0% found this document useful (0 votes)
282 views50 pages

P V ™ PD6200 Analog Input Flow Rate/Totalizer: Instruction Manual

LIM-6200
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
282 views50 pages

P V ™ PD6200 Analog Input Flow Rate/Totalizer: Instruction Manual

LIM-6200
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 50

PROVU™ PD6200 Analog Input Flow Rate/Totalizer

Instruction Manual

MeterView Pro
USB Install

• 1/8 DIN Digital Panel Flow Rate/Totalizers with NEMA 4X, IP65 Front
• 0-20 mA, 4-20 mA, 0-5 V, 1-5 V, and ±10 V Inputs
• Dual-Line 6-Digit Display, 0.6" (15 mm) & 0.46" (12 mm)
• Isolated 24 VDC @ 200 mA Transmitter Power Supply
• 2 or 4 Relays with Interlocking Capability + Isolated 4-20 mA Output Options
• Free PC-Based, On-Board, MeterView Pro USB Programming Software
• No Assembly Required
• Display Rate & Total at the Same Time
• Rate in Units per Second, Minute, Hour, or Day
• Total, Grand Total or Non-Resettable Grand Total
• Front Panel or Remote Total Reset
• Password Protection for Total Reset
• Total Stored in Non-Volatile Memory
• Assign Any Relay for Rate or Total
• 4-20 mA Output for Rate or Total
• Sampling Relay
• Display Open Channel Flow with Programmable Exponent Feature
• 32-Point Linearization & Square Root Extraction
• Optional SunBright Display Models for Outdoor Applications
• Operating Temperature Range: -40 to 65°C (-40 to 149°F)
• UL & C-UL Listed. E160849; 508 Industrial Control Equipment
• Input Power Options: 85-265 VAC / 90-265 VDC or 12-24 VDC / 12-24 VAC
• Programmable Display, Function Keys & Digital Input
• External 4-Relay & Digital I/O Modules
• RS-232 & RS-485 Serial Communication Options with Modbus RTU
• Wide Assortment of NEMA 4X Enclosures for up to Ten Meters
• Light / Horn & Reset Button Accessory
• Control Station Accessory for Remote Operation of PROVU
• 3-Year Warranty

PRECISION DIGITAL CORPORATION


233 South Street • Hopkinton MA 01748 USA
Tel (800) 343-1001 • Fax (508) 655-8990
www.predig.com
PROVU™ PD6200 Analog Input Flow Rate/Totalizer Instruction Manual

Disclaimer
The information contained in this document is FREE MeterView Pro
subject to change without notice. Precision Digital
makes no representations or warranties with
Programming Software
respect to the contents hereof and specifically
disclaims any implied warranties of
merchantability or fitness for a particular purpose.
See Warranty Information and Terms &
Conditions on www.predig.com for complete
details.

• Read complete instructions prior to installation


and operation of the meter.

• Risk of electric shock or personal injury.


• This product is not recommended for life support
applications or applications where malfunctioning The meter can be powered from the USB connection. When
could result in personal injury or property loss. using the USB connection, DO NOT apply AC or DC power to
Anyone using this product for such applications the meter.
does so at his/her own risk. Precision Digital The easiest and quickest way to program your PROVU
Corporation shall not be held liable for damages meter is to use the FREE MeterView Pro
resulting from such improper use. programming software. This software is loaded into
the meter and connects and installs directly to your
PC with a USB cable. We recommend that the first
WARNING thing you do after taking the meter out of the box is
Cancer and Reproductive Harm - www.P65Warnings.ca.gov connect the PROVU to your PC with the provided USB
cable – do not use a different cable. DO NOT apply
Limited Warranty AC or DC power to the meter while your PC is
Precision Digital Corporation warrants this connected to the meter as it will disrupt the USB
product against defects in material or connection. You don’t even have to apply an input
workmanship for the specified period under signal.
“Specifications” from the date of shipment from MeterView Pro programming software is intuitive, and
the factory. Precision Digital’s liability under this most customers can get their meter programmed as
limited warranty shall not exceed the purchase they like without even looking in the manual.
value, repair, or replacement of the defective unit.
See Warranty Information and Terms &
Conditions on www.predig.com for complete Watch MeterView Pro Software Video at
details. www.predig.com/meterviewpro

Registered Trademarks
All trademarks mentioned in this document are In addition to programming, the software may be used
the property of their respective owners. for:
• Monitoring
© 2022 Precision Digital Corporation. • Datalogging using your PC
All rights reserved. • Generating and saving programming files for
later use
Once your meter is programmed the way you want it,
you can wire it up for your application per the
instructions in this manual and install it. If you find that
you need to make adjustments to the programming
after the meter is installed, you can use the front
panel buttons and the instructions in this manual to do
so.

2
PROVU™ PD6200 Analog Input Flow Rate/Totalizer Instruction Manual

Table of Contents
Introduction .......................................................................................................... 6
Using the PD6200 Like a PD6000 Process Meter ......................................... 6
Ordering Information ........................................................................................... 6
Specifications..................................................................................................... 10
General ........................................................................................................... 10
Process Input ................................................................................................. 11
Rate/Totalizer ................................................................................................. 11
Relays ............................................................................................................. 12
Isolated 4-20 mA Transmitter Output .......................................................... 12
USB Connection ............................................................................................ 13
On-Board Digital Input (F4) ........................................................................... 13
Modbus® RTU Serial Communications........................................................ 13
MeterView Pro Software................................................................................ 13
Compliance Information .................................................................................... 14
Safety .............................................................................................................. 14
Electromagnetic Compatibility ..................................................................... 14
EU Declaration of Conformity ........................................................................... 14
Safety Information ............................................................................................. 14
Installation .......................................................................................................... 14
Unpacking ...................................................................................................... 14
Panel Mounting Instructions ........................................................................ 15
Mounting Dimensions .................................................................................. 15
Installation Overview ..................................................................................... 16
MeterView Pro Software................................................................................ 16
MeterView Pro Installation........................................................................... 16
Transmitter Supply Voltage Selection (P+, P-) ........................................... 17
Connections ................................................................................................... 17
Connectors Labeling ................................................................................... 17
Power Connections ..................................................................................... 18
Signal Connections ..................................................................................... 18
Modbus RTU Serial Communications ......................................................... 18
Relay Connections ...................................................................................... 18
Switching Inductive Loads ........................................................................... 19
F4 Digital Input Connections ....................................................................... 19
4-20 mA Output Connections ...................................................................... 19
Analog Output Power Supply ...................................................................... 19
External Relay & Digital I/O Connections .................................................... 20
Remote Operation of Meter ......................................................................... 20
Interlock Relay Feature ............................................................................... 20
Setup and Programming ................................................................................... 21
Front Panel Buttons and Status LED Indicators ........................................ 21
Display Functions & Messages .................................................................... 22
Main Menu ...................................................................................................... 24
Setting Numeric Values ................................................................................ 24
Setting Up the Rate/Totalizer Meter (setup)................................................ 24
Setting the Input Signal (Input) .................................................................. 25
Setting the Totalizer Features (total) ........................................................ 25
Setting the Display Units or Custom Tags (units) ..................................... 25
Setting the Decimal Point (dEc.pt)............................................................... 26
Programming the Rate/Totalizer (prog) ...................................................... 26
Setting the Display Parameter & Intensity (dsplay) ................................... 29
Display Intensity (d-Inty) ........................................................................... 29
Setting the Relay Operation (relay) ........................................................... 30
Relay Assignment (Assign) ........................................................................ 30
Setting the Relay Action .............................................................................. 30
Programming Set and Reset Points ............................................................ 31
Setting Fail-Safe Operation ......................................................................... 31
Programming Time Delay............................................................................ 31
Relay Action for Loss of 4-20 mA Input (Loop Break) ................................. 31

3
PROVU™ PD6200 Analog Input Rate/Totalizer Instruction Manual

Relay and Alarm Operation Diagrams ......................................................... 32


High Alarm Operation (Set > Reset)................................................................ 32
Low Alarm Operation (Set < Reset) ............................................................ 32
High Alarm with Fail-Safe Operation (Set > Reset)..................................... 32
Low Alarm with Fail-Safe Operation (Set < Reset) ..................................... 32
Time Delay Operation ................................................................................. 33
Total Relay Sampling Operation ................................................................. 33
Relay Operation Details ................................................................................ 34
Overview ..................................................................................................... 34
Relays Auto Initialization ............................................................................. 34
Fail-Safe Operation ..................................................................................... 34
Front Panel LEDs ........................................................................................ 34
Latching and Non-Latching Relay Operation .............................................. 34
Non-Latching Relay (Auto) ......................................................................... 35
Non-Latching Relay with Manual Reset (A-nman) ....................................... 35
Latching Relay with Clear (LatcH) .............................................................. 35
Latching Relay (Lt-Clr) ............................................................................. 35
Acknowledging Relays ................................................................................ 36
Setting Up the Interlock Relay (Force On) Feature ..................................... 36
Scaling the 4-20 mA Analog Output (Aout) ................................................. 37
Reset Menu (reset) ....................................................................................... 37
Manual Control Menu (Contrl)..................................................................... 37
Setting Up the Password (pass) ................................................................... 38
Protecting or Locking the Meter .................................................................. 38
Total Reset Password & Non-Resettable Total ........................................... 38
Making Changes to a Password Protected Meter ....................................... 38
Disabling Password Protection.................................................................... 38
Advanced Features Menu ............................................................................. 39
Advanced Features Menu & Display Messages.......................................... 39
Noise Filter (filter) ................................................................................... 40
Noise Filter Bypass (bypass) ...................................................................... 40
Rounding Feature (round) .......................................................................... 40
Modbus RTU Serial Communications (serial) .......................................... 40
Select Menu (SElEct) ................................................................................. 41
Input Signal Conditioning (Functn) ............................................................. 41
Low-Flow Cutoff (CutofF) ........................................................................... 42
Totalizer Count Up/Down (Count) ............................................................... 42
Analog Output Programming (AoutPr) ....................................................... 43
Programmable Function Keys User Menu (user) ....................................... 44
Internal Source Calibration (ICAL) .............................................................. 45
Meter Operation ................................................................................................. 46
Front Panel Buttons Operation .................................................................... 46
Function Keys Operation .............................................................................. 46
F4 Operation .................................................................................................. 46
Maximum/Minimum Readings ...................................................................... 46
Totalizer Overflow Displays Total to 9 Digits.............................................. 46
Troubleshooting................................................................................................. 47
Diagnostics Menu (diag) .............................................................................. 47
Testing the Display LEDs ............................................................................ 47
Determining Software Version..................................................................... 47
Reset Meter to Factory Defaults ................................................................... 47
Factory Defaults & User Settings ................................................................ 48
Troubleshooting Tips .................................................................................... 49

4
PROVU™ PD6200 Analog Input Rate/Totalizer Instruction Manual

Table of Figures
Figure 1: 1/8 DIN Panel Cutout and Mounting ................................................. 15
Figure 2. Meter Dimensions - Side View .......................................................... 15
Figure 3. Meter Dimensions - Top View ........................................................... 15
Figure 4: Transmitter Supply Voltage Selection ............................................. 17
Figure 5. PD6200-##0 Connectors Label ......................................................... 17
Figure 6. PD6200-##2 Connectors Label ......................................................... 17
Figure 7. PD6200-##3 Connectors Label ......................................................... 17
Figure 8. PD6200-##4 Connectors Label ......................................................... 17
Figure 9. PD6200-##5 Connectors Label ......................................................... 17
Figure 10. PD6200-##7 Connectors Label ....................................................... 17
Figure 11. Power Connections ......................................................................... 18
Figure 12. Transmitter Powered by Internal Supply ....................................... 18
Figure 13. Transmitter Powered by External Supply or Self-Powered ......... 18
Figure 14. Voltage Input Connections ............................................................. 18
Figure 15. Relay Connections........................................................................... 18
Figure 16. AC and DC Loads Protection .......................................................... 19
Figure 17. Low Voltage DC Loads Protection ................................................. 19
Figure 18. F4 Digital Input Connections .......................................................... 19
Figure 19. 4-20 mA Output Connections ......................................................... 19
Figure 20. Analog Output Supply Powering Other Devices........................... 19
Figure 21. Expansion Module & DIN Rail Mounting Kit .................................. 20
Figure 22. External Relays Module Connections ............................................ 20
Figure 23. Digital I/O Module Connections ...................................................... 20
Figure 24. Meter to Control Station Connection ............................................. 20
Figure 25. Interlock Connection ....................................................................... 20

