HVAC

Application Controllers
DAC-304

Description Specifications
The DAC-304 is a fully programmable, Native BACnet™ Advanced Application Controller that
communicates on an RS-485 LAN using the BACnet MS/TP protocol. The DAC-304 is designed for a BACnet Device Profile
BACnet Advanced Application Controller
wide-range of applications that have small local I/O requirements. It also supports BACstats and other (B-AAC)
Delta LINKnet devices.
Inputs
Features 3 Universal inputs - 10 bit (supporting 0-5v,
—Native BACnet firmware 0-10V, 10kΩ, 4-20mA)

Outputs
—BACnet MS/TP communications 4 Binary triac outputs

—Supports 4 BACstat network sensors on LINKnet Jumper selection for internal or external power
for room sensing and control or 2 Delta Field on binary outputs
Modules on LINKnet for I/O expansion LED status indication of each output

—Easy to mount housing Technology


32-bit processor
—Fully programmable in GCL+
1 MB (8 megabit) Flash memory

—Application database can be flash loaded over the 127 KB SRAM (for database)
network
LED indication of CPU and SCAN status
Application —Controller firmware can be flash loaded over the Device Addressing
The DAC-304 is suitable for controlling various network Set via DIP switch and jumpers, or software
packaged units and equipment with small I/O setup
requirements such as Fan Coil units, Unit Ventilators —Supports Modbus capability via flash loading in the
and Heat Pumps. Communications Ports
field
Main LAN (NET1)
BACnet MS/TP @ 9600, 19200, 38400 or
The fully programmable DAC-304 can be tailored to —Supports flash loading Modbus upgrades via 76800 bps (default)
specific applications by creating and modifying BACnet hardware key (maximum of 99 devices per BACnet MS/TP
objects and GCL+ programs. segment)
—Derived Network Addressing (DNA) for simple SubLAN (NET2)
integration into a standard network architecture Delta LINKnet @ 76800 bps (maximum 4
devices on LINKnet, with no more than 2
—Service port DFM devices)

Document Edition 3.0 January 2007


HVAC

Application Controllers
DAC-304: Board Layout Diagram Specifications (Continued)
Connectors
Removable screw-type terminal connectors

Wiring Class
Class 2

Power
24 VAC

6VA, 54VA maximum with fully loaded BO’s

Ambient
32° to 131°F (0° to 55°C)

10 - 90% RH (non-condensing)

Dimensions
7 5/8 x 4 x 1 7/8 in. (19.2 x 10.2 x
4.8 cm) with housing

0.551 lb. (250 g) with housing

Compliance
CE

FCC

Listings
C-UL Listed

UL 916 Listed

BTL Listed
Accessories Ordering
RPT-768—Delta Network Repeater for BACnet MS/TP Order the DAC-304 with the desired options according
to the following product number:
TRM-768—Delta Network Terminator for BACnet MS/TP
DAC-304—3 Inputs, 4 BO’s
CON-768—Delta Network Converter
DAC-304-V2—3 Inputs, 4 BO’s (V2* Firmware)

*Note: Not all features described in this document are


available when this option is selected.