OSI PI Connector in Factory Talk Vantage Point - Error RPC Invoke Failed - 10400 No Read Access - Secure Object

This document describes an error that occurs when adding an OSI PI Connector in FactoryTalk View SE - "RPC Invoke Failed -10400 No Read Access - Secure Object". The error occurs because the OSIPI Connector requires read access on the PI server's PITUNING database table, which can be resolved by giving the PIWorld user read access to PITUNING. The document provides troubleshooting steps and a screenshot to illustrate the necessary security permissions.

Uploaded by

krishna kiran
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
334 views3 pages

OSI PI Connector in Factory Talk Vantage Point - Error RPC Invoke Failed - 10400 No Read Access - Secure Object

This document describes an error that occurs when adding an OSI PI Connector in FactoryTalk View SE - "RPC Invoke Failed -10400 No Read Access - Secure Object". The error occurs because the OSIPI Connector requires read access on the PI server's PITUNING database table, which can be resolved by giving the PIWorld user read access to PITUNING. The document provides troubleshooting steps and a screenshot to illustrate the necessary security permissions.

Uploaded by

krishna kiran
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

2/3/2020 698806 - OSI PI Connector in Factory Talk Vantage Point - Error RPC Invoke Failed -10400 No Read Access

Read Access - Secure Object

Rockwell Automation Home  Support Center  Search Knowledgebase

OSI PI Connector in Factory Talk Vantage Point - Error RPC Invoke


Failed -10400 No Read Access - Secure Object
698806 | Date Created: 04/17/2015 | Last Updated: 01/12/2018
 Print
Access Level: TechConnect

Question
When Adding OSI PI Connector in Vantage Point Manager displays the following error message

RPC Invoke Failed -10400 No Read Access - Secure Object Error.

The events recorded in the event log are as below:

2015-04-11 21:46:02,022 [5012] ERROR Connector.PICommon.MiddleTier.Connector


Client: c - Unable to read valid FT historian test value for M022-PIMASTER
System.Runtime.InteropServices.COMException (0x8004072A): RPC Invoke
failed[-10400] No Read Access - Secure Object at
PISDK.IPIDispatch.RPCInvoke(String bstrTable, Int32 MajorVer, Int32 MinorVer,
String bstrMethod, Array& parrArgumentListIn, Array& parrArgumentListOut,
PIAsynchStatus asynchStatus) at
DataWorks.MI.Connector.PICommon.MiddleTier.Connector.IsFTHistorian(String
piServerName)

2015-04-11 21:46:02,053 [5012] ERROR Connector.OSIPI.MiddleTier.PlugIn Client:


domain-name\username|::1|::1 - RPC Invoke failed[-10400] No Read Access -
Secure Object

Environment
https://rockwellautomation.custhelp.com/app/answers/detail/a_id/698806 1/3
2/3/2020 698806 - OSI PI Connector in Factory Talk Vantage Point - Error RPC Invoke Failed -10400 No Read Access - Secure Object

Factory Talk Vantage Point ver 6.1 (tested)


Windows Server 2008 R2
PI Server on another computer.

Answer
OSIPI Connector requires read-access on the target PI server's PITUNING database table.
Specifically this can be accomplished by giving read access on PITUNING to PIWorld

NOTE: User in the PI-SDK is Connected as PIOperator as opposed to piadmin (as Vantage Point
needs 'NO' Write access to the PI Server) in the VantagePoint Server.

Below is the screen shot attached.

 
DISCLAIMER
This knowledge base web site is intended to provide general technical information on a particular
subject or subjects and is not an exhaustive treatment of such subjects. Accordingly, the information in
this web site is not intended to constitute application, design, software or other professional
engineering advice or services. Before making any decision or taking any action, which might affect
your equipment, you should consult a qualified professional advisor.

ROCKWELL AUTOMATION DOES NOT WARRANT THE COMPLETENESS, TIMELINESS OR ACCURACY OF


ANY OF THE DATA CONTAINED IN THIS WEB SITE AND MAY MAKE CHANGES THERETO AT ANY TIME IN ITS
SOLE DISCRETION WITHOUT NOTICE. FURTHER, ALL INFORMATION CONVEYED HEREBY IS PROVIDED TO

https://rockwellautomation.custhelp.com/app/answers/detail/a_id/698806 2/3
2/3/2020 698806 - OSI PI Connector in Factory Talk Vantage Point - Error RPC Invoke Failed -10400 No Read Access - Secure Object

USERS "AS IS." IN NO EVENT SHALL ROCKWELL BE LIABLE FOR ANY DAMAGES OF ANY KIND INCLUDING
DIRECT, INDIRECT, INCIDENTAL, CONSEQUENTIAL, LOSS PROFIT OR DAMAGE, EVEN IF ROCKWELL
AUTOMATION HAVE BEEN ADVISED ON THE POSSIBILITY OF SUCH DAMAGES.

ROCKWELL AUTOMATION DISCLAIMS ALL WARRANTIES WHETHER EXPRESSED OR IMPLIED IN


RESPECT OF THE INFORMATION (INCLUDING SOFTWARE) PROVIDED HEREBY, INCLUDING THE IMPLIED
WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE, MERCHANTABILITY, AND NON-
INFRINGEMENT. Note that certain jurisdictions do not countenance the exclusion of implied warranties;
thus, this disclaimer may not apply to you.

https://rockwellautomation.custhelp.com/app/answers/detail/a_id/698806 3/3

You might also like