Application Note SolarEdge - Seccionamento Automático Por Dispositivo Diferencial Residual Nas Entradas CC Integrado Ao Inversor
Application Note SolarEdge - Seccionamento Automático Por Dispositivo Diferencial Residual Nas Entradas CC Integrado Ao Inversor
3 August 2021
Capacitive discharge current - Discharge current is generated mainly by the parasitic capacitance of the PV modules to
PE. The module type, the environmental conditions (rain, humidity) and even the distance of the modules from the roof
can affect the discharge current. Other factors that may contribute to the parasitic capacitance are the inverter’s internal
capacitance to PE and external protection elements such as lightning protection.
During operation, the DC bus is connected to the alternating current grid via the inverter. Thus, a portion of the
alternating voltage amplitude arrives at the DC bus. The fluctuating voltage constantly changes the charge state of the
parasitic PV capacitor (i.e. capacitance to PE). This is associated with a displacement current, which is proportional to the
capacitance and the applied voltage amplitude.
Residual current - if there is a fault, such as defective insulation, where an energized cable comes into contact with a
grounded person, an additional current flows, known as a residual current.
In installations where the local electric code requires an RCD with a lower leakage setting, the discharge current might result in
nuisance tripping of the external RCD. To avoid nuisance tripping of the external RCD and to ensure correct operation after the
installation, it is important to select the correct RCD. An RCD with a rating of 30mA may trip at a leakage as low as 15mA
(according to IEC 61008). High quality RCDs typically trip at a value closer to their rating.