User's Manual: Sinexcel AHF One-Set and Multi-Set System (25 600A)
User's Manual: Sinexcel AHF One-Set and Multi-Set System (25 600A)
Version: V2.0
Filed date: Aug-21-2012
BOM No.: A81150060
Sinexcel Electric Co., Ltd. provides full technical supports for clients. Users may contact the local agent or customer
service center of the company, or the headquarters directly for help.
Module Description
Sinexcel AHF module rating: Sinexcel XXX AHF 4 3L/R L
25A/35A/50A/60A/75A/100A L:LCD
R:Rack mounting
H:Wall mounting
Notices
Please describe the installation method (racking or wall-mounting) when ordering Sinexcel AHF!
Safety Precautions
This manual describes the installation and operation methods of Sinexcel AHF.
Please read the manual carefully before installation.
The commissioning and maintenance of Sinexcel AHF shall be conducted by engineer(s) appointed by the manufacturer or the agent,
otherwise personal injury and device damages might be caused; the maker shall not be responsible for such kinds of damages.
Sinexcel AHF is only for commercial/industrial use, it can’t be used as energy-saving equipment related with any life-support
devices.
The product is grade A AHF equipment. Wireless disturbance might be caused when it is used as energy-saving equipment, thus
additional measures are required in this condition.
Normative References
This equipment meets CE 73/23 & 93/68 (low voltage safety) , 89/336 (EMC), and the EMC standards (C-Tick) of Austrilia and New Zealand:
This AHF fully meets the equipment’s safety standards in working zone. There is dangerous voltage with AHF but that only maintenance personnel
can access. As the components with dangerous voltage has protective cap which must be opened by tools, thus the possibility of touching dangerous
high voltage is very small. There is no any danger when you operate the equipment according to relevant regulations and the procedures specifed in
the manual.
1.1 Introduction
In this chapter, we shall introduce Sinexcel AHF and the requirements of position selection and wiring of related equipments.
As different sites have different conditions, only the general installation procedures and methods shall be introduced for installation
personnel. Please install the device according to the actual conditions of the site.
It is not allowed to electrify the AHF unless getting the consent of the engineer after commissioning.
AHF shall be installed according to the manual by qualified engineer(s). The specifications and installation instructions of other devices shall be
provided when delivery.
Standard Sinexcel AHF system can be connected with three-phase four-wire (earthing) TN, TT, IT AC distribution system (IEC60364-3) and
three-phase four-wire system . For IT AC distribution system, a 4-polar breaker is needed for input, see relevant IT system standards for details.
Notices
If wall-mounting mode is selected, 150mm must be kept at least for air ventilation between the air inlet/outlet and the wall!
If standard rack mounting mode is selected, please select the rack that the air can flow through both of the front and back doors.
If necessary, the indoor ventilating fan should be installed to avoid room temperature increasing. And air strainer is needed if there is too
much dust in the air.
Note: Sinexcel AHF can only be installed on the surface of concrete or other nonflammable materials. Three installation methods are
available including rack mounting installation, flat mounting installation and wall mounting installation.
2 Chapter I One-Set System Installation
1.3.2 Storage
If it is unnecessary to install Sinexcel AHF immediately, it shall be stored in the house and avoid high humidity and high temperature
(see table 8-2).
1.4 Positioning
Module design is adopted for the case of Sinexcel AHF, which is convenient to the positioning and transport of the equipment.
To prolong the service life, the location of Sinexcel AHF shall meet following requirements:
Easy to connect wires;
Enough operating space;
Good ventilation to satisfy the heat emission requirement;
No corrosive gas in the air;
No devices of producing high humidity and high temperature;
Not dusty environment;
Satisfy fire control requirement;
Working temperature: -5℃—+45℃.
Open the upper cover of Sinexcel AHF, you may see power supply terminals and CT input wiring terminals. The control panel in the
front of AHF is equipped to display the basic operating states and warning information. For rack mounting installation, the air inlet is in
the front and the air outlet is at the back of the equipment; for wall-mounting installation, air inlet is at the lower and the air outlet is at
the upper.
