Cooling Methods of A Transformer From IEC 60076 - Part-2
Cooling Methods of A Transformer From IEC 60076 - Part-2
Cooling methods
1.1. Identification symbols
Transformers shall be identified according to the cooling method employed. For liquid-immersed transformers, this
identification is expressed by a four-letter code as described below.
First letter: Internal cooling medium:
− A: air
− W: water
Fourth letter: Circulation mechanism for external cooling medium:
− N: natural convection
− F: forced circulation (fans, pumps)
NOTE: In this standard, the use of insulating liquids K and L is considered only for safety and environmental
reasons.
NOTE:
− In a transformer designated as having forced directed insulating liquid circulation (second code letter D),
the rate of liquid flow through the main windings is determined by the pumps and is not, in principle, determined by
the loading.
− A minor fraction of the flow of liquid through the cooling equipment may be directed as a controlled bypass to
provide cooling for core and other parts outside the main windings.
− Regulating windings and/or other windings having relatively low power may also have non-directed circulation of
bypass liquid.
− In a transformer with forced, non-directed cooling (second code letter F), the rates of flow of liquid through all the
windings are variable with the loading, and not directly related to the pumped flow through the cooling equipment.
− ONAN/ONAF. The transformer has a set of fans which may be put into service as desired at high loading. The
insulating liquid circulation is by thermosiphon effect only, in both cases.
− ONAN/OFAF. The transformer has cooling equipment with pumps and fans but is also specified with a reduced
rated power under natural cooling (for example, in case of failure or reduction of auxiliary power).
2. Normal cooling conditions
2.1. Air-cooled transformers
Normal ambient temperature limits for power transformers are given in IEC 60076-1. With regard to normal
temperature rise requirements, the temperatures at the intended installation site should not exceed:
− + 40 °C at any time
− + 30 °C monthly average, of the hottest month
− + 20 °C yearly average.
NOTE: The average temperatures are to be derived from meteorological data as follows (refer IEC 60076-1).
Monthly average temperature:
– half the sum of the average of the daily maxima and the average of the daily minima during a particular month, over many
years;
Yearly average temperature:
– one-twelfth of the sum of the monthly average temperatures.