Connection Rating RF Flange ASME 150#
C1 13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
C 14 Packing Lubrication & Isolation Expanded Graphite VTA
C 15 Bonnet Bolts Bonnet Nuts ASTM A193 B7 ASTM A194 2H
C 16 Ball Material Stem Material 316 SS 316 SS
C1 17 Leakage Rate Seat Material ISO 5028 Rate A PTFE
C 18 NACE Requirement Yes
C 19 Type Stroking Time Pneumatic Piston / Spring return 12 Seconds
20 Size Safety Factor VTA in 1.3
21 Actuator Orientation Actuator Form Horizontal Cylinder
22 Ingress Protection Electrical Protection IP65 Eex i
23 Instrument Air Supply 80-120 Psig
24 Action on Air Failure Action on Power Failure Closed Closed
ACTUATOR 25 Fireproofing No
26 Solenoid Valve Schematic Detail Yes Type-1
27 Limit Switch Closed Limit Swich Open Yes Yes
28 Mounting Position Solenoid Power Supply Top 24VDC
29 Manual Reset No
30 Mechanical Position Indicator Red Closed / Green Open
C 31 Partial Stroke Facility No
31 Signal Cable 1/2" NPT
ELECTRICAL 32 Control Cable -
CONNECTIONS 33 Solenoid Cable 3/4" NPT
34
Fl id
35 Fluid H d b Gas
Hydrocarbon G
36 Phase Gas
37 Operating Pressure 104 psig
C 38 Design Pressure 165 psig
39 Operating Temperature 120 ºF
40 Design Temperature 150 ºF
PROCESS DATA
C 41 Max. Diff. Pressure for Actuator Size 165 psig
42
43 Line Size and Sch. Inlet Outlet 6 in Sch. 40 6 in Sch. 40
44 Speed of Operation Design VTA
45 (Seconds) Actual VTA
46
Notes
1. VTA : Vendor to advice
2. Actuated ball valve and actuator shall be provided with 316 SS nameplate engraved or die stamped with Valve Tag No., Manufacturer's Name,
Model No., Valve Size & Rating.
3. Vendor shall be responsible for the proper design and selection of valve, actuator, and accessories based on the information furnished
C1 in this specification. This Data Sheet shall refer to SNO-I-ES-013, Instrument Specification for Shutdown and Blowdown Valve
4. Actuator shall be sized based on valve manufacturer's required Torque values with 130% minimum safety margin to open or close the valve
against full ANSI rated differential pressure at minimum pneumatic supply pressure of 60 psig.
5. Vendor shall provide Torque table containing breaking, running and seating torques for valves and actuator along with Quotation.
Vendor shall provide the torque table and calculation for COMPANY approval.
6. Actuator and accessories shall be supplied fully assembled, tubed and tested ready for installation.
7. Solenoid valve coil shall be provided with reverse polarity protection diodes, integral outlet box and terminal strip for cable connection.
8. Three way valve shall be universal type. Solenoid Coil shall be Class H.
Air filter regulator shall be 316 SS Material and equipped with pressure gauge on inlet and outlet of air filter regulator.
C1 9. All SDV & BDV shall be designed & tested as per API 6D
C1 10. Valve Stem Shall be Anti-Blowout Type.

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 103 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
1 Tag No. Quantity BDV-6123G 1 (One)
2 Manufacturer Model VTA VTA
3 Contract No. Requisition Item No.
4 Location Central Processing Plant
GENERAL
5 P&ID No. SNO-R-PI-606
6 Service SNO-V-6053 to LP Flare Header
C 7 Line No. 2"-HG-1506-1A
8 Area Classification Zone-2, Gr. IIB, T3
C1 9 Valve Type Valve Code Trunnion Mounted Ball BA003
C 10 Body Size Body Form 2 in Ball
C1 11 Body Material Port Size ASTM A216 WCB Full Bore
C 12 Connection Rating RF Flange ASME 150#
C1 13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
C 14 Packing Lubrication & Isolation Expanded Graphite VTA
C 15 Bonnet Bolts Bonnet Nuts A193 B7 A194 2H
C 16 Ball Material Stem Material CS+ENP 76μm CS+ENP 76μm
C1 17 Leakage Rate Seat Material ISO 5028 Rate A (TSO) PTFE
C 18 NACE Requirement No
C 19 Type Stroking Time Pneumatic Piston / Spring return 4 Seconds
20 Size Safety Factor VTA in 1.3
21 Actuator Orientation Actuator Form Horizontal Cylinder
22 Ingress Protection Electrical Protection IP65 Eex i
23 Instrument Air Supply 80-120 Psig
24 Action on Air Failure Action on Power Failure Open Open
ACTUATOR 25 Fireproofing No
26 Solenoid Valve Schematic Detail Yes Type-2
27 Limit Switch Closed Limit Swich Open Yes Yes
28 Mounting Position Solenoid Power Supply Top 24VDC
29 Manual Reset No
30 Mechanical Position Indicator Red Closed / Green Open
C 31 Partial Stroke Facility No
31 Signal Cable 1/2" NPT
ELECTRICAL 32 Control Cable -
CONNECTIONS 33 Solenoid Cable 3/4" NPT
34
35 Fl id
Fluid H d b Gas
Hydrocarbon G
36 Phase Gas
37 Operating Pressure 104 psig
C 38 Design Pressure 165 psig
39 Operating Temperature 120 ºF
40 Design Temperature 150 ºF
PROCESS DATA
C 41 Max. Diff. Pressure for Actuator Size 165 psig
42
43 Line Size and Sch. Inlet Outlet 2 in Sch. 80 2 in Sch. 80
44 Speed of Operation Design VTA
45 (Seconds) Actual VTA
46
Notes
1. VTA : Vendor to advice
2. Actuated ball valve and actuator shall be provided with 316 SS nameplate engraved or die stamped with Valve Tag No., Manufacturer's Name,
Model No., Valve Size & Rating.
3. Vendor shall be responsible for the proper design and selection of valve, actuator, and accessories based on the information furnished
C1 in this specification. This Data Sheet shall refer to SNO-I-ES-013, Instrument Specification for Shutdown and Blowdown Valve
4. Actuator shall be sized based on valve manufacturer's required Torque values with 130% minimum safety margin to open or close the valve
against full ANSI rated differential pressure at minimum pneumatic supply pressure of 60 psig.
5. Vendor shall provide Torque table containing breaking, running and seating torques for valves and actuator along with Quotation.
Vendor shall provide the torque table and calculation for COMPANY approval.