As a modular design, in 25 A / 35 A AHF,the height is 200 mm and width is 260 mm. It is very flexible to install with the small
dimensions and light weight. In 50 A / 60 A AHF, the height is 200 mm, and in 75 A / 100 A AHF, the height is 232 mm. In both of them,
the width are standard 19 inches cabinet size, so the AHF can be chose to install in the 19 inches cabinet shared with the other equipment.
It can also be placed in other cooling cabinet equipment above, in order to save a space, recommend direct articulated near the wall of the
load.
Warning
As each Sinexcel AHF module is about 16kg~40kg, two persons are enough for short-distance transport; but for long-distance transport, the transport
equipments shall be needed.
Make sure that the weight of Sinexcel AHF is within the loading capacity of small transport equipment, see table 8-5
Small trailer or other similar transport equipment can be used to transport Sinexcel AHF.
Back Cable-in method and upper Cable-in method are provided, the selection of Cable-in method is decided by the installation method of
AHF.
During wiring, remove the upper cover to access to the Cable-in hole and connection terminals.
Notice
For IT electric-net system, four-polar protector is needed to be installed for external input distribution and external output distribution of Sinexcel AHF.
To avoid wrong warning when the earth leakage current tester is used in the Multi-Set system, the earth leakage current tester shall be
installed on the previous input distribution terminal.
The filter RFI inside AHF shall have an earth leakage current within the value range from 3.5mA to 300mA. Please confirm the
sensitivity of each differential of previous input distribution and next distribution (to load).
Warning
Before the wiring of Sinexcel AHF, please make sure you clearly know the position and state of the switches connecting AHF’s input power and electric
supply distribution.
Make sure these switches are in off state, and affix warning labels to avoid other people’s operations to these swithes.
A/B/C/PE M6 6 4 M8 8 6
N M6 6 4 M8 8 6
Note:
1. The current of neutral cable may exceed rated current, generally it’s 1.732 times of the rated current, and the system shall be designed
by 3 times of the rated current.
2. Protective earth wire: When connecting the cabinet and the main earth system, the shortest length wiring method should be adopted.
Earth wire should be selected with available cross sectional area according to power failure class, cable length and protective type.
According to AS / IEC 60950-1, 16mm2 is advised.
3. See Chapter III Installation Diagram for positions of connection terminals.
Warning
Violation of earth requirements might cause electromagnetic interference, electric shock and fire.
Table 1-2 Distance between Joint Point of Equipement and the Floor
AHF Sinexcel AHF Minimum Distance (mm)
Input Terminal 284
Important
The operations stated in this section must be conducted by authorized persons. Please contact the customer service department of our company if there
is any problem.
After final positioning of the equipment, please refer to the wiring diagram in Chapter III to connect the power cables as per the
following steps:
1. Confirm that all the distribution switches of Sinexcel AHF are turned off, and affix warning labels beside these switches to avoid other
people’s operations.
2. Open the upper cover of Sinexcel AHF to access to the terminal base connecting power cable.
3. Connect the protective earth and other earth cables to the earth connection point PE of Sinexcel AHF (PE is on the same PCBA with
connection base of input cable). All the AHF cabinets shall be earthed).
Note: the wiring of earth wire and central wire must meet related local and national regulations.
4. Mark and connect the input cables according to installation type.
Warning
If the AHF hasn’t been installed when the debugging engineer arrives, please make safe insulation to the power cables that are used t connect to the
AHF.
2.1 Introduction
Please install Multi-Set system according to the installation steps of one-set system and the requirements hereunder.
Figure 2-2 and 2-3 describe the installation diagram of rack mounting AHF parallel connection in cabinets, including 6 units of Sinexcel
050 AHF (total capacity of 300A) or 6 units of Sinexcel 100 AHF (total capacity of 600A). Figure 2-4 describes the installation diagram
of units of wall mounting AHF parallel connection.
6 Chapter II Multi-Set System Installation
Figure 2-2 Installation Diagram of rack mounting Figure 2-3 Installation Diagram of rack mounting
AHF parallel connection ( 6 units of 50A) AHF parallel connection ( 6 units of 100A)
2. It’s easy to control the wire connection, which contributes to the reliability improvement of the system and convenience for
maintenance on site.
