Zero Sequence Behaviour of A Double-Circuit Overhead Line
Zero Sequence Behaviour of A Double-Circuit Overhead Line
a r t i c l e i n f o a b s t r a c t
Article history: Positive, negative and zero sequence series impedances (in /km units) are the first step for power flow
Received 19 November 2013 and short circuit analyses and are also necessary for setting the distance relays. The paper is devoted to
Received in revised form 11 June 2014 the computation of zero sequence series impedance (in /km units) (self and mutual) in double-circuit
Accepted 13 July 2014
overhead lines (OHLs) with one or more earth wires. A systematic comparison with matrix approaches
demonstrates that IEC 60909-2 formula adds the zero sequence self and the zero sequence mutual
Keywords:
impedance between the two circuits. This approximation of having a unique value of zero sequence
Sequence impedances
impedance is misleading and gives great errors when phase-to-ground short circuit occurs along a cir-
Double-circuit OHL
Multiconductor Cell Analysis
cuit. It is worth noting that the zero sequence mutual impedance between parallel circuits installed on
Clarke’s equivalent circuit the same tower may be as high as 50% (or more) of the zero sequence self impedance of a circuit alone.
Consequently, zero sequence mutual impedance between the two circuits cannot be neglected or mixed.
MCA (Multiconductor Cell Analysis) shows that the simplified IEC approach underestimates heavily (more
than 18%, depending upon the spacing between the circuits) the phase-to-ground fault current for a fault
occurrence along one circuit of the double circuit.
© 2014 Published by Elsevier B.V.
http://dx.doi.org/10.1016/j.epsr.2014.07.011
0378-7796/© 2014 Published by Elsevier B.V.
420 R. Benato et al. / Electric Power Systems Research 116 (2014) 419–426
Table 1
Nomenclature Data assumed in the MCA of 400 kV double-circuit OHL in UK grid.
7
IEW
0.3 7, EW 0.3
1
I0
6.93 m 6.93 m I0 2
0.3 0.3 I0 3
1, R 4, T I0 circuit a
10.16 m 10.16 m I0
2, S 0.3 0.3 5, S I0 4
Fig. 1. National Grid UK typical double-circuit overhead line (not to scale) with
asymmetric phasing (RST-TSR also called low-reactance phasing). Fig. 2. Zero sequence scheme of a double circuit OHL with one earth wire.
R. Benato et al. / Electric Power Systems Research 116 (2014) 419–426 421
applied. This yields the reduced matrix Zph red which includes the It is possible to demonstrate that Eqs. (2) and (3) can be re-
effect of the earth wire: written as:
Z ph red
z 2ca ew
z0 ca = z0 − 3 · ˝/km (4)
z11 z 12 z 13 z 14 z 15 z 16 z ew
z
21 z 22 z 23 z 24 z 25 z 26 z 2ca ew
z0 = 3 · zm −3· ˝/km (5)
z z 36
a b ca cb
z ew
31 z 32 z 33 z 34 z 35
z41 z 42 z 43 z 44 z 45 z 46 where z0 = z11 + z12 + z13 [/km] is the zero sequence impedance of
one circuit; zca ew [/km] is the mutual impedance between circuit
z51 z 52 z 53 z 54 z 55 z 56
a (phases 1, 2 and 3) and the earth wire ew; zew [/km] is the self
z z 62 z 63 z 64 z 65 z
impedance of earth wire ew; zm ca cb [/km] is the average mutual
61 66
impedance between the phases of circuits a and b.