6. Actuator and accessories shall be supplied fully assembled, tubed and tested ready for installation.
7. Solenoid valve coil shall be provided with reverse polarity protection diodes, integral outlet box and terminal strip for cable connection.
8. Three way valve shall be universal type. Solenoid Coil shall be Class H.
Air filter regulator shall be 316 SS Material and equipped with pressure gauge on inlet and outlet of air filter regulator.
C1 9. All SDV & BDV shall be designed & tested as per API 6D
C1 10. Valve Stem Shall be Anti-Blowout Type.

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 104 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
C 1 Tag No. Quantity XV-6070A / 6070B 2 (Two)
C 2 Manufacturer Model VTA VTA
C 3 Contract No. Requisition Item No.
C 4 Location Central Processing Plant
GENERAL
C 5 P&ID No. SNO-R-PI-010B
C 6 Service From SAHC Unit to Sulphuric Acid Storage Tank
C 7 Line No. 4"-SA-0151-1B / 4"-SA-0001-1B
C 8 Area Classification Zone-2, Gr. IIB, T3
C1 9 Valve Type Valve Code Trunnion Mounted Ball BA032
C 10 Body Size Body Form 4 in Ball
C 11 Body Material Port Size A216 WCB Full Bore
C 12 Connection Rating RF Flange ASME 150#
C1 13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
C 14 Packing Lubrication & Isolation Expanded Graphite VTA
C 15 Bonnet Bolts Bonnet Nuts A193 B7M A194 2HM
C 16 Ball Material Stem Material 316SS 316SS
C1 17 Leakage Rate Seat Material ISO 5028 Rate A PTFE
C 18 NACE Requirement Yes
C 19 Type Stroking Time Pneumatic Piston / Spring return 8 Seconds
C 20 Size Safety Factor VTA in 1.3
C 21 Actuator Orientation Actuator Form Horizontal Cylinder
C 22 Ingress Protection Electrical Protection IP65 Eex i
C 23 Instrument Air Supply 80-120 Psig
C 24 Action on Air Failure Action on Power Failure Closed Closed
ACTUATOR C 25 Fireproofing No
C 26 Solenoid Valve Schematic Detail Yes Type-10
C 27 Limit Switch Closed Limit Swich Open Yes Yes
C 28 Mounting Position Solenoid Power Supply Top 24VDC
C 29 Manual Reset No
C 30 Mechanical Position Indicator Red Closed / Green Open
C 31 Partial Stroke Facility No
C 31 Signal Cable 1/2" NPT
ELECTRICAL C 32 Control Cable -
CONNECTIONS C 33 Solenoid Cable 3/4" NPT
C 34
Fl id
C 35 Fluid H d b Gas
Hydrocarbon G
C 36 Phase Gas
C 37 Operating Pressure 104 psig
C 38 Design Pressure 155 psig
C 39 Operating Temperature 120 ºF
C 40 Design Temperature 150 ºF
PROCESS DATA
C 41 Max. Diff. Pressure for Actuator Size 155 psig
C 42
C 43 Line Size and Sch. Inlet Outlet 4 in Sch. 40 4 in Sch. 40
C 44 Speed of Operation Design VTA
C 45 (Seconds) Actual VTA
C 46
Notes
1. VTA : Vendor to advice
2. Actuated ball valve and actuator shall be provided with 316 SS nameplate engraved or die stamped with Valve Tag No., Manufacturer's Name,
Model No., Valve Size & Rating.
3. Vendor shall be responsible for the proper design and selection of valve, actuator, and accessories based on the information furnished
C1 in this specification. This Data Sheet shall refer to SNO-I-ES-013, Instrument Specification for Shutdown and Blowdown Valve
4. Actuator shall be sized based on valve manufacturer's required Torque values with 130% minimum safety margin to open or close the valve
against full ANSI rated differential pressure at minimum pneumatic supply pressure of 60 psig.
5. Vendor shall provide Torque table containing breaking, running and seating torques for valves and actuator along with Quotation.
Vendor shall provide the torque table and calculation for COMPANY approval.
6. Actuator and accessories shall be supplied fully assembled, tubed and tested ready for installation.
7. Solenoid valve coil shall be provided with reverse polarity protection diodes, integral outlet box and terminal strip for cable connection.
8. Three way valve shall be universal type. Solenoid Coil shall be Class H.
Air filter regulator shall be 316 SS Material and equipped with pressure gauge on inlet and outlet of air filter regulator.
C1 9. All SDV & BDV shall be designed & tested as per API 6D
C1 10. Valve Stem Shall be Anti-Blowout Type.

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 105 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
C 1 Tag No. Quantity XV-6020A / 6020C 2 (Two)
C 2 Manufacturer Model VTA VTA
C 3 Contract No. Requisition Item No.
C 4 Location Central Processing Plant
GENERAL
C 5 P&ID No. SNO-R-PI-034B
C 6 Service Emergency Condensate Storage Tank Inlet
C 7 Line No. 8"-HL-XXXX-1A / 8"-HL-XXXX-1A
C 8 Area Classification Zone-2, Gr. IIB, T3
C1 9 Valve Type Valve Code Trunnion Mounted Ball BA005
C 10 Body Size Body Form 8 in Ball
C 11 Body Material Port Size ASTM A216 WCB Full Bore
C 12 Connection Rating RF Flange ASME 150#
C1 13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
C 14 Packing Lubrication & Isolation Expanded Graphite VTA
C 15 Bonnet Bolts Bonnet Nuts A193 B7 A194 2H
C 16 Ball Material Stem Material CS+ENP 76μm CS+ENP 76μm
C1 17 Leakage Rate Seat Material ISO 5028 Rate A PTFE
C 18 NACE Requirement No
C 19 Type Stroking Time Pneumatic Piston / Spring return 15 Seconds
C 20 Size Safety Factor VTA in 1.3
C 21 Actuator Orientation Actuator Form Horizontal Cylinder
C 22 Ingress Protection Electrical Protection IP65 Eex i
C 23 Instrument Air Supply 80-120 Psig
C 24 Action on Air Failure Action on Power Failure Closed Closed
ACTUATOR C 25 Fireproofing No
C 26 Solenoid Valve Schematic Detail Yes Type-10
C 27 Limit Switch Closed Limit Swich Open Yes Yes
C 28 Mounting Position Solenoid Power Supply Top 24VDC
C 29 Manual Reset No
C 30 Mechanical Position Indicator Red Closed / Green Open
C 31 Partial Stroke Facility No
C 31 Signal Cable 1/2" NPT
ELECTRICAL C 32 Control Cable -
CONNECTIONS C 33 Solenoid Cable 3/4" NPT
C 34
Fl id
C 35 Fluid St bili d Condensate
Stabilized C d t
C 36 Phase Oil
C 37 Operating Pressure 149 psig
C1 38 Design Pressure 225 psig
C 39 Operating Temperature AMB ºF
C 40 Design Temperature 200 ºF
PROCESS DATA
C1 41 Max. Diff. Pressure for Actuator Size 225 psig
C 42
C 43 Line Size and Sch. Inlet Outlet 8 in Sch. 20 8 in Sch. 20
C 44 Speed of Operation Design VTA
C 45 (Seconds) Actual VTA
C 46
Notes
1. VTA : Vendor to advice
2. Actuated ball valve and actuator shall be provided with 316 SS nameplate engraved or die stamped with Valve Tag No., Manufacturer's Name,
Model No., Valve Size & Rating.
