Modeling Techniques and Stability Analysis Tools For Grid-Connected Converters
Modeling Techniques and Stability Analysis Tools For Grid-Connected Converters
ABSTRACT Large-scale integration of renewable generation interfaced to the network through power elec-
tronic converters has led to drastic changes in power system dynamics. In islanded microgrids or weak
grids, different control concepts for the synchronization of converters have been proposed to provide virtual
inertia and improve their resilience against transient events, ensuring safe operation without heavy redundant
design. The complexity of these power-related control algorithms and their interaction with the inner control
loops causes problems in frequency components above the range of traditional studies which calls on
modeling techniques with a wider bandwidth. This work aims to provide an outline of modeling methods
for grid-connected converter dynamics from subsynchronous to switching sideband frequency range and
relevant analyzing tools. The major contributions of this work are: 1. Theoretical foundations and the
derivation processes are discussed for each of the modeling methods within the time domain, frequency
domain and harmonic domain. 2. Similarities and differences between these methods are highlighted and
recommendations are given regarding different grid situations. 3. A case study with an active front end
converter is shown and the analysis results are validated by simulation and Hardware-in-the-Loop (HiL) test,
illustrating the effectiveness of these methods.
INDEX TERMS Grid-connected converters, stability analysis, impedance-based analysis, harmonic stability.
This work is licensed under a Creative Commons Attribution 4.0 License. For more information, see https://creativecommons.org/licenses/by/4.0/
450 VOLUME 3, 2022
and the parameters which could trigger resonances [4]. How- Besides DPM, the Harmonic State-Space (HSS) modeling
ever, building the state-space model requires knowledge of the is also an effective method for modeling systems with multi-
structure and parameters of the system. Hence, when model- frequency coupling. The HSS method was first developed
ing a power electronics-based system, a change in the number for the analysis of helicopter blade dynamics [14], and was
of converters or the control loop may lead to a new state-space then utilized for motor drive systems in order to capture the
matrix. This problem is solved by the Component Connection frequency coupling of nonlinear and time-varying compo-
Method (CCM) to some extent [5], yet the exact parameters nents [2]. The DPM and HSS modeling methods are based on
of the whole system are still necessary. The focus of the the same initial hypotheses and they both utilize the method
frequency domain (FD) impedance modeling instead lies in of frequency segmentation to make the system time-invariant.
the extrinsic properties of the converter output port and the However, HSS takes the form of the exponential Fourier se-
power network input port [6]. Such a model can either be built ries while the DPM appears to be trigonometric, and thus
mathematically or measured in the real physical system [7]; leading to different mathematical representations of electrical
hence grey-box systems can be analyzed accordingly. Further, states. More importantly, for small-signal analysis, the HSS
according to [8], the linearized state-space transfer function model was derived directly from the time series Linear Time-
is equivalent to the impedance model when the voltage state Periodic (LTP) state-space equation. In contrast, the DPs are
variable is considered as the input and the current state vari- derived by integrating the system variables over a moving time
able as the output. window [4]. This leads to different properties and a different
However, in renewable power plants and microgrids, con- range of applications.
verters working in parallel could be using different switching Stability analysis also develops with the ever-improving
frequencies, modulation techniques and topologies with bidi- modeling methods. Basically, stability assessment can be
rectional operation [2]. Also, coupling between power-related categorized into signal frequency response-based [6] and
controllers, inner voltage/current loops, and PLLs becomes energy-based [15]. Energy-based methods have gained atten-
much more severer. This tends to bring unexpected harmonics tion in renewable integration to the power grid as they give
at frequencies ranging from hundreds of Hz to kHz due to the insight into the system from the perspective of power flow.
frequency coupling from the multiplication of several time- The whole power system is always stable as long as each
varying signals and bidirectional interaction [9]. In this case, component stays in the passivity region [16]. In contrast, a
the nonlinear time-variant characteristic of converters are so system oscillation mode is obtained from signal-based meth-
obvious and the coupling between DC and AC components ods so that specific harmonics damping techniques are utilized
are so severe that they can no longer be approximated as a to satisfy the grid code requirements. Moreover, with HD
time-invariant system. Modeling approaches such as multi- modeling methods, time- and frequency-domain analysis can
frequency averaging [10] and harmonic linearization [7] could be used in one unified model, and therefore more dedicated
solve this problem to some extent by introducing frequency controllers can be designed accordingly [17], [18]. Besides
shifting. However, the describing function and harmonic bal- these numerical analysis methods, transient stability analysis
ance approaches enforce the single input to a single output with a large signal non-linear model in phase plane provides a
map. Thus, the resultant model is actually part of the linear visualized way to analyze the stability and performance under
time-periodic system. To better analyze the effect of switch- larger disturbance [19]–[21].