By applying three equal current generators I0 [12] to one circuit If in Fig. 2 the zero sequence current generators are imposed at
of the double-circuit it is possible, after some passages, to compute both circuits, there is a mix of zero sequence self impedances with
both the zero sequence self impedance of the supplied circuit and zero sequence mutual ones namely:
the mutual one between the two circuits by means of:
Z ph red
Z ph red
U 01 z11 z 16 I
z 16 I
z 12 z 13 z 14 z 15
U 01 z11 z 12 z 13 z 14 z 15 0
0 U z
U z
z 26 I 02 21 z 22 z 23 z 24 z 25 z 26 I 0
02 21 z 22 z 23 z 24 z 25
0 U z z 36 I 0
U z z 36 I 03 31 z 32 z 33 z 34 z 35
03 31 z 32 z 33 z 34 z 35 = ·
= · 0 U 04 z41 z 42 z 43 z 44 z 45 z 46 I 0
U 04 z41 z 42 z 43 z 44 z 45 z 46 0
U 05 z51 z 56 I 0
z 56 0
z 52 z 53 z 54 z 55
U 05 z51 z 52 z 53 z 54 z 55
U z I
U z z 62 z 63 z 64 z 65 z
0 06 61 z 62 z 63 z 64 z 65 z66 0
06 61 66
z01 + z0m1 cb
z11 + z12 + z13 z01
z +z
z +z +z z 02 0m2 cb
21 22 23 02
z +z
z +z +z z 03 0m3 cb
31 32 33 03 = ·I (6)
= · I0 = ·I z0m4 ca + z04 0
z41 + z42 + z43 z0m4 ca 0
z0m5 ca + z05
z51 + z52 + z53 z0m5 ca
z
z +z +z z 0m6 ca+z 06
61 62 63 0m6 ca
The three zero sequence self impedances are different for each Therefore in the (6 × 1) column of the matrix in (6), it is impos-
conductor 1, 2 and 3 and are given by: sible to have a clear distinction between the zero sequence self
and the mutual impedances. The average value of the six elements
U 01 U 02 U 03 inside the column can be expressed as:
z 01 = ; z 02 = ; z 03 =
I0 I0 I0
In order to have a unique zero sequence self impedance of the z 2ca ew
z 0 av = z 0 + 3 · z m ca cb −6· (7)
circuit, this average value can be computed: z ew
Fig. 5. Zero sequence circuit with “manifested” mutual impedances. Fig. 6. Phase-to-ground short circuit occurring at midline.
R. Benato et al. / Electric Power Systems Research 116 (2014) 419–426 423
Table 2
Comparison values.
I1p at the midline [kA] I1p at sending-end [kA] I1p at receiving-end [kA]
Over a period of many years, the Central Electricity Generat- The measured impedances for a double-circuit 400 kV line are
ing Board (CEGB) in the UK, the predecessor of National Grid summarized in Table 3, and compared with the calculated values
Electricity Transmission (NGET), carried out impedance on the base of data in Table 1.
424 R. Benato et al. / Electric Power Systems Research 116 (2014) 419–426
Table 3
A
Comparison between measured and calculated values.
Zaa Za= Zaa - Zab
Parameter (/km) 400 kV double-circuit OHL, 4 mm × 400 mm A
C Zc=Zab
Measured Calculated
Zab
C
zS 0.041 + j0.424 0.0474 + j0.4466
zM 0.023 + j0.148 0.0305 + j0.1683 Zbb B Zb= Zbb - Zab
z1 0.018 + j0.276 0.0168 + j0.2783
z0 0.087 + j0.720 0.1084 + j0.7832 1) B 2)
z0M 0.079 + j0.380 0.0914 + j0.4153
Fig. B1. Transformation from circuit (1) with “embedded” mutual impedance to
circuit (2) with “manifested” mutual impedance.
Appendix B. Equivalent circuits taking zero sequence Solving this system, it is possible to obtain the values of Za , Zb
mutual impedance into account and Zc of the equivalent wye circuit:
3 2
In the equivalent circuit the impedance is Za + Zb . Z 0 = 1.1 · E PV · − (C.4)
I 1P I 3P
The three equations expressing Za , Zb and Zc in terms of Zaa , Zbb
and Zab are: Once the diagonal sequence matrix ZS has been computed, it
is easy to compute the phase matrix Zpha by means of Fortescue
Z aa = Z a + Z c matrix F (as clearly shown in Appendix A). Once the YTOT has been
Z bb = Z b + Z c computed the faulty regime can be evaluated with a suitable par-
Z aa + Z bb − 2Z ab = Z a + Z b tition of it as in Fig. C1.
