50TCM - 50Hz: Package Rooftop Units - 50Hz
50TCM - 50Hz: Package Rooftop Units - 50Hz
Quality Assurance
Certificate Reg. No:
04 100 950420
50TCM – 50Hz
Nominal Cooling Capacity 6 – 12.5 Tons
HFC R - 410A Refrigerant
The 50TCM units are single side discharge rooftop cooling unit utilizing electric heat as an option. Units are pre-
wired, pre-charged with R-410A refrigerant, and tested at the factory. These units can be placed on the side of a
building or can be placed on a roof without roof curbs. Each unit is designed to occupy a minimal space. Piping and
drain connections are readily accessible.
Page 1
Table of Contents
Features / Benefits .......................................................................................................................................................... 2
Shipping Information / Options / Accessories ................................................................................................................. 4
Model No. Nomenclature ................................................................................................................................................ 6
AHRI Capacity Ratings ................................................................................................................................................... 7
Physical Data .................................................................................................................................................................. 8
Unit Dimensional Drawing ............................................................................................................................................ 10
Cooling Capacities ....................................................................................................................................................... 16
Fan Performance Table ............................................................................................................................................... 21
Fan RPM at Motor Pulley / Sound Rating .................................................................................................................... 24
Electrical Data / Electric Heater Data .......................................................................................................................... 25
Wiring Schematic .......................................................................................................................................................... 27
Application Data ............................................................................................................................................................ 32
Guide Specifications ..................................................................................................................................................... 33
Features / Benefits
Every compact one-piece unit arrives fully assembled, charged, tested, and ready to run.
Durable-Dependable Construction
Designed for durability in any climate, the weather-resistant cabinets are constructed of galvanized steel,
bonderized, and all exterior panels are coated with a pre-painted baked enamel finish. The paint finish is non-
chalking, and is capable of withstanding ASTM (American Society for Testing and Materials) B117 500-hour Salt
Spray Test. All internal cabinet panels are primed, permitting longer life and a more attractive appearance for the
entire unit. Totally enclosed condenser-fan motor and permanently lubricated bearings provide additional unit
dependability.
Indoor-Air Quality
Non corrosive sloped condensate pans minimize biological growth in rooftop units in accordance with ASHRAE
(American Society of Heating, Refrigeration and Air Conditioning Engineers) Standard 62-99 (IAQ). 2”inch filters
provide for greater particle reduction in the return air.
Terminal boards, located in the unit control box, facilitate connections to room thermostat, outdoor thermostat(s) and
electric heater. Service panels can be quickly removed, permitting easy servicing. Both power and control
connections are made on the same side of the unit to simplify installation. In addition, color-coded wires permit easy
tracing and diagnostics.
Easy Installation
All units feature base rail design with forklift slots and rigging holes for easier maneuvering. Durable packaging
protects all units during shipment and storage. Convenient side by side openings permit installation very close to
face of buildings or on roof top. The non-corrosive sloped condensate pan minimizes residual condensate in off
cycle. An external, field-supplied P-trap is required. Field-installed electric heaters are available up to 34.7 kW.
Page 2
Installation Features
Performance Features
- HFC R-410A non-ozone depleting refrigerant
- ASHRAE Compliant
- EER’s up to 12.5
- TXV refrigerant metering device
- Two independent refrigerant circuits, each with a scroll compressor
o
- Low outdoor temperature cooling operation down to 40 F
- Liquid filter drier standard on each circuit
- Fresh air intake capable
- Non-corrosive sloped condensate drain pan in accordance to ASHRAE 62 standard
- Thermally protected and permanently lubricated condenser and evaporator fan motors
- Angle type return air section with washable type filters
Page 3
Shipping Information
1
Unit data with Condenser and Evaporator Al/Cu Coils
DIMENSIONS (MM)
EST. WT. (KG)
Net With Wooden create above
Unit Model Number
GROSS
NET LENGTH WIDTH DEPTH LENGTH WIDTH DEPTH
(with Skid)
50TCMA07AXA1-0A0A0 275 285 1051 1888 1187 1089 1943 1219
50TCMD08AXA1-0A0A0 345 360 1048 2238 1510 1207 2292 1543
50TCMD09AXA1-0A0A0 388 403 1253 2238 1510 1412 2292 1543
50TCMD12AXA1-0A0A0 393 408 1253 2238 1510 1412 2292 1543
50TCMD14AXA1-0A0A0 489 504 1253 2238 1510 1412 2292 1543
NOTES:
1. Please refer to product nomenclature for ordering information.
2. See application data for assistance.
Page 4
Factory Options and Accessories
Connect the rooftop to an existing BAS without complicated translators or adapter modules using the RTU
Open controller. This new controller speaks the 4 most common building automation system languages (BACNET,
Modbus, Johnson N2, and LonWorks). Use this controller when you have an existing BAS.
PremierLink
This CCN controller regulates your rooftop’s performance to tighter tolerances and expanded limits, as well as
facilitates zoning systems and digital accessories. It also unites your Carrier HVAC equipment together on one,
coherent CCN network. The PremierLink can be factory-installed, or easily field-installed.
This accessory protects your compressor by preventing short-cycling in the event of some other failure, prevents
the compressor from restarting for 30 seconds after stopping. Not required with PremierLink, RTU Open, or
authorized commercial thermostats.
Use these differential pressure switches to detect a filter clog or indoor fan motor failure. When used in conjunction
with a compatible unit controller/thermostat, the switches will activate an alarm to warn the appropriate personnel.
The winter start kit by Carrier extends the low ambient limit of your rooftop to 25°F (-4°C). The kit by-passes the low
pressure switch, preventing nuisance tripping of the low pressure switch. Other low ambient precautions may still be
prudent.
Some applications need larger horsepower motors, some need more airflow, and some need both. Regardless of the
case, your Carrier expert has a factory installed combination to meet your application. A wide selection of motors and
pulleys (drives) are available, factory installed, to handle nearly any application.
Electric Heaters
Carrier offers a full-line of field-installed accessory heaters. The heaters are very easy to use, install and are all pre-
engineered and certified.
Page 5
Model Number Nomenclature - 50TCM - R410A Series
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
5 0 T C M A 0 7 A 9 A 1 - 0 A 0 A 0
Brand/Packaging
0 = Standard
Electrical Options
A = None
Unit Heat Type
50 = Cooling /
Electric Heat RTU
Service Options
0 = None
Nominal Ton
07 = 6 Ton
08 = 7.5 Ton
09 = 8.5 Ton Design Review
12 = 10 Ton - = Factory Assigned
14 = 12.5 Ton
Page 6
AHRI Capacity Rating
Net Cooling Capacity Net Cooling Net Cooling Standard Standard
Unit 50TCM Nominal Ton Standard CFM EER
(BTU/hr) Capacity (Watt) Capacity (Ton) m3/hr L/s
A07 6.0 2400 66500 19496 5.5 11.2 4075 1133
D08 7.5 3000 86500 25359 7.2 12.5 5094 1416
D09 8.5 3400 94000 27558 7.8 11.9 5773 1604
D12 10.0 4000 113500 33274 9.5 11.5 6792 1888
D14 12.5 4800 135500 39724 11.3 11.0 8150 2265
Page 7
Unit Physical Data (English)
Unit 50TCM A07 D08 D09 D12 D14
Unit Dimensions 41.3x74.3x46.7 41.2x88.1x59.4 49.3x88.1x59.4
Unit Operating Weight 606 761 855 866 1078
Refrigeration System
Compressor No.# / Type 1 / Scroll 2 / Scroll
Refrigerant type Puron ® R410A
Circuts No.# 1 2
Charge per Circuit (1-Down/2-Up) -LBS 16.20 8.71/8.82 9.48/9.92 10.65/10.63 12.79/12.24
Metering Device Acutrol
Filter Drier Qty 1 2
High Pressure Switch (Trip/ Reset)- PSIG 630 / 505
Low Pressure Switch (Trip/ Reset)- PSIG 54 / 117
Condenser Coil *
Coil Type 3/8" helical grooved copper tube, 0.75" Aluminum LSW fins.
Standard Coil Material Cu/Al
Rows / FPI 2 / 17 1 / 20 2 / 20
Face Area (ft2) 21.3 20.5 25.1
Coil test Pressure (PSIG) 450
Condenser Fan & Motor
Approx. Air Flow Rate (CFM) 5000 6400 7800 7500 7000
Quantity 1 2 1
Diameter (in) / No. of Blades 26/3 22/3 30/4
Motor Type Induction Motor - Totally Enclosed
Motor HP - RPM 1/3-960 1/3-1200 1-950
Evaporator Coil *
Coil Type 3/8" helical grooved copper tube, 0.75" Aluminum LSW fins.
Standard Coil Material Cu/Al
Rows / FPI 4/15 3/15 4/15
Face Area (ft2) 7.3 8.9 11.1
Coil test Pressure (PSIG) 350
Drain Pan connection Size (in) 3/4
Return Air Filter Qty/ Size (in) 4 / 16x16x2 4 / 16x20x2 4 / 20x20x2
Evaporator Fan & Motor section
Fan Quantity / Fan Size (in) 1 / 10 x 10 1 / 15 x 15
Fan Type Centrifugal - Forward Blade
Drive Type Belt
Motor Type Induction Motor - TEFC
Standard Static Drive
Motor Qty 1
Maximum BHP 1.4 2 2.4
FLA 2.6 3.4
Efficiency @ Full Load 80% 81%
RPM Range 855-1211 570-808 665-903
Shaft Diamter (in) 5/8 7/8
Motor Frame Size 56Y
Medium Static Drive
Motor Qty 1
Maximum BHP 2.4 3.1 3.9
FLA 3.4 4.4 7.4
Efficiency @ Full Load 81%
RPM Range 1077-1393 692-896 808-1040 837-1015
Shaft Diamter (in) 7/8
Motor Frame Size 56Y 56HZ 145TY
High Static Drive
Motor Qty 1
Maximum BHP 3.1 3.9 4.2
FLA 4.4 7.4 9.8
Efficiency @ Full Load 81%
RPM Range 1211-1568 881-1140 957-1160
Shaft Diamter (in) 7/8 1 1/8
Motor Frame Size 56HZ 145TY S184T
Page 8
Unit Physical Data (SI)
Unit 50TCM A07 D08 D09 D12 D14
Unit Dimensions 1051x1888x1187 1048x2238x1510 1253x2238x1510
Unit Operating Weight 275 345 388 393 489
Refrigeration System
Compressor No.# / Type 1 / Scroll 2 / Scroll
Refrigerant type Puron ® R410A
Circuts No.# 1 2
Charge per Circuit (1-Down/2-Up) - kG 7.35 3.95 / 4.00 4.30 / 4.50 4.83 / 4.82 5.80 / 5.55
Metering Device Acutrol
Filter Drier Qty 1 2
High Pressure Switch (Trip/ Reset) - bar 43 / 34
Low Pressure Switch (Trip/ Reset) - bar 4/8
Condenser Coil *
Coil Type 3/8" helical grooved copper tube, 0.75" Aluminum LSW fins.