ing modulation and resultant frequency coupling, harmonic- In this work, the derivation process and theoretical back-
domain (HD) models of converters need to be built [11]. ground of the above-mentioned modeling are discussed. Then,
The traditional phasor modeling approach was built on the the relevant stability analysis methods are derived. Some rep-
assumption of “Sinusoidal-Steady-State” or “Quasi-Steady- resentative work among recent research works are reviewed
State” whereby the dynamic process is relatively slow com- and a comparison is given on their properties and applicable
pared to the fundamental frequency. Therefore, it cannot scenarios. A case study on an active front end converter with
predict precisely the fast dynamic response of switched power these methods is presented in order to validate their accuracy
electronics-based systems. To address this issue, a method and provide an example of the application scenario. Analy-
based on the generalized averaging method (GAM) called sis results are validated by both PLECS simulation and HiL
the dynamic phasor modeling (DPM) was proposed by S.R. test.
Sanders and used to model a series resonant converter [12].
Dynamic phasor (DP)-based methods are actually a time- II. MODELING METHODS
variant Fourier decomposition with a sliding time window set Traditionally, there are two mainstream modeling routes,
according to the critical fundamental working period. Thus, namely, time-domain modeling and frequency-domain mod-
it has a bandwidth close to twice the fundamental frequency eling. Each methodology has its own strengths and is in-
and could predict the synchronous oscillation precisely with terchangeable due to the same physical theorem and circuit
a significant reduction in calculation time compared to the topology behind it. Recent studies have made the boundary
electromagnetic transient (EMT) simulation, as the complex of time and FD even vaguer with the combination of TD
calculation of the switching process is avoided and the simu- state equations and Fourier decomposition [17]. In this sec-
lation step size can be increased [13]. tion, three modeling methods are discussed regarding their
2) DIFFERENTIAL PROPERTY
The derivative of kth -order phasor can be expressed as:
dXk (t )/dt = dx/dtk (t ) − jkωs Xk (t ). (16)
As the state-based dynamic models can generally be ex-
pressed as dtd x(t ) = f {x(t ), u(t )}, where u(t ) is the time-series
input signal. The DP derivative can be expressed as:
d
xk = −jkωs xk + f (x, u)k , (17)
dt
substituted with the electrical states of the basic circuit com-
ponents, the state equation of which can be derived as shown
in Table 2.
3) PRODUCT PROPERTY
For the two time series waveform x1 (t ) and x2 (t ), the product
of their phasors is:
small-signal impedance modeling methods is summarized as vs qk = vs k−i qi , (19)
shown in Table 1. i
where vs and q denote the voltage waveform of the power
B. DYNAMIC PHASOR MODELING source and PWM switching function, respectively. Therefore,
Different from the transfer function dominant methods men- a link between the source and load component can be estab-
tioned above, the GAM to obtain the DPM is based on the lished accordingly.
property that any TD waveform x(t ) can be represented inside As discussed above, the essence of DPM is to retain the
the interval τ ∈(τ − T, τ ] by the following Fourier series [41]: dominant Fourier coefficients term to describe the major
characteristics of the system. For instance, when analyzing
∞
high-frequency PWM switching circuits, the DC component
x(τ ) = Xk (t )e jkωs τ , (13) should be addressed to capture the low-frequency behavior.
k=−∞ Then the result would be the same as the state-space averaged
model. For resonant converters with some predominantly fun-
with ωs = 2π fs and Xk (t ) being the complex Fourier coeffi- damental frequency, first-order and the dominant harmonic
cients, also named phasors. The dynamic kth -order phasor at DPs should be retained to capture the major sinusoidal re-
time t, Xk (t ), can be expressed as: sponse and the zeroth-order coefficients of those states that
t
exhibit slowly varying behavior [12]. As the DPM is a large
1
Xk (t ) = x(τ )e−jkωs τ dτ = xk (t ). (14) signal model that varies relatively slowly over time, a larger
T t−T simulation step size can be used compared to EMT mod-
els. In [42], the stability criterion for interfacing between
Where xk (t ) denotes the average kth -order phasor over the DPM and EMT is given. However, as the amount of DPs
period T . The major advantages of the DPM over traditional being considered increases, the calculation complexity of the
methods come from the three important properties. model raises significantly, which defeats the purpose of saving
computing resources. The multi-frequency DPM is for small = Ak−m xm e(jkωs +s )t + Bk−m km e(jkωs +s )t
signal analysis when the system is linearized to form a Linear k,m∈Z k,m∈Z
Time-Invariant (LTI) system. Also, it is worth mentioning that (23)
when the initial phase is extracted from the DP model and
expressed in the form of a generalized dq (GDQ) transforma- jkωs + s xk = Ak−m xm + Bk−m um . (24)
tion, a GDQ model is then derived, which puts an emphasis m∈Z m∈Z
on the phase difference so that the power transmission is more
Consequently, the steady state equilibrium can be derived
convenient to calculate accordingly [43]. Combined with the
as:
concept of sequence component, unbalance faults analysis can
be performed [44]. Ẋ = ( [A] − N) X + [B]U , (25)
It follows that the DPM could be used for both large-signal
transient simulation [45]–[49] and steady-state stability as- where:
sessment [50]–[52]. In both cases, it can be coupled with other ⎡ ⎤
.. .. ·
modeling methods by an appropriate interface. The trade-
⎢ . . ·· ⎥
off between model precision and system complexity can be ⎢ A0 −1 A−2
A ⎥
⎢ ⎥ same with
achieved by proper selection of the phasor sequence. [A] = ⎢
⎢ · · · A 1 A0 A−1 ···⎥ ⎥ , [B] (26)
⎢ A 2 A1 A0
⎥
⎣ ⎦
· .. ..