3. The user can read the total loads of the Multi-Set system through the LCD of each one-set.
3.1 Introduction
In this chapter we shall mainly introduce the installation size of Sinexcel AHF series so as to provide convenience for the user to fix and
install.
To satisfy the requirements of different users, two kinds of different appearance designs are provided, including Racking module with
LCD and wall-mount module with LCD.
In Figure 3-1, Racking with LCD of Sinexcel 025/035 AHF’s size and installation position are described; the user may design fixing
holes and install the equipment according to the sizes in the Figure. The 3D view is shown in Figure 3-5.
260
200
89
40
455
486
Figure 3-1 Racking with LCD of Sinexcel 025/035 AHF’s Size and Installation Diagram
In Figure 3-2, Racking module with LCD of Sinexcel 050/060 AHF’s size and installation position are described; the user may design
fixing holes and install the equipment according to the sizes in the Figure. The 3D view is shown in Figure 3-6.
Chapter III Installation Diagram 9
Figure 3-2 Racking with LCD of Sinexcel 050/060 AHF’s Size and Installation Diagram
In Figure 3-3, Racking module with LCD of Sinexcel 075 AHF’s size and installation position are described; the user may design fixing
holes and install the equipment according to the sizes in the Figure. The 3D view is shown in Figure 3-7.
484
466
R3,5 440
89 232
71,5
575
606
Figure 3-3 Racking with LCD of Sinexcel 075 AHF’s Size and Installation Diagram
In Figure 3-4, Racking module with LCD of Sinexcel 100 AHF’s size and installation position are described; the user may design fixing
holes and install the equipment according to the sizes in the Figure. The 3D view is shown in Figure 3-8.
10 Chapter III Installation Diagram
484
466
R3,5 440
89 232
71,5
575
606
Figure 3-4 Racking with LCD of Sinexcel 100 AHF’s Size and Installation Diagram
Figure 3-5 Racking with LCD of Sinexcel 025/035 AHF’s 3D view Figure 3-6 Racking with LCD of Sinexcel 050/060 AHF’s 3D
view
Chapter III Installation Diagram 11
Figure 3-7 Racking with LCD of Sinexcel 075 AHF’s 3D view Figure 3-8 Racking with LCD of Sinexcel 100 AHF’s 3D view
In Figure 3-9, Wall-mount module with LCD of Sinexcel 025/035 AHF’s size and installation position are described; the user may
design fixing holes and install the equipment according to the sizes in the Figure. The 3D view is shown in Figure 3-13.
260
200
436 460
180
Figure 3-9 Wall-mount with LCD of Sinexcel 025/035 AHF’s Size and Installation Diagram
In Figure 3-10, Wall-mount module with LCD of Sinexcel 050/060 AHF’s size and installation position are described; the user may
design fixing holes and install the equipment according to the sizes in the Figure. The 3D view is shown in Figure 3-14.
12 Chapter III Installation Diagram
Figure 3-10 Wall-mount with LCD of Sinexcel 050/060 AHF’s Size and Installation Diagram
In Figure 3-11, Wall-mount module with LCD of Sinexcel 075 AHF’s size and installation position are described; the user may design
fixing holes and install the equipment according to the sizes in the Figure. The 3D view is shown in Figure 3-15.
440
232 235
601 625
360
Figure 3-11 Wall-mount with LCD of Sinexcel 075 AHF’s Size and Installation Diagram
Chapter III Installation Diagram 13
In Figure 3-12, Wall-mount module with LCD of Sinexcel 100 AHF’s size and installation position are described; the user may design
fixing holes and install the equipment according to the sizes in the Figure. The 3D view is shown in Figure 3-16.
440
232 235
601
625
360
Figure 3-12 Wall-mount with LCD of Sinexcel 100 AHF’s Size and Installation Diagram
Figure 3-13 Wall-mount Sinexcel 025/035 AHF’s 3D view Figure 3-14 Wall-mount Sinexcel 050/060 AHF’s 3D view
14 Chapter III Installation Diagram
Figure 3-15 Wall-mount Sinexcel 075 AHF’s 3D view Figure 3-16 Wall-mount Sinexcel 100 AHF’s 3D view
Figure 3-17 and 3-18 are Sinexcel 025/035 AHF’s wiring diagrams, from which we can see the positions of terminals of power cable and
CT cable.