Standard Coil Material Cu / Al
Rows / FPI 2 / 17 1 / 20 2 / 20
Face Area (m2) 1.98 1.90 2.33
Coil test Pressure (bar) 31
Condenser Fan & Motor
Approx. Air Flow Rate (m3/hr) 8492.0 10867.2 13244.4 12735 11886
Quantity 1 2 1
Diameter (mm) / No. of Blades 660 / 3 559 / 3 762 / 4
Motor Type Induction Motor - Totally Enclosed
Motor HP - RPS 1/3-38 1/3 - 47 1-37
Evaporator Coil *
Coil Type 3/8" helical grooved copper tube, 0.75" Aluminum LSW fins.
Standard Coil Material Cu/Al
Rows / FPI 4 / 15 3 / 15 4 / 15
Face Area (m2) 0.7 0.8 1.0
Coil test Pressure (bar) 23.8
Drain Pan Connection Size (mm) 19
Return Air Filter Qty x Size (in) 4 / 16x16x2 4 / 16x20x2 4 / 20x20x2
Evaporator Fan & Motor section
Fan Quantity / Fan Size (mm) 1 / 254 x 254 1 / 381 x 381
Fan Type Centrifugal - Forward Blade
Drive Type Belt
Motor Type Induction Motor - TEFC
Standard Static Drive
Motor Qty 1
Maximum kW 1.0 1.5 1.8
FLA 2.6 3.4
Efficiency @ Full Load 80% 81%
RPS Range 14.3 - 20.2 9.5 - 13.5 11.1 - 15.1
Shaft Diamter (mm) 15.9 22.2
Motor Frame Size 56Y
Medium Static Drive
Motor Qty 1
Maximum kW 1.8 2.3 2.9
FLA 3.4 4.4 7.4
Efficiency @ Full Load 81%
RPS Range 18.0 - 23.2 11.5 - 14.9 13.5 - 17.3 14.0 - 16.9
Shaft Diamter (mm) 22.2
Motor Frame Size 56Y 56HZ 145TY
High Static Drive
Motor Qty 1
Maximum kW 2.3 2.9 3.1
FLA 4.4 7.4 9.8
Efficiency @ Full Load 81%
RPS Range 20.2 - 26.1 14.7 - 19.0 16.0 - 19.3
Shaft Diamter (mm) 22.2 28.5
Motor Frame Size 56HZ 145TY S184T
Page 9
&85%6 :(,*+76',0(16,2167&007
8
:
'LPHQVLRQV7&."
Page 10
&85%6 :(,*+76',0(16,2167&007 (cont.)
5$."
'LPHQVLRQV7&."
6HUYLFH&OHDUDQFH
Page 11
&85%6 :(,*+76',0(16,2167&0'
5$.%
5$.%
'LPHQVLRQV7&.%
Page 12
&85%6 :(,*+76',0(16,2167&0' (cont.)
5$.%
5$.%
'LPHQVLRQV7&.%
6HUYLFH&OHDUDQFH
Page 13
&85%6 :(,*+76',0(16,2167&0'
5$.%
5$.%
'LPHQVLRQV7&.%
Page 14
&85%6 :(,*+76',0(16,2167&0'cont
$&/5&30'(3"7*5: $(
5$.%
5$.%
C10329
'LPHQVLRQV7&.%
6HUYLFH&OHDUDQFH
C08337
Page 15
Cooling Capacities
50TCM - A07 - 6 Tons - (50Hz-400V)
Evaporator Air - CFM/BPF
Temp (F)
1800 / 0.075 2100 / 0.106 2400 / 0.141 2700 / 0.178 2900 / 0.199
Air Entering
Evaporator Air - EWB (F)
Condenser (Edb)
62 67 72 62 67 72 62 67 72 62 67 72 62 67 72
TC 67,602 72,823 76,377 69,485 74,302 78,096 71,229 75,295 79,527 74,296 76,072 80,878 74,435 76,646 81,673
75 SHC 60,536 49,388 38,285 65,332 52,207 39,766 68,456 54,462 41,267 68,190 56,315 42,926 71,000 57,840 44,053
kW 3.33 3.37 3.40 3.35 3.39 3.42 3.36 3.40 3.44 3.37 3.40 3.45 3.38 3.41 3.46
TC 63,982 69,633 74,843 66,055 71,180 76,274 68,432 72,454 77,250 70,183 73,557 78,048 71,301 74,110 78,457
85 SHC 58,986 48,782 38,211 63,835 52,244 40,034 66,264 55,394 41,420 68,589 58,647 42,669 69,682 60,407 43,290
kW 3.80 3.84 3.89 3.81 3.85 3.90 3.83 3.87 3.91 3.84 3.88 3.93 3.86 3.88 3.93
TC 60,834 66,971 72,826 63,558 68,514 74,368 66,024 69,764 75,573 68,154 70,736 76,499 69,287 71,252 77,004
95 SHC 56,889 47,470 37,324 60,856 51,212 39,375 63,234 54,738 41,223 65,274 58,130 43,020 66,359 60,096 44,173
kW 4.30 4.35 4.40 4.32 4.36 4.41 4.34 4.37 4.43 4.35 4.38 4.44 4.37 4.39 4.45
TC 59,279 65,416 72,243 62,709 67,144 73,774 65,287 68,351 74,883 67,534 69,430 75,822 68,748 70,013 76,322
105 SHC 53,763 45,584 35,935 56,874 49,586 38,174 59,212 53,207 40,184 61,250 56,885 42,190 62,350 58,967 43,433
kW 4.71 4.79 4.85 4.77 4.81 4.86 4.79 4.82 4.88 4.81 4.83 4.89 4.82 4.83 4.89
TC 54,531 59,427 66,651 57,883 60,995 68,056 60,348 62,219 69,077 62,501 63,354 69,982 63,687 64,035 70,487
115 SHC 49,457 43,438 34,227 52,497 47,413 36,540 54,733 51,129 38,634 56,685 54,708 40,813 57,761 56,799 42,181
kW 5.25 5.36 5.41 5.34 5.37 5.43 5.36 5.38 5.44 5.38 5.39 5.45 5.39 5.39 5.46
TC 52,036 56,206 63,548 55,303 57,763 64,913 57,757 58,973 65,947 59,804 60,156 66,761 60,616 60,947 67,227
120 SHC 47,194 42,295 33,252 50,157 46,290 35,618 52,383 49,961 37,782 54,239 53,466 39,943 55,301 55,275 41,352
kW 5.54 5.64 5.70 5.63 5.66 5.72 5.65 5.66 5.73 5.67 5.67 5.74 5.68 5.68 5.75
TC 48,643 51,870 59,194 51,715 53,407 60,528 54,037 54,629 61,437 55,696 56,024 62,214 56,802 57,112 62,632
125 SHC 44,027 40,257 31,575 46,807 44,214 33,947 48,908 47,722 36,080 50,708 50,707 38,249 51,691 51,658 39,595
kW 5.89 5.97 6.06 5.98 6.01 6.07 6.01 6.02 6.09 6.03 6.03 6.10 6.04 6.04 6.10
LEGEND
BPF — Bypass Factor Ldb — Leaving Dry-Bulb
Edb — Entering Dry-Bulb Lwb — Leaving Wet-Bulb
Ewb — Entering Wet-Bulb TC — Total Capacity (1000 Btuh) Gross
SHC — Sensible Heat Capacity (1000 Btuh) Gross kW — Compressor Motor Power Input
Bold, Italics - Standard Ratings
Notes:
1. Direct interpolation is permissible. Do not extrapolate. 3. The SHC is based on 80 F edb temprature of air entering evaporator coil.
2. The following formaulas may be used. - Below 80 F edb, subtract (corr factor x cfm) from SHC.
tldb = tedb — sensible capacity (Btuh) - Above 80 F edb, add (corr factor x cfm) to SHC.
1.10 x cfm ENTERING AIR DRY-BULB TEMP (F)
tlwb = Wet-bulb temprature corresponding to enthalphy of air leaving evaporater coil (hlwb). 79 78 77 76 75 under 75
BF
81 82 83 84 85 over 85
hlwb = hewb — total capacity (Btuh) Correction Factor
4.5 x cfm 0.05 1.04 2.07 3.11 4.14 5.18 Use
Where: hewb = Enthaply of air entering evaporator coil. 0.10 0.98 1.96 2.94 3.92 4.90 formula
0.20 0.87 1.74 2.62 3.49 4.36 shown
4. Cooling capacities are gross and do not include deductions for indoor fan motor heat. 0.30 0.76 1.53 2.29 3.05 3.82 below.*
5. Variable Air Volume units will operate down to 70 cfm/ton. Performance at 70 cfm/ton is limited to
unloaded operation and may be additinally limited to edb and ewb conditions. - Interpolation is permissible.