··
C. HARMONIC STATE-SPACE
. .
Similar to the DPM, the HSS is based on the principle that TD
variables can be transferred to the FD by utilizing (13). Thus, T same with
X = · · · x−1 x0 x1 · · · , (27)
when a small signal disturbance est appears, the state matrix U
of the system becomes [53]:
N = diag · · · , −j2ωs , −jωs , 0, jωs , j2ωs , · · · . (28)
x(t ) = est xk ejkωs t , (20) where [·] denotes the Toeplitz matrix or diagonal-constant
k∈Z matrix which is used for convolution calculation. According
the differentiation of (20) could be expressed as: to (C), the HSS method provides a unified way to construct
a multi-frequency model which is linearized around operating
trajectories in the harmonic basis of the period Ts .
ẋ(t ) = jkωs + s xk e(jkωs +s )t , (21)
In fact, harmonic linearization can be regarded as a combi-
k∈Z
nation of FD stabilization and perturbation linearization [25].
for an arbitrary LTP model: Thus, power electronic converters of any topology, which
can be expressed by a state-space model, can be easily
ẋ(t ) = A(t )x(t ) + B(t )u(t ) transferred to an HSS model: single-phase converters [54],
(22)
y(t ) = C(t )x(t ) + D(t )u(t ) transformers [55], three-phase converters under both balanced
and unbalanced situation [43], [56] and especially modu-
the HSS variable update equation can be derived as (23). lar multilevel converters that have the nature of nonlinear
The coefficients of same frequency on each side of the inter-resonance between sub-modules [40], [57]. Similar to
equation should be equal, so the exponents can be eliminated, the DPM, the selection of harmonics under consideration
then the kth-order HSS equation is obtained: has been a critical concern for HSS regarding computational
burden. The specific simulation time comparison of different
jkωs + s xk e(jkωs +s )t = Ak ejkωs t · xm e(jmωs +s )t orders of harmonics of a single-phase transformer has been
k∈Z k∈Z m∈Z made in [58], indicating that the computation duration of
the model increases quadratically with the harmonic order.
+ Bk ejkωs t · um e(jmωs +s )t
An effective solution to this problem is to select the critical
k∈Z m∈Z
harmonics according to the impedance/admittance map [59].
= Ak xm ej(k+m)ωs t+st + Bk um ej(k+m)ωs t+st By considering only the harmonic components with steady-
k,m∈Z k,m∈Z state impedance larger than a certain threshold or significantly
exact passive component or control loop of it that affects the B. STATE-SPACE EIGENVALUE ANALYSIS
stability of the whole system in a perturbation and observation The eigenvalue analysis has been a widely used method for
(P&O) manner. Further, the PF analysis is extended from accessing the stability and oscillation mode of the traditional
the oscillation frequency points to critical frequency ranges power systems. The state matrix A of a small-signal linearized
where the eignloci are close to or tend to encircle (−1, j0) LTI model can be extracted to form the characteristic equa-
[74]. Active damping techniques can be adapted accordingly tion:
to enlarge the PM and GM of the critical converters within
critical frequency ranges. det(sI − A) = 0, (30)
The norm-based stability criterion has been proposed to
simplify analyses and indicate the stability margin levels [75]– the resultant eigenvalues could be an indication of the dy-
[77]. Nevertheless, the resultant stability criteria are actually namic modes of the power system. And the participation rate
sufficient and unnecessary conditions because the system can calculated by the corresponding left and right eigenvectors
be stable even if its stability requirements are not met. To can also reveal the impact of the grid-connected converters on
further reduce the conservatism, the relevant stability margin the instability [4]. However, the PFs of the state-space model
was regulated according to Gerschgorin’s Theorem when the are all scalars instead of transfer functions with frequency-
infinity-norm is used [77]. domain impedance ratio matrices. Thus, they can only predict
the PFs of each node under oscillation modes instead of
2) PASSIVITY-BASED CRITERIA port dynamic over a frequency range [74]. That is, the PF
Passivity is mathematically defined when a one port network analysis with state-space models offers limited guidance in
system only absorbs energy from the outside physical world, controller design to optimize the oscillation damping. This
namely: problem is solved by nonlinear modular state-space modeling
+∞ +∞ of power-electronics systems [61], in which the VSCs models
1 are based on reduced-order impedance model and nonlinear
v(t )i(t )dt = V jω I ∗ (jω)dω
−∞ 2π −∞ PLL dynamic is considered. By tuning different parameters,
the nonlinear model can be linearized at different equilibrium
1 +∞
= Re Z (jω) I (jω) 2 jω ≥ 0. points with the resultant Jacobian matrix. The eigenvalues
π 0 distribution trend gives information on the system damping
(29) ability of different oscillation modes in response to the pa-
The stability of a passive system is inherently guaranteed be- rameter change.
