OSI PI Connector in Factory Talk Vantage Point - Error RPC Invoke Failed - 10400 No Read Access - Secure Object
OSI PI Connector in Factory Talk Vantage Point - Error RPC Invoke Failed - 10400 No Read Access - Secure Object
Question
When Adding OSI PI Connector in Vantage Point Manager displays the following error message
Environment
https://rockwellautomation.custhelp.com/app/answers/detail/a_id/698806 1/3
2/3/2020 698806 - OSI PI Connector in Factory Talk Vantage Point - Error RPC Invoke Failed -10400 No Read Access - Secure Object
Answer
OSIPI Connector requires read-access on the target PI server's PITUNING database table.
Specifically this can be accomplished by giving read access on PITUNING to PIWorld
NOTE: User in the PI-SDK is Connected as PIOperator as opposed to piadmin (as Vantage Point
needs 'NO' Write access to the PI Server) in the VantagePoint Server.
DISCLAIMER
This knowledge base web site is intended to provide general technical information on a particular
subject or subjects and is not an exhaustive treatment of such subjects. Accordingly, the information in
this web site is not intended to constitute application, design, software or other professional
engineering advice or services. Before making any decision or taking any action, which might affect
your equipment, you should consult a qualified professional advisor.
https://rockwellautomation.custhelp.com/app/answers/detail/a_id/698806 2/3
2/3/2020 698806 - OSI PI Connector in Factory Talk Vantage Point - Error RPC Invoke Failed -10400 No Read Access - Secure Object
USERS "AS IS." IN NO EVENT SHALL ROCKWELL BE LIABLE FOR ANY DAMAGES OF ANY KIND INCLUDING
DIRECT, INDIRECT, INCIDENTAL, CONSEQUENTIAL, LOSS PROFIT OR DAMAGE, EVEN IF ROCKWELL
AUTOMATION HAVE BEEN ADVISED ON THE POSSIBILITY OF SUCH DAMAGES.
https://rockwellautomation.custhelp.com/app/answers/detail/a_id/698806 3/3