3. Vendor shall be responsible for the proper design and selection of valve, actuator, and accessories based on the information furnished
C1 in this specification. This Data Sheet shall refer to SNO-I-ES-013, Instrument Specification for Shutdown and Blowdown Valve
4. Actuator shall be sized based on valve manufacturer's required Torque values with 130% minimum safety margin to open or close the valve
against full ANSI rated differential pressure at minimum pneumatic supply pressure of 60 psig.
5. Vendor shall provide Torque table containing breaking, running and seating torques for valves and actuator along with Quotation.
Vendor shall provide the torque table and calculation for COMPANY approval.
6. Actuator and accessories shall be supplied fully assembled, tubed and tested ready for installation.
7. Solenoid valve coil shall be provided with reverse polarity protection diodes, integral outlet box and terminal strip for cable connection.
8. Three way valve shall be universal type. Solenoid Coil shall be Class H.
Air filter regulator shall be 316 SS Material and equipped with pressure gauge on inlet and outlet of air filter regulator.
C1 9. All SDV & BDV shall be designed & tested as per API 6D
C1 10. Valve Stem Shall be Anti-Blowout Type.

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 106 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
C 1 Tag No. Quantity XV-6020B / 6020D 2 (Two)
C 2 Manufacturer Model VTA VTA
C 3 Contract No. Requisition Item No.
C 4 Location Central Processing Plant
GENERAL
C 5 P&ID No. SNO-R-PI-034B
C 6 Service Emergency Condensate Storage Tank Outlet
C 7 Line No. 24"-HL-XXXX-1A / 24"-HL-XXXX-1A
C 8 Area Classification Zone-2, Gr. IIB, T3
C1 9 Valve Type Valve Code Trunnion Mounted Ball BA005
C 10 Body Size Body Form 24 in Ball
C 11 Body Material Port Size ASTM A216 WCB Full Bore
C 12 Connection Rating RF Flanged ASME 150#
C1 13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
C 14 Packing Lubrication & Isolation Expanded Graphite VTA
C 15 Bonnet Bolts Bonnet Nuts A193 B7 A194 2H
C 16 Ball Material Stem Material CS+ENP 76μm CS+ENP 76μm
C1 17 Leakage Rate Seat Material ISO 5028 Rate A PTFE
C 18 NACE Requirement No
C 19 Type Stroking Time Pneumatic Piston / Spring return VTA
C 20 Size Safety Factor VTA in 1.3
C 21 Actuator Orientation Actuator Form Horizontal Cylinder
C 22 Ingress Protection Electrical Protection IP65 Eex i
C 23 Instrument Air Supply 80-120 Psig
C 24 Action on Air Failure Action on Power Failure Closed Closed
ACTUATOR C 25 Fireproofing No
C 26 Solenoid Valve Schematic Detail Yes Type-10
C 27 Limit Switch Closed Limit Swich Open Yes Yes
C 28 Mounting Position Solenoid Power Supply Top 24VDC
C 29 Manual Reset No
C 30 Mechanical Position Indicator Red Closed / Green Open
C 31 Partial Stroke Facility No
C 31 Signal Cable 1/2" NPT
ELECTRICAL C 32 Control Cable -
CONNECTIONS C 33 Solenoid Cable 3/4" NPT
C 34
Fl id
C 35 Fluid St bili d Condensate
Stabilized C d t
C 36 Phase Oil
C 37 Operating Pressure ATM psig
C 38 Design Pressure 50 psig
C 39 Operating Temperature 120 ºF
C 40 Design Temperature 150 ºF
PROCESS DATA
C 41 Max. Diff. Pressure for Actuator Size 50 psig
C 42
C 43 Line Size and Sch. Inlet Outlet 24 in Sch. 20 24 in Sch. 20
C 44 Speed of Operation Design VTA
C 45 (Seconds) Actual VTA
C 46
Notes
1. VTA : Vendor to advice
2. Actuated ball valve and actuator shall be provided with 316 SS nameplate engraved or die stamped with Valve Tag No., Manufacturer's Name,
Model No., Valve Size & Rating.
3. Vendor shall be responsible for the proper design and selection of valve, actuator, and accessories based on the information furnished
C1 in this specification. This Data Sheet shall refer to SNO-I-ES-013, Instrument Specification for Shutdown and Blowdown Valve
4. Actuator shall be sized based on valve manufacturer's required Torque values with 130% minimum safety margin to open or close the valve
against full ANSI rated differential pressure at minimum pneumatic supply pressure of 60 psig.
5. Vendor shall provide Torque table containing breaking, running and seating torques for valves and actuator along with Quotation.
Vendor shall provide the torque table and calculation for COMPANY approval.
6. Actuator and accessories shall be supplied fully assembled, tubed and tested ready for installation.
7. Solenoid valve coil shall be provided with reverse polarity protection diodes, integral outlet box and terminal strip for cable connection.
8. Three way valve shall be universal type. Solenoid Coil shall be Class H.
Air filter regulator shall be 316 SS Material and equipped with pressure gauge on inlet and outlet of air filter regulator.
C1 9. All SDV & BDV shall be designed & tested as per API 6D
C1 10. Valve Stem Shall be Anti-Blowout Type.

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 107 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
C 1 Tag No. Quantity SDV-8032A / 8032B 2 (Two)
C 2 Manufacturer Model VTA VTA
C 3 Contract No. Requisition Item No.