cause the energy dissipation process always drives the system With the increase of control complexity and power elec-
back to its equilibrium point [78]. Consequently, the passivity tronic converter penetration rate, the order of the system
criterion of the one port system can be defined as [79]: becomes larger. Thus, the difficulty of building and deriving
r Z (s) does not have right half plane (RHP) poles and the the system model increases significantly. This problem was
entire Nyquist curve is within the RHP solved by the CCM, which defines each critical part as a sub-
r Z (s) has a non-negative real part for every ω system and connects them according to their linear algebraic
Compared with impedance-ratio-based methods, passivity- relation. Its modular structure also improves the extensibility
based methods are more suitable for multi-converter systems. of the model [5].
When the impedance of the converters within the system all
satisfy the passivity margin criterion, their summation will C. FLOQUET-THEORY-BASED METHOD
also be in between the passivity region with an even larger The Floquet theory illustrates the relationship between LTP
passivity margin. For example, as depicted in Fig. 5, a pas- and LTI systems [81]. By introducing the time-periodic ma-
sivity margin angle of α is required for the system to make trix P(t, t0 ), any LTP system can be transformed into an LTI
−1 −1
sure possible resonance is well damped. Zinv1 and Zinv2 are the model. According to [82], the solution of an LTP system (22)
⎡ ⎤
Where d denotes small variation of signals. This principle Dc1 Dc2 − 23 k pc I m 1
3 k pc I m
1
3 k pc I m
also applies for HSS models. Thus, the linearized ⎢ ⎥
Dc = ⎣ Dc3 Dc4 1
3 k pc I m − 23 k pc I m 1
3 k pc I m ⎦
(42)
close-loop HSS model can be built by considering the
small-signal instant of the topology electrical states and Dc5 Dc6 1
3 k pc I m
1
3 k pc I m − 23 k pc I m
the controller. Set the topology state variables as X p =
T Where:
dI ga dI gb dI gc dV Ca dV Cb dV Cc dI ca dI cb dI cc dV dc , inputs Bc1 = − 23 cos θ C = k pc cos(θ − 23 π )
T c1
U p = dV pcca dV pccb dV pccc dSa dSb dSc . Moreover, the Bc2 = − 3 cos(θ − 3 π ) C c2
2 2
= kic cos(θ − 23 π )
T
controller state variables are set as X c = dX 1 d dX 2 d dX q , Bc3 = − 23 cos(θ + 23 π ) C c3 = −kic sin(θ − 23 π )
T
inputs U c = dV ∗dc dV dc dI ca dI cb dI cc and outputs
Bc4 = 23 sin θ C c4 = k pc cos(θ + 23 π )
Y c = [dSa dSb dSc ]T , where d denotes the small-signal 2
disturbance and the physical meaning of the variables Bc5 = 3 sin(θ − 3 π )2
C c5 = kic cos(θ + 23 π )
2
are shown in Fig. 9. Assuming that the PLL can track Bc6 = 3 sin(θ + 3 π )2
C c6 = −kic sin(θ + 23 π )
the grid frequency perfectly, ideal Park and Inverse Park Dc1 = k pv k pc [cos θ ]
transformation are used in the controller model to link the
static and synchronized reference frames. Consequently, the Dc2 = −k pv k pc [cos(θ )]
HSS model of the converter topology and the controller can Dc3 = k pv k pc cos(θ − 23 π )
be derived as: (37) shown at the bottom of this page.
Dc4 = −k pv k pc cos(θ − 23 π )
⎡ ⎤ Dc5 = k pv k pc cos(θ + 23 π )
1
L2 I m ZmZm Zm Zm Zm
Dc6 = −k pv k pc cos(θ + 23 π ) .
⎢ Zm 1
Zm ⎥
⎢ L2 I m
Zm Zm Zm ⎥ I m and Zm denote the m = (2n + 1)-order identity matrix
⎢ Z 1 ⎥
⎢ m Zm I m Z m Z m Z m ⎥ and zero matrix as the Toeplitz matrix of these two kinds
⎢ L2
⎥
⎢ Zm ZmZm Zm Zm Zm ⎥ are themselves. n denotes the number of harmonics being
⎢ ⎥
⎢ Zm ZmZm Zm Zm Zm ⎥ considered in the model.