5
PROVU™ PD6200 Analog Input Rate/Totalizer Instruction Manual

Introduction Ordering Information


Front, back and in between, the PROVU meter boasts Standard Models
specifications, features and functionality that make it 85-265 VAC 12-24 VDC
the only 1/8 DIN analog input flow rate/totalizer you Options Installed
Model Model
will ever need. The number one feature that makes PD6200-6R0 PD6200-7R0 No options
the PROVU such a useful device is its built-in 24 VDC
PD6200-6R2 PD6200-7R2 2 relays
@ 200 mA power supply to drive the transmitter. This
feature not only saves the cost of an external power PD6200-6R3 PD6200-7R3 4-20 mA output
supply, but also greatly simplifies wiring. In addition, PD6200-6R4 PD6200-7R4 4 relays
there is a second 24 VDC @ 40 mA power supply PD6200-6R5 PD6200-7R5 2 relays & 4-20 mA output
provided with the 4-20 mA output option. PD6200-6R7 PD6200-7R7 4 relays & 4-20 mA output
The second most important feature about these
meters is they can display flow rate and total at the
SunBright Display Models
same time. In fact, the 6-digit dual line display can be 85-265 VAC 12-24 VDC
Options Installed
Model Model
programmed for a wide variety of flow applications,
including: flow rate and tag, total and tag, total and PD6200-6H0 PD6200-7H0 No options
grand total, and even non-resettable grand total. PD6200-6H2 PD6200-7H2 2 relays
Another reason why the PROVU Meter is the only flow PD6200-6H3 PD6200-7H3 4-20 mA output
rate/totalizer you will ever need is its NEMA 4X rated PD6200-6H4 PD6200-7H4 4 relays
front panel. This means you can install the PROVU in PD6200-6H5 PD6200-7H5 2 relays & 4-20 mA output
panels exposed to moisture, dust and other adverse PD6200-6H7 PD6200-7H7 4 relays & 4-20 mA output
conditions. The PROVU is also available with an
optional Sunbright display which means you can Accessories
install and read the PROVU in direct sunlight. Model Description
PDA1002 DIN rail mounting kit for two devices
Other key features include four relays and 4-20 mA
PDA1004 4 SPST (Form A) relays module
output option, remote total reset, advanced input
PDA1044 4 digital inputs & 4 digital outputs module
signal conditioning like square root extraction and
programmable exponent for open channel flow. PDA1232 RS-232 serial adapter
PDA1485 RS-485 serial adapter
Finally, all these features and capabilities can easily PDA7485-I RS-232 to RS-485 isolated converter
be programmed with free MeterView Pro software. PDA8008 USB Adapter
PDA8232-N USB to RS-232 non-isolated converter
PDA8485-I USB to RS-485 isolated converter
Using the PD6200 Like a PDA-LH Light / horn accessory
PD6000 Process Meter MOD-LH
PDA2360
Light / horn / enclosure modification
Plastic control stations series
The PD6200 is essentially a PD6000 process meter PD659 Signal isolators, splitters, & conditioners
with flow totalization capability. The flow totalization PD9501 Multi-function calibrator
capability can easily be de-activated for customers PD9502 Low-cost signal generator
that would prefer their PD6200 behave like a PD6000 PDX6901 Snubber: 0.01 μF/470 Ω, 250 VAC
process meter. For instructions on how to do this, see
Setting Up the Rate/Totalizer Meter (setup) on page Enclosures
24 for details. Series Meters Material
PDA2300 1-10 Plastic NEMA 4X
PDA2500 1-6 Plastic NEMA 4X
PDA2600 1-6 Stainless Steel NEMA 4X
PDA2700 1-6 Painted Steel NEMA 4
PDA2800 1-2 Plastic NEMA 4X
PDA3400 1-3 Plastic NEMA 4X

Need help selecting the right enclosure?


Go to www.predig.com/esu

Replacement Option Cards


Model Options Installed
PD1102 2 relays
PD1103 4-20 mA output
PD1104 4 relays
PD1105 2 relays & 4-20 mA output
PD1107 4 relays & 4-20 mA output

6
PROVU™ PD6200 Analog Input Flow Rate/Totalizer Instruction Manual

Light / Horn Accessories

PROVU Meter Shown in a PDA2301 Enclosure with MOD-LHRB1 Red Light / Horn and Button.
Meter & Enclosure Sold Separately. Assembly Required.

MOD-LH PDA-LH & PDA-BUTTON

Model Description Model Description


Red Light / Horn and Button with PDA-LHR Red Light / Horn
MOD-LHRB1
Holes Drilled in Enclosure(1) Green Light / Horn
PDA-LHG
Green Light / Horn and Button with
MOD-LHGB1 PDA-LHY Yellow Light / Horn
Holes Drilled in Enclosure(1)
Yellow Light / Horn and Button with PDA-LHB Blue Light / Horn
MOD-LHYB1
Holes Drilled in Enclosure(1) PDA-LHW White Light / Horn
Blue Light / Horn and Button with PDA-LHW White Light / Horn
MOD-LHBB1
Holes Drilled in Enclosure(1)
PDA-LH5C Light / Horn with User Choice of
White Light / Horn and Button with Red, Green, Yellow, Blue or White
MOD-LHWB1
Holes Drilled in Enclosure(1) Light
Light / Horn with User Choice of
PDA-BUTTON1R Red Button
Red, Green, Yellow, Blue or White
MOD-LH5CB1 PDA-BUTTON1G Green Button
Light, Button, and Holes Drilled in
Enclosure(1) PDA-BUTTON1B Blue Button
Note:
1. This MOD supplies the Light / Horn and Button. The enclosure
comes pre-drilled with holes for Light / Horn and Button and the
user performs the installation and wiring. Controller and enclosure
are sold separately. The Light / Horn hole is in the back left corner
of the enclosure and the Button is centered on the cover of the
enclosure below the controller about an inch off the bottom of the
cover except on the PDA3400 series where it is mounted on the
side of the enclosure.

7
PROVU™ PD6200 Analog Input Rate/Totalizer Instruction Manual

PDA2360 Control Stations Signal Splitter & Conditioner Accessories

Model Description
Signal Isolator with One 4-20 mA
PD659-1MA-1MA
Input and One 4-20 mA Output
Model Description Signal Splitter with One 4-20 mA
PD659-1MA-2MA
PDA2360-E Emergency button Input and Two 4-20 mA Outputs
PDA2361-A Ack button Signal Conditioner with One 0-10
PD659-1V-1MA
PDA2361-B Blank button VDC Input and One 4-20 mA Output
PDA2361-R Reset button Signal Conditioner with One
PD659-1MA-1V 4-20 mA Input and One 0-10 VDC
PDA2361-T Tare button
Output
PDA2361-S Stop button
PDA2361-Q Silence button
PDA2362-AR Ack and Reset buttons
PDA2362-BB Two blank buttons
PDA2364-MRUE Menu, right, up, enter buttons
Note: Control stations with one button may be connected directly to the
meter via the F4 terminal. A PDA1044 (4) digital inputs & (4) digital
outputs module is required to operate the control stations of more than
one button. See Remote Operation of Meter on page 20 for details.

8
PROVU™ PD6200 Analog Input Rate/Totalizer Instruction Manual

Helpful Videos Connect a PROVU to a PC Using


MeterView Pro
Precision Digital's PROVU Series is a powerful line of Learn how easy it is to use MeterView Pro software.
1/8 DIN meters that boasts advanced functionality for
various applications. The following videos might be of
interest.

PROVU Series Overview


Learn about all the meters in the PROVU Series.

https://www.predig.com/videos/PC_Connect

Connect a 2-Wire 4-20 mA Transmitter to


https://www.predig.com/videos/E4gmQrAeT8o
a PROVU
Learn how to connect your transmitter to a PROVU.

PROVU Multi-Pump Alternation


Learn how to use the PROVU as a pump controller.

https://www.predig.com/videos/4-
20_mA_Connections

https://www.predig.com/videos/PumpControl MeterView Pro USB Programming


Software
Learn how easy it is to program a PROVU PD6000
process meter.
PROVU Function Keys Tutorial
Learn how the PROVU’s function keys increase the
utility of the PROVU.

https://www.predig.com/videos/MVPro_SW

https://www.predig.com/videos/WMBYKlavW-Q

9
PROVU™ PD6200 Analog Input Rate/Totalizer Instruction Manual

Specifications Power
Options
85-265 VAC 50/60 Hz; 90-265 VDC, 20 W max;
12-24 VDC, 12-24 VAC, 15 W max.
Except where noted all specifications apply to Powered over USB for configuration only.
operation at +25°C. Fuse Required external fuse: UL Recognized,
5 A max, slow blow; up to 6 meters may
General share one 5 A fuse
Normal Mode Greater than 60 dB at 50/60 Hz
Display Line 1: 0.6" (15 mm) high, red LEDs
Rejection
Line 2: 0.46" (12 mm) high, red LEDs
6 digits: each (-99999 to 999999), with lead Isolation 4 kV input/output-to-power line
zero blanking. 500 V input-to-output or output-to-P+ supply
Display Eight user selectable intensity levels. Overvoltage Installation Overvoltage Category II:
Intensity Default value is six. Category Local level with smaller transient
overvoltages than Installation Overvoltage
Display 5/second (200 ms)
Category III.
Update Rate
Environmental Operating temperature range:
LED Status See Front Panel Buttons and Status LED -40 to 65°C (-40 to 149°F)
Indicators Indicators on page 21 for details. Storage temperature range:
Overrange Display flashes 999999 -40 to 85°C (-40 to 185°F)
Relative humidity:
Underrange Display flashes -99999
0 to 90% non-condensing
Display Display Line 1:
Rate, total, grand total, alternate (rate/total, Connections Removable screw terminal blocks accept
Assignment
rate/grand total, rate/units, total/units, and 12 to 22 AWG wire, RJ45 for external
grand total/units), set points, max/min, and relays, digital I/O, and serial communication
Modbus input. adapters.
Display Line 2: Enclosure 1/8 DIN, high impact plastic, UL 94V-0,
Same as Display Line 1; plus units, tag or color: black
turned off. Front Panel NEMA 4X, IP65
Additional displays are available if
parameter total is off, and parameter Mounting 1/8 DIN panel cutout required:
d-SCAL is on: gross weight, gross & net 3.622" x 1.772" (92 mm x 45 mm)
weight, PV1, PV2, and PCT (refer to Two panel mounting bracket assemblies
PD6000 instruction manual. are provided.
Programming Four front panel buttons, digital inputs, or Tightening Screw terminal connectors: 5 lb-in
Methods PC with MeterView Pro software. Torque (0.56 Nm)

Noise Filter Programmable from 2 to 199 Overall 4.68" x 2.45" x 5.64"


(0 will disable filter) Dimensions (119 mm x 62 mm x 143 mm)
(W x H x D)
Filter Bypass Programmable from 0.1 to 99.9% of
calibrated span Weight 9.5 oz (269 g)

Recalibration All ranges are calibrated at the factory. Warranty 3 years parts & labor. See Warranty
Recalibration is recommended at least Information and Terms & Conditions on
every 12 months. www.predig.com for complete details.
Max/Min Max/min readings reached by the process
Display are stored until reset by the user or until
power to the meter is turned off.
Rounding Select 1, 2, 5, 10, 20, 50, or 100
(e.g. rounding = 10, value = 123.45,
display = 123.50).
Password Three programmable passwords restrict
modification of programmed settings and
two prevent resetting the totals.
Pass 1: Allows use of function keys and
digital inputs
Pass 2: Allows use of function keys, digital
inputs and editing set/reset points
Pass 3: Restricts all programming, function
keys, and digital inputs.
Total: Prevents resetting the total manually
Gtotal: Prevents resetting the grand total
manually
Non-Volatile All programmed settings are stored in
Memory non-volatile memory for a minimum of ten
years if power is lost.

10
PROVU™ PD6200 Analog Input Rate/Totalizer Instruction Manual

Process Input Rate/Totalizer


Inputs Field selectable: 0-20 mA, 4-20 mA Rate Display -99999 to 999999, lead zero blanking.
10 V (0-5 V, 1-5 V, 0-10 V) Indication “R” LED illuminates while displaying rate.
Modbus PV (Slave) Total Display 0 to 999,999; automatic lead zero blanking.
Isolated Terminals P+ & P-: 24 VDC 10%. & Total “T” LED is illuminated while displaying total
Transmitter All models selectable for 24, 10, or 5 VDC Overflow or grand total.
Power Supply supply (internal jumper J4). 85-265 VAC Up to 999,999,999 with total-overflow
models rated @ 200 mA max, 12-24 VDC feature. “oF” is displayed to the left of total
powered models rated @ 100 mA max. overflow and ▲ LED is illuminated.
5 & 10 VDC supply rated @ 50 mA max. Total Up to five decimal places or none:
Refer to Figure 4: Transmitter Supply Voltage Decimal Point d.ddddd, d.dddd, d.ddd, d.dd, d.d, or dddddd
Selection on page 17 for details. Total decimal point is independent of rate
When the Light / Horn is powered by the decimal point.
transmitter power supply, see MOD-LH Totalizer Calculates total based on rate and field
Light / Horn's transmitter power supply programmable multiplier to display total in
specification in MOD-LH manual for engineering units. Time base must be
additional details. Light / Horn power not selected according to the time units in
available for 5 or 10 VDC supplies. which the rate is displayed.
Accuracy ±0.03% of calibrated span ±1 count, Totalizer Totalizer rolls over when display exceeds
square root & programmable exponent Rollover 999,999,999. Relay status reflects display.
accuracy range: 10-100% of calibrated Total Program total reset for automatic with
span Overflow 0.1 second delay and set point 1 for
Temperature 0.005% of calibrated span/C max from Override 999,999
Drift 0 to 65C ambient, 0.01% of calibrated Totalizer Up to eight, user selectable under setup
span/C max from -40 to 0C ambient Presets menu. Any set point can be assigned to
Input Signal Linear, square root, programmable total and may be programmed anywhere in
Conditioning exponent, or round horizontal tank volume the range of the meter for total alarm
calculation indication.
Multi-Point 2 to 32 points Programmable 0.1 and 999.9 seconds; applied to the first
Linearization Delay relay assigned to total or grand total.
Programmable User selectable from 1.0001 to 2.9999 for On Release If the meter is programmed to reset total to
Exponent open channel flow zero automatically when the preset is
reached, then a delay will occur before the
Round Diameter & Length: 999.999 inch or cm
total is reset.
Horizontal calculates volume in gallons or liters
Tank respectively. Total Reset User selectable via front panel button, F4
terminal at back of meter, external contact
Low-Flow 0.1 to 999,999 (0 disables cutoff function).
closure on digital inputs, automatically via
Cutoff Point below at which display always shows
user selectable preset value and time
zero.
delay, or through serial communications.
Decimal Point Up to five decimal places or none:
Total Reset Total and grand total passwords may be
d.ddddd, d.dddd, d.ddd, d.dd, d.d, or dddddd
Password entered to prevent resetting the total or
Calibration Input Range Minimum Span grand total from the front panel.
Range Input 1 & Input 2
Non-Resettable The grand total can be programmed as a
4-20 mA 0.15 mA Total non-resettable total by entering the
10 V 0.10 V password “050873”.
An error message will appear if the input 1
and input 2 signals are too close together.
Input Voltage ranges: greater than 500 k • Once the Grand Total has been programmed as
Impedance Current ranges: 50 - 100  (depending on “non-resettable” the feature CANNOT be
internal resettable fuse impedance) disabled.
Input Current input protected by an internal
Overload resettable fuse, 30 VDC max. Fuse resets
automatically after fault is removed.
HART The meter does not interfere with existing
Transparency HART communications; it displays the
4-20 mA primary variable and it allows the
HART communications to pass through
without interruption. The meter is not
affected if a HART communicator is
connected to the loop. The meter does not
display secondary HART variables.

