Asenware FP100 Addressable Fire Alarm System Installation Guide

The document provides an overview and specifications for the AW-FP100 Series Fire Alarm Control Panel from Asenware. Key points include: - It is an intelligent panel designed for most applications and can be configured with other panels or control systems. - A 7-inch touchscreen display provides real-time fire alarm, trouble, and supervisory information. - It can connect up to 250 devices on a single loop and includes battery backups to power the system for 8 hours. - The panel supports network connectivity, remote monitoring, and integration with other systems like GSM, IP, cloud, and Modbus.

Uploaded by

francky souk
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
732 views

Asenware FP100 Addressable Fire Alarm System Installation Guide

The document provides an overview and specifications for the AW-FP100 Series Fire Alarm Control Panel from Asenware. Key points include: - It is an intelligent panel designed for most applications and can be configured with other panels or control systems. - A 7-inch touchscreen display provides real-time fire alarm, trouble, and supervisory information. - It can connect up to 250 devices on a single loop and includes battery backups to power the system for 8 hours. - The panel supports network connectivity, remote monitoring, and integration with other systems like GSM, IP, cloud, and Modbus.

Uploaded by

francky souk
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 64

Addressable Fire Alarm Control Panel

AW-FP100 Series
Product Overview

• Asenware AW-FP100 Series Fire Alarm Control Panel are intelligent panel which are carefully
designed to make it suitable for most of applications. It can be configured with other panels or
control systems. It’s user friendly functionality makes it suitable to program and configure the
devices. 7” touchscreen display gives the information for fire alarm, trouble , supervisory and
other related information all the time.

Suitable for big project

One loop can connect 250 devices

1-2 loop: 12V5AH*2pcs lead acid batteries, standby 8 hours

3-8 loop: 12V17AH*2pcs lead acid batteries, standby 8 hours


1 . 7 " To u c h s c r e e n L C D C o l o r D i s p l a y

2. 2-Wire cable for all addressable devices

3. Network Available

4. Options:GSM/IP/Cloud/Modbus

5. Graphic remote monitor access system

6. CAN BUS Network System

7. Addressable bell
在此输入您的封面副标题
Wiring Diagram
The Panel of Internal Terminal

在此输入您的封面副标题
Panel to Panel Connect

Note: The first panel and the last panel need to install a 120 Ω Resistor
If user do not install a 120 Ω Resistor, the panel will show AC Power Fault
Photograph of Wring diagram

: Connect the AC mains


Problems you may encounter during use
1. : Wire is 2.When the Resistor 3.When the are not
exposed to the outside removed, Panel will connected properly, the panel screen
a part, but the panel appear . can
can work normally.
Problems you may encounter during use

Be careful not to damage the


.

If it is damaged, please
replace it in time.

Otherwise, if th touch the


mainboard, the IC card of the
mainboard will burn out and
out
too.
Addressable Smoke detector AW-D101
Addressable Heat detector AW-D102
Addressable Smoke and Heat detectorAW-D103
Strobe sounder base
AW-D105 Asenware Addressable Manual Call Point
Addressable strobe sounder AW-D106

Features:
• Addressable-analog
communication
• Low Standby current
• High decibel rating
• Flash period of 1 sec
Addressable bell -Model AW-D109

Features:
• Addressable-analog communication
• Low Standby current
• High decibel rating
Addressable Module
Addressable monitor module AW-D110
Problems you may encounter during use
Problems you may encounter during use
Addressable supervisory module AW-D111
Problems you may encounter during use

Connect the Beam


Addressable control module AW-D112
Addressable relay module AW-D113
Addressable isolator module AW-D114
Problems you may encounter during use

• Q: Why the panel shows

• A: (1) Wiring error

(2)No resistor installed


Addressable repeater AW-D116

Convenient to know the location of th event


more precisely.
LEDs for Fire,supervisory and Alarm are also
provide with ACK push button.From slience
button,panel and remote nofification
appliances can be silenced.
Base on EN54-2 and EN54-4
Addressable annunciator boardAW-D117 D118

Feature:

One AW-D117 can be connected


with 4 pieces of AW-D118 for
maximum 120 zones.