Bp = ⎢⎢ Zm ZmZm Zm Zm Zm ⎥
⎥ (38) For symmetrical Sinusoidal PWM modulation (SPWM),
⎢ −[V ⎥
⎢ Zm ZmZm dc0 ]
Zm Zm ⎥ the Fourier decomposition of the switching signal in upper
⎢ L1 ⎥
⎢ Z Zm −[V dc0 ]
Zm ⎥ arm of phase A can be expressed as [94]: (43) shown at the
⎢ m ZmZm ⎥
⎢ L1
⎥ bottom of the next page. Where Mr is the modulation rate, ωsw
⎣ Zm ZmZm Zm Zm −[V L1
dc0 ]
⎦
and ω0 are the switching and fundamental angular frequency,
Zm ZmZm [ICcao] [IC cbo] [I cco ]
Cdc m and n denote the order of the carrier wave and the adja-
dc dc
⎡ ⎤ cent harmonic wave, respectively. The expression besselj(·)
−N Zm Zm
denotes the Bessel function of the first kind, which is:
Ac = ⎣ kiv I m −N Zm ⎦ (39)
(−1)k x (2k+n)
Zm Zm −N ∞
⎡ ⎤ besselj(n, x) = . (44)
Im −Im Zm Zm Zm k!(k + n)! 2
k=0
Bc = ⎣ k pv I m −k pv I m Bc1 Bc2 Bc3 ⎦ (40)
Zm Zm Bc4 Bc5 Bc6 Other signals can be derived by changing the initial phases of
⎡ ⎤ the mathematical expression. The resultant time-series wave-
k pc [cos θ] kic [cos θ ] −kic 23 sin θ form is shown in Fig. 16, the modulation rate is 15 and the
Cc = ⎣ C c1 C c2 C c3 ⎦ (41) harmonics calculated is 255th . The switching function pro-
C c4 C c5 C c6 vides a link between DC and AC components and reproduces
Ap =
⎡ −R2 −1 ⎤
L2 Im − N Zm Zm L2 I m Zm Zm Zm Zm Zm Zm
⎢ −R2 −1 ⎥
⎢ Zm L2 I m − N Zm Z m L2 I m Zm Zm Zm Zm Zm ⎥
⎢ −R2 −1 ⎥
⎢
⎢
Zm Zm L2 I m − N Zm Zm L2 I m Zm Zm Zm Zm ⎥
⎥
⎢ 1
−N Zm −1 ⎥
⎢ C Im Zm Zm Zm C Im Zm Zm Zm ⎥
⎢ Zm 1
Zm −N −1 ⎥
⎢ C Im Zm Zm Zm C Im Zm Zm ⎥
⎢ Zm Zm 1
−N −1 ⎥ (37)
⎢ C Im Zm Zm Zm Zm C Im Zm ⎥
⎢ −R1
− [S a0 ] ⎥
L1 I m − N
1
⎢ Zm Zm Zm L1 I m Z m Zm Zm Zm L1 ⎥
⎢ S ⎥
⎢ Zm Zm Zm Zm 1 −R1
−N − [L1b0 ] ⎥
⎢ L1 I m Zm Zm L1 I m Zm ⎥
⎢ ⎥
⎣ Zm Zm Zm Zm Zm 1
L1 I m Zm Zm −R1
L1 m − N
I − [S L1
c0 ]
⎦
[Sa0 ] [Sb0 ] [Sc0 ] −1
Zm Zm Zm Zm Zm Zm Cdc Cdc Cdc RLoad Cdc I m − N
462 VOLUME 3, 2022
based on the relation in Fig. 17, the close-loop HSS state
iteration can be derived as:
.
dX p = A p dX p + B p1 dU p1 + B p2 dY c
= A p dX p + B p1 dU p1
+ B p2 C c dX c + Dc1 dU c1 + Dc2 dX p1
= A p dX p + B p2 Dc2 dX p1 + B p2C c dX c
FIGURE 16. Fourier Decomposition of PWM switching signal. + B p1 dU p1 + B p2 Dc1 dU c1 , (45)
dẊ c = Ac dX c + Bc1 dU c1 + Bc2 dU c2
= Ac dX c + Bc1 dU c1 + Bc2 dX p1 . (46)
the harmonics introduces by the switching behavior. Thus, the Further, to obtain the I/O relation between different electri-
more harmonics being calculated, the more it appears like a cal states, set the combined states as dXa , voltage disturbance
square wave. at the point of common connection (PCC) and DC-link volt-
Fig. 17 shows the schematic diagram of the combined age reference as input dUa , the state variables of the topology
topology and controller model. As illustrated by the dashed as the outputs dYa , and the resultant state matrices as Aa , Ba ,
blue arrow, the state variable of the topology model is the C a and Da . The HTF can be established as [95]:
input of the control model, and the outputs of the control
model act as inputs of the topology model. This coupling rela- Ha (s) = C(sI − Aa )−1 Ba + Da . (48)
tionship between the two systems requires further regulation
of the state matrix to form the compacted linearized system, By setting s as zero and considering up to the 35th order
but the deviation process is not shown in [93]. One way to harmonic components, a steady-state linear mapping between
combine the two parts and eliminate the duplicate states is the Fourier coefficients of the converter electrical states and
shown below. voltage disturbance can be built as shown in Fig. C. The
In order to derive the compacted model, first consider the figure can be interpreted as HD coupling admittance since
variation of the DC-link voltage reference signal as controller the converter input current is seen as the output of the HTF.