426 R. Benato et al. / Electric Power Systems Research 116 (2014) 419–426
The study of short circuit leads to the following equations: [4] R. Benato, Multiconductor analysis of underground power transmission sys-
tems: EHV AC cables, Elect. Power Syst. Res. 79 (January (1)) (2009) 27–38,
iphaS = Y 1 uphaS + Y 2 ux + Y 3 uphaR (C.5) http://dx.doi.org/10.1016/j.epsr.2008.05.016.
[5] R. Benato, L. Caciolli, Sequence impedances of insulated cables:
0 = Y 4 uphaS + Y 5 ux + Y 6 uphaR (C.6) measurements versus computations, in: Transmission and Distribu-
tion Conference and Exposition (T&D), IEEE PES, Orlando, FL, 2012,
iphaR = Y 7 uphaS + Y 8 ux + Y 9 uphaR (C.7) http://dx.doi.org/10.1109/TDC.2012.6281574.
[6] R. Benato, M. Forzan, M. Marelli, A. Orini, E. Zaccone, Harmonic
where the vector ix is null (see Fig. C1). From Eq. (C.6), it is rather behaviour of HVDC cables, Elect. Power Syst. Res. 89 (2012) 215–222,
immediate to obtain the unknown vector ux : http://dx.doi.org/10.1016/j.epsr.2012.03.012.
[7] IEC 60909-2. Short-circuit currents in three-phase A.C. systems. Part 2: Data of
ux = −Y 5 −1 · (Y 4 uphaS + Y 6 uphaR ) (C.8) electrical equipment for short-circuit current calculations, 2nd ed., 2008–2011.
[8] British Electricity International Modern Power Station Practice, EHV Transmis-
If Y5 is of large dimensions, its inversion can benefit from the sion, Permagon, Oxford, UK, 1991.
[9] R. Benato, A. Paolucci, EHV AC Undergrounding electrical power. Performance
partition techniques and parallel computing [3]. and planning Series: Power Systems, Springer, 2010, ISBN 978-1-84882-866-7
(translated also in Chinese).
[10] J.R. Carson, Wave propagation in overhead wires with ground return, Bell Syst.
References Tech. J. 5 (1926) 539–554.
[11] G. Kron, Tensor Analysis of Networks, John Wiley & Sons, Inc., New York, 1939.
[1] F. Calero, Mutual impedance in parallel lines – protective relaying and fault [12] C.L. Fortescue, Method of symmetrical co-ordinates applied to the solution of
location considerations, in: Proceedings of 4th International Conference on polyphase networks, AIEE Trans. 37 (Part II) (1918) 1027–1140.
Power System Protection and Automation, November, New Delhi, India, 2007, [13] F.M. Gatta, F. Iliceto, S. Lauria, New Formulae for the computation of zero
pp. I1–I30. sequence impedance of EHV overhead lines, L’Energia Elettrica 79 (2002) (in
[2] P.G. McLaren, I. Fernando, H. Liu, E. Dirks, G.W. Swift, C. Steele, Enhanced double Italian).
circuit line protection, IEEE Trans. Power Deliv. 12 (July (1)) (1997) 1100–1108. [14] E. Clarke, Circuit analysis of a-c power systems Symmetrical and Related Com-
[3] R. Benato, S. Dambone Sessa, F. Guglielmi, Determination of steady-state and ponents, 1, J. Wiley & Sons, 1950.
faulty regimes of overhead lines by means of multiconductor cell analysis [15] IEC 60909-0. Short-circuit currents in three-phase A.C. systems. Part 0: Calcu-
(MCA), Energies 5 (2012) 2771–2793, http://dx.doi.org/10.3390/en5082771. lation of currents, 1st ed., 2001–2007.