*Correction Factor = 1.10 x (1 - BF) x (edb - 80).
Page 16
Cooling Capacities (Continued)
50TCM - D08 - 7.5 Tons - (50Hz-400V)
Evaporator Air - CFM/BPF
Temp (F)
2250 / 0.098 2625 / 0.126 3000 / 0.152 3375 / 0.185 3750 / 0.206
Air Entering
Evaporator Air - EWB (F)
Condenser (Edb)
62 67 72 62 67 72 62 67 72 62 67 72 62 67 72
TC 83,305 91,307 96,838 85,808 93,420 98,292 87,908 94,597 99,305 90,558 95,700 100,387 92,004 96,295 101,036
75 SHC 73,659 61,796 48,759 79,482 66,013 50,742 83,975 69,244 52,366 88,621 72,973 54,345 85,332 75,242 55,617
kW 3.71 3.68 3.70 3.70 3.68 3.71 3.69 3.69 3.71 3.68 3.69 3.72 3.69 3.69 3.73
TC 79,486 87,533 95,240 82,029 89,889 96,773 84,308 91,420 97,763 87,415 92,900 98,864 89,479 93,652 99,428
85 SHC 70,413 59,070 47,429 76,091 63,607 49,730 79,985 67,248 51,485 83,575 71,713 53,673 84,518 74,524 55,008
kW 4.32 4.32 4.32 4.33 4.31 4.33 4.32 4.31 4.33 4.31 4.31 4.34 4.31 4.32 4.35
TC 77,570 85,631 94,421 80,458 87,981 96,523 83,095 89,571 97,828 86,195 91,177 99,012 88,016 92,035 99,595
95 SHC 73,850 61,844 49,795 79,533 66,794 52,707 82,889 70,875 55,022 86,197 76,091 57,785 88,018 79,195 59,448
kW 4.98 5.04 5.04 5.01 5.04 5.05 5.04 5.03 5.06 5.04 5.03 5.06 5.03 5.04 5.07
TC 69,946 77,442 85,990 73,222 79,499 88,097 75,870 80,904 89,431 78,770 82,397 90,753 80,417 83,225 91,425
105 SHC 66,424 55,707 44,639 70,836 60,312 47,503 73,406 64,205 49,821 76,212 69,003 52,672 77,805 71,838 54,436
kW 5.41 5.52 5.55 5.46 5.54 5.56 5.50 5.54 5.57 5.54 5.55 5.57 5.54 5.55 5.58
TC 62,712 69,242 77,591 66,199 71,108 79,552 68,782 72,384 80,848 71,481 73,812 82,156 72,988 74,572 82,806
115 SHC 61,696 52,564 41,898 65,127 57,206 44,750 67,668 60,980 47,095 70,324 65,564 50,046 71,806 68,362 51,891
kW 6.23 6.35 6.49 6.30 6.40 6.50 6.35 6.43 6.50 6.41 6.46 6.51 6.45 6.48 6.51
TC 59,541 66,318 74,676 63,753 68,065 76,545 66,237 69,423 77,808 68,938 70,762 79,102 70,412 71,542 79,780
120 SHC 58,258 50,825 40,463 61,572 55,366 43,272 63,992 59,094 45,589 66,595 63,584 48,495 68,049 66,272 50,350
kW 6.76 6.76 6.94 6.84 6.81 6.95 6.90 6.84 6.96 6.96 6.88 6.97 7.00 6.90 6.97
TC 55,970 60,802 69,255 59,233 62,545 71,009 61,579 63,808 72,184 64,179 65,152 73,396 65,632 66,063 74,019
125 SHC 55,972 49,286 39,138 59,235 53,779 41,983 61,580 57,475 44,319 64,180 61,919 47,272 65,633 64,470 49,110
kW 7.14 7.26 7.49 7.22 7.31 7.53 7.29 7.35 7.55 7.36 7.39 7.56 7.40 7.41 7.56
LEGEND
BPF — Bypass Factor Ldb — Leaving Dry-Bulb
Edb — Entering Dry-Bulb Lwb — Leaving Wet-Bulb
Ewb — Entering Wet-Bulb TC — Total Capacity (1000 Btuh) Gross
SHC — Sensible Heat Capacity (1000 Btuh) Gross kW — Compressor Motor Power Input
Bold, Italics - Standard Ratings
Notes:
1. Direct interpolation is permissible. Do not extrapolate. 3. The SHC is based on 80 F edb temprature of air entering evaporator coil.
2. The following formaulas may be used. - Below 80 F edb, subtract (corr factor x cfm) from SHC.
tldb = tedb — sensible capacity (Btuh) - Above 80 F edb, add (corr factor x cfm) to SHC.
1.10 x cfm ENTERING AIR DRY-BULB TEMP (F)
tlwb = Wet-bulb temprature corresponding to enthalphy of air leaving evaporater coil (hlwb). 79 78 77 76 75 under 75
BF
81 82 83 84 85 over 85
hlwb = hewb — total capacity (Btuh) Correction Factor
4.5 x cfm 0.05 1.04 2.07 3.11 4.14 5.18 Use
Where: hewb = Enthaply of air entering evaporator coil. 0.10 0.98 1.96 2.94 3.92 4.90 formula
0.20 0.87 1.74 2.62 3.49 4.36 shown
4. Cooling capacities are gross and do not include deductions for indoor fan motor heat. 0.30 0.76 1.53 2.29 3.05 3.82 below.*
5. Variable Air Volume units will operate down to 70 cfm/ton. Performance at 70 cfm/ton is limited to
unloaded operation and may be additinally limited to edb and ewb conditions. - Interpolation is permissible.
*Correction Factor = 1.10 x (1 - BF) x (edb - 80).
Page 17
Cooling Capacities (Continued)
50TCM - D09 - 8.5 Tons - (50Hz-400V)
Evaporator Air - CFM/BPF
Temp (F)
2550 / 0.077 2975 / 0.111 3400 / 0.140 3650 / 0.169 4250 / 0.193
Air Entering
Evaporator Air - EWB (F)
Condenser (Edb)
62 67 72 62 67 72 62 67 72 62 67 72 62 67 72
TC 94,796 105,114 116,069 99,041 108,553 119,409 102,511 110,893 122,038 105,680 112,805 124,081 107,466 114,214 125,772
75 SHC 83,773 71,727 58,510 90,437 77,678 62,226 96,556 83,362 65,831 101,811 88,659 69,208 102,214 93,617 72,563
kW 4.35 4.46 4.59 4.40 4.51 4.63 4.43 4.54 4.67 4.48 4.56 4.70 4.60 4.58 4.72
TC 89,812 99,380 110,428 94,039 102,395 113,937 97,370 104,698 116,379 100,522 106,485 118,254 103,532 108,182 119,818
85 SHC 80,717 69,420 56,447 86,824 75,348 60,289 92,771 80,962 63,876 97,561 86,169 67,251 100,482 91,357 70,591
kW 4.94 5.06 5.19 5.00 5.10 5.25 5.04 5.13 5.28 5.08 5.15 5.31 5.11 5.18 5.34
TC 83,989 93,368 103,939 87,930 95,978 106,944 91,757 98,105 109,317 95,271 99,717 111,121 98,135 101,312 112,645
95 SHC 76,848 67,001 54,103 83,156 72,815 57,836 89,054 78,370 61,456 92,464 83,453 64,855 95,244 88,039 68,224
kW 5.59 5.73 5.86 5.63 5.76 5.90 5.69 5.79 5.93 5.75 5.81 5.96 5.79 5.83 5.98
TC 77,883 85,789 97,104 81,803 88,496 99,821 85,789 90,613 101,876 89,065 92,683 103,498 92,012 94,753 104,830
105 SHC 72,703 64,039 51,663 79,393 69,863 55,362 83,261 75,372 58,939 86,441 79,987 62,314 89,301 83,869 65,659
kW 6.41 6.52 6.71 6.47 6.56 6.75 6.52 6.59 6.79 6.57 6.64 6.81 6.62 6.68 6.84
TC 71,531 78,044 89,148 75,800 80,364 91,870 79,464 82,585 94,119 82,512 84,811 95,543 85,202 86,697 96,688
115 SHC 68,065 60,055 48,121 72,463 65,613 51,842 75,966 70,291 55,484 78,880 74,086 58,783 81,451 77,758 62,057
kW 7.26 7.35 7.52 7.32 7.39 7.58 7.37 7.42 7.64 7.42 7.45 7.67 7.46 7.48 7.70
TC 71,681 77,508 88,891 75,890 79,759 91,546 79,548 82,435 93,661 82,617 84,604 95,386 85,322 86,410 96,595
120 SHC 66,529 58,959 47,144 70,437 64,225 50,837 73,831 68,669 54,434 76,680 72,400 57,834 79,190 76,128 61,131
kW 7.70 7.77 7.94 7.75 7.80 7.99 7.80 7.84 8.04 7.85 7.87 8.10 7.89 7.90 8.13
TC 67,705 72,037 83,312 71,723 74,575 85,788 75,153 77,233 87,627 78,076 79,321 89,001 80,612 81,158 90,153
125 SHC 62,717 56,828 45,240 66,440 61,255 48,919 69,617 65,478 52,463 72,324 69,193 55,764 74,674 72,962 59,051
kW 8.31 8.37 8.53 8.36 8.40 8.58 8.41 8.44 8.62 8.46 8.47 8.65 8.50 8.50 8.68
LEGEND
BPF — Bypass Factor Ldb — Leaving Dry-Bulb
Edb — Entering Dry-Bulb Lwb — Leaving Wet-Bulb
Ewb — Entering Wet-Bulb TC — Total Capacity (1000 Btuh) Gross
SHC — Sensible Heat Capacity (1000 Btuh) Gross kW — Compressor Motor Power Input
Bold, Italics - Standard Ratings
Notes:
1. Direct interpolation is permissible. Do not extrapolate. 3. The SHC is based on 80 F edb temprature of air entering evaporator coil.