input set U c1 , the DC-link voltage and converter output cur- It can be seen that voltage disturbance at a fundamental fre-
rent disturbance as controller input set U c2 , the disturbance in quency can trigger a current disturbance at both fundamental
the PCC voltage as topology input set U p1 and the switch- frequency and around the switching frequency and vice versa.
ing signal as topology input set U p2 and grid side current Besides, the resonant zone can also be predicted as encircled
disturbance. Separate the input matrix of the two systems in red, which is consistent with the major components of the
accordingly and merge the state matrices of the two systems THD shown in Fig. 14(b).
1 ma
sa (t ) = + sin (ω0t + θ0 )
2 2
⎡
2⎣
+∞
∞
besselj n, mM2r π mπ
+ sin cos (mωswt + nω0t )
π π 2
m=1,3··· n=0,±2···
⎤
+∞
∞
besselj n, mM2r π mπ
+ cos sin (mωswt + nω0t )⎦ . (43)
π 2
m=2,4··· n=±1,±3...
VI. CONCLUSION
FIGURE 19. HiL test setup. In this paper, three mainstream modeling methods and rel-
evant analysis tools are discussed for the study of grid-
connected converters in the following aspects: derivation pro-
D. HARDWARE-IN-THE-LOOP VALIDATION cess, key feature, and application scenarios. The small-signal
In order to validate previous analysis, HiL tests with the aid impedance model deals with low-frequency and synchronize
of PLECS RT-Box have been done. The setup of HiL test stability issues. The TD nonlinear large-signal model can
is shown in Fig. 19. The system parameters are the same as also be used to aid the controller design with the visualized
shown in Table 4. phase plane portrait. Besides, HD modeling methods could
Similar to the simulation, an 8 Hz frequency drop is added extend the range of interest to the switching frequency and the
to the PLL reference frequency is triggered at 0.45 s. The wide-band controller dynamic. More specifically, the DPM
resultant converter output voltage and Fast Fourier transform could be used for both large-signal TD simulation and stability
results are shown in Fig. 20 and the PLL error signal is analysis with the system order properly selected, while HSS is
shown in Fig. 21. The medium frequency at around 700 Hz more suitable for steady-state harmonic stability assessment
can be observed in Fig. 20(b), which agrees with the result due to its LTP nature and complex-valued state matrices. A
of the GNC analysis. The PLL frequency error signal con- case study with a three-phase VSC further validates these
forms to the phase plane trajectory, the dynamic is better methods and gives a paradigm on how they are utilized with
damped than simulation which is caused by sampling delay in PWM converters. This critical evaluation of the modeling and
real-time system. Also, the magnitudes harmonic components analysis tools gives the engineers theoretical guidance for the
are consistent with the major components shown in the HSS design and evaluation of power electronics-dominated power
admittance map. systems.
[44] Q. Zhong, Q. Shi, G. Wang, and H. Li, “Short circuit analysis of PV [64] J. Lyu, X. Zhang, J. Huang, J. Zhang, and X. Cai, “Comparison of
inverter under unbalanced conditions with dynamic phasor sequence harmonic linearization and harmonic state space methods for impedance
components,” in Proc. IEEE Power Energy Soc. Gen. Meeting, 2016, modeling of modular multilevel converter,” in Proc. Int. Power Electron.
pp. 1–5. Conf., 2018, pp. 1004–1009.
[45] A. Nazari, Y. Xue, J. K. Motwani, I. Cvetkovic, D. Dong, and D. [65] C. Wildrick, F. Lee, B. Cho, and B. Choi, “A method of defining the load
Boroyevich, “Dynamic phasor modeling of multi-converter systems,” impedance specification for a stable distributed power system,” IEEE
in Proc. IEEE Energy Convers. Congr. Expo., 2021, pp. 2716–2721. Trans. Power Electron., vol. 10, no. 3, pp. 280–285, May 1995.
