Liebert® APS™ MBC: Rack-Mount Maintenance Bypass Cabinet
Liebert® APS™ MBC: Rack-Mount Maintenance Bypass Cabinet
The Liebert APS MBC (maintenance bypass cabinet) is designed for commercial/industrial use only. It is
not intended for use with life-support or other designated critical devices. Maximum load must not exceed
that shown on the rating label. Install and operate the unit only in a clean indoor environment, free of
conductive contaminants, moisture, flammable liquids, gases and corrosive substances. The Liebert APS
MBC contains no user-serviceable parts. Refer all faults to your local dealer, local Vertiv™ representative or
Vertiv™ Technical Support.
The Liebert APS MBC UPS system is designed for use on a properly earthed (grounded) 200-240 VAC,
50 or 60 Hz supply. The system must be installed by qualified personnel. A qualified electrician must
review and approve customer supplied wiring, circuit breakers, and intended loads and verify correct
input, output, and earth connections to ensure compliance with the technical standards and local
electrical codes of practice.
WARNING! Risk of electric shock. Can cause equipment damage, injury and death. A battery
can present a risk of electrical shock and high short-circuit current.
The following precautions must be observed before replacing the battery pack:
The Liebert APS MBC is designed and manufactured to ensure personal safety, but improper use can
result in electrical shock or fire. To ensure safety, observe the following precautions:
• Turn Off and unplug the Liebert APS MBC before cleaning it.
• Clean the unit with a dry cloth. Do not use liquid or aerosol cleaners.
• Never block or insert any objects into the ventilation holes or other openings of the Liebert
APS MBC.
• Do not place the Liebert APS MBC power cord where it might be damaged.
This LiebertAPS MBC contains no user-serviceable parts except the internal battery pack. The unit’s
On/Off push buttons do not electrically isolate internal parts. Under no circumstances attempt to gain
access internally, due to the risk of electric shock or burn.
The Liebert APS MBC complies with the requirements of EMC Directive 2004/108/EC and the published
technical standards. Continued compliance requires installation in accordance with these instructions
and use of accessories approved by Vertiv™.
NOTICE
This is a Category C2 UPS product. In a residential environment, this product may cause radio
interference, in which case the user may be required to take additional measures.
Operate the unit in an indoor environment only in an ambient temperature range of 0-40°C (32-104°F).
Install it in a clean environment, free from moisture, flammable liquids, gases and corrosive substances.
Do not continue to use the Liebert APS MBC if the front panel indications are not in accordance with
these operating instructions or the performance alters in use. Refer all faults to your Vertiv™
representative or Technical Support.
Never block or insert any object into the ventilation holes or other openings.
DO NOT CONNECT equipment that could overload the UPS or demand DC current from the Liebert APS
MBC, for example: electric drills, vacuum cleaners, laser printers, hair dryers or any appliance using
half-wave rectification.
Storing magnetic media on top of the Liebert APS MBC may result in data loss or corruption.
Turn Off and isolate the Liebert APS MBC before cleaning it. Use only a soft cloth, never liquid or aerosol
cleaners.
SYMBOL DESCRIPTION
AC input
AC output
Recycle
Bonded to ground
AC voltage
The Liebert APS MBC provides maximum system availability to business-critical equipment allowing the
transfer of connected equipment to an alternate power path for full isolation of the UPS for maintenance.
The UPS can be turned Off and removed from service with no interruption of power to connected
equipment.
2.1 Features
• Supports 8, 10, 15 or 20 kVA power, depending on model
• High-speed transfer switch
• Compact design
• Multiple power-path indicators
• Easily accessible terminal blocks
• Rack-mountable or tower orientation
• Integral output distribution options via optional PODs
ITEM DESCRIPTION
1 Plastic Bezel
NOTE: When the switch is in the Maintenance Bypass position, the connected equipment is not
protected by the UPS and is susceptible to any AC mains/utility anomalies and outages.
The POD ports, POD breakers and input/output terminal blocks are on the rear of the Liebert APS MBC,
as shown in Parts on the rear of APS MBC on page 11.
NO. DESCRIPTION
3 POD breaker
While in UPS Mode, the UPS supplies continuous, high-quality AC power. In this operating mode, the
connected equipment is protected by the UPS. The maintenance-bypass switch is rotated toward the
UPS indicator (green) in this mode.
NO. DESCRIPTION
1 AC input
2 MBC
3 Liebert APS
4 Connected load
While in the Maintenance Bypass mode, the MBC provides an alternate path for power to the connected
equipment. If the UPS must be taken out of service for limited maintenance or repair, manual activation of
the bypass immediately transfers the equipment from the UPS inverter to the bypass source. In this mode,
the connected equipment is not protected from utility/mains power abnormalities or outages. The
maintenance bypass switch is rotated toward the Bypass Indicator (amber) in this mode.
NO. DESCRIPTION
1 AC input
2 MBC
3 Liebert APS
4 Connected load
• Inspect the unit for shipping damage. If any shipping damage is founded, report it to the
carrier.
• Check against the delivery list to verify that the types of the accessories are complete and
correct. If there is any discrepancy, contact the carrier and your Vertiv™ representative
immediately.
If the Liebert APS MBC will be installed in a rack enclosure, see the following for the installation
procedures:
NOTE: The MBC is rack-mountable. If the Liebert APS UPS will be rack mounted and there is no UPS in
the rack, install the UPS before installing the MBC. If there is a UPS in the rack and the UPS is
operating, turn off the UPS, disconnect the local input breaker and loads, and remove the UPS Input/
Output cables according to the corresponding UPS user manual.
1. Locate the rack-mount rails from the APS MBC packaging and review the following procedures
to install the rails onto the vertical pole of the rack.