2. The following formaulas may be used. - Below 80 F edb, subtract (corr factor x cfm) from SHC.
tldb = tedb — sensible capacity (Btuh) - Above 80 F edb, add (corr factor x cfm) to SHC.
1.10 x cfm ENTERING AIR DRY-BULB TEMP (F)
tlwb = Wet-bulb temprature corresponding to enthalphy of air leaving evaporater coil (hlwb). 79 78 77 76 75 under 75
BF
81 82 83 84 85 over 85
hlwb = hewb — total capacity (Btuh) Correction Factor
4.5 x cfm 0.05 1.04 2.07 3.11 4.14 5.18 Use
Where: hewb = Enthaply of air entering evaporator coil. 0.10 0.98 1.96 2.94 3.92 4.90 formula
0.20 0.87 1.74 2.62 3.49 4.36 shown
4. Cooling capacities are gross and do not include deductions for indoor fan motor heat. 0.30 0.76 1.53 2.29 3.05 3.82 below.*
5. Variable Air Volume units will operate down to 70 cfm/ton. Performance at 70 cfm/ton is limited to
unloaded operation and may be additinally limited to edb and ewb conditions. - Interpolation is permissible.
*Correction Factor = 1.10 x (1 - BF) x (edb - 80).
Page 18
Cooling Capacities (Continued)
50TCM - D12 - 10 Tons - (50Hz-400V)
Evaporator Air - CFM/BPF
Temp (F)
3000 / 0.061 3500 / 0.087 4000 / 0.117 4500 / 0.146 5000 / 0.177
Air Entering
Evaporator Air - EWB (F)
Condenser (Edb)
62 67 72 62 67 72 62 67 72 62 67 72 62 67 72
TC 117,319 126,635 133,517 120,555 129,085 136,226 120,555 129,085 136,226 125,885 131,612 139,974 126,352 132,497 141,221
75 SHC 103,482 85,468 66,691 111,492 90,987 69,774 114,255 94,771 71,749 119,540 98,419 74,772 115,796 101,099 76,576
kW 5.08 5.14 5.23 5.09 5.17 5.27 5.11 5.20 5.31 5.12 5.21 5.32 5.17 5.22 5.35
TC 112,254 122,512 131,590 116,040 125,632 133,824 116,040 125,632 133,824 121,585 128,623 136,410 123,432 129,435 137,463
85 SHC 101,678 84,789 66,705 109,358 91,653 70,033 111,738 96,316 72,218 117,082 100,916 74,716 118,885 103,796 76,522
kW 5.91 5.95 6.06 5.92 5.98 6.09 5.94 6.00 6.12 5.95 6.01 6.13 5.97 6.03 6.15
TC 106,032 116,259 127,536 110,419 119,203 130,277 110,419 119,203 130,277 116,401 122,315 132,790 118,183 123,193 133,528
95 SHC 97,862 82,598 65,954 105,689 89,581 69,982 106,351 94,488 72,633 112,112 99,392 75,332 113,829 102,510 77,073
kW 6.77 6.87 6.94 6.84 6.89 6.98 6.86 6.90 7.02 6.86 6.91 7.02 6.88 6.92 7.04
TC 98,856 108,839 120,381 103,936 111,676 123,218 103,936 111,676 123,218 110,358 114,654 126,223 112,060 115,495 127,000
105 SHC 93,327 79,812 63,506 100,106 86,893 67,837 100,106 91,871 70,742 106,292 96,789 73,972 107,931 100,033 75,952
kW 7.51 7.68 7.77 7.61 7.71 7.80 7.68 7.73 7.82 7.70 7.73 7.83 7.72 7.74 7.84
TC 87,466 95,619 107,577 92,684 98,404 110,141 92,684 98,404 110,141 98,786 101,367 112,842 100,377 102,200 113,553
115 SHC 87,315 75,946 60,357 92,524 83,069 64,727 92,524 88,006 67,775 98,616 92,950 71,001 100,203 95,606 73,044
kW 7.80 7.98 8.17 7.92 8.04 8.19 8.01 8.07 8.21 8.03 8.08 8.21 8.06 8.09 8.22
TC 82,271 89,456 101,242 87,254 92,101 103,754 87,254 92,101 103,754 93,146 95,084 106,320 94,687 96,050 106,985
120 SHC 78,984 69,532 55,216 83,768 76,195 59,339 83,768 80,665 62,197 89,425 85,103 65,197 90,904 87,269 67,137
kW 8.56 8.73 8.97 8.68 8.81 9.01 8.79 8.85 9.03 8.82 8.85 9.03 8.85 8.87 9.05
TC 76,521 81,918 93,952 81,234 84,436 96,318 81,234 84,436 96,318 86,992 88,112 99,000 88,439 89,123 99,563
125 SHC 73,461 66,293 52,522 77,986 72,848 56,630 77,986 75,892 59,475 83,513 80,621 62,592 84,902 82,871 64,460
kW 9.17 9.32 9.61 9.30 9.40 9.66 9.42 9.46 9.70 9.47 9.48 9.72 9.50 9.51 9.73
LEGEND
BPF — Bypass Factor Ldb — Leaving Dry-Bulb
Edb — Entering Dry-Bulb Lwb — Leaving Wet-Bulb
Ewb — Entering Wet-Bulb TC — Total Capacity (1000 Btuh) Gross
SHC — Sensible Heat Capacity (1000 Btuh) Gross kW — Compressor Motor Power Input
Bold, Italics - Standard Ratings
Notes:
1. Direct interpolation is permissible. Do not extrapolate. 3. The SHC is based on 80 F edb temprature of air entering evaporator coil.
2. The following formaulas may be used. - Below 80 F edb, subtract (corr factor x cfm) from SHC.
tldb = tedb — sensible capacity (Btuh) - Above 80 F edb, add (corr factor x cfm) to SHC.
1.10 x cfm ENTERING AIR DRY-BULB TEMP (F)
tlwb = Wet-bulb temprature corresponding to enthalphy of air leaving evaporater coil (hlwb). 79 78 77 76 75 under 75
BF
81 82 83 84 85 over 85
hlwb = hewb — total capacity (Btuh) Correction Factor
4.5 x cfm 0.05 1.04 2.07 3.11 4.14 5.18 Use
Where: hewb = Enthaply of air entering evaporator coil. 0.10 0.98 1.96 2.94 3.92 4.90 formula
0.20 0.87 1.74 2.62 3.49 4.36 shown
4. Cooling capacities are gross and do not include deductions for indoor fan motor heat. 0.30 0.76 1.53 2.29 3.05 3.82 below.*
5. Variable Air Volume units will operate down to 70 cfm/ton. Performance at 70 cfm/ton is limited to
unloaded operation and may be additinally limited to edb and ewb conditions. - Interpolation is permissible.
*Correction Factor = 1.10 x (1 - BF) x (edb - 80).
Page 19
Cooling Capacities (Continued)
50TCM - D14 - 12.5 Tons - (50Hz-400V)
Evaporator Air - CFM/BPF
Temp (F)
3600 / 0.041 4200 / 0.058 4800 / 0.088 5400 / 0.111 5900 / 0.131
Air Entering
Evaporator Air - EWB (F)
Condenser (Edb)
62 67 72 62 67 72 62 67 72 62 67 72 62 67 72
TC 137,377 147,352 161,040 141,096 150,955 161,759 144,161 153,854 163,532 147,138 155,516 164,987 150,115 156,170 165,515
75 SHC 125,475 103,167 78,288 135,267 111,416 86,857 140,395 119,371 90,691 144,619 126,486 94,321 148,844 129,714 96,027
kW 6.54 6.57 6.59 6.52 6.56 6.60 6.54 6.56 6.62 6.54 6.57 6.63 6.54 6.57 6.64
TC 132,570 143,462 154,554 136,517 146,897 158,168 140,582 149,254 160,237 144,647 151,000 161,730 146,324 151,850 162,319
85 SHC 123,464 102,284 81,003 132,641 110,563 86,091 138,032 118,207 90,480 143,423 125,535 94,581 145,086 129,028 96,530
kW 7.57 7.56 7.58 7.53 7.55 7.58 7.53 7.55 7.60 7.53 7.55 7.61 7.54 7.55 7.62
TC 125,256 137,940 149,720 130,956 140,868 152,617 135,826 143,178 154,703 139,702 144,904 156,342 141,378 145,679 156,980
95 SHC 119,777 100,358 79,588 129,106 108,428 84,346 134,676 116,223 88,909 138,519 123,726 93,282 140,181 127,233 95,427
kW 8.54 8.66 8.64 8.62 8.65 8.65 8.65 8.65 8.67 8.64 8.65 8.68 8.63 8.64 8.69
TC 116,767 130,199 143,082 123,543 133,503 145,924 129,251 135,962 147,948 133,618 137,661 149,493 135,295 138,443 150,092
105 SHC 114,304 97,274 77,232 122,497 105,685 82,184 128,157 113,699 86,878 132,487 121,244 91,390 134,149 124,925 93,552
kW 9.36 9.61 9.63 9.49 9.65 9.63 9.60 9.65 9.64 9.64 9.65 9.65 9.64 9.64 9.65
TC 102,026 112,282 127,304 108,287 115,750 130,150 113,501 118,406 132,105 117,948 120,848 133,584 119,818 121,815 134,178
115 SHC 104,909 90,867 72,791 111,347 99,359 77,866 116,708 107,426 82,660 121,281 115,271 87,256 123,203 118,915 89,502
kW 9.69 9.85 10.09 9.79 9.92 10.09 9.88 9.97 10.09 9.97 10.03 10.09 10.01 10.05 10.09
TC 99,266 108,630 123,952 105,263 112,036 126,995 110,419 114,455 129,051 114,679 116,841 130,515 116,658 117,904 131,147
120 SHC 95,822 83,878 67,191 101,611 91,848 72,077 106,587 99,438 76,657 110,700 106,599 81,089 112,610 110,105 83,237
kW 10.56 10.72 11.00 10.66 10.79 11.04 10.76 10.84 11.04 10.85 10.89 11.04 10.89 10.92 11.04
TC 93,279 100,645 116,145 99,033 103,801 119,288 103,896 106,369 121,455 108,061 108,752 123,140 109,914 110,371 123,827
125 SHC 90,522 80,976 64,690 96,106 88,889 69,709 100,824 96,385 74,433 104,867 103,433 79,010 106,664 105,998 81,247
kW 11.35 11.49 11.81 11.46 11.55 11.87 11.56 11.61 11.90 11.65 11.67 11.93 11.70 11.71 11.94
LEGEND
BPF — Bypass Factor Ldb — Leaving Dry-Bulb
Edb — Entering Dry-Bulb Lwb — Leaving Wet-Bulb
Ewb — Entering Wet-Bulb TC — Total Capacity (1000 Btuh) Gross
SHC — Sensible Heat Capacity (1000 Btuh) Gross kW — Compressor Motor Power Input
Bold, Italics - Standard Ratings
Notes:
1. Direct interpolation is permissible. Do not extrapolate. 3. The SHC is based on 80 F edb temprature of air entering evaporator coil.