11
PROVU™ PD6200 Analog Input Rate/Totalizer Instruction Manual

Relays Isolated 4-20 mA Transmitter


Rating 2 or 4 SPDT (Form C) internal and/or Output
4 SPST (Form A) external; rated 3 A
@ 30 VDC and 125/250 VAC resistive load; Output Source Rate/process, total, grand total, max, min,
1/14 HP (≈ 50 W) @ 125/250 VAC for set points 1-8, or manual control mode
inductive loads Scaling Range 1.000 to 23.000 mA for any display range.
Noise Noise suppression is recommended for Calibration Factory calibrated:
Suppression each relay contact switching inductive 4.000 to 20.000 = 4-20 mA output
loads. See Switching Inductive Loads on
page 19 for details. Analog Out 23.000 mA maximum for all parameters:
Programming Overrange, underrange, max, min, and
Relay Relays may be assigned to rate, total, break
Assignment grand total, or Modbus input.
Accuracy ± 0.1% FS ± 0.004 mA
Deadband 0-100% of span, user programmable
Temperature 0.4 µA/C max from 0 to 65C ambient,
High or Low User may program any alarm for high or Drift 0.8 µA/C max from -40 to 0C ambient
Alarm low trip point. Unused alarm LEDs and Note: Analog output drift is separate from
relays may be disabled (turn off). input drift.
Relay •
Automatic (non-latching) and/or
Isolated Terminals I+ & R: 24 VDC 10%. May be
Operation manual reset
Transmitter used to power the 4-20 mA output or other
• Latching (requires manual Power Supply devices.
acknowledge) with or without clear
• Pump alternation control (2-8 relays) All models rated @ 40 mA max.
• Sampling (based on set point and time) External Loop 35 VDC maximum
• Off (disable unused relays and enable Power Supply
Interlock feature)
Output Loop Power supply Minimum Maximum
• Manual on/off control mode
Resistance
Relay Reset User selectable via front panel button, F4 24 VDC 10  700 
(Acknowledge) terminal at back of meter, external contact 35 VDC 100  1200 
closure on digital inputs, automatically via (external)
user selectable preset value and time
delay, or through serial communications. Additional The PD659-1MA-2MA can split the optional
4-20 mA 4-20 mA output into two isolated 4-20 mA
Time Delay 0 to 999.9 seconds, on & off relay time Outputs outputs
delays. Programmable and independent for
each relay. 0-10 VDC The PD659-1MA-1V can convert the
Output optional 4-20 mA output to a 0-10 VDC
Fail-Safe Programmable and independent for each output
Operation relay.
Note: Relay coil is energized in non-alarm
condition. In case of power failure, relay
will go to alarm state.
Auto When power is applied to the meter, relays
Initialization will reflect the state of the input to the
meter.
Additional An external module, model PDA1004, is
Relays available to add 4 SPST 3 A relays to the
meter.

12
PROVU™ PD6200 Analog Input Rate/Totalizer Instruction Manual

USB Connection Modbus® RTU Serial


Function Programming only Communications
Compatibility USB 2.0 Standard, Compliant Slave Id 1 – 247 (Meter address)
Connector Micro-B receptacle Baud Rate 300 - 19,200 bps
Type
Transmit Programmable between 0 and 199 ms
Cable USB A Male to Micro-B Cable Time Delay
Driver Microsoft® Windows® XP/Vista/7/8/10 Data 8 bit (1 start bit, 1 or 2 stop bits)
Power USB port provides power to the meter. Parity Even, Odd, or None with 1 or 2 stop bits
DO NOT apply AC or DC power to the
meter while the USB port is in use. Byte-To-Byte 0.01 – 2.54 second
Timeout
Turn Around Less than 2 ms (fixed)
On-Board Digital Input (F4) Delay

Function Reset total, remote operation of front-panel Note: Refer to the PROVU Modbus Register Tables located
buttons, acknowledge/reset relays, reset at www.predig.com for details.
max/min values. See Function Keys &
Digital I/O Available Settings on page 44 for
a complete list of capabilities. MeterView Pro Software
Contacts 3.3 VDC on contact. Connect normally Availability Download directly from meter or from
open contacts across F4 to COM www.predig.com/download_software
Logic Levels Logic High: 3 to 5 VDC System Microsoft® Windows® XP/Vista/7/8/10
Logic Low: 0 to 1.25 VDC Requirements
Communications USB 2.0 (for programming only)
Additional I/O Up to 2 external modules, model PDA1044
(Standard USB A to Micro USB B)
with 4 digital inputs and 4 digital outputs
each can be added. RS-232 adapter, RS-485 adapter and
RS-485 to USB converter
(programming, monitoring, and data
logging)
Configuration Configure meters one at a time
Power USB port provides power to the meter.
DO NOT apply AC or DC power to the
meter while the USB port is in use.

13
PROVU™ PD6200 Analog Input Rate/Totalizer Instruction Manual

Compliance Information EU Declaration of


Safety Conformity
EU Declaration of Conformity is available in the
UL & c-UL USA & Canada
Documentation CD provided with the product under
Listed UL 508 Industrial Control Equipment
the EU DoC menu.
UL File Number E160849
Front Panel UL Type 4X, NEMA 4X, IP65; panel

Low Voltage
gasket provided
EN 61010-1
Safety Information
Directive Safety requirements for measurement,
control, and laboratory use
• Read complete instructions prior to installation
and operation of the meter.
Electromagnetic Compatibility
Emissions EN 55022
• Risk of electric shock or personal injury.
Class A ITE emissions requirements
• Hazardous voltages exist within enclosure.
Radiated Class A
Emissions
Installation and service should be performed only
by trained service personnel.
AC Mains Class A
Conducted
Emissions
Immunity EN 61326-1
Measurement, control, and laboratory
equipment
Installation
EN 61000-6-2 There is no need to remove the meter from its
EMC heavy industrial generic immunity case to complete the installation, wiring, and
standard setup of the meter for most applications.
RFI - 80 -1000 MHz 10 V/m 80% AM (1 kHz) Instructions are provided for changing the
Amplitude 1.4 - 2.0 GHz 3 V/m 80% AM (1 kHz) transmitter power supply to output 5 or 10 VDC
Modulated 2.0 - 2.7 GHz 1 V/m 80% AM (1 kHz) instead of 24 VDC. See Figure 4: Transmitter
Electrical ±2kV AC mains, ±1kV other Supply Voltage Selection on page 17.
Fast
Transients
Electrostatic ±4kV contact, ±8kV air Unpacking
Discharge Remove the meter from box. Inspect the
RFI - 10V, 0.15-80 MHz, 1kHz 80% AM packaging and contents for damage. Report
Conducted damages, if any, to the carrier.
AC Surge ±2kV Common, ±1kV Differential If any part is missing or the meter malfunctions,
Surge 1KV (CM) please contact your supplier or the factory for
Power- 30 A/m 70%V for 0.5 period assistance.
Frequency
Magnetic
Field
Voltage Dips 40%V for 5 & 50 periods
70%V for 25 periods
Voltage <5%V for 250 periods
Interruptions

Note:
Testing was conducted on meters installed through the
covers of grounded metal enclosures with cable shields
grounded at the point of entry representing installations
designed to optimize EMC performance.

14
PROVU™ PD6200 Analog Input Rate/Totalizer Instruction Manual

Panel Mounting Instructions Mounting Dimensions


• Prepare a standard 1/8 DIN panel cutout –
3.622" x 1.772" (92 mm x 45 mm). Refer to
Figure 1: 1/8 DIN Panel Cutout and Mounting
below for more details.
• Clearance: allow at least 6.0" (152 mm) behind
the panel for wiring.
• Panel thickness: 0.04" - 0.25" (1.0 mm - 6.4 mm).
Recommended minimum panel thickness to
maintain Type 4X rating: 0.06" (1.5 mm) steel
panel, 0.16" (4.1 mm) plastic panel.
• Remove the two mounting brackets provided with
the meter (back-off the two screws so that there is
¼" (6.4 mm) or less through the bracket. Slide the
bracket toward the front of the case and remove). Figure 2. Meter Dimensions - Side View
• Insert meter into the panel cutout.

R + - NO NC C NO NC C NO NC C NO NC C

Install mounting brackets and tighten the screws


against the panel. To achieve a proper seal,
tighten the mounting bracket screws evenly until
meter is snug to the panel along its short side.
DO NOT OVER TIGHTEN, as the rear of the
panel may be damaged.
A
3.622" (92 mm)

Square Corners to 0.060"


(1.5mm) Max Radius
B 1.772"
(45mm) Panel Cutout
to DIN 43700

Tolerances:
A: +0.032 (+0.8mm)
-0.000 (-0.0mm)
B: +0.024 (+0.6mm)
-0.000 (-0.0mm)
Figure 3. Meter Dimensions - Top View

DO NOT apply AC or DC power to the meter when using the


USB connection.

Figure 1: 1/8 DIN Panel Cutout and Mounting

15
PROVU™ PD6200 Analog Input Rate/Totalizer Instruction Manual

2. Once the driver is installed, an AutoPlay


Installation Overview dialog should appear for the drive
We recommend the following sequence for getting the “MAINSTAL.” Click “Open folder to view
meter into service: files.”
1. DO NOT apply AC or DC power to the meter.
2. Connect the meter to the PC with the USB cable
provided. DO NOT use a different USB cable.
3. If MeterView Pro (MVPro) is already installed in
your computer, then the program will launch If the computer does not display an AutoPlay
automatically in most systems. If the program dialog for the drive “MAINSTAL,” you should
does not start automatically, double-click on the open My Computer and double-click on the
MVPro icon. drive labeled “MAINSTAL.”
4. If MVPro is not installed, follow the instructions
provided below.
5. Use MVPro to configure the meter for your
application.
3. Double-click on the file named “MAStart.”
6. Disconnect the USB cable from the meter.
The program will open a few windows and
7. Apply power and signal and check operation of
install two programs on your computer.
the meter.
Simply follow the on-screen instructions until
8. Install the meter and put into service.
you see one of the dialogs below. If you
9. Make any programming adjustments using the
receive a “User Account Control” warning,
front panel buttons.
click “Yes.”
MeterView Pro Software
The easiest and quickest way to program your PROVU
meter is to use the FREE MeterView Pro
programming software. This software is loaded into
the meter and connects and installs directly to your
PC with the USB cable provided. DO NOT use a
different USB cable. We recommend that the first
thing you do after taking the meter out of the box is
connect the PROVU to your PC with the provided USB
cable. DO NOT apply AC or DC power to the meter
while your PC is connected to the meter as it will 4. If there is an update available, click the
disrupt the USB connection. It is not necessary to “Update” button to install the new version.
apply an input signal. Otherwise, click “Configure” to begin
programming your meter.
MeterView Pro programming software is intuitive, and
most customers can get their meter programmed as
they like without even looking in the manual.

Watch Meterview Pro Software Video at


www.predig.com/meterviewpro

MeterView Pro Installation


1. Connect one end of the provided USB cable
to the meter and the other end to the
computer. The computer will automatically
install the driver software it needs to talk to Note: If you decide to update your MeterView Pro
the meter. Follow the on-screen instructions software, once the installation has completed, you
and allow sufficient time for the process to will be asked if you want to update the setup files
complete. This can take a few minutes. If the located on the meter itself. This way, you will
process is interrupted, then it could leave the always have the most current version on the meter
system in an unstable condition. for future installs.

• Only one meter may be connected at a time.


Attaching multiple meters will cause a conflict • DO NOT unplug the meter while the new
with the meter software. installation files are being written to it. The meter
• DO NOT apply AC or DC power to the meter will display uwrite during the process and you
when using the USB connection. will receive an on-screen notification once the
process is complete.

16
PROVU™ PD6200 Analog Input Rate/Totalizer Instruction Manual

Transmitter Supply Voltage RELAY2


6 5 4
RELAY1
3 2 1

Selection (P+, P-) NO NC C NO NC C

All meters, including models equipped with the


12-24 VDC power option, are shipped from the
factory configured to provide 24 VDC power for SIGNAL
P+ P- F4 COM V+ mA+ 1 2 3 4 5 6 7 8
+ -
the transmitter or sensor. 1 2 3 4 5 6 1 2

If the transmitter requires 5 or 10 VDC excitation,


M-LINK POWER
the internal jumper J4 must be configured
accordingly. Figure 6. PD6200-##2 Connectors Label
To access the voltage selection jumper:
1. Remove all the connectors. MA OUT
3 2 1
2. Unscrew the back cover.
3. Slide the back cover about 1 inch. I- I+ R
24 V
4. Configure the J4 jumper, located behind the
input signal connector, for the desired SIGNAL
excitation voltage as shown. P+ P- F4 COM V+ mA+ 1 2 3 4 5 6 7 8
+ -
1 2 3 4 5 6 1 2

M-LINK POWER

Figure 7. PD6200-##3 Connectors Label

RELAY4 RELAY3 RELAY2 RELAY1


6 5 4 3 2 1 6 5 4 3 2 1

NO NC C NO NC C NO NC C NO NC C

SIGNAL
Figure 4: Transmitter Supply Voltage Selection P+ P- F4 COM V+ mA+ 1 2 3 4 5 6 7 8
+ -
1 2 3 4 5 6 1 2

Connections M-LINK POWER


All connections are made to removable screw
terminal connectors located at the rear of the Figure 8. PD6200-##4 Connectors Label
meter.
RELAY2 RELAY1 MA OUT
6 5 4 3 2 1 3 2 1

R

NO NC C NO NC C I- I+
Use copper wire with 60°C or 60/75°C insulation 24 V
for all line voltage connections. Observe all safety
regulations. Electrical wiring should be performed SIGNAL
in accordance with all applicable national, state, P+ P- F4 COM V+ mA+ 1 2 3 4 5 6 7 8
+ -
1 2 3 4 5 6 1 2
and local codes to prevent damage to the meter
and ensure personnel safety. M-LINK POWER

Figure 9. PD6200-##5 Connectors Label

Connectors Labeling RELAY4 RELAY3 RELAY2 RELAY1 MA OUT


The connectors’ label, affixed to the meter, shows the 6 5 4 3 2 1 6 5 4 3 2 1 3 2 1

location of all connectors available with requested NO NC C NO NC C NO NC C NO NC C I- I+ R


configuration. 24 V

Note: ## on the following figures refers to power and


display options. (Example: PD6200-6H5) SIGNAL
P+ P- F4 COM V+ mA+ 1 2 3 4 5 6 7 8
+ -
1 2 3 4 5 6 1 2

M-LINK POWER

Figure 10. PD6200-##7 Connectors Label

SIGNAL
P+ P- F4 COM V+ mA+ 1 2 3 4 5 6 7 8
+ - • DO NOT connect any equipment other than
Precision Digital’s expansion modules, cables, or
1 2 3 4 5 6 1 2

M-LINK POWER meters to the RJ45 M LINK connector. Otherwise


damage will occur to the equipment and the
Figure 5. PD6200-##0 Connectors Label meter.

