A6V12505054 - Automation Station PXC7 - en
A6V12505054 - Automation Station PXC7 - en
Automation stations
PXC7
Type summary
Standardized hardware
PXC7.E400S, M, and L are based on the same hardware and all have the same look and
feel. Interfaces like RS485 are enabled and disabled according to the type specification.
1)
For details on engineering, see PXC4, PXC5 & PXC7 Planning overview, A6V13054435.
2)
Depending on the behavior of the third-party MS/TP devices.
2
Siemens Schweiz AG A6V12505052_en--_b
Smart infrastructure 2022-06-20
TXM input/output modules
Universal module with/without local operation and LCD TXM1.8U, TXM1.8U-ML CM2N8173
Super universal module with/without local operation and LCD TXM1.8X, TXM1.8X-ML CM2N8174
Product documentation
Related documents such as environmental declarations, CE declarations, etc., can also be
downloaded at the following Internet address:
www.siemens.com/bt/download
3
Siemens Schweiz AG A6V12505052_en--_b
Smart infrastructure 2022-06-20
Technical and mechanical design
4
Siemens Schweiz AG A6V12505052_en--_b
Smart infrastructure 2022-06-20
LED displays
5 Hz 5 Hz
2s 1s 2s 1s
5
Siemens Schweiz AG A6V12505052_en--_b
Smart infrastructure 2022-06-20
Notes
Safety & Security
CAUTION
National safety regulations
Failure to comply with national safety regulations may result in personal injury and property
damage.
● Observe national provisions and comply with the appropriate safety regulations.
Ambient temperature -5...50 °C (23...122 °F) Ambient temperature -5...45 °C (23...113 °F)
CAUTION
Risk of overheating for failure to comply with ambient temperature
Burning and damage to the device
● Ensure sufficient ventilation to comply with the permissible ambient temperature within
the panel or installation box. The temperature must be at least 10 K (18° F) lower
outside the installation box.
Installation
WARNING
Electric shock
Incorrect installation of the device may lead to electric shock injuries when touching the
device!
● Install the device in a lockable cabinet or use terminal covers.
● Do not install the device in locations where children are likely to be present.
● Conductors with a cross-section of 0.5 mm2 (AWG24) or greater shall comply with the
requirements of IEC 60332-1-2 and IEC 60332-1-3 or IEC TS 60695-11-21.
6
Siemens Schweiz AG A6V12505052_en--_b
Smart infrastructure 2022-06-20
Technical data
Power supply
Functional ground (US) The terminal for the functional ground must be
Functional earth connected on the installation side with the building
grounding system (PE).
Screw terminals for wire cross sections up to Max. 2.5 mm2 (14 AWG)
Power consumption
Full load AC 71 VA
Full load DC 66 W
Function data
Hardware information
Storage 2 GB RAM
8 GB eMMC
7
Siemens Schweiz AG A6V12505052_en--_b
Smart infrastructure 2022-06-20
Interfaces
Ethernet interface
Cabling (in-house cabling only), cable type 10 Mbps: Min. CAT3, shielded cable is recommended
100 Mbps: Min. CAT5, shielded cable is recommended
The COM interfaces can be used either for Modbus or for MS/TP, according to type and
configuration.
Baud rate 300, 600, 1200, 2400, 4800, 9600, 19200, 38400,
57600, 76800, 115200 (depending on the configuration)
Cabling (in-house cabling only) 3-wire cable, shielded cable recommended (shield must
Cable length be connected to building earth in the mounting panel)
Max. 1000 m (3300 ft)
8
Siemens Schweiz AG A6V12505052_en--_b
Smart infrastructure 2022-06-20
WLAN interface
Nominal voltage DC 24 V
Switchable in parallel with DC 24 V power supply For details, see: TX-I/O- engineering and installation,
module TXS1.12F4 CM110562
Cu-wire or Cu-strand with wire end sleeve 1 x 0.6 mm ∅ to 2.5 mm2 (22 to 14 AWG)
or 2 x 0.6 mm ∅ to 1.0 mm2 (22 to 18 AWG)
Cu-strand without wire end sleeve 1 x 0.6 mm ∅ to 2.5 mm2 (22 to 14 AWG)
or 2 x 0.6 mm ∅ to 1.5 mm2 (22 to 16 AWG)
9
Siemens Schweiz AG A6V12505052_en--_b
Smart infrastructure 2022-06-20
Conformity
BACnet. B-BC
1)
Environmental compatibility The product environmental declaration 1) contains data
on environmentally compatible product design and
assessments (RoHS compliance, materials
composition, packaging, environmental benefit,
disposal).
1)
Documents can be downloaded at http://siemens.com/bt/download.
10
Siemens Schweiz AG A6V12505052_en--_b
Smart infrastructure 2022-06-20
FCC Statement
This equipment has been tested and found to comply with the limits for a Class B digital
device, pursuant to part 15 of the FCC Rules. These limits are designed to provide
reasonable protection against harmful interference in a residential installation. This
equipment generates, uses and can radiate radio frequency energy and, if not installed and
used in accordance with the instructions, may cause harmful interference to radio
communications. However, there is no guarantee that interference will not occur in a
particular installation. If this equipment does cause harmful interference to radio or television
reception, which can be determined by turning the equipment off and on, the user is
encouraged to try to correct the interference by one or more of the following measures:
● Reorient or relocate the receiving antenna.
● Increase the separation between the equipment and receiver.
● Connect the equipment into an outlet on a circuit different from that to which the receiver
is connected.
● Consult the dealer or an experienced radio/TV technician for help.
This device complies with Part 15 of the FCC rules. Operation is subject to the following two
conditions:
1. This device may not cause harmful interference, and
2. this device must accept any interference received, including interference that may cause
undesired operation
FCC Caution: Changes or modifications not expressly approved by Siemens Switzerland
Ltd. could void user authority to operate the equipment. United States representative
https://new.siemens.com/us/en/products/buildingtechnologies/home.html
Disposal
11
Siemens Schweiz AG A6V12505052_en--_b
Smart infrastructure 2022-06-20
Warranty
Technical data on specific applications are valid only together with Siemens products listed
under "Equipment combinations". Siemens rejects any and all warranties in the event that
third-party products are used.
Connection terminals
3 4 5 6 7 10 11
66 67 68 69 70 71 72 73 74 75 76 77 78 79
7 Functional ground (must be connected on the installation side with the building
grounding system (PE).
12
Siemens Schweiz AG A6V12505052_en--_b
Smart infrastructure 2022-06-20
Dimensions
All dimensions in mm and inches.
PXC7
198 (7.80") 3 (0.12") 74.5 (2.93")
117 (41.61")
124 (4.88")
110 (4.33")
45 (1.77")
67 (2.64")
4.1 (0.16") 26.6 (1.05")
13
Siemens Schweiz AG A6V12505052_en--_b
Smart infrastructure 2022-06-20
Issued by
© Siemens Switzerland Ltd, 2022
Siemens Switzerland Ltd
Technical specifications and availability subject to change without notice.
Smart Infrastructure
Global Headquarters
Theilerstrasse 1a
CH-6300 Zug
+41 58 724 2424
www.siemens.com/buildingtechnologies
Document ID A6V12505052_en--_b
Edition 2022-06-20