2. The following formaulas may be used. - Below 80 F edb, subtract (corr factor x cfm) from SHC.
tldb = tedb — sensible capacity (Btuh) - Above 80 F edb, add (corr factor x cfm) to SHC.
1.10 x cfm ENTERING AIR DRY-BULB TEMP (F)
tlwb = Wet-bulb temprature corresponding to enthalphy of air leaving evaporater coil (hlwb). 79 78 77 76 75 under 75
BF
81 82 83 84 85 over 85
hlwb = hewb — total capacity (Btuh) Correction Factor
4.5 x cfm 0.05 1.04 2.07 3.11 4.14 5.18 Use
Where: hewb = Enthaply of air entering evaporator coil. 0.10 0.98 1.96 2.94 3.92 4.90 formula
0.20 0.87 1.74 2.62 3.49 4.36 shown
4. Cooling capacities are gross and do not include deductions for indoor fan motor heat. 0.30 0.76 1.53 2.29 3.05 3.82 below.*
5. Variable Air Volume units will operate down to 70 cfm/ton. Performance at 70 cfm/ton is limited to
unloaded operation and may be additinally limited to edb and ewb conditions. - Interpolation is permissible.
*Correction Factor = 1.10 x (1 - BF) x (edb - 80).
Page 20
Fan Performance Table
Unit 50TCM - A07 - 6 Tons - 400V - 50Hz
Air flow 0.2 0.4 0.6 0.8 1
Rate (CFM) RPM KWI BHP RPM KWI BHP RPM KWI BHP RPM KWI BHP RPM KWI BHP
1800 822 0.48 0.51 927 0.62 0.66 1018 0.76 0.82 1100 0.91 0.98 1174 1.07 1.15
1950 872 0.58 0.62 973 0.74 0.79 1061 0.89 0.95 1140 1.05 1.13 1213 1.21 1.31
2100 923 0.70 0.75 1019 0.86 0.92 1104 1.03 1.10 1182 1.20 1.29 1253 1.36 1.48
2250 974 0.84 0.90 1067 1.01 1.08 1149 1.18 1.27 1224 1.34 1.46 1294 1.53 1.66
2400 1026 0.99 1.06 1115 1.17 1.26 1195 1.36 1.46 1268 1.53 1.66 1336 1.72 1.87
2550 1079 1.17 1.25 1164 1.36 1.46 1241 1.54 1.67 1312 1.73 1.88 1379 1.93 2.10
2700 1132 1.34 1.46 1214 1.54 1.67 1289 1.75 1.90 1358 1.95 2.12 1422 2.16 2.35
2850 1186 1.56 1.69 1264 1.77 1.92 1336 1.98 2.15 1404 2.20 2.39 1467 2.42 2.63
Legend:
Normal Font - Field Installed Drive Package
Bold Font - Standard Drive Package + Standard Motor.
Italics Font - Medium Drive Package + Medium Static Motor.
Bold , Italics Font - High Drive Package + High Static Motor.
RPM - Revolutions Per Minute
KWI - Kilo Watts Input to Motor
BHP - Brake Horsepower Input to Fan
CFM - Cubic Feet per Minute
in.wg - Inch Water Gage
Notes:
1. Do not adjust motor rpm such that motor maximum bhp and/or watts is exceeded at the maximum operatin cfm.
2. Static Pressure (i.e Filters) must be added to external static pressure before entering fan performance table.
3. Interpolation is permissible. Do not extrapolate.
4. Fan performance is based on wet coils, clean filters and casing loses.
5. Extensive motor and drive testing on these units ensures that the full brake horsepower and watts range of the motor can be utilized with confidence. Using your fan motors up to the watts
or bhp rating shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.
6. Bold data shows the range of air flow rate for unit management system, other rpms require field-supplied drive.
7. Use of field-supplied motor may affect wiring size. Contact your Carrier representative for details.
8. Conversion - Bhp to KWI
Bhp X 0.746
KWI=
Motor efficiency
Page 21
Fan Performance Table (Continued)
Unit 50TCM - D09 - 8.5 Tons - 400V - 50Hz
Air flow 0.2 0.4 0.6 0.8 1
Rate (CFM) RPM KWI BHP RPM KWI BHP RPM KWI BHP RPM KWI BHP RPM KWI BHP
2550 477 0.40 0.43 556 0.53 0.57 624 0.66 0.71 685 0.79 0.85 742 0.91 0.99
2763 503 0.48 0.52 578 0.62 0.67 644 0.76 0.82 704 0.90 0.97 759 1.04 1.13
2975 529 0.58 0.62 601 0.74 0.79 665 0.89 0.95 724 1.04 1.11 777 1.18 1.28
3188 556 0.69 0.74 625 0.86 0.92 687 1.02 1.09 744 1.16 1.26 796 1.33 1.44
3400 583 0.82 0.88 650 0.99 1.06 710 1.16 1.24 765 1.32 1.43 816 1.49 1.62
3613 611 0.96 1.03 675 1.14 1.22 733 1.32 1.42 787 1.48 1.61 836 1.67 1.81
3825 639 1.11 1.19 701 1.31 1.40 757 1.48 1.61 809 1.67 1.81 857 1.86 2.02
3950 668 1.29 1.38 727 1.49 1.60 781 1.67 1.81 832 1.87 2.03 879 2.07 2.25
4250 696 1.47 1.58 753 1.67 1.81 806 1.88 2.04 855 2.09 2.27 901 2.30 2.50
Legend:
Normal Font - Field Installed Drive Package
Bold Font - Standard Drive Package + Standard Motor.
Italics Font - Medium Drive Package + Medium Static Motor.
Bold , Italics Font - High Drive Package + High Static Motor.
RPM - Revolutions Per Minute
KWI - Kilo Watts Input to Motor
BHP - Brake Horsepower Input to Fan
CFM - Cubic Feet per Minute
in.wg - Inch Water Gage
Notes:
1. Do not adjust motor rpm such that motor maximum bhp and/or watts is exceeded at the maximum operatin cfm.
2. Static Pressure (i.e Filters) must be added to external static pressure before entering fan performance table.
3. Interpolation is permissible. Do not extrapolate.
4. Fan performance is based on wet coils, clean filters and casing loses.
5. Extensive motor and drive testing on these units ensures that the full brake horsepower and watts range of the motor can be utilized with confidence. Using your fan motors up to the watts
or bhp rating shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.
6. Bold data shows the range of air flow rate for unit management system, other rpms require field-supplied drive.
7. Use of field-supplied motor may affect wiring size. Contact your Carrier representative for details.
8. Conversion - Bhp to KWI
Bhp X 0.746
KWI=
Motor efficiency
Page 22
Fan Performance Table (Continued)
Unit 50TCM - D14 - 12.5 Tons - 400V - 50Hz
Air flow 0.2 0.4 0.6 0.8 1
Rate (CFM) RPM KWI BHP RPM KWI BHP RPM KWI BHP RPM KWI BHP RPM KWI BHP
3700 621 0.95 1.03 679 1.11 1.21 734 1.29 1.40 786 1.46 1.59 837 1.65 1.79
4063 663 1.18 1.28 717 1.35 1.47 769 1.54 1.67 818 1.73 1.88 866 1.92 2.09
4375 706 1.44 1.56 757 1.63 1.77 805 1.82 1.98 852 2.03 2.20 897 2.24 2.43
4688 749 1.74 1.89 797 1.94 2.11 843 2.16 2.34 887 2.37 2.57 930 2.59 2.81
5000 793 2.08 2.26 838 2.30 2.50 881 2.52 2.74 923 2.74 2.98 965 2.97 3.23
5313 837 2.48 2.69 880 2.70 2.93 921 2.94 3.19 961 3.17 3.44 1000 3.42 3.71
5700 882 2.91 3.16 922 3.15 3.42 961 3.39 3.68 999 3.64 3.95 1037 3.87 4.20
Legend:
Normal Font - Field Installed Drive Package
Bold Font - Standard Drive Package + Standard Motor.
Italics Font - Medium Drive Package + Medium Static Motor.
Bold , Italics Font - High Drive Package + High Static Motor.
RPM - Revolutions Per Minute
KWI - Kilo Watts Input to Motor
BHP - Brake Horsepower Input to Fan
CFM - Cubic Feet per Minute
in.wg - Inch Water Gage
Notes:
1. Do not adjust motor rpm such that motor maximum bhp and/or watts is exceeded at the maximum operatin cfm.
2. Static Pressure (i.e Filters) must be added to external static pressure before entering fan performance table.
3. Interpolation is permissible. Do not extrapolate.
4. Fan performance is based on wet coils, clean filters and casing loses.
5. Extensive motor and drive testing on these units ensures that the full brake horsepower and watts range of the motor can be utilized with confidence. Using your fan motors up to the watts
or bhp rating shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.