17
PROVU™ PD6200 Analog Input Rate/Totalizer Instruction Manual

Power Connections The current input is protected against current


overload by an internal resettable fuse. The display
Power connections are made to a two-terminal may or may not show a fault condition depending on
connector labeled POWER. The meter will operate the nature of the overload.
regardless of DC polarity connection. The + and -
The fuse limits the current to a safe level when it
symbols are only a suggested wiring convention.
There are separate models for low voltage and high detects a fault condition, and automatically resets
itself when the fault condition is removed.
voltage power. See Ordering Information on page 6
for details.
POWER Voltage (V) Connections
+ - The following figures show examples of voltage
connections.
There are no switches or jumpers to set up for voltage
inputs. Setup and programming is performed through
the front panel buttons or MeterView Pro software.
AC or DC
POWER
Required External Fuse:
5 A max, 250 V Slow Blow
Figure 11. Power Connections

Signal Connections
Signal connections are made to a six-terminal
connector labeled SIGNAL. The COM (common)
terminal is the return for the 4-20 mA and the 10 V
input signals. Figure 14. Voltage Input Connections
The meter is capable of accepting any voltage from -
10 VDC to +10 VDC.
Current (mA) Connections
The following figures show examples of current
connections. Modbus RTU Serial
There are no switches or jumpers to set up for current Communications
inputs. Setup and programming is performed through
the front panel buttons or MeterView Pro software. Serial communications connection is made to an
RJ45 connector labeled M-LINK. For interfacing to the
PROVU, use the PDA1232 for RS-232 or the PDA1485
for RS-485. The same port is used for interfacing with
all expansion modules (e.g. external relays, digital
I/O).

Relay Connections
Relay connections are made to two six-terminal
connectors labeled RELAY1 – RELAY4. Each relay’s
C terminal is common only to the normally open (NO)
Figure 12. Transmitter Powered by Internal Supply and normally closed (NC) contacts of the
corresponding relay. The relays’ C terminals should
not be confused with the COM (common) terminal of
the INPUT SIGNAL connector.

RELAY4 RELAY3 RELAY2 RELAY1


6 5 4 3 2 1 6 5 4 3 2 1

NO NC C NO NC C NO NC C NO NC C

Figure 15. Relay Connections


Figure 13. Transmitter Powered by External
Supply or Self-Powered

18
PROVU™ PD6200 Analog Input Rate/Totalizer Instruction Manual

Switching Inductive Loads F4 Digital Input Connections


The use of snubbers to suppress electrical noise is A digital input, F4, is standard on the meter. This
strongly recommended when switching inductive digital input should be connected with a normally
loads to prevent disrupting the microprocessor’s open contact across F4 and COM, or with an active
operation. The snubbers also prolong the life of the low signal applied to F4. It can be used to reset the
relay contacts. Suppression can be obtained with total, for remote operation of front-panel buttons, to
resistor-capacitor (RC) networks assembled by the acknowledge/reset relays, or to reset max/min values.
user or purchased as complete assemblies. Refer to See Function Keys & Digital I/O Available Settings on
the following circuits for RC network assembly and page 44 for a complete list of capabilities.
installation: P+ P- F4 COM V+ mA+
1 2 3 4 5 6

C
C R
Figure 18. F4 Digital Input Connections
R

Figure 16. AC and DC Loads Protection 4-20 mA Output Connections


Choose R and C as follows: Connections for the 4-20 mA transmitter output are
R: 0.5 to 1  for each volt across the contacts made to the connector terminals labeled mA OUT.
C: 0.5 to 1 µF for each amp through closed contacts The 4-20 mA output may be powered internally or
Notes: from an external power supply.
1. Use capacitors rated for 250 VAC.
2. RC networks may affect load release time of
24 V
Internal Power Supply 24 V

and Analog Output


solenoid loads. Check to confirm proper mA OUT mA OUT
operation. RELAY1 I- I+ R RELAY1 I- I+ R
3 2 1 3 2 1 3 2 1 3 2 1
3. Install the RC network at the meter's relay screw
terminals. An RC network may also be installed
across the load. Experiment for best results. + - + - - +
4-20 mA Input 12-35 VDC
4-20 mA
Remote Display, PLC, Power
Input Meter
Chart Recorder, Etc. Supply

Active Output Loop Passive Output Loop

Figure 19. 4-20 mA Output Connections

Analog Output Power Supply


The internal 24 VDC power supply powering the
analog output may be used to power other devices, if
Use a diode with a reverse breakdown voltage two to three
the analog output is not used. The I+ terminal is the
times the circuit voltage and forward current at least as large
as the load current. +24 V and the R terminal is the return.
24 V
+ -
Figure 17. Low Voltage DC Loads Protection
I- I+ R
3 2 1
RC Networks (Snubbers) Available
from Precision Digital
RC networks are available from Precision Digital and
should be applied to each relay contact switching an
inductive load. Part number: PDX6901. 24 VDC
Powered
Note: Relays are de-rated to 1/14th HP (50 watts) Device

with an inductive load.


Figure 20. Analog Output Supply Powering Other
Devices

19
PROVU™ PD6200 Analog Input Rate/Totalizer Instruction Manual

External Relay & Digital I/O Remote Operation of Meter


Connections The meter can be operated via the front panel push
buttons or a remote control station using the
The relay and the digital I/O expansion modules
PDA1044 Digital I/O module as illustrated in Figure
PDA1004 & PDA1044 are connected to the meter
24. Meter to Control Station Connection.
using a CAT5 cable provided with each module. The
two RJ45 connectors on the expansion modules are
identical and interchangeable; they are used to
connect additional modules to the system.
Note: The jumper located between the RJ45
connectors of the PDA1044 must be removed
on the second digital I/O module in order for the
system to recognize it as module #2.

• DO NOT connect or disconnect the expansion


modules with the power on! More detailed Figure 24. Meter to Control Station Connection
instructions are provided with each optional
expansion module.
Interlock Relay Feature
As the name implies, the interlock relay feature
reassigns one, or more, alarm/control relays for use
as interlock relay(s). Interlock contact(s) are wired to
digital input(s) and activate the interlock relay. This
feature is enabled by configuring the relay, and the
corresponding digital input(s), see Setting Up the
Interlock Relay (Force On) Feature on page 36.
In the example below, an Interlock Contact switch is
connected to a digital input, which will be used to
force on (energize) the Interlock Relay. The Interlock
Figure 21. Expansion Module & DIN Rail Mounting Relay and the Control Relay are connected in series
Kit with the load.
• When the Interlock Contact is closed (safe), the
Interlock Relay energizes, allowing power to flow
to the Control Relay; the corresponding front
panel LED is on.
RLY5 RLY6 RLY7 RLY8 • When the Interlock Contact is open, the
1 2 3 4 5 6 7 8 corresponding front panel LED flashes (locked
out), the Interlock Relay is de-energized,
NO C NO C NO C NO C preventing power from flowing to the Control
Figure 22. External Relays Module Connections Relay and the load.
.

1 2 3 4 5 6 7 8 9 10

+5 I1 I2 I3 I4 O1 O2 O3 O4 G

Figure 25. Interlock Connection


5 VDC DI 1-4 DO 1-4 GND
Figure 23. Digital I/O Module Connections

20
PROVU™ PD6200 Analog Input Rate/Totalizer Instruction Manual

Setup and Programming Front Panel Buttons and Status


LED Indicators
There is no need to recalibrate the meter
when first received from the factory.
The meter is factory calibrated prior to
shipment for milliamps and volts with
calibration equipment that is certified to NIST
standards.

Overview
There are no jumpers to set for the meter input
selection.
Setup and programming is done using MeterView Pro Button Symbol Description
or through the front panel buttons.
Menu
After power and input signal connections have been
completed and verified, apply power to the meter.
Right arrow/F1

Up arrow/F2

Enter/F3

LED State Indication


1-8 Steady Alarm condition based on set
and reset points, independent
of relay status in certain
configurations. (Available on all
meter configurations, including
those without relays installed)
1-8 Flashing Relay interlock switch open
1-8 & M Flashing Relay in manual control mode
R Steady Rate
T Steady Total
T Flashing Meter in Tare mode
G&T Steady Grand Total
▲ Steady Total overflow (“oF” is
displayed to the left of total
overflow and ▲ LED is
illuminated)
M Flashing Analog ouput in manual control
mode

• Press the Menu button to enter or exit the


Programming Mode at any time.
• Press the Right arrow button to move to the next
digit during digit
or decimal point programming.
• Press or hold the Up arrow button to scroll
through the menus, decimal point, or to
increment the value of a digit.
• Press the Enter button to access a menu or to
accept a setting.
• Press and hold the Menu button for three
seconds to access the advanced features of the
meter.

21
PROVU™ PD6200 Analog Input Rate/Totalizer Instruction Manual

Display Functions & Messages Display Functions & Messages


The meter displays various functions and messages Display Parameter Action/Setting
during setup, programming, and operation. The Description
following table shows the main menu functions and GT CF Grand total Program grand total
messages in the order they appear in the menu. conversion conversion factor
factor
Display Functions & Messages
GT rst Grand total Program grand total rest
Display Parameter Action/Setting reset mode: auto or manual
Description
Auto Automatic Press Enter to set
setup Setup Enter Setup menu
automatic total reset
Input Input Enter Input selection
T dly Time delay Program time delay for
menu
total auto reset
nmA 4-20 mA Set meter for 4-20 mA
input nmAn Manual Press Enter to reset total
manually
volt 0-10 VDC Set meter for 10 VDC
input dsplay Display Enter the Display menu
Total Total Enable or disable Line 1 Line 1 Press Enter to assign the
totalizer features Main display parameter
(default: PV or rate)
d-SCAL Dual-scale Enter d-SCAL menu and
select Yes for dual- scale Line 2 Line 2 Press Enter to assign the
or No for single scale small display parameter
display (default: total)
units Units Select the display d-Inty Display Set display intensity level
units/tags intensity from 1 to 8
rate Rate Select the display units RELaY Relay Enter the Relay menu
for rate
Assign Assignment Assign relays to rate,
total Total Select the display units total, or grand total
for total
Asign1 Assign 1 Relay 1 assignment
Gtotal Grand Total Select the display units
for grand total totAL Total Assign relay to total
Dec pt Decimal Set decimal point for rate, G total Grand total Assign relay to grand
point total, grand total total
prog Program Enter the Program menu nm bus Modbus Select to display Modbus
InCAL Input Enter the Input input or to assign
Calibration Calibration menu Modbus input as the
analog output source
sCalE Scale Enter the Scale menu
rate Rate Assign relay to rate
Cal Calibrate Enter the Calibrate menu
RLY 1 Relay 1 Relay 1 setup
Inp 1 Input 1 Calibrate input 1 signal or
program input 1 value Act 1 Action 1 Set relay 1 action
Dis 1 Display 1 Program display 1 value Auto Automatic Set relay for automatic
Inp 2 Input 2 Calibrate input 2 signal or reset
program input 2 value A-nman Auto-manual Set relay for automatic &
(up to 32 points) manual reset
Dis 2 Display 2 Program display 2 value any time
(up to 32 points) LatCH Latching Set relay for latching
Error Error Error, calibration not operation (relays
successful, check signal assigned to rate)
or programmed value Lt-CLr Latching- Set relay for latching
T tb Total time Program total time base cleared operation with manual
base reset only after alarm
condition has cleared
T CF Total Program total conversion (relays assigned to rate)
conversion factor
factor Altern Alternate Set relay for pump
alternation control (relays
T rst Total reset Program total rest mode: assigned to rate)
auto or manual
Sanmpl Sampling Set relay for sampling
GT tb Grand total Program grand total time operation
time base base

22
PROVU™ PD6200 Analog Input Rate/Totalizer Instruction Manual

Display Functions & Messages Display Functions & Messages


Display Parameter Action/Setting Display Parameter Action/Setting
Description Description
OFF Off Disable relay and front Rst tr Reset tare Reset tare (Used when
panel status LED Total is no only)
(Select Off to enable
Interlock feature) Contrl Control Enter Control menu
Set 1 Set 1 Program set point 1 Auto Automatic Press Enter to set relays
and analog output for
RSt 1 Reset 1 Program reset point 1 automatic operation
RLY 2 Relay 2 Relays 2-8 setup
nmAn Manual Press Enter to manually
Note: Relays 5-8 are
control relays or analog
shown, only if expansion
output operation
relay module is installed.
FaiLSF Fail-safe Enter Fail-safe menu pass Password Enter the Password
menu
FLS 1 Fail-safe 1 Set relay 1 fail-safe
operation Pass 1 Password 1 Set or enter Password 1
on On Enable fail-safe operation Pass 2 Password 2 Set or enter Password 2
off Fail-safe off Disable fail-safe Pass 3 Password 3 Set or enter Password 3
operation
Total Total Set or enter password for
DeLAY Delay Enter relay Time Delay password manual reset
menu
Gtotal Grand total Set or enter password for
DLY 1 Delay 1 Enter relay 1 time delay password manual reset
setup
nonrst Non- Non-resettable grand
On 1 On Set relay 1 On time delay resettable total set after entering
OFF 1 Off Set relay 1 Off time delay “050873” for Gtotal
password
break Loop break Set relay condition if loop
break detected unloc Unlocked Program password to
(For mA input only) lock meter
iGnorE Ignore Ignore loop break locd Locked Enter password to unlock
condition meter
(Processed as a low
999999 Flashing Overrange condition
signal condition) -99999 display Underrange condition
On On Relay goes to alarm
condition when loop
break is detected
OFF Off Relay goes to non-alarm
condition when loop
break is detected
Aout Analog Enter the Analog output
output scaling menu
Dis 1 Display 1 Program display 1 value
Out 1 Output 1 Program output 1 value
(e.g. 4.000 mA)
Dis 2 Display 2 Program display 2 value
Out 2 Output 2 Program output 2 value
(e.g. 20.000 mA)
reset Reset Press Enter to access the
Reset menu
Rst Gt Reset Press Enter to reset
grand total grand total
Rst Hi Reset high Press Enter to reset max
display
Rst Lo Reset low Press Enter to reset min
display
Rst HL Reset Press Enter to reset max
high & low & min displays
Rst t Reset total Press Enter to reset total