CT_C
CT_C CT_B
CT_B CT_A
CT_A
CT_C_GND
CT_C_GND
CT_B_GND
CT_B_GND
CT_A_GND
CT_A_GND
PE
PE NN
NN CB
CB A
A
Figure 3-17 Racking Sinexcel 025/035 AHF’s wiring diagram Figure 3-18 Wall-mount Sinexcel 025/035 AHF’s wiring diagram
Figure 3-19 and 3-20 are Sinexcel 025/035 AHF’s wiring diagrams, from which we can see the positions of terminals of power cable and
CT cable.
CT_C
CT_B
CT_C CT_A
CT_B
CT_A
CT_A_GND
CT_C_GND CT_A_GND
CT_B_GND CT_A_GND
CT_A_GND PE
PE N
N C
C B
B A
A
Figure 3-19 Racking Sinexcel 050/060 AHF’s wiring diagram Figure 3-20 Wall-mount Sinexcel 050/060 AHF’s wiring diagram
Figure 3-21 and 3-22 are Sinexcel 075 AHF’s wiring diagrams, from which we can see the positions of terminals of power cable and CT
Chapter III Installation Diagram 15
cable.
CT_C
CT_C
CT_B CT_B
CT_A CT_A
CT_C_GND
CT_C_GND
CT_B_GND
CT_B_GND
CT_A_GND
CT_A_GND
PE PE
N N
C C
B
B A
A
Figure 3-21 Racking Sinexcel 075 AHF’s wiring diagram Figure 3-22 Wall-mount Sinexcel 075 AHF’s wiring diagram
Figure 3-23 and 3-24 are Sinexcel 100 AHF’s wiring diagrams, from which we can see the positions of terminals of power cable and CT
cable.
CT_C CT_C
CT_B CT_B
CT_A CT_A
CT_C_GND
CT_C_GND
CT_B_GND
CT_B_GND
CT_A_GND
CT_A_GND
PE PE
N N
C
C B
B
A A
Figure 3-23 Racking Sinexcel 100 AHF’s wiring diagram Figure 3-24 Wall-mount Sinexcel 100 AHF’s wiring diagram
16 Chapter IV Running and Operating Steps
Sinexcel AHF has six main wiring terminals with outside; refer to 3.1.3 System Wiring Terminal for details.
Input A—A phase input terminal
Input B—B phase input terminal
Input C—C phase input terminal
N—Neutral input terminal
PE—system earth terminal, as the housing of the system is metallic, in order to avoid personal accident, please connect the
earth via this terminal before powering on the system.
J14, J15 or J36 or J67, J68 - external CT vice edge terminals, J14, J15 (50A / 60A) or J36 (25A/ 35A) or J67, J68 (75A/ 100A)
terminal from the outside joint in maximum allowable current for 5A
J14, J15 or J36 or J67, J68 has six wiring positions in total and refer to table 4-1 for details:
Table 4-1 External CT terminal corresponding table
Warning
AHF output terminal shall be electrified when powering on AHF.
If the load is connected to AHF output terminal, please confirm whether it’s safe to electrify the load. If the load is not ready to be electrified, DO keep
the load away from AHF output terminal.
2. Close the disconnecting switch which disconnecting the power supply and AHF
The LCD screen will be light and the LED indicator light flickers in green color by doing so. And about 20 seconds later, the indicator
light will be green in steady. If there are faults in equipment, the LED indicator will be red, and the AHF cannot be power on.
Warning
In order to avoid personal hurt, if you want to repair or dismantle the housing after powering off, please test the input terminal by the multimeter to
ensure no power inside! It’s advised to open the cover five minutes later after powering off.
5.1 Introduction
This chapter mainly introduces the LCD display and setup parameters, the user may operate and control the device through LCD.
LCD user-friendly interface has 320*240 dot matrix display, LCD may give real-time alarm message and provide 500 alarm records for
inquiry that are reliable basis for fault diagnosis.
The user may make operations through LCD panel, view the input/output/load parameters and waves, and get the current working status
and alarm message of Sinexcel AHF. The LCD can also display the version information of system software and monitoring software.