6. Bold data shows the range of air flow rate for unit management system, other rpms require field-supplied drive.
7. Use of field-supplied motor may affect wiring size. Contact your Carrier representative for details.
8. Conversion - Bhp to KWI
Bhp X 0.746
KWI=
Motor efficiency
Page 23
Fan RPM at Motor Pulley Settings
Unit MOTOR PULLEY TURNS OPEN - ENGLISH
Freq. Drive Package
50TCM 0 1/2 1 1 1/2 2 2 1/2 3 3 1/2 4 4 1/2 5
Standard Static 1211 1176 1140 1104 1069 1033 998 962 926 891 855
A07 Medium Static 1393 1362 1330 1298 1267 1235 1203 1172 1140 1108 1077
High Static 1568 1532 1496 1461 1425 1389 1354 1318 1283 1247 1211
Standard Static 808 784 760 736 713 689 665 641 618 594 570
D08 Medium Static 896 875 855 835 814 794 774 753 733 713 692
High Static 1140 1114 1088 1062 1036 1010 985 959 933 907 881
Standard Static 808 784 760 736 713 689 665 641 618 594 570
50Hz D09 Medium Static 896 875 855 835 814 794 774 753 733 713 692
High Static 1140 1114 1088 1062 1036 1010 985 959 933 907 881
Standard Static 808 784 760 736 713 689 665 641 618 594 570
D12 Medium Static 1045 1021 998 974 950 926 903 879 855 831 808
High Static 1160 1140 1120 1099 1079 1059 1038 1018 998 977 957
Standard Static 903 879 855 831 808 784 760 736 713 689 665
D14 Medium Static 1015 998 980 962 944 926 908 891 873 855 837
High Static 1160 1140 1120 1099 1079 1059 1038 1018 998 977 957
dB – Decibel
NOTES:
1. Measurements are expressed in terms of sound power. Do not compare these values to sound pressure values because sound pressure accounts for
specific environment factors which do not match individual applications. Sound power values are independent of the environment and therefore more
accurate.
2. A–Weighted sound ratings filter out very high and very low frequencies, to better approximate the response of an “average” human ear.
Page 24
Electrical Data
50TCM Compressor
OFM IFM Electric Heater
Drive Power No.1 No.2
MCA MOCP
Unit Size package Supply Application
Indoor Motor V / Ph / Hz RLA LRA RLA LRA Qty HP FLA HP FLA Heater P.N FLA
(KW)
10.6 74.0 - - 1 1/3 2.8 1.4 2.6 - - - 18.7 25
10.6 74.0 - - 1 1/3 2.8 1.4 2.6 CRHEATER106A00 4.2 6.0 18.7 25
10.6 74.0 - - 1 1/3 2.8 1.4 2.6 CRHEATER108A00 8.0 11.5 18.7 25
Standard
10.6 74.0 - - 1 1/3 2.8 1.4 2.6 CRHEATER109A00 9.7 14.0 20.8 25
10.6 74.0 - - 1 1/3 2.8 1.4 2.6 CRHEATER108A00,108A00 16.0 23.1 32.1 35
10.6 74.0 - - 1 1/3 2.8 1.4 2.6 CRHEATER108A00,109A00 17.7 25.6 35.3 40
10.6 74.0 - - 1 1/3 2.8 2.4 3.4 - - - 19.5 30
10.6 74.0 - - 1 1/3 2.8 2.4 3.4 CRHEATER106A00 4.2 6.0 19.5 30
10.6 74.0 - - 1 1/3 2.8 2.4 3.4 CRHEATER108A00 8.0 11.5 19.5 30
A07 Medium 400/3/50
10.6 74.0 - - 1 1/3 2.8 2.4 3.4 CRHEATER109A00 9.7 14.0 21.8 30
10.6 74.0 - - 1 1/3 2.8 2.4 3.4 CRHEATER108A00,108A00 16.0 23.1 33.1 35
10.6 74.0 - - 1 1/3 2.8 2.4 3.4 CRHEATER108A00,109A00 17.7 25.6 36.3 40
10.6 74.0 - - 1 1/3 2.8 3.1 4.4 - - - 20.5 30
10.6 74.0 - - 1 1/3 2.8 3.1 4.4 CRHEATER106A00 4.2 6.0 20.5 30
10.6 74.0 - - 1 1/3 2.8 3.1 4.4 CRHEATER108A00 8.0 11.5 20.5 30
High
10.6 74.0 - - 1 1/3 2.8 3.1 4.4 CRHEATER109A00 9.7 14.0 23.0 30
10.6 74.0 - - 1 1/3 2.8 3.1 4.4 CRHEATER108A00,108A00 16.0 23.1 34.4 35
10.6 74.0 - - 1 1/3 2.8 3.1 4.4 CRHEATER108A00,109A00 17.7 25.6 37.5 40
6.8 43.0 6.1 43.0 2 1/3 1.8 2.0 2.6 - - - 19.9 25
6.8 43.0 6.1 43.0 2 1/3 1.8 2.0 2.6 CRHEATER116A00 9.7 13.9 20.6 25
6.8 43.0 6.1 43.0 2 1/3 1.8 2.0 2.6 CRHEATER113A00 11.5 16.5 23.9 25
Standard
6.8 43.0 6.1 43.0 2 1/3 1.8 2.0 2.6 CRHEATER114A00 19.3 27.9 38.1 40
6.8 43.0 6.1 43.0 2 1/3 1.8 2.0 2.6 CRHEATER115A00 22.9 33.1 44.6 45
6.8 43.0 6.1 43.0 2 1/3 1.8 2.0 2.6 CRHEATER114A00,116A00 29.0 41.8 55.5 60
6.8 43.0 6.1 43.0 2 1/3 1.8 2.4 3.4 - - - 20.7 25
6.8 43.0 6.1 43.0 2 1/3 1.8 2.4 3.4 CRHEATER116A00 9.7 13.9 21.6 25
6.8 43.0 6.1 43.0 2 1/3 1.8 2.4 3.4 CRHEATER113A00 11.5 16.5 24.9 25
D08 Medium 400/3/50
6.8 43.0 6.1 43.0 2 1/3 1.8 2.4 3.4 CRHEATER114A00 19.3 27.9 39.1 40
6.8 43.0 6.1 43.0 2 1/3 1.8 2.4 3.4 CRHEATER115A00 22.9 33.1 45.6 50
6.8 43.0 6.1 43.0 2 1/3 1.8 2.4 3.4 CRHEATER114A00,116A00 29.0 41.8 56.5 60
6.8 43.0 6.1 43.0 2 1/3 1.8 3.9 7.4 - - - 24.7 30
6.8 43.0 6.1 43.0 2 1/3 1.8 3.9 7.4 CRHEATER116A00 9.7 13.9 26.6 30
6.8 43.0 6.1 43.0 2 1/3 1.8 3.9 7.4 CRHEATER113A00 11.5 16.5 29.9 30
High
6.8 43.0 6.1 43.0 2 1/3 1.8 3.9 7.4 CRHEATER114A00 19.3 27.9 44.1 45
6.8 43.0 6.1 43.0 2 1/3 1.8 3.9 7.4 CRHEATER115A00 22.9 33.1 50.6 60
6.8 43.0 6.1 43.0 2 1/3 1.8 3.9 7.4 CRHEATER114A00,116A00 29.0 41.8 61.5 70
7.6 51.5 6.2 52.0 2 1/3 1.8 2.0 2.6 - - - 21.9 25
7.6 51.5 6.2 52.0 2 1/3 1.8 2.0 2.6 CRHEATER116A00 9.7 13.9 21.9 25
7.6 51.5 6.2 52.0 2 1/3 1.8 2.0 2.6 CRHEATER113A00 11.5 16.5 23.9 25
Standard
7.6 51.5 6.2 52.0 2 1/3 1.8 2.0 2.6 CRHEATER114A00 19.3 27.9 38.1 40
7.6 51.5 6.2 52.0 2 1/3 1.8 2.0 2.6 CRHEATER115A00 22.9 33.1 44.6 45
7.6 51.5 6.2 52.0 2 1/3 1.8 2.0 2.6 CRHEATER114A00,116A00 29.0 41.8 55.5 60
7.6 51.5 6.2 52.0 2 1/3 1.8 2.4 3.4 - - - 22.7 30
7.6 51.5 6.2 52.0 2 1/3 1.8 2.4 3.4 CRHEATER116A00 9.7 13.9 22.7 30
7.6 51.5 6.2 52.0 2 1/3 1.8 2.4 3.4 CRHEATER113A00 11.5 16.5 24.9 30
D09 Medium 400/3/50
7.6 51.5 6.2 52.0 2 1/3 1.8 2.4 3.4 CRHEATER114A00 19.3 27.9 39.1 40
7.6 51.5 6.2 52.0 2 1/3 1.8 2.4 3.4 CRHEATER115A00 22.9 33.1 45.6 50
7.6 51.5 6.2 52.0 2 1/3 1.8 2.4 3.4 CRHEATER114A00,116A00 29.0 41.8 56.5 60
7.6 51.5 6.2 52.0 2 1/3 1.8 3.9 7.4 - - - 26.7 30
7.6 51.5 6.2 52.0 2 1/3 1.8 3.9 7.4 CRHEATER116A00 9.7 13.9 26.7 30
7.6 51.5 6.2 52.0 2 1/3 1.8 3.9 7.4 CRHEATER113A00 11.5 16.5 29.9 30
High
7.6 51.5 6.2 52.0 2 1/3 1.8 3.9 7.4 CRHEATER114A00 19.3 27.9 44.1 45
7.6 51.5 6.2 52.0 2 1/3 1.8 3.9 7.4 CRHEATER115A00 22.9 33.1 50.6 60
7.6 51.5 6.2 52.0 2 1/3 1.8 3.9 7.4 CRHEATER114A00,116A00 29.0 41.8 61.5 70
Page 25
Electrical Data (Continued)
50TCM Compressor
OFM IFM Electric Heater
Drive Power No.1 No.2
MCA MOCP
Unit Size package Supply Application
Indoor Motor V / Ph / Hz RLA LRA RLA LRA Qty HP FLA HP FLA Heater P.N FLA
(KW)
7.8 51.5 7.8 51.5 1 1 3.4 2.0 2.6 - - - 23.6 30
7.8 51.5 7.8 51.5 1 1 3.4 2.0 2.6 CRHEATER116A00 9.7 13.9 23.6 30
7.8 51.5 7.8 51.5 1 1 3.4 2.0 2.6 CRHEATER113A00 11.5 16.5 23.9 30
Standard
7.8 51.5 7.8 51.5 1 1 3.4 2.0 2.6 CRHEATER114A00 19.3 27.9 38.1 40
7.8 51.5 7.8 51.5 1 1 3.4 2.0 2.6 CRHEATER115A00 22.9 33.1 44.6 45
7.8 51.5 7.8 51.5 1 1 3.4 2.0 2.6 CRHEATER114A00,116A00 29 41.8 55.5 60
7.8 51.5 7.8 51.5 1 1 3.4 3.1 4.4 - - - 25.4 30
7.8 51.5 7.8 51.5 1 1 3.4 3.1 4.4 CRHEATER116A00 9.7 13.9 25.4 30
7.8 51.5 7.8 51.5 1 1 3.4 3.1 4.4 CRHEATER113A00 11.5 16.5 26.1 30