23
PROVU™ PD6200 Analog Input Rate/Totalizer Instruction Manual

Main Menu Setting Numeric Values


The main menu consists of the most commonly used The numeric values are set using the Right and Up
functions: Reset, Control, Setup, and Password. arrow buttons. Press Right arrow to select next digit
• Press Menu button to enter Programming Mode, and Up arrow to increment digit value. The digit being
then press the Up arrow button to scroll main changed is displayed brighter than the rest. Press and
menu. hold Up to auto-increment the display value. If
negative numbers are allowed, the first digit position
• Press Menu, at any time, to exit and return to
will include a negative symbol (-) after the 9.
Run Mode. Changes made to settings prior to
pressing Enter are not saved. Press the Enter button, at any time, to accept a
setting or Menu button to exit without saving changes.
• Changes to the settings are saved to memory
only after pressing Enter/F3.
• The display moves to the next menu every time a
setting is accepted by pressing Enter/F3.

Setting Up the Rate/Totalizer


Meter (setup)
The Setup menu is used to select:
1. Input signal the meter will accept and enable
totalizer features
2. Select the display units/tags
3. Select the decimal point position
4. Meter programming & input calibration
5. Display parameter and intensity
6. Relay operation
7. 4-20 mA analog output scaling
Press the Enter button to access any menu or press
Up arrow button to scroll through choices. Press the
Menu button to exit at any time.

24
PROVU™ PD6200 Analog Input Rate/Totalizer Instruction Manual

Setting the Input Signal (Input) Setting the Display Units or


Enter the Input menu to set up the meter to display Custom Tags (units)
current (nmA) or voltage (Volt) inputs. Use this menu to enter the unit or custom tag that will
The current input is capable of accepting any signal be displayed if:
from 0 to 20 mA. Select current input to accept 1. Alternating rate, total, or grand total and
0-20 mA or 4-20 mA signals. units is selected in the units menu, or
The voltage input is capable of accepting any signal 2. d unit is selected as the line 2 parameter.
from -10 to +10 VDC. Select voltage input to accept
See the Setting the Display Parameter & Intensity
0-5, 1-5, 0-10, or 10 VDC signals.
(dsplay) flow chart on page 28 to access the display
Setting the Totalizer Features menu to show the unit or tag on line 2. The
engineering units or custom legends can be set using
(total) the following 7-segment character set:
To simply not display the total, select alternative Display Character Display Character
display parameters in the display (dsplay) menu.
0 0 k K
Enable or disable the totalizer features by selecting
“Yes” or “no” after the input type has been set up. If
1 1 l L

the totalizer features are disabled, all the totalizer 2 2 nm m


features and functions are hidden from the menus. 3 3 n n
Level and process meter features and functions are 4 4 O O
added to the menus. 5 5 o o
If disabling the total parameter by selecting no, 6 6 p P
please refer to the PD6000 manual for instructions on 7 7 q q
setting up the meter parameters. 8 8 r r
Notes:
1. The totalizer continues working in the background.
9 9 s S

2. When selecting "no" for Total, the meter now


A A t t

functions as a PD6000 Process Meter. We strongly


b b u u
suggest that you download and use the PD6000 C C v V
instruction manual while in this mode of operation. c c uw w
d d x X
e E y Y
f F z Z
g G - -
9 g / /
H H [ ]
h h ] [
I I = =
I i ! Degree(<)
j J Space
Notes:
1. Degree symbol represented by (<) if programming
with MeterView Pro.
2. The letters “m” and “w” use two 7-segment LEDs
each; when selected the characters to the right are
shifted one position.
3. Press and hold up arrow to auto-scroll the
characters in the display.

25
PROVU™ PD6200 Analog Input Rate/Totalizer Instruction Manual

Setting the Decimal Point (dEc.pt) Multi-Point Calibration & Scaling


The decimal point may be set with up to five decimal The meter is set up at the factory for 2-point linear
places or with no decimal point at all. The rate, total, calibration. The number of points for multi-point
and grand total decimal points are independent. calibration/scaling is set up in the Advanced Features
The decimal point selection should be made prior to menu. Up to 32 linearization points may be selected.
scaling, calibrating or programming the meter. See Multi-Point Linearization (Linear) menu on page
Pressing the Right arrow moves the decimal point one 41 for details.
place to the right until no decimal point is displayed
then it moves to the leftmost position. Pressing the Up Input Calibration Method (InCAL)
arrow moves the decimal point one place to the left.
There are two methods of calibrating (or scaling) the
display to show the correct engineering units.
Programming the Rate/Totalizer • Use the Scale menu to enter the scaling without a
signal source.
(prog)
• Use the Calibrate menu to apply a signal from a
The meter may either be scaled (SCALE) without signal source.
applying an input or calibrated (Cal) by applying an
input. The meter comes factory calibrated to NIST
standards, so for initial setup, it is recommended to
use the (SCALE) function.
The Program menu contains the following menus:
1. Scale without a signal source
2. Calibrate with a calibrated signal source
3. Total time base & conversion factor
4. Grand total time base & conversion factor
5. Total reset mode for total & grand total
Process inputs may be scaled or calibrated to any
display within the range of the meter. Note: The Scale and Calibrate functions are exclusive
of each other. The meter uses the last function
Note: The Scale and Calibrate functions are programmed. Only one of these methods can be
exclusive of each other. The meter uses the last employed at a time. The Scale and Calibrate
function programmed. Only one of these methods functions can use up to 32 points (default is 2). The
can be employed at a time. The Scale and Calibrate number of points should be set in the Advanced menu
functions can use up to 32 points (default is 2). The prior to scaling and calibration of the meter. See
number of points should be set in the Advanced Multi-Point Linearization (Linear) on page 41 for
menu prior to scaling and calibration of the meter. details.
See Multi-Point Linearization (Linear) menu on page
41 for details.
The process input may be calibrated or scaled to any Scaling the Meter (SCALE)
display value within the range of the meter. The process inputs (4-20 mA and 10 VDC) can be
scaled to display the process variable in engineering
units.
A signal source is not needed to scale the meter;
simply program the inputs and corresponding display
values.

Additional parameters, not needed for most


applications, are programmed in the Advanced
Features menu; see Advanced Features Menu on page
39.

26
PROVU™ PD6200 Analog Input Rate/Totalizer Instruction Manual

Error Message (Error) Calibrating the Meter with External


An error message indicates that the calibration or Source (Cal)
scaling process was not successful.
After the error message is displayed, the meter The meter can be calibrated to display the process
reverts to the input prior to the failure during variable in engineering units by applying the
calibration or scaling and to input 1 during internal appropriate input signal and following the calibration
calibration, allowing the appropriate input signal to be procedure.
applied or programmed. The use of a calibrated signal source is strongly
The error message might be caused by any of the recommended to calibrate the meter.
following conditions:
1. Input signal is not connected to the proper
terminals or it is connected backwards*.
2. Wrong signal selection in Setup menu*.
3. Minimum input span requirements not
maintained.
4. Input 1 signal inadvertently applied to calibrate
input 2*.
*Not relevant when scaling the meter.

For instructions on how to program numeric values


see Setting Numeric Values on page 24.

Minimum Input Span Note: Inputs for the above example are:
The minimum input span is the minimum difference Input 1: 4.00 mA; Display 1: 0.0 Gallons
between input 1 and input 2 signals required to Input 2: 20.00 mA; Display 2: 15000.0 Gallons
complete the calibration or scaling of the meter.
Input range Input 1 & input 2 span
4-20 mA 0.15 mA Warm up the meter for at least 15 minutes before
10 VDC 0.10 VDC performing calibration to ensure specified
accuracy.

27
PROVU™ PD6200 Analog Input Rate/Totalizer Instruction Manual

Time Base, Total Conversion Factor Total & Grand Total Reset
& Total Reset The totals can be programmed for automatic or
manual reset. In the automatic reset mode, a
The time base, total conversion factor, and total reset
programmable time delay is available to reset the total
menus are located in the Program menu.
or grand total after the assigned preset is reached.
The total and grand total have their own independent The totals can also be reset via the front panel button,
settings. This means that one can be displaying the via a switch across the on-board F4 terminal, the
value in gallons while the other displays in million PDA1044 digital I/O expansion module, or via a
gallons, liters, m3, etc. Modbus command.

Non-Resettable Totalizer
The total and grand total can be password-protected
to prevent unauthorized resets. The grand total can
be programmed as a non-resettable total. See Total
Reset Password & Non-Resettable Total on page 38
for details.

Time Base
The time base is the amount of time over which the
rate parameter should accrue. For example, if the rate
was ten and the time base was in minutes, then the
total would increase by ten every one minute.

Total & Grand Total Conversion


Factor
The total & grand total conversion factor is the
amount by which the rate is multiplied before it is
added to the total or grand total. For Example, if the
rate was ten per second and the total conversion
factor was 100, the total would increase by 1000
every second. This is useful, for instance, if you want
to show rate in gallons and total in thousands of
gallons.

28
PROVU™ PD6200 Analog Input Rate/Totalizer Instruction Manual

Setting the Display Parameter & Selecting engineering units or custom legends as
display line 2 (d unit) will display the unit or tag
Intensity (dsplay) selected for the rate, total, or grand total displayed on
Display line 1 can be programmed to display: line 1.
1. Rate value For example, if line 1 is set to total, selecting
2. Total or grand total d unit to display on line 2 will have the total appear
3. Toggle rate/total on line 1, and the total unit appear on line 2.
4. Toggle rate/G-total After setting up the input and the display, press the
5. Relay set points Menu button to exit programming and skip the rest of
6. Toggle rate and units the setup menu. Press the Menu button again and the
Up arrow to reach the Program menu and complete
7. Toggle total and units
the scaling or calibration of the meter.
8. Toggle grand total and units
9. Max, min, or max & min values
10. Modbus input Display Flow Rate, Total or Grand
Display line 2 can be programmed to display: Total
1. Engineering units or custom legends Line 1 can be programmed to display flow rate, total,
for line 1 or grand total, and line 2 can be programmed to
2. Rate value display flow rate, total, grand total, engineering units,
3. Total or grand total custom legends, or be turned off. Both lines can also
4. Toggle rate/total display relay set points, or max and min values.
5. Toggle rate/G-total
6. Relay set points
7. Toggle rate and units
8. Toggle total and units
9. Toggle grand total and units
10. Max, min, or max & min values
11. Modbus input
12. Off (no display)

Display Toggling Between Reading


& Units
The PD6200 can be programmed so that line 1 and
line 2 toggle between the reading and their
engineering units. For instance, line 1 displays flow
rate, line 2 displays total, and the display toggles to
show their units.

Display Intensity (d-Inty)


The meter has eight display intensity levels to give the
best performance under various lighting conditions.
Select intensity 8 for outdoor applications. The default
intensity setting is 6.

29
PROVU™ PD6200 Analog Input Rate/Totalizer Instruction Manual

Setting the Relay Operation Relay Assignment (Assign)


(relay) The relays can be assigned to any of the following
This menu is used to set up the operation of the parameters:
relays. 1. Rate for low or high alarm indication
2. Total for alarm indication
3. Grand total for alarm indication
4. Modbus input process variable
• During setup, the relays do not follow the input
and they will remain in the state found prior to
entering the Relay menu.

1. Relay assignment
a. Rate for low and high alarm
b. Total
c. Grand total Setting the Relay Action
d. Modbus input process variable Operation of the relays is programmed in the Action
2. Relay action menu. The relays may be set up for any of the
following modes of operation:
a. Automatic reset only (non-latching)
1. Automatic reset (non-latching)
b. Automatic + manual reset at any time
(non-latching) 2. Automatic + manual reset at any time
(non-latching)
c. Latching (manual reset only)
3. Latching (manual reset only, at any time)
d. Latching with Clear (manual reset only
after alarm condition has cleared) 4. Latching with Clear (manual reset only after
alarm condition has cleared)
e. Pump alternation control (automatic
reset only) 5. Pump alternation control (automatic reset only)
f. Sampling (the relay is activated for a 6. Sampling (the relay is activated for a user-
user-specified time) specified time)
g. Off (relay state controlled by Interlock 7. Off (relay state controlled by Interlock feature)
feature) The following graphic shows relay 1 action setup;
3. Set and reset points relay 2-8 are set up in a similar fashion.
4. Fail-safe operation
a. On (enabled)
b. Off (disabled)
5. Time delay
a. On delay (0-999.9 seconds)
b. Off delay (0-999.9 seconds)
6. Relay action for loss (break) of 4-20 mA input
(ignore, on, off)

30
PROVU™ PD6200 Analog Input Rate/Totalizer Instruction Manual

Programming Set and Reset Relay Action for Loss of 4-20 mA


Points Input (Loop Break)
High alarm indication: program set point above reset A loop break condition is triggered when the 4-20 mA
point. input signal drops below 0.005 mA. Each relay may
Low alarm indication: program set point below reset be programmed to go to one of the following
point. conditions when the meter detects the loss of the
The deadband is determined by the difference input signal (i.e. < 0.005 mA):
between set and reset points. Minimum deadband is 1. Turn On (Go to alarm condition)
one display count. If the set and reset points are 2. Turn Off (Go to non-alarm condition)
programmed with the same value, the relay will reset 3. Ignore (Process as a low signal condition)
one count below the set point. The following graph shows the loop break relay
operation for a high alarm relay.