The panel has two functional parts: LCD display and menu/operation keys.
Voltage
Current
Harmonics Analysls
Temperature
Settings
Alarm Events
Power ON/OFF
Normal Alarm
Table 5-1 Sinexcel AHF operation and control panel parts description
Buttons/Indicators Functions
Up Move upwards
Down Move downwards
Enter Confirm key
Esc Cancel key
Normal System is normal
Alarm System fault
Press the Up and Down simultaneously, turn into the Power OFF menu;
Press the Up and Enter simultaneously, the LCD screen will be lighter;
Press the Down and Enter simultaneously, the LCD screen will be darker;
Press the Esc and Enter simultaneously for 10 seconds, turn into the senior parameter settings menu (the function only for special
personnel).
RMS Voltage
L1-Voltage Waveform
L2-Voltage Waveform
L3-Voltage Waveform
We can see the 3-phase grid voltage, frequency as well as the THDU of from the interface as figure 5-2 shown. We can see the phase
voltage information from the menu in figure 5-3 by pressing the Enter button.
Select Current in the main interface to enter the current selection interface as figure 5-4 shown to view the parameters and waveforms,
select Load Current option to enter the corresponding interface as figure 5-5 shown to view the 3-phase current and THDI, if you want to
view the waveforms, select the corresponding phase and then press Enter to view.
In the same way, If we want to view harmonic analysis, please press the Enter button to enter the interface as figure 5-6 shown.
THD Voltage&Current
L1-Harmonic Spectrum
1 5 10 15 20 25 30 35 40 45 50
L2-Harmonic Spectrum
L3-Harmonic Spectrum
From figure5-6, we can view the information about grid voltage THDU, load current THDI and grid current THDI by selecting the
THDI voltage & current. Also we can view the relevant harmonic spectrums by press the Enter button if we want to know the spectrums.
For example, if we want to view the THDI of L1, please select L1 – harmonic spectrum and press the Enter button to enter the interface
20 Chapter V Operation and Control Panel
as 5-7 shown. We can clear know that the comparison of L1 load current THDI of before compensation and after compensation. We can
Select the temperature and press the Enter button to enter the interface as figure 5-8 shown.
Internal Temp.[1]:65℃
Internal Temp.[2]:65℃
Internal Temp.[3]:65℃
Internal Temp.[4]:65℃
Internal Temp.[5]:65℃
Internal Temp.[6]:65℃
From figure 5-8, we can know that there 6 temperature in all. The internal temp.1 to 3 show the temperature of inverters in L1 to L3. The
There are 3 kinds of settings in the system settings as shown in figure 5-9. The user may enter the interface by entering the password, the
people who haven’t password shall not be allowed to enter, only the personnel who are trained by Sinexcel can operate!
In this interface, there are many settings options including system parameters, system display, and system communication. We can enter
each menu by selecting the submenu and pressing the Enter button.
Entering the system display settings interface as the figure 5-10 shown, we can move the cursor by pressing the Up/Down button, then
the cursor is blinking, so the settings will be changed by pressing the Up/Down button, and the press the Enter to finish the settings.
Other settings is no longer to introduce in the section, all the settings shall be saved in the system.
Language:English
Sinexcel Electric Co., Ltd.
The history records shall record all faults in running including the fault types, starting time and ending time, to facilitate the maintenance
personnel to find the fault and make proper maintenance. General the history records are not allowed to be cleared.
Chapter VI Accessaries
Notices
When buying CT, DO check the transformation ratio of CT is allowed by Sinexcel, and check whether the external CT ratio is consistent to the actual
CT ratio, if it’s not, it might cause abnormity or bad effect.
The precision of external current transformer is required higher than 0.2, if lower one is selected, the compensation precision of Sinexcel
might be affected.
Notices
When selecting CT transformation ratio, it’s advised to select according to the load current, as it may make better harmonic compensation to produce
better effect. It is recommended that the input current of CT is 2~4 times to the load current. For example, if the maximum load current is 1000A,
2000:5~4000:5 is the better selection.
External CT is required to select three in 3-phase 4-wire to respectively install on L1, L2 and L3, required to select two in 3-phase 3-wire
to respectively install on L1 and L3.