C 4 Location Central Processing Plant
GENERAL
C 5 P&ID No. SNO-R-PI-126
C 6 Service Export Gas
C 7 Line No. 3"-HG-XXXX-6B
C 8 Area Classification Zone-2, Gr. IIB, T3
C1 9 Valve Type Valve Code Trunnion Mounted Ball BA044
C 10 Body Size Body Form 3 in Ball
C 11 Body Material Port Size ASTM A216 WCB Full Bore
C 12 Connection Rating RF Flanged ASME 600#
C1 13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
C 14 Packing Lubrication & Isolation Expanded Graphite VTA
C 15 Bonnet Bolts Bonnet Nuts A193 B7M A194 2HM
C 16 Ball Material Stem Material CS+ENP 76μm A564 630, H1150M+ENP 76 μm
C1 17 Leakage Rate Seat Material ISO 5028 Rate A . PTFE OR NYLON
C 18 NACE Requirement Yes
C 19 Type Stroking Time Pneumatic Piston / Spring return 6 Seconds
C 20 Size Safety Factor VTA in 1.3
C 21 Actuator Orientation Actuator Form Horizontal Cylinder
C 22 Ingress Protection Electrical Protection IP65 Eex i
C 23 Instrument Air Supply 80-120 Psig
C 24 Action on Air Failure Action on Power Failure Closed Closed
ACTUATOR C 25 Fireproofing No
C 26 Solenoid Valve Schematic Detail Yes Type 1
C 27 Limit Switch Closed Limit Swich Open Yes Yes
C 28 Mounting Position Solenoid Power Supply Top 24VDC
C 29 Manual Reset No
C 30 Mechanical Position Indicator Red Closed / Green Open
C 31 Partial Stroke Facility No
C 31 Signal Cable 1/2" NPT
ELECTRICAL C 32 Control Cable -
CONNECTIONS C 33 Solenoid Cable 3/4" NPT
C 34
Fl id
C 35 Fluid H d b Gas
Hydrocarbon G
C 36 Phase Gas
C 37 Operating Pressure 852 psig
C 38 Design Pressure 1300 psig
C 39 Operating Temperature 100 ºF
C 40 Design Temperature 150 ºF
PROCESS DATA
C 41 Max. Diff. Pressure for Actuator Size 1300 psig
C 42
C 43 Line Size and Sch. Inlet Outlet 3 in Sch. 160 3 in Sch. 160
C 44 Speed of Operation Design VTA
C 45 (Seconds) Actual VTA
C 46
Notes
1. VTA : Vendor to advice
2. Actuated ball valve and actuator shall be provided with 316 SS nameplate engraved or die stamped with Valve Tag No., Manufacturer's Name,
Model No., Valve Size & Rating.
3. Vendor shall be responsible for the proper design and selection of valve, actuator, and accessories based on the information furnished
C1 in this specification. This Data Sheet shall refer to SNO-I-ES-013, Instrument Specification for Shutdown and Blowdown Valve
4. Actuator shall be sized based on valve manufacturer's required Torque values with 130% minimum safety margin to open or close the valve
against full ANSI rated differential pressure at minimum pneumatic supply pressure of 60 psig.
5. Vendor shall provide Torque table containing breaking, running and seating torques for valves and actuator along with Quotation.
Vendor shall provide the torque table and calculation for COMPANY approval.
6. Actuator and accessories shall be supplied fully assembled, tubed and tested ready for installation.
7. Solenoid valve coil shall be provided with reverse polarity protection diodes, integral outlet box and terminal strip for cable connection.
8. Three way valve shall be universal type. Solenoid Coil shall be Class H.
Air filter regulator shall be 316 SS Material and equipped with pressure gauge on inlet and outlet of air filter regulator.
C1 9. All SDV & BDV shall be designed & tested as per API 6D
C1 10. Valve Stem Shall be Anti-Blowout Type.

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 108 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
C1 1 Tag No. Quantity SDV-3102B / 3202B 2 (Two)
C1 2 Manufacturer Model VTA VTA
C1 3 Contract No. Requisition Item No.
C1 4 Location Central Processing Plant
GENERAL
C1 5 P&ID No. SNO-R-PI-401 / 411
C1 6 Service Lean TEG
C1 7 Line No. 3"-G-1603-6A / 3"-G-2603-6A
C1 8 Area Classification Zone-2, Gr. IIB, T3
C1 9 Valve Type Valve Code Trunnion Mounted Ball BA013
C1 10 Body Size Body Form 3 in Ball
C1 11 Body Material Port Size A216 WCB Full Bore
C1 12 Connection Rating RF Flange ASME 600#
C1 13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
C1 14 Packing Lubrication & Isolation Expanded Graphite VTA
C1 15 Bonnet Bolts Bonnet Nuts ASTM A193 B7 ASTM A194 2H
C1 16 Ball Material Stem Material CS+ENP 76μm A564 630, H1150M+ENP 76 μm
C1 17 Leakage Rate Seat Material ISO 5028 Rate A PTFE OR NYLON
C1 18 NACE Requirement No
C1 19 Type Stroking Time Pneumatic Piston / Spring return 6 Seconds
C1 20 Size Safety Factor VTA in 1.3
C1 21 Actuator Orientation Actuator Form Horizontal Cylinder
C1 22 Ingress Protection Electrical Protection IP65 Eex i
C1 23 Instrument Air Supply 80-120 Psig
C1 24 Action on Air Failure Action on Power Failure Closed Closed
ACTUATOR C1 25 Fireproofing No
C1 26 Solenoid Valve Schematic Detail Yes Type 1
C1 27 Limit Switch Closed Limit Swich Open Yes Yes
C1 28 Mounting Position Solenoid Power Supply Top 24VDC
C1 29 Manual Reset No
C1 30 Mechanical Position Indicator Red Closed / Green Open
C1 31 Partial Stroke Facility No
C1 31 Signal Cable 1/2" NPT
ELECTRICAL C1 32 Control Cable -
CONNECTIONS C1 33 Solenoid Cable 3/4" NPT
C1 34
Fl id
C1 35 Fluid L
Lean TEG
C1 36 Phase Liquid
C1 37 Operating Pressure 890 psig
C1 38 Design Pressure 1300 psig
C1 39 Operating Temperature 130 ºF
C1 40 Design Temperature 150 ºF
PROCESS DATA
C1 41 Max. Diff. Pressure for Actuator Size 1300 psig
C1 42
C1 43 Line Size and Sch. Inlet Outlet 3 in Sch. 160 3 in Sch. 160
C1 44 Speed of Operation Design VTA
C1 45 (Seconds) Actual VTA
C1 46
Notes
1. VTA : Vendor to advice
2. Actuated ball valve and actuator shall be provided with 316 SS nameplate engraved or die stamped with Valve Tag No., Manufacturer's Name,
Model No., Valve Size & Rating.
