0% found this document useful (0 votes)
79 views4 pages

Mos Spuf 450 Polycell

Generally the sequence of work described below should be carried out by a insulation specialist approved by the Superintendent Officer. All works carried out should be strictly in accordance with the manufacturer’s specification. This ensures that works are completed satisfactorily, thus, the long term performance of the material is assured.

Uploaded by

Hurin Aufa
Copyright
© Public Domain
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
79 views4 pages

Mos Spuf 450 Polycell

Generally the sequence of work described below should be carried out by a insulation specialist approved by the Superintendent Officer. All works carried out should be strictly in accordance with the manufacturer’s specification. This ensures that works are completed satisfactorily, thus, the long term performance of the material is assured.

Uploaded by

Hurin Aufa
Copyright
© Public Domain
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

Method Statement

SPUF 450
SPRAY- ON POLYURETHANE FOAM
TWO-COMPONENT CLOSED CELL POLYURETHANE RIGID
SPRAY-ON FOAM

General

Generally the sequence of work described below should be carried out by a insulation specialist
approved by the Superintendent Officer. All works carried out should be strictly in accordance
with the manufacturer’s specification. This ensures that works are completed satisfactorily, thus,
the long term performance of the material is assured.

Areas of Application
SPUF 450 is used to insulate areas as indicated below:-

 R.C. Flat Roof  Metal Deck


 Inverted Roof  Wood Wall
 Build Up Roof-Retrofit  Gypsum Board

Application Method

Surface Preparation

A. Built-up Roof (Retrofit)

1. All loose gravel, dust and residue shall be removed using power vacuum equipment, power
sweeper, air blowing, or other suitable means.
2. The roof shall be thoroughly inspected or tested to determine if moisture is present within
the roof assembly. Saturated insulation must be removed and replaced with compatible
materials.
3. The existing roof shall be thoroughly inspected for adhesion between felts, insulation, and
deck. Areas of poor adhesion should be fastened. Blisters, buckles, wrinkles and fish
mouths shall be cut out and/or fastened.
4. All soft mastic or other materials that impede polyurethane adhesion shall be removed.
5. Remove or refasten all loose base flashing, counter flashing and gravel stops as required.
6. The need may exist for structural design analysis to determine expansion joint requirements.
Existing expansion joints should be inspected and repaired if necessary.
7. Lightning rods shall be masked prior to foaming. Lightning rod cables shall not be embedded
in the polyurethane foam and should be removed prior to foaming. Electrical and mechanical
conduits should be relocated or raised above the finished roof surface.

Page 1 of 4
Method Statement

B. Metal Deck

1. The metal roof deck shall be constructed of a minimum 22-gauge steel. Construction shall
conform to local building codes.
2. Ferrous Metal: Sandblast iron and steel surfaces which are not primed, shop painted, or
otherwise protected in accordance with SSPC SP-6, Commercial Blast Cleaning. Remove
loose rust and unsound primer from shop-primed iron and steel surfaces by scraping or wire
brushing.
3. Non-Ferrous Metal: Clean galvanized metal, aluminum, and stainless steel surfaces as
recommended by the manufacturer issuing the warranty.
4. If the metal surface is free of loose scale, rust, weathered or chalking paint, it can be
cleaned using compressed air jet, vacuum equipment, and hand or power broom to remove
loose dirt. Grease, oil or other contaminants shad be removed with proper cleaning
solutions.
5. Fluted metal decks require a suitable method of covering or filling the flutes prior to
polyurethane foam application. Flutes may be covered with mechanically fastened board
stock, open weave mesh fabric, or filled with precut board stock or spray applied
polyurethane foam.

C. Concrete

1. Remove loose dirt, dust and debris by using compressed air, vacuum equipment or
brooming. Oil, grease, form release agents or other contaminants shall be removed with
proper cleaning solutions.
2. All joint openings in concrete decks that exceed 6mm (1/4 Inch) shall be grouted or caulked
prior to application of polyurethane foam.
3. Priming is required on concrete surfaces, and it is recommended that poured concrete decks
be permitted to cure for twenty-eight (28) days prior to the application of primer or sprayed
Polyurethane foam.
4. Sprayed polyurethane foam is not recommended for lightweight or insulating concretes
unless tests have been made to determine that adequate adhesion can be obtained or unless
an overpayment is installed.