2. Install the cage nuts in the middle square holes of the 1U and 2U height space, the upper
square holes of the 3U and 6U height spaces and in the lower square holes of the 5U and 8U
height spaces.
NOTE: The height space indicates the whole U-height space counted from the top of the Liebert APS
UPS. The 1U and 2U height spaces are used to install the guide rails. The 3U, 6U, 5U and 8U height
spaces are used to install the securing brackets of the Liebert APS MBC.
3. Using the hook on the rear flange of the rack-mount rail, clip it onto the rear vertical pole and
use the provided four M6 x 16 screws to secure them, as shown in Attaching the rear of the
rack-mount rail kit on page 16.
NO. DESCRIPTION
1 Guide rail
2 Hook
3 Vertical rail
4 M6 x 16 screws (4 places)
4. Using the provided four M6 x 16 screws, secure the front of the rack-mount rails onto the
vertical pole.
5. Remove the MBC from the shipping carton, lift and place it on the guide rails, then slide it into
the rack as shown in Installing the Liebert APS MBC on page 17.
NOTE: The Liebert APS MBC weighs 30 kg (66 lb). Please be careful when lifting it. Lifting may require
two people.
MODEL
ITEM
ASMBCR2 SERIES ASMBCR1 SERIES ASMBCRG SERIES ASMBCRW SERIES
MODEL
ITEM
ASMBCR2 SERIES ASMBCR1 SERIES ASMBCRG SERIES ASMBCRW SERIES
The Liebert APS unit model number determines the section to follow for the installation of the APS MBC.
200/100-240/120 Input / Output; Transformer- Connections for Liebert APS UPS 200/100 to 240/120-V
AS5 or ASE
Free Input/Output on page 24
200/100-240/120 Input / Output; Transformer- Connections for Liebert APS UPS 200/100 to 240/120-V
AS6 or ASF
Free Input/Output on page 24
NOTE: The upper terminal block connects with the UPS; The lower terminal block connects with the
local power input and loads.
NO. DESCRIPTION
1 Cover
2 Retaining screws
3 Knockouts
Figure 3.5 MBC lower terminal block (from main AC source/to main distribution panel)
Figure 3.7 MBC lower terminal block (from main AC source/to main distribution panel)
input, L-N-PE (50 Hz) or L-L-G (60 Hz)
254
220/127 Do Not Use 127 127
(Do Not Use)
173
200/100 100 100 200
(Do Not Use)
190
220/110 110 110 220
(Do Not Use)
199
230/115 115 115 230
(Do Not Use)
254
220/127 127 127 220
(Do Not Use)
4.1 Starting Up
To start the UPS while connected to the Maintenance Bypass:
1. Set the rotary, maintenance-bypass switch to the UPS position on the front of the Liebert APS
MBC.
2. Close the UPS input breaker and the MBC output breaker on the front of the MBC.
3. Close the input breaker located in the local AC-power panel that provides power to the UPS
system.
4. Start the Liebert APS UPS according to its user manual (see SL-25510, which shipped with the
UPS).
5. The load is now supplied with conditioned power through the UPS.
6. Close the corresponding POD breaker, if any PODs are installed.
Bypass not present Call qualified service personnel to restore power to local power
Bypass Indicator (amber)
not illuminated APS MBC input cable is not
Refer to Cable Selection on page 17
connected to bypass.
UPS output power not present Turn on UPS, refer to UPS user manual.
UPS Indicator (green) not UPS input and/or output cable
illuminated is not connected to the APS Refer to Cable Selection on page 17
MBC.
The output breaker is not Close MBC output breaker (see Components on Front with Bezel Removed on page 10
Output Indicator (amber) closed. for its position)
not illuminated The load cable is not connected
Refer to Cable Selection on page 17
to the APS MBC.
Close MBC output breaker and/or POD breakers, refer to Components on Front with
Liebert APS MBC will not The MBC output breaker and/or
Bezel Removed on page 10 and Parts on the rear of APS MBC on page 11 for their
start some/all connected POD breaker is open.
positions
loads
Overload on APS MBC. Recalculate load requirement and choose a proper version.
POD MODEL
PARAMETER
PD2-101 PD2-102 PD2-103 PD2-104 PD2-105
Dimension, W x D x H, in (mm)
Weight, lb (kg)
Electrical Specification
POD MODEL
PARAMETER
PD2-106 PD2-107 PD2-108 PD2-109
Dimension, W x D x H, in (mm)
Weight, lb (kg)
Electrical Specification
POD MODEL
PARAMETER
PD2-200 PD2-201 PD2-202 PD2-204
Dimensions, W x D x H, in (mm)
Weight, lb (kg)
Electrical Specification
NOTICE
Risk of improper connections. Can cause improper operation.
When inserting, make sure that the colors of the PP75 terminals correspond to the colors of the
POD port.
3. Align the installation holes of the POD with those on the MBC, and attach the POD as shown in
Remove Cover and Attach the POD on page 31.
NO. DESCRIPTION
2 PP75 terminals
3 POD
ITEM SPECIFICATION
General
Compliant Safety Standards UL 1778-4th Edition, CSA C22.2 No. 107.3, IEC62040-1:2008
Mechanical
Environmental
Input Parameters
200/208/220/230/240V ~ L + N + PE
Nominal Input Voltage 220/380V ~ 240/415V ~ L1 + L2 +L3 + N + PE
100/200V ~ 120/240V ~ L1 + L2 +N + PE
Output Parameters
200/208/220/230/240V ~ L + N + PE
Output Voltage 100/100/173/200 - 120/120/208/240V ~
100/200 110/220 115/230 120/208 120/240 127/220 ~ L1 + L2 +N + PE