3. Vendor shall be responsible for the proper design and selection of valve, actuator, and accessories based on the information furnished
C1 in this specification. This Data Sheet shall refer to SNO-I-ES-013, Instrument Specification for Shutdown and Blowdown Valve
4. Actuator shall be sized based on valve manufacturer's required Torque values with 130% minimum safety margin to open or close the valve
against full ANSI rated differential pressure at minimum pneumatic supply pressure of 60 psig.
5. Vendor shall provide Torque table containing breaking, running and seating torques for valves and actuator along with Quotation.
Vendor shall provide the torque table and calculation for COMPANY approval.
6. Actuator and accessories shall be supplied fully assembled, tubed and tested ready for installation.
7. Solenoid valve coil shall be provided with reverse polarity protection diodes, integral outlet box and terminal strip for cable connection.
8. Three way valve shall be universal type. Solenoid Coil shall be Class H.
Air filter regulator shall be 316 SS Material and equipped with pressure gauge on inlet and outlet of air filter regulator.
C1 9. All SDV & BDV shall be designed & tested as per API 6D
C1 10. Valve Stem Shall be Anti-Blowout Type.

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 109 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
C1 1 Tag No. Quantity SDV-4032A 1 (One)
C1 2 Manufacturer Model VTA VTA
C1 3 Contract No. Requisition Item No.
C1 4 Location Central Processing Plant
GENERAL
C1 5 P&ID No. SNO-R-PI-701
C1 6 Service Acid gas from acid gas removal unit
C1 7 Line No. 24"-GA-XXXX-1N
C1 8 Area Classification Zone-2, Gr. IIB, T3
C1 9 Valve Type Valve Code Trunnion Mounted Ball BA100
C1 10 Body Size Body Form 24 in Ball
C1 11 Body Material Port Size ASTM A351 CF8M Full Bore
C1 12 Connection Rating RF Flange ASME 150#
C1 13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
C1 14 Packing Lubrication & Isolation Expanded Graphite VTA
C1 15 Bonnet Bolts Bonnet Nuts ASTM A193 B8M CL2 ASTM A194 8M
C1 16 Ball Material Stem Material 316 SS 316 SS
C1 17 Leakage Rate Seat Material ISO 5028 Rate A PTFE
C1 18 NACE Requirement Yes
C1 19 Type Stroking Time Pneumatic Piston / Spring return 24 Seconds
C1 20 Size Safety Factor VTA in 1.3
C1 21 Actuator Orientation Actuator Form Horizontal Cylinder
C1 22 Ingress Protection Electrical Protection IP65 Eex i
C1 23 Instrument Air Supply 80-120 Psig
C1 24 Action on Air Failure Action on Power Failure Closed Closed
ACTUATOR C1 25 Fireproofing No
C1 26 Solenoid Valve Schematic Detail Yes Type 1
C1 27 Limit Switch Closed Limit Swich Open Yes Yes
C1 28 Mounting Position Solenoid Power Supply Top 24VDC
C1 29 Manual Reset No
C1 30 Mechanical Position Indicator Red Closed / Green Open
C1 31 Partial Stroke Facility No
C1 31 Signal Cable 1/2" NPT
ELECTRICAL C1 32 Control Cable -
CONNECTIONS C1 33 Solenoid Cable 3/4" NPT
C1 34
Fl id
C1 35 Fluid A id Gas
Acid G
C1 36 Phase Gas
C1 37 Operating Pressure 17 psig
C1 38 Design Pressure 100 psig
C1 39 Operating Temperature 120 ºF
C1 40 Design Temperature 150 ºF
PROCESS DATA
C1 41 Max. Diff. Pressure for Actuator Size 100 psig
C1 42
C1 43 Line Size and Sch. Inlet Outlet 24 in Sch. 10 24 in Sch. 10
C1 44 Speed of Operation Design VTA
C1 45 (Seconds) Actual VTA
C1 46
Notes
1. VTA : Vendor to advice
2. Actuated ball valve and actuator shall be provided with 316 SS nameplate engraved or die stamped with Valve Tag No., Manufacturer's Name,
Model No., Valve Size & Rating.
3. Vendor shall be responsible for the proper design and selection of valve, actuator, and accessories based on the information furnished
C1 in this specification. This Data Sheet shall refer to SNO-I-ES-013, Instrument Specification for Shutdown and Blowdown Valve
4. Actuator shall be sized based on valve manufacturer's required Torque values with 130% minimum safety margin to open or close the valve
against full ANSI rated differential pressure at minimum pneumatic supply pressure of 60 psig.
5. Vendor shall provide Torque table containing breaking, running and seating torques for valves and actuator along with Quotation.
Vendor shall provide the torque table and calculation for COMPANY approval.
6. Actuator and accessories shall be supplied fully assembled, tubed and tested ready for installation.
7. Solenoid valve coil shall be provided with reverse polarity protection diodes, integral outlet box and terminal strip for cable connection.
8. Three way valve shall be universal type. Solenoid Coil shall be Class H.
Air filter regulator shall be 316 SS Material and equipped with pressure gauge on inlet and outlet of air filter regulator.
C1 9. All SDV & BDV shall be designed & tested as per API 6D
C1 10. Valve Stem Shall be Anti-Blowout Type.

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 110 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
C1 1 Tag No. Quantity SDV-4032 1 (One)
C1 2 Manufacturer Model VTA VTA
C1 3 Contract No. Requisition Item No.