D. Wood

1. Plywood shall be exterior grade not less than 12mm (1/2 inch) thick, nailed firmly in place.
Attachment must meet building code requirements for resistance to wind uplift.
2. Plywood shall contain no more than 18% water, as measured in accordance with ASTM D
4444-84, or ASTM D 4442-84.
3. All untreated and unpainted surfaces shall be primed with an exterior grade primer. Priming
is required to minimize moisture absorption and eliminate potential polyurethane foam
adhesion problems.
4. Plywood joints in excess of 6mm (1/4 Inch) shall be taped or filled with a suitable sealant
material.
5. Deck shall be free of loose dirt, grease, oil or other contaminants prior to priming or foam
application.
6. Remove loose dirt or debris by use of compressed air, vacuum or brooming. No washing
shall be permitted.
7. Tongue & Groove, Sheathing, Planking: Due to the frequency of joints, possibility of variable
openings and effects of aging and shrinking, these surfaces must be overlaid with minimum
6mm (1/4 Inch) thick exterior grade plywood or suitable covering.

Page 2 of 4
Method Statement

E. Other Surfaces (i.e. Gypsum Board, Isocyanurate Board)

1. These materials are generally used over fluted metal decks and must be fastened to achieve
necessary wind uplift requirements.
2. Boards shall be firmly butted together along all edges without gaps or openings. Joints
exceeding 1/4 inch shall be caulked with a suitable sealant material.
3. Special care must be taken to prevent these materials from getting wet in storage on the job
site and after installation prior to being protected by polyurethane foam. Moisture exposure
will damage these materials and may be a cause for replacement.
4. Remove loose dirt and debris by using compressed air, vacuum or light brooming. No power
brooming is permitted due to possibility of damage.
5. The installed materials shall be protected from spills of contaminants such as oil, grease,
solvents, etc., as these materials cause soiling that cannot be readily removed from the
board surfaces.

POLYURETHANE FOAM APPLICATION

A. Inspection

1. Prior to application of the foam, the surface shall be inspected to insure that conditions
required as above have been met.
2. Substrate shall have sufficient slope to eliminate excessive ponding water. Ponding is defined
as “an area of 10m² (100 sq.ft) or more which holds in excess of 12mm (1/2”) of water as
measured 24 hours after a rainfall.” If the substrate does not have sufficient slope, then the
ponding water must be eliminated by building in slope by the application of polyurethane
foam, channeling the polyurethane foam or by the proper placement of drains, or a
combination thereof.
3. The polyurethane foam application shall not proceed during periods of inclement weather.
The applicator shall not apply the polyurethane foam below the temperature and/or humidity
specified by the manufacturer for ambient air and substrate. Wind barriers may be used if
wind conditions could affect the quality of installation.

B. Application

1. The spray polyurethane foam shall be applied in accordance with the manufacture’s
specification and instructions.
2. Areas to be built-up to remove ponding water are to be filled in with spray polyurethane foam
before the specified thickness of polyurethane foam is applied to the entire roof surface.
3. The spray polyurethane foam must be applied in a minimal pass thickness of 1/2 inch.
4. Spray polyurethane foam thickness shall be a minimum of one inch (or more if specified). The
polyurethane foam shall be applied uniformly over the entire surface with a tolerance of plus
1/4” per inch of thickness minus 0”, except where variations are required to insure proper
drainage or to complete a feathered edge.
5. The spray polyurethane foam shall be uniformly terminated a minimum of 100mm(4 inches)
above the roofline at all penetrations (except drains, parapet walls, or building junctions).
Foamed in place cants shall be smooth and uniform to allow positive drainage.
6. Detailing skylights is particularly important in that the spray polyurethane foam MUST be
terminated below existing weep holes. DO NOT COVER WEEP HOLES WITH FOAM OR
COATING.

Page 3 of 4
Method Statement

Curing

The polyurethane foam surface shall be allowed to cure sufficiently. The full thickness of
polyurethane foam in any area shall be completed prior to the end of each day. If due to
weather conditions more than 24 hours elapse between polyurethane foam and coating
application, the polyurethane foam shall be inspected for UV degradation, oxidation or
contamination. If any of the above conditions exist, the surface shall be prepared in
conformity with the recommendations of the manufacturer issuing the warranty.

Protection

1. Protect the freshly applied waterproof membrane from rain, dirt, grease or other loose
materials during its drying time.
2. The Contractor should also take precautions to protect the SPUF 450 from any
mechanical damage during the construction of other trade of works.

Note : Information of this method of statement is to the best of our knowledge. However, we have no control over the method of
application and the amount of care taken when using this product and therefore, the liability of POLYCELL Sdn Bhd is
limited to the quality of the delivered material.

Polycell Sdn Bhd


No.14 Jalan PJS 1/30,Taman Petaling Utama, 46000 Petaling Jaya, Selangor
Tel : +603-7783 4368, +603-7496 2788 Fax : + 603- 7783 4369
Web site : http://www.polycell.com.my/ email : [email protected], [email protected]

Page 4 of 4

You might also like