D12 Medium 400/3/50
7.8 51.5 7.8 51.5 1 1 3.4 3.1 4.4 CRHEATER114A00 19.3 27.9 40.4 45
7.8 51.5 7.8 51.5 1 1 3.4 3.1 4.4 CRHEATER115A00 22.9 33.1 46.9 50
7.8 51.5 7.8 51.5 1 1 3.4 3.1 4.4 CRHEATER114A00,116A00 29 41.8 57.8 60
7.8 51.5 7.8 51.5 1 1 3.4 4.2 9.8 - - - 30.8 35
7.8 51.5 7.8 51.5 1 1 3.4 4.2 9.8 CRHEATER116A00 9.7 13.9 30.8 35
7.8 51.5 7.8 51.5 1 1 3.4 4.2 9.8 CRHEATER113A00 11.5 16.5 32.9 35
High
7.8 51.5 7.8 51.5 1 1 3.4 4.2 9.8 CRHEATER114A00 19.3 27.9 47.1 50
7.8 51.5 7.8 51.5 1 1 3.4 4.2 9.8 CRHEATER115A00 22.9 33.1 53.6 60
7.8 51.5 7.8 51.5 1 1 3.4 4.2 9.8 CRHEATER114A00,116A00 29 41.8 64.5 70
9.7 64.0 10.6 74.0 1 1 3.4 2.4 3.4 - - - 29.5 35
9.7 64.0 10.6 74.0 1 1 3.4 2.4 3.4 CRHEATER116A00 9.7 13.9 29.5 35
9.7 64.0 10.6 74.0 1 1 3.4 2.4 3.4 CRHEATER113A00 11.5 16.5 29.5 35
Standard
9.7 64.0 10.6 74.0 1 1 3.4 2.4 3.4 CRHEATER114A00 19.3 27.9 39.1 40
9.7 64.0 10.6 74.0 1 1 3.4 2.4 3.4 CRHEATER115A00 22.9 33.1 45.6 50
9.7 64.0 10.6 74.0 1 1 3.4 2.4 3.4 CRHEATER114A00,116A00 29 41.8 56.5 60
9.7 64.0 10.6 74.0 1 1 3.4 3.9 7.4 - - - 33.5 40
9.7 64.0 10.6 74.0 1 1 3.4 3.9 7.4 CRHEATER116A00 9.7 13.9 33.5 40
9.7 64.0 10.6 74.0 1 1 3.4 3.9 7.4 CRHEATER113A00 11.5 16.5 33.5 40
D14 Medium 400/3/50
9.7 64.0 10.6 74.0 1 1 3.4 3.9 7.4 CRHEATER114A00 19.3 27.9 44.1 45
9.7 64.0 10.6 74.0 1 1 3.4 3.9 7.4 CRHEATER115A00 22.9 33.1 50.6 60
9.7 64.0 10.6 74.0 1 1 3.4 3.9 7.4 CRHEATER114A00,116A00 29 41.8 61.5 70
9.7 64.0 10.6 74.0 1 1 3.4 4.2 9.8 - - - 35.9 45
9.7 64.0 10.6 74.0 1 1 3.4 4.2 9.8 CRHEATER116A00 9.7 13.9 35.9 45
9.7 64.0 10.6 74.0 1 1 3.4 4.2 9.8 CRHEATER113A00 11.5 16.5 35.9 45
High
9.7 64.0 10.6 74.0 1 1 3.4 4.2 9.8 CRHEATER114A00 19.3 27.9 47.1 50
9.7 64.0 10.6 74.0 1 1 3.4 4.2 9.8 CRHEATER115A00 22.9 33.1 53.6 60
9.7 64.0 10.6 74.0 1 1 3.4 4.2 9.8 CRHEATER114A00,116A00 29 41.8 64.5 70
Maximum Deviation From Average Voltage Determine maximum deviation from average voltage.
= 100 X
Average Voltage (AB) 397 - 392 =5v
(BC) 404 - 397 =7v
Example: Supply Voltage is 400V - 3ph - 60Hz (AC) 457 - 397 =2v
AB = 392v Average Maximum Deviation is 7v.
BC = 404v Voltage = Determine Percentage Voltage Imbalance.
AC = 395v % Voltage 7
= 100 = 1.76%
Imbalance 397
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%
IMPORTANT: If the supply voltage phase imbalance is more than 2% contact your local electric utility company
Page 26
Page 27
Page 28
Page 29
Page 30
Page 31
APPLICATION DATA
Min operating ambient temp (cooling)
In mechanical cooling mode, your Carrier rooftop can safely operate down to an outdoor ambient temperature of
40°F (4°C) and 25°F (- 4°C), with an accessory winter start kit.
The maximum operating ambient temperature for cooling mode is 125°F (52°C).
Airflow
Due to Carrier’s internal unit design, air path, and specially designed motors, the full horsepower (maximum
continuous BHP) band, can be used with the utmost confidence. There is no need for extra safety factors, as
Carrier’s motors are designed and rigorously tested to use the entire, listed BHP range without either
nuisance tripping or premature motor failure.
Sizing a rooftop
Bigger isn’t necessarily better. While an air conditioner needs to have enough capacity to meet the load, it doesn’t
need excess capacity. In fact, having excess capacity typically results in very poor part load performance and
humidity control.
Using higher design temperatures than ASHRAE recommends for your location, adding “safety factors” to the
calculated load, and rounding up to the next largest unit, are all signs of oversizing air conditioners. Oversizing can
cause short-cycling, and short cycling leads to poor humidity control, reduced efficiency, higher utility bills, drastic
indoor temperature swings, excessive noise, and increased wear and tear on the air conditioner.
Rather than oversizing an air conditioner, wise contractors and engineers “right-size” or even slightly undersize air
conditioners. Correctly sizing an air conditioner controls humidity better; promotes efficiency; reduces utility bills;
extends equipment life, and maintains even, comfortable temperatures.
Winter start
Carrier’s winter start kit extends the low ambient limit of your rooftop to 25°F (- 4°C). The kit bypasses the low
pressure switch, preventing nuisance tripping of the low pressure switch. Other low ambient precautions may still
be prudent.
Page 32
GUIDE SPECIFICATIONS - 50TCM
Cooling Only/Electric Heat Packaged Rooftop
HVAC Guide Specifications
Size Range: 6 to 12.5 Nominal Tons
System Description
Small-Capacity Self-Contained Air Conditioners (50TCM)
Outdoor, rooftop mounted, electrically controlled, heating and cooling unit utilizing hermetic scroll
compressor(s) for cooling duty and electric for heating duty.
Quality Assurance
1. Unit shall achieve ASHRAE 90.1 minimum efficiency requirements (2010 version).
2. Unit shall be designed to conform to ASHRAE 15, 2001.
3. Unit shall be rated in accordance with AHRI Standards 210/240 and 340/360.
4. Insulation and adhesive shall meet NFPA 90A requirements for flame spread and smoke generation.
5. Unit casing shall be capable of withstanding 500 hour salt spray exposure per ASTM B117 (scribed
specimen).
6. Unit shall be designed in accordance with ISO 9001:2000, and shall be manufactured in a registered ISO
9001:2000 facility.
7. Unit shall be subjected to a completely automated run test on the assembly line. The data for each unit
will be stored at the factory, and must be available upon request.
8. Unit shall be designed in accordance with UL Standard 1995, including tested to withstand rain.
Product General
1. Factory assembled, single piece heating and cooling rooftop unit. Contained within the unit enclosure shall
be all factory wiring, piping, controls, and special features required prior to field start up.
2. Unit shall use environmentally safe, Puron refrigerant.
3. Unit shall be installed in accordance with the manufacturer’s instructions.
4. Unit must be selected and installed in compliance with local, state, and federal codes.
5. Interior cabinet surfaces shall be insulated with closed cell foam minimum ½ -in. thick, minimum density
3
3.1lb/ft .
Unit Cabinet
1. Unit cabinet shall be constructed of galvanized steel, and shall be bonderized and coated with a pre
painted baked enamel finish on all externally exposed surfaces.
2 . Unit cabinet exterior paint shall be: film thickness, (dry) 76mm minimum, gloss (per ASTM D523, 60°F):
60, Hardness: H 2H Pencil hardness.