[46] Z. Shuai, Y. Peng, J. M. Guerrero, Y. Li, and Z. J. Shen, “Transient [66] X. Feng, J. Liu, and F. Lee, “Impedance specifications for stable DC
response analysis of inverter-based microgrids under unbalanced con- distributed power systems,” IEEE Trans. Power Electron., vol. 17, no. 2,
ditions using a dynamic phasor model,” IEEE Trans. Ind. Electron., pp. 157–162, Mar. 2002.
vol. 66, no. 4, pp. 2868–2879, Apr. 2019. [67] S. Sudhoff, S. Glover, P. Lamm, D. Schmucker, and D. Delisle, “Admit-
[47] D. Shu, X. Xie, V. Dinavahi, C. Zhang, X. Ye, and Q. Jiang, “Dynamic tance space stability analysis of power electronic systems,” IEEE Trans.
phasor based interface model for EMT and transient stability hybrid Aerosp. Electron. Syst., vol. 36, no. 3, pp. 965–973, Jul. 2000.
simulations,” IEEE Trans. Power Syst., vol. 33, no. 4, pp. 3930–3939, [68] J. Liu, X. Feng, F. Lee, and D. Borojevich, “Stability margin monitoring
Jul. 2018. for DC distributed power systems via perturbation approaches,” IEEE
[48] H. Wang, K. Jiang, M. Shahidehpour, and B. He, “Reduced-order Trans. Power Electron., vol. 18, no. 6, pp. 1254–1261, Nov. 2003.
state space model for dynamic phasors in active distribution net- [69] L. Fan and Z. Miao, “Admittance-based stability analysis: Bode plots,
works,” IEEE Trans. Smart Grid, vol. 11, no. 3, pp. 1928–1941, nyquist diagrams or eigenvalue analysis?,” IEEE Trans. Power Syst.,
May 2020. vol. 35, no. 4, pp. 3312–3315, Jul. 2020.
[49] D. Shu, Y. Wei, V. Dinavahi, K. Wang, Z. Yan, and X. Li, “Cosimu- [70] Y. Liao and X. Wang, “Impedance-based stability analysis for inter-
lation of shifted-frequency/dynamic phasor and electromagnetic tran- connected converter systems with open-loop RHP poles,” IEEE Trans.
sient models of hybrid LCC-MMC DC grids on integrated CPU– Power Electron., vol. 35, no. 4, pp. 4388–4397, Apr. 2020.
GPUs,” IEEE Trans. Ind. Electron., vol. 67, no. 8, pp. 6517–6530, [71] D. Lumbreras, E. L. Barrios, A. Urtasun, A. Ursúa, L. Marroyo, and
Aug. 2020. P. Sanchis, “On the stability of advanced power electronic converters:
[50] D. Venkatramanan and V. John, “Dynamic phasor modeling and sta- The generalized bode criterion,” IEEE Trans. Power Electron., vol. 34,
bility analysis of SRF-PLL-based grid-tie inverter under islanded no. 9, pp. 9247–9262, Sep. 2019.
conditions,” IEEE Trans. Ind. Appl., vol. 56, no. 2, pp. 1953–1965, [72] Y. Li et al., “Stability analysis and location optimization method for
Mar./Apr. 2020. multiconverter power systems based on nodal admittance matrix,” IEEE
[51] J. Vega-Herrera, C. Rahmann, F. Valencia, and K. Strunz, “Analysis Trans. Emerg. Sel. Topics Power Electron., vol. 9, no. 1, pp. 529–538,
and application of quasi-static and dynamic phasor calculus for stability Feb. 2021.
assessment of integrated power electric and electronic systems,” IEEE [73] Y. Zhu, Y. Gu, Y. Li, and T. C. Green, “Participation analysis in
Trans. Power Syst., vol. 36, no. 3, pp. 1750–1760, May 2021. impedance models: The grey-box approach for power system stability,”
[52] R. Dimitrovski and M. Luther, “Generalized dynamic phasor model of IEEE Trans. Power Syst., vol. 37, no. 1, pp. 343–353, Jan. 2022.
an MMC using novel mathematical framework,” in 2020 IEEE Power [74] Y. Liao, X. Wang, and X. Wang, “Frequency-domain participation
Energy Soc. Gen. Meeting (PESGM), 2020, pp. 1–5. analysis for electronic power systems,” IEEE Trans. Power Electron.,
[53] S. Almer and U. Jönsson, “Harmonic analysis of pulse-width modulated vol. 37, no. 3, pp. 2531–2537, Mar. 2022.
systems,” Automatica, vol. 45, no. 4, pp. 851–862, Apr. 2009. [75] S. Chandrasekaran, D. Borojevic, and D. Lindner, “Input filter interac-
[54] J. B. Kwon, X. Wang, F. Blaabjerg, C. L. Bak, A. R. Wood, and tion in three phase AC-DC converters,” in Proc. 30th Annu. IEEE Power
N. R. Watson, “Harmonic instability analysis of a single-phase grid- Electron. Specialists Conf. Rec., 1999, pp. 987–992.
connected converter using a harmonic state-space modeling method,” [76] Z. Liu, J. Liu, W. Bao, and Y. Zhao, “Infinity-norm of impedance-based
IEEE Trans. Ind. Appl., vol. 52, no. 5, pp. 4188–4200, Sep. 2016. stability criterion for three-phase AC distributed power systems with
[55] K. Gao, R. Xie, and G. Zhang, “Harmonic analysis of nonlinear periodic constant power loads,” IEEE Trans. Power Electron., vol. 30, no. 6,
network using the dynamic harmonic domain,” in Proc. 7th Int. Forum pp. 3030–3043, Jun. 2015.