Note: Changes are not saved until the reset point has
been accepted.

Setting Fail-Safe Operation


In fail-safe mode of operation, the relay coil is
energized when the process variable is within safe
limits and the relay coil is de-energized when the alarm
condition exists. The fail-safe operation is set
independently for each relay. Select on to enable or
select off to disable fail-safe operation.

Programming Time Delay


The On and Off time delays may be programmed for
each relay between 0 and 999.9 seconds. The relays
will transfer only after the condition has been
maintained for the corresponding time delay.
The On time delay is associated with the set point.
The Off time delay is associated with the reset point.

31
PROVU™ PD6200 Analog Input Rate/Totalizer Instruction Manual

Relay and Alarm Operation High Alarm with Fail-Safe


Diagrams Operation (Set > Reset)
The following graphs illustrate the operation of the
relays, status LEDs, and ACK button.
High Alarm Operation (Set > Reset)

Note: Relay coil is energized in non-alarm condition. In case of power failure,


relay will go to alarm state.

For Manual reset mode, ACK can be pressed anytime to turn "off" relay. To
Low Alarm with Fail-Safe
detect a new alarm condition, the signal must go below the set point, and then go
above it.
Operation (Set < Reset)

Low Alarm Operation (Set < Reset)

Note: Relay coil is energized in non-alarm condition. In case of power failure,


relay will go to alarm state.

For Manual reset mode, ACK can be pressed anytime to turn "off" relay. To
detect a new alarm condition, the signal must go below the set point, and then go
above it.

32
PROVU™ PD6200 Analog Input Rate/Totalizer Instruction Manual

Time Delay Operation Total Relay Sampling Operation


The following graphs show the operation of the time Total Preset = 100
delay function. 300

200

100

Sample Sample Sample


Time Time Time

Relay

LED

When the total reaches the preset, the relay trips and
the sample time starts. After the sample time has
elapsed, the relay resets. The cycle repeats every
time the preset value is added to the total.

When the signal crosses the set point, the On time delay
timer starts and the relay trips when the time delay has
elapsed. If the signal drops below the set point (high
alarm) before the time delay has elapsed, the On time
delay timer resets and the relay does not change state.
The same principle applies to the Off time delay.
Note: If “Automatic or Manual (A-nmAn)” reset mode is
selected, the LED follows the reset point and
not the relay state when the relay is
acknowledged.

33
PROVU™ PD6200 Analog Input Rate/Totalizer Instruction Manual

Relay Operation Details Front Panel LEDs


The alarm status LEDs on the front panel are
Overview available on all meters, even those without relays
The relay capabilities of the meter expand its installed, and provide status indication for the
usefulness beyond simple indication to provide users following:
with alarm and control functions. These capabilities
include front panel alarm status LEDs as well as LED Status LED Status
either 2 or 4 optional internal relays and/or 4 external 1 Alarm 1 5 Alarm 5
relays expansion module. Typical applications include 2 Alarm 2 6 Alarm 6
high and low temperature, level, pressure or flow
alarms, control applications such as simple on/off 3 Alarm 3 7 Alarm 7
pump control, pump alternation control for up to 8 4 Alarm 4 8 Alarm 8
pumps, and basic batch control. There are four basic
ways the relays can be used: Note: LEDs 5-8 require the external relay module
1. High and Low Alarms with Latching or Non- PDA1004 to be connected.
Latching Relays The meter is supplied with four alarm points that
2. Simple On/Off Control with 100% Adjustable include front panel LEDs to indicate alarm conditions.
Deadband This standard feature is particularly useful for alarm
3. Sampling (Based on Time) applications that require visual-only indication. The
4. Pump Alternation Control for up to 8 Pumps LEDs are controlled by the set and reset points
programmed by the user. When the display reaches a
set point for a high or low alarm, the corresponding
Relays Auto Initialization alarm LED will turn on. When the display returns to
When power is applied to the meter, the front panel the reset point the LED will go off. The front panel
LEDs and alarm relays will reflect the state of the LEDs respond differently for latching and non-latching
input to the meter. The following table indicates how relays.
the alarm LEDs and relays will react on power-up For non-latching relays, the LED is always off during
based on the set and reset points: normal condition and always on during alarm
HI or LO Set Reset
Power-
Relay & condition, regardless of the state of the relay (e.g.
Alarm # Up
Alarm Point Point
Reading
LED Relay acknowledged after alarm condition).
1 HI 1000 500 499 Off For latching relays, the alarm LEDs reflect the status
2 LO 700 900 499 On of the relays, regardless of the alarm condition. The
3 LO 250 400 499 Off following tables illustrate how the alarm LEDs function
4 HI 450 200 499 On
in relation to the relays and the acknowledge button
(Default: F3 key assigned to ACK).
Fail-Safe Operation
The following table indicates how the relays behave Latching and Non-Latching Relay
based on the fail-safe selection for each relay: Operation
Fail-Safe Non-Alarm State Alarm State Power
Selection Failure The relays can be set up for latching (manual reset)
NO NC NO NC or non-latching (automatic reset) operation.
Off Open Closed Closed Open Relays
go to Relay terminology for following tables
non-
alarm Terminology Relay Condition
state On Alarm (Tripped)
On Closed Open Open Closed Relays Off Normal (Reset)
go to
alarm Ack Acknowledged
state

The On and Off terminology does not refer to the


Note: NO = Normally Open, NC = Normally Closed. status of the relay’s coil, which depends on the fail-
This refers to the condition of the relay contacts when safe mode selected.
the power to the meter is off.

• In latching relay mode, if Fail-Safe is off, latched


relays will reset (unlatch) when power is cycled.

34
PROVU™ PD6200 Analog Input Rate/Totalizer Instruction Manual

Non-Latching Relay (Auto) Latching Relay with Clear (LatcH)


In this application, the meter is set up for automatic In this application, the meter is set up for manual
reset (non-latching relay). Acknowledging the alarm reset at any time. Acknowledging the alarm even if
while it is still present has no effect on either the LED the alarm condition is still present resets the relay and
or the relay. When the alarm finally goes away, the turns off the LED.
relay automatically resets and the LED also goes off.
Manual reset any time
Automatic reset only Condition LED Relay
Condition LED Relay Normal Off Off
Normal Off Off Alarm On On
Alarm On On Ack Off Off
Ack (No effect) On On
Normal Off Off
Latching Relay (Lt-Clr)
In this application, the meter is set up for manual reset
Non-Latching Relay with Manual only after the signal passes the reset point (alarm
Reset (A-nman) condition has cleared). Acknowledging the alarm while it
is still present has no effect on either the LED or the
In this application, the meter is set up for automatic
relay. When the alarm is acknowledged after it returns to
and manual reset at any time (non-latching relay). the normal state, the LED and the relay go off. Notice
The LED and the relay automatically reset when the that the LED remains on, even after the meter returns to
meter returns to the normal condition.
the normal condition. This is because, for latching relays,
In addition, the relay can be manually reset while the the alarm LED reflects the status of the relay, regardless
alarm condition still exists, but the LED will stay on of the alarm condition.
until the meter returns to the normal condition.
Manual reset only after alarm condition has
Automatic + manual reset at any time cleared
Condition LED Relay Condition LED Relay
Normal Off Off Normal Off Off
Alarm On On Alarm On On
Normal Off Off Ack (No effect) On On
Next Alarm On On Normal On On
Ack On Off Ack Off Off
Normal Off Off

35
PROVU™ PD6200 Analog Input Rate/Totalizer Instruction Manual

Acknowledging Relays Setting Up the Interlock Relay


There are three ways to acknowledge relays (Force On) Feature
programmed for manual reset: Relays 1-4 can be set up as interlock relays. To set
1. Via the programmable front panel function keys up the relays for the interlock feature:
F1-F3 (Example: F3 assigned to ACK). 1. Access the Setup – Relay – Action menu and set
the action to off.

2. Remotely via a normally open push button wired


to the F4 terminal at the rear of the instrument. 2. In the Advanced features – User menu program
P+ P- F4 COM V+ mA+ any of the digital inputs to Force On any of the
1 2 3 4 5 6 internal relays (1-4).

3. Connect a switch or dry contact between the +5V


3. One of the digital inputs and the +5 V terminals terminal and the corresponding digital input (dI-1
on the digital I/O expansion module. to dI-4) terminal.
SW2
Digital I/O Module
1 2 3 4 5 6 7 8 9 10 SW1

+5 I1 I2 I3 I4 O1 O2 O3 O4 G
1 2 3 4 5 6 7 8 9 10

DI 1-4 DO 1-4
GND +5 I1 I2 I3 I4 O1 O2 O3 O4 G

ACK
5 VDC DI 1-4 DO 1-4 GND
When the ACK button or the assigned digital input is
closed, all relays programmed for manual reset are
acknowledged.
Interlock Relay Operation Example
Relays 1 & 2 are configured to energize (their front
panel LEDs are steady on) when SW1 & SW2
switches (above) are closed. If the contacts to these
digital inputs are opened, the corresponding front
panel LEDs flash indicating this condition. The
processes being controlled by the interlock relay will
stop, and will re-start only after the interlock relay is
re-activated by the digital inputs (switches).
Note: If multiple digital inputs are assigned to the
same relay, then the corresponding logic is (AND) –
i.e. both switches must be closed to activate the relay.

36
PROVU™ PD6200 Analog Input Rate/Totalizer Instruction Manual

Scaling the 4-20 mA Analog Reset Menu (reset)


Output (Aout) The Reset menu is used to reset the totals and maximum
or minimum reading (peak or valley) reached by the
The 4-20 mA analog output can be scaled to provide
process; both may be reset at the same time by selecting
a 4-20 mA signal for any display range selected. “reset high & low” (rst HL). If total is set to no, the tare
No equipment is needed to scale the analog output; value used to zero the display may be reset by selecting
simply program the display values to the “reset tare” (rst tr).
corresponding mA output signal.
The Analog Output menu is used to program the
4-20 mA output based on display values. Manual Control Menu (Contrl)
The Manual Control menu is used to control the
For further details, see Setting Numeric Values, 4-20 mA analog output and the relays manually,
page 24, Relay Action for Loss of 4-20 mA Input ignoring the input. Each relay and analog output can
(Loop Break), page 31. be programmed independently for manual control.
Selecting automatic control sets all relays and analog
output for automatic operation.

37
PROVU™ PD6200 Analog Input Rate/Totalizer Instruction Manual

Setting Up the Password (pass) Making Changes to a Password


The Password menu is used for programming three Protected Meter
levels of security to prevent unauthorized changes to If the meter is password protected, the meter will
the programmed parameter settings and to program display the message Locd (Locked) when the Menu
the non-resettable totalizer. button is pressed. Press the Enter button while the
message is being displayed and enter the correct
password to gain access the menu. After exiting the
Pass 1: Allows use of function keys and digital programming mode, the meter returns to its password
inputs protected condition.
Pass 2: Allows use of function keys, digital inputs
and editing set/reset points Disabling Password Protection
Pass 3: Restricts all programming, function keys, To disable the password protection, access the
and digital inputs. Password menu and enter the correct password
Total: Prevents resetting the total manually twice, as shown below. The meter is now unprotected
Gtotal: Prevents resetting the grand total manually until a new password is entered.

Protecting or Locking the Meter


Enter the Password menu and program a six-digit
password.
For instructions on how to program numeric values
see Setting Numeric Values on page 24.

If the correct six-digit password is entered, the meter


displays the message unLoc (unlocked) and the
protection is disabled until a new password is
programmed.
If the password entered is incorrect, the meter
displays the message Locd (Locked) for about two
seconds, and then it returns to Run Mode. To try
Total Reset Password & Non- again, press Enter while the Locked message is
Resettable Total displayed.
The total and the grand total can be password-
protected to prevent unauthorized total resets. Did you forget the password?
The grand total can be programmed as a non- The password may be disabled by entering a
resettable total by entering the password “050873”. master password once. If you are authorized to
make changes, enter the master password 508655
to unlock the meter.

• Once the Grand Total has been programmed as


“non-resettable” the feature CANNOT be
disabled.

