Beam - Timber Prop - 500Wx500D - 1st - 20200730
Beam - Timber Prop - 500Wx500D - 1st - 20200730
Issue 1st
Date : 30-Jul-20
Design by : RC
Checked by : RN
SITE CLIENT
FARS CONTRACT C18W02
CHI KAN
NTERMODEL TRANSFER TERMINAL BUILDING
CALCS BY RC TITLE DWG No. SHEET NO
CHECKED BY RN Proposed Falsework for 500W x 500D Beam 20/041/PD/051 OF
DATE 30-Jul-20 Design Criteria Design Rev 1st 1
I) Reference Documents
The following standards and codes of practice have been used for the preparation of these calculations.
th
1. Steel Designer Manual - 4 Edition
2. BS5975 Code of Practice for Falsework - 2008
3. CIRIA Report 108
4. Code of Practice on Wind Effects, Hong Kong 2004
nd
5. Formwork a Guide to Good Practice - 2 Edition
Loadings:
Falsework - This Design Cal is only checking the 500W x 500D beam, with 150mm thk slab (max.)
Also applicable to beam with smaller size
Thickness = 150 mm
Therefore
Design Load = 5.68 KN/m2
Width = 500 mm
Depth = 500 mm
Therefore
Design Load = 14.25 KN/m2
SITE CLIENT
FARS CONTRACT C18W02
CHI KAN
INTERMODEL TRANSFER TERMINAL BUILDING
CALCS BY RC TITLE DWG No. SHEET NO
CHECKED BY RN Proposed Falsework for 500W x 500D Beam 20/041/PD/051 OF
DATE 30-Jul-20 Check Plywood- Form Face Design Rev 1st 3
Applied load = 14.3 kN/m2 Span (L) = 300mm Support width (B) = 47mm
= 1.76kN/m
= 0.000205 m
= 0.20mm
d (allow) d = L/270
= 300 mm ÷ 270
= 1.11mm > 0.20mm O.K.
SITE CLIENT
APPLIED LOADING
Distributed Loads
End1 End2 End1 End2
1.70 1.70 kN/m .... at 0.000 0.500 m
4.28 4.28 kN/m .... at 0.500 1.000 m
1.70 1.70 kN/m .... at 1.000 1.500 m
1. Bending Moment
BM (allow) = 0.814KNm
= 0.81 kNm > 0.31 kNm ∴ OK
2. Shear
SF (allow) = 4.67 KN
= 4.67kN > 1.41 kN ∴ OK
3. Deflection
(allow) = L ÷ 270 = 900 mm ÷ 270
= 3.33 mm > 0.78 mm ∴ OK
SITE CLIENT
FARS CONTRACT C18W02
CHI KAN
NTERMODEL TRANSFER TERMINAL BUILDING
CALCS BY RC TITLE DWG No. SHEET NO
CHECKED BY RN Proposed Falsework for 500W x 500D Beam 20/041/PD/051 OF
DATE 30-Jul-20 Check Secondary bearer Design Rev 1st 5
Computer Output :
Beam Length 3.30 m
Moment of Inertia 714.93 cm4
Elastic Modulus 8554 N/mm2
APPLIED LOADING
Distributed Loads
End1 End2 End1 End2
7.25 7.25 kN/m .... at 0.000 3.300 m
1. Bending Moment
BM (allow) = 1.48KNm
= 1.48 kNm > 0.52 kNm ∴ OK
2. Shear
SF (allow) = 8.48 KN
= 8.48kN > 3.48 kN ∴ OK
3. Deflection
(allow) = L ÷ 270 = 900 mm ÷ 270
= 3.33 mm > 0.31 mm ∴ OK
SITE CLIENT
FARS CONTRACT C18W02
CHI KAN
INTERMODEL TRANSFER TERMINAL BUILDING
CALCS BY RC TITLE DWG No. SHEET NO
CHECKED BY RN Proposed Falsework for 500W x 500D Beam 20/041/PD/051 OF
DATE 30-Jul-20 Check Primary bearer Design Rev 1st 7
Timber prop
Use 50x100 SC4 timber 6.74kN Max. reaction
from previous design check of primary bearer
Properties of Prop
The longest length of prop (L) = 1000 mm (on safe side)
Width of Props = 50 mm Depth of Props = 100 mm
Area of Props = 5000 mm2
Moment of Inertia (Iyy) = 1041666.7 mm^4
Radius of gyration ry = 14.43 mm
Find the effective length (Le) for buckling about the weak axis, y-y axis,
Number of braces on the prop = 0
L/1 = 1000.00 mm
Check all modification factors: K3, K7 and K12 (Refer to 5268 Part 1988 table 17)
K3 = 1.75 K8 = 1.1
Calculate the permissble compression stress = Grade compression stress (σ) x K factors
= 9.64 N/mm2 > 1.35 N/mm2
The applied loading OK