As an optional part, the user may select split or fix type current transformer, and the split CT is easy to be installed, while fix CT must be
installed in case of power disconnection of customer terminal.
Note: external CT of Sinexcel AHF is advised to be installed at the load side, namely CT is installed between Sinexcel AHF and the load,
in this way, only three CTs can meet the demand, as shown in figure 6-1: refer to table 4-2 for the detailed wiring numbers.
CT
S1
SOURCE LOAD
S2
Sinexcel AHF
There are three ways to choose if the CTs are installed at the load side with the capacitance in the input side of load, as shown in figure
6-2.
Chapter VI Accessaries 25
CT
S1
SOURCE LOAD
S2
CT
S1 S2
Sinexcel AHF
CT
S1
SOURCE
LOAD
S2
Sinexcel AHF
CT
S1
SOURCE
LOAD
S2
Sinexcel AHF
It is suggested that the CTs can be installed at the supply side if the load side is not suitable for the CT installation. Three CTs are
installed on phase A, B and C, as shown in figure 6-3. The arrows direction is the positive direction which should keep the same with the
CT
S1
SOURCE LOAD
S2
Sinexcel AHF
There are two ways to choose if the CTs are installed at the supply side with the capacitance in the input side of load, as shown in figure
6-4.
CT
S1
SOURCE LOAD
S2
Sinexcel AHF
CT
S1
SOURCE LOAD
S2
1
S1 S2 CT
C
Sinexcel AHF
The way to install CTs with the capacitance in the input side of load is shown in figure 6-5.
Chapter VI Accessaries 27
CT
S11
SOURCE LOAD
S22
CT
S1 S2
Sinexcel AHF
The parallel connection of two CTs’ output side is shown in figure 6-6:
S2 S1
Sinexcel AHF
S2 S1
CT
S1
SOURCE LOAD
S2
A CT
S1 S2 B Sinexcel AHF
1#
Sinexcel AHF
C
N#
In the parallel connection system, if the current transformer can be installed between Sinexcel and load, it’s allowed to install two current
transformers that have consistent transformation ratio, one is installed at the power side and the other one is installed at the output
28 Chapter VI Accessaries
terminal of the system. And then connect the two CT output terminals in parallel and install on J14/J15/J36/J67/J78 terminal of Sinexcel,
the installation mode of two CTs is described as figure 6-7 shown, the arrowhead’s direction must be consistent to the arrowhead’s
direction on the housing of CT. and the length of signal cable AB must be equal to AC.
Remark: Load side and supply side are both suitable for single AHF. But in parallel configuration system, only the load side is
suggested.
6.2 CT Cable
In Sinexcel AHF products, CT cable is also an optional part. All of the cables are twisted line, each group comprises six cables: yellow +
black, green + black and red + black.
Notices
Six cables have same length in each group for accurate work of the system.
Each phase of cable is required to use twisted-pair, the shield twisted-pair is better, to avoid the interruption of other signals!
Sinexcel AHF
S1 L1
S1
S2
S1 L2
Sinexcel AHF
S2
S2
Sinexcel AHF S1
S1
S2
S1
Sinexcel AHF S2
S2
The CT cable specification depends on the length. The STP cable RVVSP 2×2.5 should be suggested for Sinexcel AHF while the length
is less than 15m, the RVVSP 2×4 should be suggested for Sinexcel AHF while the length is more than 15m and less than 30m, and
please contact Sinexcel Electric while the length is more than 30m.
When connecting and installing external CT, it’s specified to connect yellow line to L1, green line to L2 and red line to L3. Take yellow
line as example, connect the yellow line to S1 terminal of CT1 and black to S2 terminal of CT1, as the same, connect green line to S1
Chapter VI Accessaries 29
terminal of CT2, black to S2 terminal of CT2, red line to S1 terminal of CT3, and black to S2 terminal of CT3. The connection of
We have marked the CT installation direction in the figures of 6.1, and here we shall further detail the cable-in direction as figure 6-10
shown.
PE
P2
P1
L1
P2
L2
P2
P1 L3
P1
Neutral
When external CT is connected to the system, the terminal of CT auxiliary cable must be shortly connected as figure 6-11 shown, it can’t
be disconnected until the CT auxiliary cables is connected to the corresponding terminal of Sinexcel AHF.