38
PROVU™ PD6200 Analog Input Rate/Totalizer Instruction Manual

Advanced Features Menu Advanced Features Menu & Display Messages


To simplify the setup process, functions not needed Display Parameter Action/Setting
for most applications are located in the Advanced Prog E Programmable Set meter for
Features menu. exponent programmable
Press and hold the Menu button for three seconds to exponent and enter
exponent value
access the advanced features of the meter.
rht Round Set meter for round
horizontal tank horizontal tank volume
calculation
Inch Dimension Calculate volume in
(cm) gallons or meters
dianmr Diameter Enter the tank’s
diameter in inches
Length Length Enter the tank’s length
in inches
CutofF Cutoff Set low-flow cutoff
Count Count Set total and grand
total count direction
Tot C Total Count Set total to count up or
down
Gtot C Grand Total Set grand total to count
Count up or down
Advanced Features Menu &
C Strt Count Start Set start for total or
Display Messages grand total countdown
The following table shows the functions and AoutPr Analog output Program analog output
messages of the Advanced Features menu in the programming parameters
order they appear in the menu. Source Source Select source for the
4-20 mA output
Advanced Features Menu & Display Messages
O-rang Overrange Program mA output for
Display Parameter Action/Setting display overrange
filter Filter Set noise filter value u-rang Underrange Program mA output for
bypASs Bypass Set filter bypass value display underrange
Round Round Set the rounding value Break Loop Break Set analog output
for display variables value if input loop
seriAl break is detected
Serial Set serial
communication Force Force Force analog output
parameters value for loop break
SlaV Id Slave ID Set slave ID or meter Ignore Ignore Ignore loop break
address condition
baud Baud rate Select baud rate nmAx Maximum Program maximum mA
Tr dLY output allowed
Transmit delay Set transmit delay for
serial communication nmin Minimum Program minimum mA
output allowed
Parity Parity Select parity
Even, Odd, or None Calib Calibrate Calibrate 4-20 mA
with 1 or 2 stop bits output (internal
t-byt reference source used
Time byte Set byte-to-byte
for scaling the output)
timeout
4 nmA 4 mA output Enter mA output value
SelEct Select Enter the Select menu
read by milliamp meter
(function, cutoff, out)
with at least 0.001 mA
Functn Input signal Select linear, square resolution
conditioning root, programmable
20 nmA 20 mA output Enter mA output value
exponent, or round
read by milliamp meter
horizontal tank function
with at least 0.001 mA
Linear Linear Set meter for linear resolution
function and select
user User I/O Assign function keys
number of linearization
and digital I/O
points
F1 F1 function Assign F1 function key
No PtS Number of Set meter for 2 to
key
points 32-point linearization
F2 F2 function Assign F2 function key
Square Square root Set meter for square
key
root extraction

39
PROVU™ PD6200 Analog Input Rate/Totalizer Instruction Manual

Advanced Features Menu & Display Messages Rounding Feature (round)


Display Parameter Action/Setting The rounding feature is used to give the user a
F3 F3 function Assign F3 function key steadier display with fluctuating signals. Rounding is
key used in addition to the filter function.
F4 F4 function Assign F4 function Rounding causes the display to round to the nearest
(digital input) value according to the rounding selected. See
dI I Digital input 1 Assign digital input examples below:
1 – 8, if expansion
modules connected Rounding Actual Display Actual Display
dO 1 Digital output 1 Assign digital output Selection Value Value Value Value
1 – 8, if expansion 1 12.022 12.022 12.023 12.023
modules connected
ICal Internal source Enter internal source 5 12.022 12.020 12.023 12.025
calibration calibration (used for 10 12.024 12.020 12.025 12.030
scaling the meter
without a signal source
C CAL Current Calibrating 4-20 mA
calibration current input (internal Modbus RTU Serial
reference source used Communications (serial)
for scaling the input)
The meter is equipped with serial communications
C lo Current low Calibrate low current capability as a standard feature using Modbus RTU
input (e.g. 4 mA)
Serial Communication Protocol.
C Hi Current high Calibrate high current The meter may be connected to a PC for initial
input (e.g. 20 mA)
configuration via the on-board USB connection. For
V CAL Voltage Calibrating voltage ongoing digital communications with a computer or
calibration input other data terminal equipment, an RS-232, or RS-485
V Lo Voltage low Calibrate low voltage option is required; see Ordering Information on
input (e.g. 0 V) page 6 for details.
V Hi Voltage high Calibrate high voltage
input (e.g. 10 V)
Diag Diagnostics Display parameter
settings • DO NOT connect any equipment other than
Precision Digital’s expansion modules, cables, or
LED t LED test Test all LEDs
(press menu to exit
meters to the RJ45 M LINK connector. Otherwise
test) damage will occur to the equipment and the
meter.
Info Information Display software
number and version
Erase Erase Erase MeterView Pro Notes
software stored in
meter’s memory 1. More detailed instructions are provided with each
optional serial communications adapter.
Noise Filter (filter) 2. Refer to the PROVU Modbus Register Tables
located at www.predig.com for details.
The noise filter is available for unusually noisy signals
that cause an unstable process variable display. The
noise filter averages the input signal over a certain
period. The filter level determines the length of time
over which the signal is averaged. The filter level can
be set between 2 and 199. The higher the filter level,
the longer the averaging time and so the longer it
takes the display to settle to its final value. Setting the
filter level to zero disables the filter function.
When using more than one meter in a multi-drop mode,
Noise Filter Bypass (bypass) each meter must be provided with its own unique
The noise filter bypass changes the behavior of the address. The meter address (Slave ID) may be
meter so that small variations in the signal are filtered programmed between 1 and 247. The transmit delay
out but large abrupt changes in the input signal are may be set between 0 and 199 ms. The parity can be set
displayed immediately. The bypass value determines to even, odd, or none with 1 or 2 stop bits.
the minimum amount of signal change to be displayed
immediately. All signal changes smaller than the
bypass value are filtered or averaged by the meter.
The noise filter bypass may be set between 0.1 and
99.9% of full scale.

40
PROVU™ PD6200 Analog Input Rate/Totalizer Instruction Manual

Select Menu (SElEct) Programmable Exponent


The Select menu is used to select the input signal Linearization (Prog E)
conditioner applied to the input (linear, square root, The programmable exponent can be used to linearize
programmable exponent, or round horizontal tank), the signal from level transmitters in open-channel flow
low-flow cutoff, and analog output programming. The applications using weirs and flumes.
multi-point linearization is part of the linear function
selection. Application: Open Channel Flow

The PD6200, in combination with an ultrasonic level


transmitter, makes for an economical way to measure
and display open channel flow rate and total in most
weirs and flumes. A guide such as the ISCO Open
Channel Flow Measurement Handbook can provide
the user with all the information needed: the exponent
used in the flow equation for the desired flow units
Input Signal Conditioning (Functn) and the flow rate for any given head height. For
The Function menu is used to select the input signal example, to display the open channel flow rate from a
conditioner applied to the input: linear, square root, 3" Parshall flume, the ISCO handbook advises the
programmable exponent, or round horizontal tank exponent is 1.547 and at the maximum head height of
volume calculation. The multi-point linearization is 3.0 feet, the flow rate is 3.508 MGD.
part of the linear function selection.
3" Parshall Flume Discharge Table with Head in
Meters are set up at the factory for linear function with
Feet
2-point linearization. The linear function provides a Formula: CFS = 0.9920 H1.547
display that is linear with respect to the input signal.
GPM = 445.2 H1.547
MGD = 0.6411 H1.547
Multi-Point Linearization (Linear) Where: H = head in feet
Meters are set up at the factory for linear function with Table 13-3
2-point linearization. Up to 32 linearization points can Head (Feet) CFS GPM MGD
be selected under the linear function. The multi-point 3.00 5.428 2436 3.508
linearization can be used to linearize the display for
rd
non-linear signals such as those from level ISCO Open Channel Flow Measurement Handbook, 3 edition

transmitters used to measure volume in odd-shaped With this information the PD6200 should be
tanks or to convert level to flow using weirs and programmed in the following fashion. This setup
flumes with complex exponent. assumes the level transmitter is programmed to
output 20 mA at the maximum head height of 1.10
feet; but any mA value at a head height with a known
flow rate may be used.
Function Desire Programming

Open Channel Set Programmable Exponent to


3" Parshall flume
Square Root Linearization Flow 1.547

(Square) Millions of Set 4 mA = 0


The square root function can be used to linearize the Flow Rate Gallons per Day 20 mA = 3.508
(MGD)
signal from a differential pressure transmitter and Time base = Day

display flow rate in engineering units. Set Totalizer Conversion Factor = 1


Millions of
Total (password protect “total” to avoid
Gallons
accidental reset)

Program meter
Non-Resettable Set non-resettable grand total
so grand total can
Grand Total password
never be reset

Display Flow Set upper display for Grand Total


Display Rate, Total, and and lower display to toggle
Grand Total between rate and total.

41
PROVU™ PD6200 Analog Input Rate/Totalizer Instruction Manual

Round Horizontal Tank Low-Flow Cutoff (CutofF)


Linearization (rHt) The low-flow cutoff feature allows the meter to be
This function automatically calculates the volume in a programmed so that the often-unsteady output from a
round horizontal tank with flat ends. This function is differential pressure transmitter, at low flow rates,
only used when Total is set to no. always displays zero on the meter.
Set the display for the desired decimal point and The cutoff value may be programmed from 0.1 to
engineering units before entering the round horizontal 999999. The meter will display zero below the cutoff
tank function. Select units, inches or cm for the tank value. Programming the cutoff value to zero disables
dimension. Enter the diameter and the length in the cutoff feature. The cutoff can be disabled to
inches and the results are given in US gallons. Enter display negative values.
the diameter and length in cm and the results are
calculated automatically in liters.
The meter can be scaled to display the volume in any Totalizer Count Up/Down (Count)
engineering unit. The totalizer count up/down menu may be used to
program the total and grand total to either count up
from 0 when reset or count down from a programmed
value when reset. Total and grand total may have
their countdown numbers programmed individually
from 0 to 999999.
Note: After Scale is displayed continue pressing the
Enter button until the meter completes the
scaling of the input and display values.
Changing the Volume from Gallons to Liters
In the above graphic, entering the 48" for the diameter
and 120" for the length of the round horizontal tank,
the meter automatically calculates that the volume of
the tank is 940.02 gallons.
1. Convert gallons to liters
1 US gallon = 3.7854 L
940.02 gal = 3558.4 L
2. Go to the Setup menu and change the decimal
point to 1 decimal.
3. Go to the Program – Scale menu and press Enter
until dis 2 is shown on the main display.
4. Press Enter and change the display 2 value to
3558.4.
5. The meter is now displaying the volume in liters.
Note: The display can be scaled to display the volume
in any engineering units.
Another way to display the volume in liters is to enter
the dimensions in cm. The meter automatically
calculates the volume in liters.

42
PROVU™ PD6200 Analog Input Rate/Totalizer Instruction Manual

Analog Output Programming Analog Output Calibration


(AoutPr) To perform the analog output calibration, it’s
recommended to use a milliamp meter with a
The Analog Output Programming menu is used to resolution of at least 0.1 µA to measure the output
program the behavior of the 4-20 mA output. The current. The values saved internally during this
following parameters and functions are programmed procedure are used for scaling the 4-20 mA output in
in this menu: the Setup menu.
1. Source: Source for generating the 4-20 mA
output (e.g. PV)
Analog Output Calibration
2. Overrange: Analog output value with display in
overrange condition Procedure
3. Underrange: Analog output value with display in 1. Wire the PD6200 4-20 mA output to a current
underrange condition loop that includes a power supply (internal or
4. Break: Analog output value when loop break is external 12 to 24 VDC), and the mA input on the
detected digital meter. See Figure 19. 4-20 mA Output
Connections on page 19 for details.
5. Max: Maximum analog output value allowed 2. Turn on all devices. Allow for a 15 to 30 minute
regardless of input warm-up.
6. Min: Minimum analog output value allowed 3. Go to the Advanced Features menu, and
regardless of input navigate to the Analog Output Programming
7. Calibrate: Calibrate the internal 4-20 mA source (AoutPr) → Calibration (Calib) menu and press
reference used to scale the 4-20 mA output Enter.
4. The display will show 4 nmA. The PD6200 mA
Analog Output Source output should now be close to 4 mA. Press Enter
The source for generating the 4-20 mA output may be and the display will show 04.000. Enter the actual
assigned to the rate/process variable, total, grand value read by the digital mA meter and press
total, maximum or minimum value reached by the Enter.
rate/process, or one of the set points, or the Modbus 5. The display will show 20 nmA. The PD6200 mA
PV input. output should now be close to 20 mA. Press
Enter and the display will show 20.000. Enter the
actual value read by the digital mA meter and
press Enter.
6. The meter will now calculate the calibration
factors and store them.
7. Press Menu to exit and return to Run mode.

Analog Output Value for Loss of


4-20 mA Input (Loop Break)
The AoutPr - Break menu is used to force the analog
output to go to a user-specified mA value if a break
condition is detected in the 4-20 mA input loop.
Selecting Ignore causes the mA output to go to the
minimum value.

43
PROVU™ PD6200 Analog Input Rate/Totalizer Instruction Manual

Programmable Function Keys Function Keys & Digital I/O Available Settings
User Menu (user) Display Description
The User menu allows the user to assign the front F On 1* Force relay 1 (*through 4) into the on
panel function keys F1, F2, and F3, the digital input state. This function is used in
F4 (a digital input located on the input signal conjunction with a digital input
connector), and up to eight additional digital inputs to expansion module to achieve interlock
access most of the menus or to activate certain functionality. See Setting Up the
functions immediately (e.g. reset total, reset grand Interlock Relay (Force On) Feature on
total, reset max & min, hold relay states, etc.). This page 36 for details.
allows the meter to be greatly customized for use in Contrl Directly access the control menu
specialized applications. disabl Disable the selected function key or
Up to eight digital outputs can be assigned to a digital I/O
number of actions and functions executed by the AcH Acknowledge all active relays that are in
meter (i.e. reset total, reset grand total, alarms, relay a manual operation mode such as auto-
acknowledgement, reset or display max, min). The manual or latching
digital outputs can be used to trigger external alarms Reset Directly access the reset menu
or lights to indicate these specific events.
Rst t Reset the total
Rst gt Reset the grand total
Rst Hi Reset the stored maximum display
value
Rst Lo Reset the stored minimum display value
Rst HL Reset the stored maximum & minimum
display values
nmenu Mimic the menu button functionality
Function Keys & Digital I/O (digital inputs only)
Available Settings rigHt Mimic the right arrow/F1 button
Refer to the following table for descriptions of each functionality (digital inputs only)
available function key or digital I/O setting. up Mimic the up arrow/F2 button
functionality (digital inputs only)
Function Keys & Digital I/O Available Settings Enter Mimic the enter/F3 button functionality
Display Description (digital inputs only)
relay Alnm 1* Provide indication when alarm 1
Directly access the relay menu
(*through 8) has been triggered (digital
Set 1* Directly access the set point menu for outputs only)
relay 1 (*through 8)
Rly d Disable all relays until a button
assigned to enable relays (Rly E) is
pressed
Rly E Enable all relays to function as they
have been programmed
O Hold Hold current relay states and analog
output as they are until a button
assigned to enable relays (Rly E) is
pressed
d Hold Hold the current display value, relay
states, and analog output momentarily
while the function key or digital input is
active. The process value will continue
to be calculated in the background.
Ln1 Hi Display maximum display value on line 1
Ln1 Lo Display minimum display value on line 1
Ln1 HL Display maximum & minimum display
values on line 1
Ln2 Hi Display maximum display value on line 2
Ln2 Lo Display minimum display value on line 2
Ln2 HL Display maximum & minimum display
values on line 2
Ln2 gt Display the grand total on line 2

44
PROVU™ PD6200 Analog Input Rate/Totalizer Instruction Manual

Internal Source Calibration (ICAL)


The meter is factory calibrated prior to shipment
for milliamps and volts with calibration equipment
that is certified to NIST standards.