Elect. Eng. Automat., 2020, pp. 616–622. [77] R. Rosso, M. Andresen, S. Engelken, and M. Liserre, “Analysis of
[56] D. Sun, X. Lu, and L. Du, “Optimal design of grid interactive inverters the interaction among power converters through their synchronization
based on harmonic state space modeling,” in Proc. IEEE Energy Con- mechanism,” IEEE Trans. Power Electron., vol. 34, no. 12, pp. 12321–
vers. Congr. Expo., 2020, pp. 5040–5045. 12332, Dec. 2019.
[57] J. Lyu, X. Zhang, X. Cai, and M. Molinas, “Harmonic state-space based [78] R. Ortega, A. Loría, P. J. Nicklasson, and H. Sira-Ramirez, Passivity-
small-signal impedance modeling of a modular multilevel converter Based Control of Euler-Lagrange Systems. Berlin, Germany: Springer,
with consideration of internal harmonic dynamics,” IEEE Trans. Power 1998.
Electron., vol. 34, no. 3, pp. 2134–2148, Mar. 2019. [79] X. Wang, F. Blaabjerg, and P. C. Loh, “Passivity-based stability analysis
[58] K. Gao, R. Xie, and G. Zhang, “Harmonic analysis of nonlinear periodic and damping injection for multiparalleled VSCs with LCL filters,” IEEE
network using the dynamic harmonic domain,” in Proc. 7th Int. Forum Trans. Power Electron., vol. 32, no. 11, pp. 8922–8935, Nov. 2017.
Elect. Eng. Automat., 2020, pp. 616–622. [80] Y.-C. Jeung, D.-C. Lee, T. Dragicevic, and F. Blaabjerg, “Design of
[59] J. Kwon, X. Wang, C. L. Bak, and F. Blaabjerg, “The modeling and har- passivity-based damping controller for suppressing power oscillations
monic coupling analysis of multiple-parallel connected inverter using in DC microgrids,” IEEE Trans. Power Electron., vol. 36, no. 4,
harmonic state space (HSS),” in Proc. IEEE Energy Convers. Congr. pp. 4016–4028, Apr. 2021.
Expo., 2015, pp. 6231–6238. [81] A. M. Lyapunov, “The general problem of the stability of motion,” Int.
[60] R. Mittal, L. Fan, and Z. Miao, “Harmonic state-space model of second- J. Control, vol. 55, no. 3, pp. 531–534, 1992. [Online]. Available: https:
order generalized integrator phase-locked loop,” in Proc. IEEE Power //doi.org/10.1080/00207179208934253
Energy Soc. Gen. Meeting, 2021, pp. 1–5. [82] H. D’Angelo, Linear Time-Varying Systems: Analysis and Synthesis,
[61] F. Cecati, R. Zhu, M. Liserre, and X. Wang, “Nonlinear mod- Ser. Allyn and Bacon Series in Electrical Engineering. Boston, MA,
ular state-space modeling of power-electronics-based power sys- USA: Allyn and Bacon, 1970.
tems,” IEEE Trans. Power Electron., vol. 37, no. 5, pp. 6102–6115, [83] P. Montagnier, R. J. Spiteri, and J. Angeles, “The control of linear
May 2022. time-periodic systems using Floquet–Lyapunov theory,” Int. J. Control,
[62] P. D. Rua, Özgür Can Sakinci, and J. Beerten, “Comparative study of vol. 77, no. 5, pp. 472–490, 2004.
dynamic phasor and harmonic state-space modeling for small-signal [84] N. R. Chaudhuri, R. Oliveira, and A. Yazdani, “Stability analysis
stability analysis,” Electric Power Syst. Res., vol. 189, Dec. 2020, of vector-controlled modular multilevel converters in linear time-
Art. no. 106626. periodic framework,” IEEE Trans. Power Electron., vol. 31, no. 7,
[63] E. Karami, G. B. Gharehpetian, and M. Madrigal, “A step forward pp. 5255–5269, Jul. 2016.
in application of dynamic harmonic domain: Phase shifting property [85] Y. Han et al., “Floquet-theory-based small-signal stability analysis of
of harmonics,” IEEE Trans. Power Del., vol. 32, no. 1, pp. 219–225, single-phase asymmetric multilevel inverters with SRF voltage control,”
Feb. 2017. IEEE Trans. Power Electron., vol. 35, no. 3, pp. 3221–3241, Mar. 2020.