VFD Sizing Calculation

The document discusses sizing a VFD system for a 5500 kW fiberiser application. It provides supply side data, ambient conditions, motor and load data, and selects an ACS 5066-A2E-M5 converter that can handle the rated load of 560A and 110% overload of 616A at operating temperatures up to 45°C.

Uploaded by

Mesafint kassie
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Page 1

abb VFD SIZING CALCULATION

Project : SAISIDHA SUGAR PVT LTD - METEC ETIHOPIA


Application: VFD system for 5500 KW for FIBERISER

A. Supply side data


Network voltage 11000 V
Supply voltage tolerance +6/-9 %
Supply frequency 50 Hz
Supply frequency tolerance +3/-6 %
Maximum short circuit power 500 MVA
Minimum short circuit power 350 MVA

B. Ambient conditions
Altitude of installation < 1000 m a.s.l.
Maximum ambient operating temerature 45 °C
Relative humidity < 95 %

C. Motor and load data


Application Fiberiser
Load characteristic Constant torque
Motor voltage 6600 V
Motor rated current (As per Datasheet) 560 A
Motor rated frequency 50 Hz
Motor pole number 6
Motor rated shaft power 5500 kW
Efficiency at rated load 97 %
Power factor at rated load 0.88
Rated speed 1000 rpm
Starting torque 100 %
Overload 110 % for 60 s every 600 s

D. Converter selection
Selected Converter ACS 5066-A2E-M5, kindly refer attached catalogue page no.16
Continuous load:
Derating factor for ambient temperature of appx 0.5% per deg C over 40 deg C 0.98

Rated continuous output current of selected converter at 40°C 585 A

Derated countinuous output current of selected converter at 45°C 570 A


(As per the ACS5000 cataloque)

As derated continuous output current of selected converter at 45 deg C (i.e. 570 A) is


greater than load (i.e. 560 A), the selected converter is suitable for rated load at 45 Deg C

110% of motor full load current (1.1 x Motor Rated Current) 616 A
Rated Overload output current of selected converter at 40°C 643.5 A
(1.1 x Converter Rated Current of 585 A)

The overload current of the selected converter at 40 deg C (i.e. 643.5 A) is


greater thab load(i.e.616A), hence the selected converter is suitable for overload condition.

Issued: Rajesh More Document: YN3A251318-5500-VSC


Check/rel.: Samir Kumar ABB Limited, India 7/15/2013 Rev. 0
Resp. dept.: DM-DM