The use of calibrated signal sources is necessary to


calibrate the internal source of the meter. The
meter’s internal source is what allows the user to
scale the meter without applying a signal.
Check calibration of the meter at least every
12 months. Each input must be recalibrated
separately.
Notes:
1. If meter is in operation and it is intended to The graphic shows the calibration of the current input.
accept only one input type (e.g. 4-20 mA), The voltage input is calibrated in a similar way.
recalibration of other input is not necessary. Tips:
2. Allow the meter to warm up for at least
• Low and high input signals can be any valid
15 minutes before performing the internal
values within the range of the meter.
source calibration procedure.
• Observe minimum input span requirements
The Internal calibration menu is part of the Advanced
between input 1 and input 2.
Features menu.
• Low input should be less than high input signal.
However, the low display can be higher than the
1. Press and hold the Menu button for three high display (i.e. 4-20 mA = 100.0 to 0.0).
seconds to access the advanced features of the
meter. Error Message (Error)
2. Press the Up arrow button to scroll to the Internal An error message indicates that the calibration or
calibration menu (ICAL) and press Enter. scaling process was not successful.
3. The meter displays either current calibration After the error message is displayed, the meter
(C CAL) or voltage calibration (V CAL), according reverts to the input prior to the failure during
to the input setup. Press Enter to start the calibration or scaling and to input 1 during internal
calibration process. calibration, allowing the appropriate input signal to be
Example of Internal Calibration for current applied or programmed.
input: The error message might be caused by any of the
following conditions:
4. The meter displays low input current message 5. Input signal is not connected to the proper
(C lo). Apply the low input signal and press terminals or it is connected backwards*.
Enter. The display flashes for a moment while the
meter is accepting the low input signal. 6. Wrong signal selection in Setup menu*.
5. After the display stops flashing, a number is 7. Minimum input span requirements not
displayed with the leftmost digit brighter than the maintained.
rest. The bright digit is the active digit that can be 8. Input 1 signal inadvertently applied to calibrate
changed by pressing the Up arrow button. Press input 2*.
the Right arrow button to move to the next digit. *Not relevant when scaling the meter.
6. Set the display value to correspond to the input
signal being calibrated, typically Minimum Input Span
4.000 mA. The minimum input span is the minimum difference
between input 1 and input 2 signals required to complete
7. The display moves to the high input calibration the calibration or scaling of the meter.
(C Hi). Apply the high input signal and press
Input range Input 1 & input 2 span
Enter.
4-20 mA 0.15 mA
8. Set the display for the high input calibration, in 10 VDC 0.10 VDC
the same way as it was set for the low input
calibration, typically 20.000 mA.

45
PROVU™ PD6200 Analog Input Rate/Totalizer Instruction Manual

Meter Operation Maximum/Minimum Readings


The meter is capable of accepting current (0-20 mA, The max & min readings (peak & valley) reached by
the process can be displayed either continuously or
4-20 mA) and voltage signals (0-5 V, 1-5 V, 0-10 V,
momentary:
10 V) and displaying these signals in engineering
units from -99999 to 999999 (e.g. a 4-20 mA signal 1. Display briefly by assigning to the F1-F3 function
could be displayed as -50.000 to 50.000). keys or to the digital inputs in the User menu.
The dual-line display can be customized by the user 2. Display continuously by assigning either display
to operate in such a way as to satisfy a specific to max/min through the Display menu.
application. Typically, the main display is used for the Any of the F1-F3 function keys (buttons) and the
process variable; while the second display is used for digital inputs can be programmed to reset the max &
engineering units, custom legend, total, grand total, or min readings. The meters are set at the factory to
set point indication. display the max reading by pressing the Up arrow/F2
The meter can be set up to display the analog input button and to use the Right arrow/F1 button to access
on the main display and the Modbus input on the the Reset menu.
second display. The relays and analog output can be
programmed to operate from the Modbus PV input. To display max reading using function key with
factory defaults:
Front Panel Buttons Operation 1. Press Up arrow/F2 button to display maximum
Button Description reading since the last reset/power-up.
Symbol 2. To reset max/min press Right arrow/F1 button to
Press to enter or exit Programming access the Reset menu. The max & min displays
Mode, view settings, or exit max/min are reset to actual values.
readings 3. Press Menu to exit max/min display reading.
Press to reset max/min readings or
other parameter/function assigned To display max/min readings continuously:
through the User menu Assign either display to Max (d Hi), Min (d Lo), or
Press to display max/min readings or toggle between Max and Min (d HL) every 10
other parameter/function assigned seconds.
through the User menu
Press to acknowledge relays or other
parameters/function assigned through
the User menu

Function Keys Operation


During operation, the programmable function keys
operate according to the way they have been
programmed in the Advanced Features – User menu.
See Programmable Function Keys User Menu (user)
on page 44 for details.
The table above shows the factory default settings for Totalizer Overflow Displays
F1, F2, and F3.
Total to 9 Digits
These flow rate/totalizers can display up to nine digits
F4 Operation of total flow with the total overflow feature.
A digital input, F4, is standard on the meter. This
digital input is programmed identically to function keys
F1, F2, and F3. The input is triggered with a contact
closure to COM, or with an active low signal. During
operation, F4 operates according to the way it has
been programmed in the Advanced Features – User
menu. See Programmable Function Keys User Menu In the diagrams above, the flow totalizer is displaying
(user) on page 44 for details. 532,831,470 by toggling between a display of
“oF 532” and “831470”. Notice the T with arrow ▲
symbol is lit up indicating the display is in overflow
mode.

46
PROVU™ PD6200 Analog Input Rate/Totalizer Instruction Manual

Troubleshooting Reset Meter to Factory Defaults


Due to the many features and functions of the meter, When the parameters have been changed in a way
it’s possible that the setup of the meter does not that is difficult to determine what’s happening, it might
agree with what an operator expects to see. be better to start the setup process from the factory
If the meter is not working as expected, refer to the defaults.
Diagnostics menu and recommendations below. Instructions to load factory defaults:
1. Enter the Advanced Features menu. See
Advanced Features Menu on page 38.
Diagnostics Menu (diag) 2. Press Up arrow to go to Diagnostics (diAG) menu
The Diagnostics menu is located in the Advanced 3. Press and hold Right arrow for three seconds,
Features menu, to access Diagnostics menu see press Enter when display flashes reset.
Advanced Features Menu on page 38. Note: If Enter is not pressed within three
seconds, the display returns to the Diagnostics
This menu allows the user to test the functionality of
menu.
all the meter LEDs, check the meter’s software and
version information, and erase the MeterView Pro 4. The meter goes through an initialization
software installation files from the meter. Press the sequence (similar as on power-up), and loads the
Enter button to view the settings and the Menu button factory default settings.
to exit at any time.
For a description of the diagnostic messages, see
Advanced Features Menu & Display Messages on
page 39.

Testing the Display LEDs


To test all LEDs on the display:
1. Go to the Diagnostics menu (diAG) and
press Enter button.
2. Press Up arrow button and scroll to
LED Test menu (led t)
3. Press the Enter button to activate the LED
Test. The meter will cycle through all digits,
decimal points, and relay indicators to
enable the operator to check that all LEDs
are functioning properly.
4. Press the Enter button again to access the
Information menu (info) or press the Menu
button to return to Run Mode.

Determining Software Version


To determine the software version of a meter:
1. Go to the Diagnostics menu (diAG) and
press Enter button.
2. Press Up arrow button and scroll to
Information menu (Info).
3. Press Enter to access the software number
(SFT) and version (UER) information. Write
down the information as it is displayed.
Continue pressing Enter until all the
information is displayed.
4. The meter returns to Run Mode after
displaying all the settings.

47
PROVU™ PD6200 Analog Input Rate/Totalizer Instruction Manual

Factory Defaults & User Settings Parameter Display Default Setting


The following table shows the factory setting for
Relay 1 action Act 1 Automatic
most parameters.
Parameter Display Default Setting Relay 1 set point Set 1 1.000

Relay 1 reset point RSt 1 0.000


Input type Input 4-20 mA
Relay 2 action Act 2 Automatic
Total total Yes

Rate / total / gr. total Relay 2 set point Set 2 2.000


Units units
mA / mA / mA
Relay 2 reset point RSt 2 0.000
Filter filter 70
Relay 3 action Act 3 Automatic
Bypass bypass 0.2
Relay 3 set point Set 3 3.000
Function Functn Linear
Relay 3 reset point RSt 3 2.500
Number of points No Pts 2
Relay 4 action Act 4 Automatic
Programming prog Scale
Relay 4 set point Set 4 4.000
Input 1 InP 1 4.000 mA
Relay 4 reset point RSt 4 3.500
Display 1 Dis 1 4.000
Fail-safe relay 1 Fls 1 Off
Input 2 InP 2 20.000 mA
Fail-safe relay 2 Fls 2 Off
Display 2 Dis 2 20.000
Fail-safe relay 3 Fls 3 Off
Decimal point ddd.ddd 3 places
Fail-safe relay 4 Fls 4 Off
Cutoff value CutofF 0.0 (disabled)
Display 1 analog
Dis 1 4.000
out
Display line 1 Line 1 Rate/Process
Output 1 value Out 1 4.000 mA
Display line 2 Line 2 Total value
Display 2 analog
Display intensity d-Inty 6 Dis 2 20.000
out

Total time base T tb Second Output 2 value Out 2 20.000 mA

Total conversion Source analog


T CF 1.000 Source Rate/process
factor output

Total reset T rst Manual Overrange output O-rang 21.000 mA

Grand total time Underrange output u-rang 3.000 mA


GT tb Second
base
Grand total Loop break output break 1.000 mA
gT CF 1.000
conversion factor
Maximum output nmAx 23.000 mA
Grand total reset gT rst Manual
Minimum output nmin 1.000 mA
Total count
Tot C Up
up/down F1 function key F1 Reset max & min

Grand tot count Gtot C Up Password 1 Pass 1 000000 (unlocked)


Relay 1
Asign1 Total Password 2 Pass 2 000000 (unlocked)
assignment
Relay 2 Password 3 Pass 3 000000 (unlocked)
Asign2 Total
assignment
Total password Total 000000 (unlocked)
Relay 3
Asign3 Rate
assignment Grand total
Gtotal 000000 (unlocked)
password
Relay 4
Asign4 Rate
assignment

48
PROVU™ PD6200 Analog Input Flow Rate/Totalizer Instruction Manual

Troubleshooting Tips
This meter is a highly sophisticated instrument with an extensive list of features and capabilities. If the front panel
buttons are used to program the meter, it may be a difficult task to keep everything straight. That is why we strongly
recommend the use of the free MeterView Pro software for all programming activities. A USB cable is provided with
the meter for programming with MeterView Pro software.
If you have programmed the meter with the front panel buttons and it is not working as intended, try re-programming
the meter using MeterView Pro software.

Symptom Check/Action
No display at all Check power at power connector
Not able to change setup or programming, Meter is password-protected, enter correct six-digit password to
Locd is displayed unlock or Master Password of 508655.
If a Low-Flow Cutoff Value has been programmed, the meter will
display zero below that point, regardless of the input – which can
appear like the meter is not responding to an input change. Check to
Meter does not respond to input change make sure the problem is not being caused by an undesired low-flow
cutoff value.
To prevent the display from showing a negative value, set the low-
flow cutoff to a value greater than zero.
Check:
Meter displays error message during 1. Signal connections
calibration (Error) 2. Input selected in Setup menu
3. Minimum input span requirements
Meter displays Check:
1. 999999 1. Input selected in Setup menu
2. -99999 2. Corresponding signal at Signal connector
Check:
1. Input signal stability and value
Display is unstable
2. Display scaling vs. input signal
3. Filter and bypass values (increase)
Display response is too slow Check filter and bypass values
Check:
Display reading is not accurate 1. Input signal conditioner selected: Linear, square root, etc.
2. Scaling or calibration
Display does not respond to input changes, Check:
reading a fixed number Display assignment, it might be displaying max, min, or set point.
Display alternates between
1. Hi and a number Press Menu to exit max/min display readings.
2. Lo and a number
Check:
Relay operation is reversed 1. Fail-safe in Setup menu
2. Wiring of relay contacts
Check:
Relay and status LED do not respond to
1. Relay action in Setup menu
signal
2. Set and reset points
Flashing relay status LEDs Relays in manual control mode or relay interlock switches opened.
Check:
Meter not communicating with application 1. Serial adapter and cable
programs 2. Serial settings
3. Meter address and baud rate
If the display locks up or the meter does not
Cycle the power to reboot the microprocessor.
respond at all
Other symptoms not described above Call Technical Support for assistance.
Note: Certain sequences of events can cause unexpected results. To solve these issues, it is best to start fresh from
factory defaults and use the manual as a step by step programming guide, rather than a random approach to
programming. To reset the meter to factory defaults, see Reset Meter to Factory Defaults on page 47. In addition, for
best results, we recommend using the free MeterView Pro software for all programming needs.

49
PROVU PD6200 Analog Input Rate/Totalizer Instruction Manual

Contact Precision Digital


Technical Support
Call: (800) 610-5239 or (508) 655-7300
Fax: (508) 655-8990
Email: [email protected]

Sales Support
Call: (800) 343-1001 or (508) 655-7300
Fax: (508) 655-8990
Email: [email protected]

Place Orders
Email: [email protected]

For the latest version of this manual please visit


www.predig.com

PRECISION DIGITAL CORPORATION


233 South Street • Hopkinton MA 01748 USA
Tel (800) 343-1001 • Fax (508) 655-8990
www.predig.com
LIM6200_P
SFT039 Ver 4.010 & up
02/22

You might also like