C1 4 Location Central Processing Plant
GENERAL
C1 5 P&ID No. SNO-R-PI-701
C1 6 Service Sour water drain to closed drain header
C1 7 Line No. 2"-SW-0401-1N
C1 8 Area Classification Zone-2, Gr. IIB, T3
C1 9 Valve Type Valve Code Trunnion Mounted Ball BA098
C1 10 Body Size Body Form 2 in Ball
C1 11 Body Material Port Size ASTM A351 CF8M Full Bore
C1 12 Connection Rating RF Flange ASME 150#
C1 13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
C1 14 Packing Lubrication & Isolation Expanded Graphite VTA
C1 15 Bonnet Bolts Bonnet Nuts ASTM A193 B8M CL2 ASTM A194 8M
C1 16 Ball Material Stem Material 316 SS 316 SS
C1 17 Leakage Rate Seat Material ISO 5028 Rate A (TSO) PTFE
C1 18 NACE Requirement Yes
C1 19 Type Stroking Time Pneumatic Piston / Spring return 4 Seconds
C1 20 Size Safety Factor VTA in 1.3
C1 21 Actuator Orientation Actuator Form Horizontal Cylinder
C1 22 Ingress Protection Electrical Protection IP65 Eex i
C1 23 Instrument Air Supply 80-120 Psig
C1 24 Action on Air Failure Action on Power Failure Closed Closed
ACTUATOR C1 25 Fireproofing No
C1 26 Solenoid Valve Schematic Detail Yes Type 1
C1 27 Limit Switch Closed Limit Swich Open Yes Yes
C1 28 Mounting Position Solenoid Power Supply Top 24VDC
C1 29 Manual Reset No
C1 30 Mechanical Position Indicator Red Closed / Green Open
C1 31 Partial Stroke Facility No
C1 31 Signal Cable 1/2" NPT
ELECTRICAL C1 32 Control Cable -
CONNECTIONS C1 33 Solenoid Cable 3/4" NPT
C1 34
Fl id
C1 35 Fluid S
Sour t
water
C1 36 Phase Liquid
C1 37 Operating Pressure 17 psig
C1 38 Design Pressure 100 psig
C1 39 Operating Temperature 120 ºF
C1 40 Design Temperature 150 ºF
PROCESS DATA
C1 41 Max. Diff. Pressure for Actuator Size 100 psig
C1 42
C1 43 Line Size and Sch. Inlet Outlet 2 in Sch. 10S 2 in Sch. 10S
C1 44 Speed of Operation Design VTA
C1 45 (Seconds) Actual VTA
C1 46
Notes
1. VTA : Vendor to advice
2. Actuated ball valve and actuator shall be provided with 316 SS nameplate engraved or die stamped with Valve Tag No., Manufacturer's Name,
Model No., Valve Size & Rating.
3. Vendor shall be responsible for the proper design and selection of valve, actuator, and accessories based on the information furnished
C1 in this specification. This Data Sheet shall refer to SNO-I-ES-013, Instrument Specification for Shutdown and Blowdown Valve
4. Actuator shall be sized based on valve manufacturer's required Torque values with 130% minimum safety margin to open or close the valve
against full ANSI rated differential pressure at minimum pneumatic supply pressure of 60 psig.
5. Vendor shall provide Torque table containing breaking, running and seating torques for valves and actuator along with Quotation.
Vendor shall provide the torque table and calculation for COMPANY approval.
6. Actuator and accessories shall be supplied fully assembled, tubed and tested ready for installation.
7. Solenoid valve coil shall be provided with reverse polarity protection diodes, integral outlet box and terminal strip for cable connection.
8. Three way valve shall be universal type. Solenoid Coil shall be Class H.
Air filter regulator shall be 316 SS Material and equipped with pressure gauge on inlet and outlet of air filter regulator.
C1 9. All SDV & BDV shall be designed & tested as per API 6D
C1 10. Valve Stem Shall be Anti-Blowout Type.

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 111 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
C1 1 Tag No. Quantity SDV-4033
C1 2 Manufacturer Model VTA VTA
C1 3 Contract No. Requisition Item No.
C1 4 Location Central Processing Plant
GENERAL
C1 5 P&ID No. SNO-R-PI-701
C1 6 Service Hydrocarbon drain to closed drain header
C1 7 Line No. 2"-DC-0402-3N
C1 8 Area Classification Zone-2, Gr. IIB, T3
C1 9 Valve Type Valve Code Trunnion Mounted Ball BA146
C1 10 Body Size Body Form 2 in Ball
C1 11 Body Material Port Size ASTM A351 CF8M Full Bore
C1 12 Connection Rating RF Flange ASME 300#
C1 13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
C1 14 Packing Lubrication & Isolation Expanded Graphite VTA
C1 15 Bonnet Bolts Bonnet Nuts ASTM A193 B8M CL2 ASTM A194 8M
C1 16 Ball Material Stem Material 316 SS 316 SS
C1 17 Leakage Rate Seat Material ISO 5028 Rate A (TSO) PTFE
C1 18 NACE Requirement Yes
C1 19 Type Stroking Time Pneumatic Piston / Spring return 4 Seconds
C1 20 Size Safety Factor VTA in 1.3
C1 21 Actuator Orientation Actuator Form Horizontal Cylinder
C1 22 Ingress Protection Electrical Protection IP65 Eex i
C1 23 Instrument Air Supply 80-120 Psig
C1 24 Action on Air Failure Action on Power Failure Closed Closed
ACTUATOR C1 25 Fireproofing No
C1 26 Solenoid Valve Schematic Detail Yes Type-1
C1 27 Limit Switch Closed Limit Swich Open Yes Yes
C1 28 Mounting Position Solenoid Power Supply Top 24VDC
C1 29 Manual Reset No
C1 30 Mechanical Position Indicator Red Closed / Green Open
C1 31 Partial Stroke Facility No
C1 31 Signal Cable 1/2" NPT
ELECTRICAL C1 32 Control Cable -
CONNECTIONS C1 33 Solenoid Cable 3/4" NPT
C1 34
Fl id
C1 35 Fluid H d b
Hydrocarbon
C1 36 Phase Liquid
C1 37 Operating Pressure 115 psig
C1 38 Design Pressure 210 psig
C1 39 Operating Temperature 107 ºF
C1 40 Design Temperature 220 ºF
PROCESS DATA
C1 41 Max. Diff. Pressure for Actuator Size 210 psig
C1 42
C1 43 Line Size and Sch. Inlet Outlet 2 in Sch. 40S 2 in Sch. 40S
C1 44 Speed of Operation Design VTA
C1 45 (Seconds) Actual VTA
C1 46
Notes
1. VTA : Vendor to advice
2. Actuated ball valve and actuator shall be provided with 316 SS nameplate engraved or die stamped with Valve Tag No., Manufacturer's Name,
Model No., Valve Size & Rating.
3. Vendor shall be responsible for the proper design and selection of valve, actuator, and accessories based on the information furnished
C1 in this specification. This Data Sheet shall refer to SNO-I-ES-013, Instrument Specification for Shutdown and Blowdown Valve
4. Actuator shall be sized based on valve manufacturer's required Torque values with 130% minimum safety margin to open or close the valve
against full ANSI rated differential pressure at minimum pneumatic supply pressure of 60 psig.
5. Vendor shall provide Torque table containing breaking, running and seating torques for valves and actuator along with Quotation.
Vendor shall provide the torque table and calculation for COMPANY approval.
6. Actuator and accessories shall be supplied fully assembled, tubed and tested ready for installation.
7. Solenoid valve coil shall be provided with reverse polarity protection diodes, integral outlet box and terminal strip for cable connection.