The short circuit device is not provided and the user should buy additionally when connecting CT.
For safety, please assure that the output side of CT in short circuit status and connect to the PE line.
L1
L2
L3
Short-
circuit
Sinexcel AHF
7.1 Introduction
As is known to all, DSP technology is wide use with its high ability in digital processing. Sinexcel AHF background monitoring system
based on the DSP, which can complete the high rate data processing and meet the system real time requirement.
Note:Only one used for serial communication, the other two used for centralized monitoring.
RS485 interface: the optimal serial interface due to the advantage in excellent resistance to noise interference, long transmission distance
and multistation ability
RS485 communication interface was shown in figure 7-2.
Note:PIN3 to RS 485+,Pin 4 to RS 485-,Pin 5 to GND,the AHF is fixed the male head. Sinexcel 025/035 AHF has a serial port of
standard RS485 interface. Sinexcel 050/060 AHF has three serial ports of standard RS485 interface.
Sinexcel AHF monitoring system can realizing data acquisition, real time control and network communication base on TI Company’s
32-bit TMS470 chip, embedded UC/OS - Ⅱ operating system, with all kinds of control program.
Monitoring board is similar to a PC machine by integrating Ethernet interface, supporting the TCP/IP protocol, having its own IP
32 Chapter VII Background monitoring
address. We can monitor and control the status of AHF by input the IP Address through IE browser, because of there is an embedded
Webserver in the AHF.
Ethernet (LAN): Ethernet connection needs switch, setting up the fixed IP address and using connecting cable named twisted pair
(namely network cable).
The expansion board is integrated in the AHF, which provides 1 RJ485 interface, 2 input interfaces and 2 output interfaces. The
expansion is shown in figure 7-3.
Generally, we name the ports from left to right as 1 # ~ 11 #, the specific functions each port is describe as table 7-4 shown:
Table 7-4 the function of expansion board
Port number Terminal interface
1# RJ45 interface
2# 1st output relay normally closed contacts
3# 1st output relay intermediate contact
4# 1st output relay normally open contacts
5# 2nd output relay normally closed contacts
6# 2nd output relay intermediate contact
7# 2nd output relay normally open contacts
8# 1st input positive
9# 1st input negative
10# 2nd input positive
11# 2nd input negative
The output port allows maximum DC current of 8A, the maximum DC voltage of 28 V and maximum AC voltage of 277V.
The input port allows minimum DC voltage of 12V, the maximum DC voltage of 24 V.
8.1 Standards
Sinexcel AHF completely meets the following standards:
Table 8-1 European and Chinese standards
Items Standards
General safety requirements of AHF operating area EN 50178:1997/IEC 50178:1997
EN 61000_6_2(2005)/EN55011,GROUP1,CALSSA
AHF EMC requirements
IEC 61000_6_2(1999)/CISPR11,GROUP1,CLASSA
AHF performance confirmation and test requirements EN 50091-3/IEC 62040-3/AS 62040-3(VFI SS 111)
The standards described in table 8-1 quotes the related articles from IEC and EN in terms of safety (60950), electromagnetic radiation
and immunity to interference (IEC/EN/AS61000 series) and structure (IEC/EN/AS60146 series and 60529)
Note: also can be used in 480V/600V/690V/1000V voltage, need to add a transformer and setting up by software.
Table 8-4 Efficiency, consumption and air exchange
Rate Power Unit Sinexcel 025/035/050/060/075/100 AHF
Power supply mode % >97
Heat exchange and air quantity (ventilation)
Rate Power kVA Sinexcel 025/035/050/060/075/100 AHF
Normal mode (full load) kW Less than 0.45/0.63/0.9/1.08/1.35/1.8
Cooling air requirement L/sec 75/75/151/151/300/300
Appendix
CT cable <15m: RVVSP 2×2.5;15m-30m: RVVSP 2×4; ≥30m: Please contact Sinexcel Electric.
Bulgy screw M8(only for wall mount) M10(only for wall mount)
Remark The cable size should be increased if the cable temperature requirements.
36 INSTALLATION LOG