Three Lines of 40 Character each


LCD
LED Indication for Alarm, Fault and
Supervisory
Push Buttons to acknowledge the
silence
Lamp Test from Key Switch
IP 30 Cabinet
Addressable power transmitter AW-D121

Designed to provide auxiliary power


when power is not enough from
panel itself to operate all devices.

Feature:
Addressable
5A@24VDC Output
EN5-D Standard
Omc;ide natteru cjarher
12V2.3AH*2 Batteries optional
Problems you may encounter during use

• Q1: When should we install the transmitter?

• A1: Under normal sutiation, the voltage of the device is 24V. When your device voltage is
between 15V and 20V, you need to install a transmitter to keep the voltage on the loop stable.

Q2: Product voltage is very low, the strobe sounder and bell can not work normal, how to do?

A2: You need to install a transmitter to keep the voltage on the loop stable.
Addressable power transmitter AW-D121
Functions:

1-increase the current for the loop

2-increase the communication distance for the loop. (The increased distance can be doubled.But
the actual communication distance is related to the load connected and the size of the cable,
because the cable has resistance. If many devices, like addressable strobe sounders are installed
in a place far away from us, a large voltage drop will occur. In this situation, the communication
distance will be decreased.)

Two versions of the current:

one is 2.5A, the other is 5A.


Addressable detector code number method
Addressable equipment code number method
Addressable equipment code number method

Addressable strobe Addressable Annunciator Addressable Annunciator


sounder code method code method Board code method
Addressable equipment code number method

Addressable Power Transmitter


Note: All modules code number method is same code method
The panel of operation method

1. first you must connect all equipment complete 2. then turn on the fire alarm panel
Specific software to set up panel inforamtion

Specific software to set up panel


inforamtion including panel setup,
TCP settings, GSM setting, device
name setting, register setting, wireless
device setting, linkage(zone setup).
Specific software to set up panel inforamtion
Panel Operation

Press LOGIN Press PASSWORD CHANGE


The panel of operation method

please click panel setup touch button,configured the panel of


name,time setup
Panel Operation
search all equipment,it's mean
Press REGISTER register equipment

1.After all the devices code 2.Press waiting for about 250 second,then
number,press The encoded device will be registered on the panel.
Problems you may encounter during use
• If the device is improperly connected or the device is not properly installed, the panel will
display communication fault.

• If the address of the device was changed, such as changing the code: 10 to 12, but you do not
re-searched on panle, the panel will display communication fault.
Problems you may encounter during use
No devices name
Problems you may encounter during use

Q: Why the panel shows

A: Yes. You can click ON to shield the fault.


Addressable equipment zone setting,you can setting the equipment in which
zone,from 1 zone to 120 zone ,note every equipment can setting four zone
Addressable equipment product type setting,you can setting the
equipment of product type

Note :all addressable module have two product type to choice


Note:detector,MCP,fire bell,horn/strobe,annunciator,power transmitter is only one type
Panel zone setting
Panel zone setting

NOTE: ZONE 2,set as show room,one conditon can activate sounder,and the delay time is
10 second.

NOTE: FireQTY The maximum number of devices is three.


Problems you may encounter during use
A2: Need to be set in the same Zone, and use the
detector or manual call point to drive strobe sounder
• A: Forget to confirm or touch “OFF” or fire bell.
TCP/IP Setting

Communication Setting: TCP/IP address of panel setting


TCP/IP is for a computer to monitor if have fire occur and fault occur in system.
TCP/IP Setting:Computer display

The software can only be used in the same LAN. One software connects less than 10 panels.
CLOUD Setting

write down the cloud address


CAN Setting

Communication Setting: CAN is for panel If have 2 panels connect a network, number 1 and
to panel connect as a network, number must register
maximum 8 pcs panel connect
GSM Setting
STATUS & OPERATION SETTING

status &operation setting:


user can enquiry every addressable equipment Note: Test means user can test every equipments
user can test every equipment,disablement every equipment Isolated means user can disable every equipments
Test the devices
Disable the Devices
CHECK THE HISTORY

history enquiry:user can check history fire event,fault event ,linkage event
Restore Factory Setting: user no need to operation
User List:if user forget password,so you can check list

Click Help to check


Level authority
Standalone Smoke Features :
ASENWARE丨Wireless Touchscreen Addressable Fire Alarm Panel