8. Three way valve shall be universal type. Solenoid Coil shall be Class H.
Air filter regulator shall be 316 SS Material and equipped with pressure gauge on inlet and outlet of air filter regulator.
C1 9. All SDV & BDV shall be designed & tested as per API 6D
C1 10. Valve Stem Shall be Anti-Blowout Type.

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 112 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
C1 1 Tag No. Quantity SDV-4015B 1 (One)
C1 2 Manufacturer Model VTA VTA
C1 3 Contract No. Requisition Item No.
C1 4 Location Central Processing Plant
GENERAL
C1 5 P&ID No. SNO-R-PI-706
C1 6 Service Utility air to WSA Condenser
C1 7 Line No. 2"-UA-0026-1C
C1 8 Area Classification Zone-2, Gr. IIB, T3
C1 9 Valve Type Valve Code Trunnion Mounted Ball BA313
C1 10 Body Size Body Form 2 in Ball
C1 11 Body Material Port Size ASTM A352 LCC Full Bore
C1 12 Connection Rating RF Flanged ASME 150#
C1 13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
C1 14 Packing Lubrication & Isolation Expanded Graphite VTA
C1 15 Bonnet Bolts Bonnet Nuts ASTM A320 Gr L7 ASTM A194 Gr 4
C1 16 Ball Material Stem Material 316 SS 316 SS
C1 17 Leakage Rate Seat Material ISO 5028 Rate A PTFE
C1 18 NACE Requirement No
C1 19 Type Stroking Time Pneumatic Piston / Spring return 4 Seconds
C1 20 Size Safety Factor VTA in 1.3
C1 21 Actuator Orientation Actuator Form Horizontal Cylinder
C1 22 Ingress Protection Electrical Protection IP65 Eex i
C1 23 Instrument Air Supply 80-120 Psig
C1 24 Action on Air Failure Action on Power Failure Closed Closed
ACTUATOR C1 25 Fireproofing No
C1 26 Solenoid Valve Schematic Detail Yes Type-1
C1 27 Limit Switch Closed Limit Swich Open Yes Yes
C1 28 Mounting Position Solenoid Power Supply Top 24VDC
C1 29 Manual Reset No
C1 30 Mechanical Position Indicator Red Closed / Green Open
C1 31 Partial Stroke Facility No
C1 31 Signal Cable 1/2" NPT
ELECTRICAL C1 32 Control Cable -
CONNECTIONS C1 33 Solenoid Cable 3/4" NPT
C1 34
Fl id
C1 35 Fluid Utilit Air
Utility Ai
C1 36 Phase Gas
C1 37 Operating Pressure 105 psig
C1 38 Design Pressure 200 psig
C1 39 Operating Temperature 90 ºF
C1 40 Design Temperature 200 ºF
PROCESS DATA
C1 41 Max. Diff. Pressure for Actuator Size 200 psig
C1 42
C1 43 Line Size and Sch. Inlet Outlet 2 in Sch. 80 2 in Sch. 80
C1 44 Speed of Operation Design VTA
C1 45 (Seconds) Actual VTA
C1 46
Notes
1. VTA : Vendor to advice
2. Actuated ball valve and actuator shall be provided with 316 SS nameplate engraved or die stamped with Valve Tag No., Manufacturer's Name,
Model No., Valve Size & Rating.
3. Vendor shall be responsible for the proper design and selection of valve, actuator, and accessories based on the information furnished
C1 in this specification. This Data Sheet shall refer to SNO-I-ES-013, Instrument Specification for Shutdown and Blowdown Valve
4. Actuator shall be sized based on valve manufacturer's required Torque values with 130% minimum safety margin to open or close the valve
against full ANSI rated differential pressure at minimum pneumatic supply pressure of 60 psig.
5. Vendor shall provide Torque table containing breaking, running and seating torques for valves and actuator along with Quotation.
Vendor shall provide the torque table and calculation for COMPANY approval.
6. Actuator and accessories shall be supplied fully assembled, tubed and tested ready for installation.
7. Solenoid valve coil shall be provided with reverse polarity protection diodes, integral outlet box and terminal strip for cable connection.
8. Three way valve shall be universal type. Solenoid Coil shall be Class H.
Air filter regulator shall be 316 SS Material and equipped with pressure gauge on inlet and outlet of air filter regulator.
C1 9. All SDV & BDV shall be designed & tested as per API 6D
C1 10. Valve Stem Shall be Anti-Blowout Type.

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 113 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
C1 1 Tag No. Quantity SDV-4035 1 (One)
C1 2 Manufacturer Model VTA VTA
C1 3 Contract No. Requisition Item No.
C1 4 Location Central Processing Plant
GENERAL
C1 5 P&ID No. SNO-R-PI-714
C1 6 Service BFW to BFW preheater
C1 7 Line No. 4"-BF-0406-6A
C1 8 Area Classification Zone-2, Gr. IIB, T3
C1 9 Valve Type Valve Code Trunnion Mounted Ball BA013
C1 10 Body Size Body Form 4 in Ball
C1 11 Body Material Port Size ASTM A216 WCB Full Bore
C1 12 Connection Rating RF Flange ASME 600#
C1 13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
C1 14 Packing Lubrication & Isolation Expanded Graphite VTA
C1 15 Bonnet Bolts Bonnet Nuts ASTM A193 B7 ASTM A194 2H
C1 16 Ball Material Stem Material CS+ENP 76μm A564 630, H1150M+ENP 76 μm
C1 17 Leakage Rate Seat Material ISO 5028 Rate D Metal
C1 18 NACE Requirement No
C1 19 Type Stroking Time Pneumatic Piston / Spring return 8 Seconds
C1 20 Size Safety Factor VTA in 1.3
C1 21 Actuator Orientation Actuator Form Horizontal Cylinder
C1 22 Ingress Protection Electrical Protection IP65 Eex i
C1 23 Instrument Air Supply 80-120 Psig
C1 24 Action on Air Failure Action on Power Failure Closed Closed
ACTUATOR C1 25 Fireproofing No
C1 26 Solenoid Valve Schematic Detail Yes Type-1
C1 27 Limit Switch Closed Limit Swich Open Yes Yes
C1 28 Mounting Position Solenoid Power Supply Top 24VDC
C1 29 Manual Reset No
C1 30 Mechanical Position Indicator Red Closed / Green Open
C1 31 Partial Stroke Facility No
C1 31 Signal Cable 1/2" NPT
ELECTRICAL C1 32 Control Cable -
CONNECTIONS C1 33 Solenoid Cable 3/4" NPT
C1 34
Fl id
C1 35 Fluid B il Feed
Boiler F d Water
W t
C1 36 Phase Liquid
C1 37 Operating Pressure 480.4 psig
C1 38 Design Pressure 728 psig
C1 39 Operating Temperature 225 ºF
C1 40 Design Temperature 480 ºF
PROCESS DATA
C1 41 Max. Diff. Pressure for Actuator Size 728 psig
C1 42
C1 43 Line Size and Sch. Inlet Outlet 4 in Sch. 120 4 in Sch. 120
C1 44 Speed of Operation Design VTA
C1 45 (Seconds) Actual VTA
C1 46
Notes
1. VTA : Vendor to advice
2. Actuated ball valve and actuator shall be provided with 316 SS nameplate engraved or die stamped with Valve Tag No., Manufacturer's Name,
Model No., Valve Size & Rating.
