13.specification Steam and Condensate System
13.specification Steam and Condensate System
Boiler house:
Type of boiler: Three-pass-boiler with continual burner
Range of load variation: from 20% til 100% (Start, Stop)
Maximum pressure: 14 bar
Working Pressure (for 230m/min). 12 bar
Pressure deviation: smaller than ± 0,5 bar
Boiler capacity:
Double wall-board till 1500 g/ m² 6 t/h, better 8 t/h
From 1500 g /m² oder Triwall-board 8 t/h, better 10 t/h
Water-preparation: Capacity 2 m³/h
Feed water tank: Capacity 4 m³
Deaeration: thermic deaeration at 103°C
(0,5 bar into feed water tank)
Piping-layout:
Please note the following items at the pipework-installation:
- optimal drainage of the pipework
- optimal deaeration of the pipework
- sufficient insulation (steam- and condensate pipes)
- sufficient compensation of thermal elongation (expansion-bows)
- sufficient fastening and fixing-points
Dimensions of the pipework: to maximum boiler capacity
Condensate return:
Please provide a condensate-station to feed high-pressure condensate and low-
pressure condensate back into the boiler by a high-pressure pump. Please, also
provide a by-pass-valve to bring the condensate back to the feedwater-tank, in
case of cold condensate after start-up in the morning.
Triplex-preheater:
Livesteam-pressure: constant 12 bar saturated steam for 230 m/min
Condensate-pressure after steam-trap: maximum 14 bar
Doublefacer:
The hotplates should be divided into two sections with adequate motor-
controlled regulation-valves.
An independent steam-supply is preferred than a cascade-control