3 . Evaporator fan compartment interior cabinet insulation shall conform to AHRI Standards 210/240 or
340/360 minimum exterior sweat criteria.
4. Base of unit shall have a minimum of four locations for thru the base gas and electrical connections
(factory installed or field installed), standard.
5. Base Rail
a) Unit shall have base rails on a minimum of 2 sides.
b) Holes shall be provided in the base rails for rigging shackles to ease maneuvering and overhead rigging.
c) Holes shall be provided in the base rail for moving the rooftop by fork truck.
d) Base rail shall be a minimum of 16 gauge thickness.
6. Condensate pan and connections:
a) Shall be a sloped condensate drain pan made of a non corrosive material.
b) Shall comply with ASHRAE Standard 62.
c) Shall use a 3/4” 14 NPT drain connection, possible either through the bottom or end of the drain pan.
Connection shall be made per manufacturer’s recommendations.
7. Top panel:
Shall be a single piece top panel on 07 size, two piece on 08 thru 14 size.
8. Electrical Connections:
All unit power wiring shall enter unit cabinet at a single, factory prepared, knock out location.
Page 33
9. Component access panels (standard):
a) Cabinet panels shall be easily removable for servicing.
b) Unit shall have one factory installed; tool less, removable, filter access panel.
c) Panels covering control box, indoor fan, indoor fan motor, and compressors shall have molded composite
handles.
d) Handles shall be UV modified, composite, permanently attached, and recessed into the panel.
e) Screws on the vertical portion of all removable access panels shall engage into heat resistant, molded
composite collars.
f) Collars shall be removable and easily replaceable using manufacturer recommended parts.
Coils
Standard Aluminum fin Copper Tube Coils:
1. Standard evaporator and condenser coils shall have aluminum lanced plate fins mechanically bonded to
seam- less internally grooved copper tubes with all joints brazed.
2. Evaporator coils shall be leak tested to 150 psig, pressure tested to 450 psig, and qualified to UL 1995
burst test at 1775 psig.
3. Condenser coils shall be leak tested to 150 psig, pressure tested to 450 psig, and qualified to UL 1995 burst
test at 1980 psig.
Refrigerant Components
1. Refrigerant circuit shall include the following control, safety, and maintenance features:
a) Fixed orifice metering system shall prevent mal distribution of two phase refrigerant by including multiple
fixed orifice devices in each refrigeration circuit. Each orifice is to be optimized to the coil circuit it
serves.
b) Refrigerant filter drier.
c) Service gauge connections on suction and discharge lines.
2. There shall be gauge line access, covered cap:
a) The plug shall be easy to remove and replace.
b) When the plug is removed, the gauge access port shall enable maintenance personnel to route their
pressure gauge lines.
c) This gauge access port shall facilitate correct and accurate condenser pressure readings by enabling the
reading with the compressor access panel on.
d) The plug shall be made of a leak proof, UV resistant, composite material.
3. Compressors:
a) Unit shall use one fully hermetic, scroll compressor for each independent refrigeration circuit.
b) Compressor motors shall be cooled by refrigerant gas passing through motor windings.
c) Compressors shall be internally protected from high discharge temperature conditions.
d) Compressors shall be protected from an over temperature and over amperage conditions by an internal,
motor overload device.
e) Compressor shall be factory mounted on rubber grommets.
f) Compressor motors shall have internal line break thermal, current overload and high pressure differential
protection.
g) Crankcase heaters shall not be required for normal operating range, unless provided by compressor
manufacturer due to refrigerant charge limits.
Condenser Fans:
1. Shall be a direct driven propeller type fan.
2. Shall have aluminum blades riveted to corrosion resistant steel spiders and shall be dynamically balanced.
Safeties:
1. Compressor over-temperature, over current.
2. Low pressure switch:
a. Units with 2 compressors shall have different sized connectors for the circuit 1 and circuit 2 low and high
pressure switches. They shall physically prevent the cross wiring of the safety switches between circuits 1
and 2.
b. Low pressure switch shall use different color wire than the high pressure switch. The purpose is to assist
the installer and service technician to correctly wire and or troubleshoot the rooftop unit.
3. High pressure switch:
a. Units with 2 compressors shall have different sized connectors for the circuit 1 and circuit 2 low and high
pressure switches. They shall physically prevent the cross wiring of the safety switches between circuits 1
and 2.
b. High pressure switch shall use different color wire than the low pressure switch. The purpose is to assist
the installer and service technician to correctly wire and or troubleshoot the rooftop unit.
4. Automatic reset, motor thermal overload protector.
Filter Section
1. Filters access is specified in the unit cabinet section of this specification.
2. Filters shall be held in place by a pivoting filter tray, facilitating easy removal and installation.
3. Shall consist of factory installed, low velocity, throw away 2 in. thick fiberglass filters.
4. Filters shall be standard, commercially available sizes.
5. Only one size filter per unit is allowed.
Operating Characteristics
1. Unit shall be capable of starting and running at 125°F (52°C) ambient outdoor temperature, meeting
maximum load criteria of AHRI Standard 210/240 or 340/360 at ± 10% voltage.
2. Compressor with standard controls shall be capable of operation down to 40°F (4°C), ambient outdoor
temperatures. Accessory winter start kit is necessary if mechanically cooling at ambient temperatures
down to 25°F (-- 4°C).
3. Unit shall discharge supply air horizontally as shown on contract drawings.
4. Unit shall be factory configured for horizontal supply and return configurations.
Thermostats
Thermostat must:
1. Energize both “W” and “G” when calling for heat.
2. Have capability to energize 2 different stages of cooling, and 2 different stages of heating.
3. Include capability for occupancy scheduling.
Electrical Requirements
Main power supply voltage, phase, and frequency must match those required by the manufacturer.
Page 35
Special Features: Options and Accessories
PremierLink controller:
1. Shall be ASHRAE 62-2001 compliant.
2. Shall accept 18-32VAC input power.
3. Shall have an operating temperature range from - 40°F (- 40°C) to 158°F (70°C), 10% - 95% RH (non-
condensing).
4. Controller shall accept the following inputs: space temperature, set point adjustment, outdoor air
temperature, indoor air quality, outdoor air quality, indoor relative humidity, compressor lock-out, fire
shutdown, enthalpy, fan status, remote time clock/door switch.
5. Shall accept a CO2 sensor in the conditioned space, and be Demand Control Ventilation (DCV) ready.
6. Shall provide the following outputs: Fan, cooling stage 1, cooling stage 2, heat stage 1, heat stage 2, heat
stage 3/ exhaust/ occupied.
7. Unit shall provide surge protection for the controller through a field installed circuit breaker.
8. Shall be Internet capable, and communicate at a Baud rate of 38.4K or faster
9. Shall have an LED display independently showing the status of activity on the communication bus, and
processor operation.
10. Shall include an EIA-485 protocol communication port, an access port for connection of either a computer or
a Carrier technician tool, an EIA-485 port for network communication to intelligent space sensors and
displays, and a port to connect an optional LonWorks plug-in communications card.
11. Shall have built-in Carrier Comfort Network (CCN) protocol, and be compatible with other CCN devices,
including ComfortLink and ComfortVIEW controllers.
12. Shall have built-in support for Carrier technician tool.
13. Software upgrades will be accomplished by local download. Software upgrades through chip replacements
are not allowed.
14. Shall be shock resistant in all planes to 5G peak, 11ms during operation, and 100G peak, 11ms during
storage.
15. Shall be vibration resistant in all planes to 1.5G @ 20-300 Hz.
16. Shall support a bus length of 4000 ft max, 60 devices per 1000 ft section, and 1 RS-485 repeater per 1000ft
sections.
Manual damper:
Manual damper package shall consist of damper, air inlet screen, and rain hood which can be preset to admit up
to 50% outdoor air for year round ventilation.
Page 36
Head Pressure Control Package:
1. Controller shall control coil head pressure by condenser fan speed modulation or condenser fan cycling and
wind baffles.
2. Shall consist of solid state control and condenser coil temperature sensor to maintain condensing
temperature between 90°F (32°C) and 110°F (43°C) at outdoor ambient temperatures down to - 20°F
(- 29°C).
Smoke detectors:
1. Shall be a Four Wire Controller and Detector.
2. Shall be environmental compensated with differential sensing for reliable, stable, and drift free sensitivity.
3. Shall use magnet activated test/reset sensor switches.
4. Shall have tool less connection terminal access.
5. Shall have a recessed momentary switch for testing and resetting the detector.
6. Controller shall include:
a) One set of normally open alarm initiation contacts for connection to an initiating device circuit on a fire
alarm control panel.
b) Two Form C auxiliary alarm relays for interface with rooftop unit or other equipment.
c) One Form C supervision (trouble) relay to control the operation of the Trouble LED on a remote test/reset
station.
d) Capable of direct connection to two individual detector modules.
e) Can be wired to up to 14 other duct smoke detectors for multiple fan shutdown applications.
Time Guard:
1. Shall prevent compressor short cycling by providing a 5 minute delay (±2 minutes) before restarting a
compressor after shutdown for any reason.
2. One device shall be required per compressor.
Electric Heat:
1. Heater element open coil resistance wire, nickel chrome alloy, 0.29 inches inside diameter, strung through
ceramic insulators mounted on metal frame. Coil ends are staked and welded to terminal screw slots.
2. Heater assemblies are provided with integral fusing for protection of internal heater circuits. Auto reset
thermo limit controls, magnetic heater contactors (24V coil) and terminal block all mounted in electric
heater control box (minimum 18 ga galvanized steel) attached to end of heater assembly.
Page 37
Notes
Page 38
Notes
Page 39
Manufacturer reserves the rights to discontinue or change at any time, specifications or designs without notice and without incurring any obligations.
Supersedes Version: N/A Page 40 Catalog Number: 50TCM-PDC01
Effective Date: 11-02-2015 Phase: 50Hz