3. Vendor shall be responsible for the proper design and selection of valve, actuator, and accessories based on the information furnished
C1 in this specification. This Data Sheet shall refer to SNO-I-ES-013, Instrument Specification for Shutdown and Blowdown Valve
4. Actuator shall be sized based on valve manufacturer's required Torque values with 130% minimum safety margin to open or close the valve
against full ANSI rated differential pressure at minimum pneumatic supply pressure of 60 psig.
5. Vendor shall provide Torque table containing breaking, running and seating torques for valves and actuator along with Quotation.
Vendor shall provide the torque table and calculation for COMPANY approval.
6. Actuator and accessories shall be supplied fully assembled, tubed and tested ready for installation.
7. Solenoid valve coil shall be provided with reverse polarity protection diodes, integral outlet box and terminal strip for cable connection.
8. Three way valve shall be universal type. Solenoid Coil shall be Class H.
Air filter regulator shall be 316 SS Material and equipped with pressure gauge on inlet and outlet of air filter regulator.
C1 9. All SDV & BDV shall be designed & tested as per API 6D
C1 10. Valve Stem Shall be Anti-Blowout Type.

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 114 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1
C1 1 Tag No. Quantity SDV-4013A 1 (One)
C1 2 Manufacturer Model VTA VTA
C1 3 Contract No. Requisition Item No.
C1 4 Location Central Processing Plant
GENERAL
C1 5 P&ID No. SNO-R-PI-704
C1 6 Service Steam to STG
C1 7 Line No. 12"-HS-0408-6K1
C1 8 Area Classification
C1 9 Valve Type Valve Code Trunnion Mounted Ball -
C1 10 Body Size Body Form 12" in Ball
C1 11 Body Material Port Size A217 WC6 Full Bore
C1 12 Connection Rating RF Flanged ASME 600#
C1 13 Fire Safe Design Anti Static API 6FA Yes, as per API 6D
VALVE BODY
C1 14 Packing Lubrication & Isolation Expanded Graphite VTA
C1 15 Bonnet Bolts Bonnet Nuts ASTM A193-B16 ASTM A194-4
C1 16 Ball Material Stem Material 316SS 316SS
C1 17 Leakage Rate Seat Material ISO 5028 Rate D Metal
C1 18 NACE Requirement No
C1 19 Type Stroking Time Pneumatic Piston / Spring return 15 Seconds
C1 20 Size Safety Factor VTA in 1.3
C1 21 Actuator Orientation Actuator Form Horizontal Cylinder
C1 22 Ingress Protection Electrical Protection IP65 Eex i
C1 23 Instrument Air Supply 80-120 Psig
C1 24 Action on Air Failure Action on Power Failure Closed Closed
ACTUATOR C1 25 Fireproofing No
C1 26 Solenoid Valve Schematic Detail Yes Type-1
C1 27 Limit Switch Closed Limit Swich Open Yes Yes
C1 28 Mounting Position Solenoid Power Supply Top 24VDC
C1 29 Manual Reset No
C1 30 Mechanical Position Indicator Red Closed / Green Open
C1 31 Partial Stroke Facility No
C1 31 Signal Cable 1/2" NPT
ELECTRICAL C1 32 Control Cable -
CONNECTIONS C1 33 Solenoid Cable 3/4" NPT
C1 34
Fl id
C1 35 Fluid St
Steam
C1 36 Phase Gas
C1 37 Operating Pressure 415.1 psig
C1 38 Design Pressure 520 psig
C1 39 Operating Temperature 842 ºF
C1 40 Design Temperature 900 ºF
PROCESS DATA
C1 41 Max. Diff. Pressure for Actuator Size 520 psig
C1 42
C1 43 Line Size and Sch. Inlet Outlet 12" in Sch. 100 12" in Sch. 100
C1 44 Speed of Operation Design VTA
C1 45 (Seconds) Actual VTA
C1 46
Notes
1. VTA : Vendor to advice
2. Actuated ball valve and actuator shall be provided with 316 SS nameplate engraved or die stamped with Valve Tag No., Manufacturer's Name,
Model No., Valve Size & Rating.
3. Vendor shall be responsible for the proper design and selection of valve, actuator, and accessories based on the information furnished
C1 in this specification. This Data Sheet shall refer to SNO-I-ES-013, Instrument Specification for Shutdown and Blowdown Valve
4. Actuator shall be sized based on valve manufacturer's required Torque values with 130% minimum safety margin to open or close the valve
against full ANSI rated differential pressure at minimum pneumatic supply pressure of 60 psig.
5. Vendor shall provide Torque table containing breaking, running and seating torques for valves and actuator along with Quotation.
Vendor shall provide the torque table and calculation for COMPANY approval.
6. Actuator and accessories shall be supplied fully assembled, tubed and tested ready for installation.
7. Solenoid valve coil shall be provided with reverse polarity protection diodes, integral outlet box and terminal strip for cable connection.
8. Three way valve shall be universal type. Solenoid Coil shall be Class H.
Air filter regulator shall be 316 SS Material and equipped with pressure gauge on inlet and outlet of air filter regulator.
C1 9. All SDV & BDV shall be designed & tested as per API 6D
C1 10. Valve Stem Shall be Anti-Blowout Type.

INSTRUMENT DATA SHEET


FOR
C1 23-May-13 SYL Approved for Construction SHUTDOWN AND BLOWDOWN
C 12-Apr-13 SYL Approved for Construction VALVES
B 28-Jan-13 HDY Issue for Approval Sheet 115 of 115
REV DATE BY DESCRIPTION Doc. No. : SNO-I-DS-001 Rev. : C1