Argus Input Modules Connection Diagram

This document provides installation instructions for the VMI100 input module, VMC100 and VMC120 output modules, VMIC100 and VMIC120 input/output modules. The VMI100 module monitors normally open fire alarm and supervisory devices. The VMC100 module controls auxiliary devices such as fire shutters by closing contacts. All modules connect to a control panel using a loop circuit and are powered by the loop. They have short circuit isolators and provide LED indicators.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
645 views2 pages

Argus Input Modules Connection Diagram

This document provides installation instructions for the VMI100 input module, VMC100 and VMC120 output modules, VMIC100 and VMIC120 input/output modules. The VMI100 module monitors normally open fire alarm and supervisory devices. The VMC100 module controls auxiliary devices such as fire shutters by closing contacts. All modules connect to a control panel using a loop circuit and are powered by the loop. They have short circuit isolators and provide LED indicators.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

INPUT module Terminal Description

INSTALLATION INSTRUCTIONS FOR THE 1 Loop line IN (+) Loop positive input
VMI100 INPUT MODULE, VMC100, The VMI100 single channel super- 2 Loop line OUT (+) Loop positive output
VMC120 OUTPUT MODULES, VMIC100 AND vised input module provides 3 Loop line IN (-) Loop negative input
VMIC120 INPUT / OUTPUT MODULES KM518520 G212030, G212032 VMI100 monitoring of normally open
G212029, G212009 4 Loop line OUT (-) Loop negative output
G212031 contact fire alarm and supervisory
1 56 12 devices. 5 Input (+) Supervised input (+)
This manual is intended as a quick reference installation guide. Please refer to the manufacturer’s control panel installation manual
6 Input (-) Supervised input (-)
for detailed system information. End of line resistor (Reol):27 Kohm.
GENERAL DESCRIPTION 7 Not used
Alarm resistor (Rw):10 Kohm.
The Vega module series is a family of microprocessor controlled interface devices permitting the monitoring and/or control of auxilia- 8 Not used
ry devices. The Vega digital communication protocol utilised by the monitoring control panel provides for high rates of information 9 Not used
exchange in combination with particular features that ensure fast and secure responses. A bi-colour LED indicator (red/green), one
per single channel, is activated by the control panel. The modules are powered by the loop. Rw 10 Not used
SHORT CIRCUIT ISOLATORS Reol 11 Not used
All Vega series modules are provided with short-circuit monitoring isolators installed on the intelligent loop circuitry and can be acti- 12 Not used
vated by the control panel.

COMMON TECHNICAL SPECIFICATIONS **

INSTALLATION Loop’s voltage range * From 18 V (min) to 40 V (max)


OUTPUT supervised module Terminal Description
The Vega modules must be used in combination Average current consumption 120 uA (@ 24 V)
1 Loop line IN (+) Loop positive input
with compatible control panels employing the Vega LED’s current consumption 6 mA (@ 24 V)
communication protocol for monitoring and control. 2 Loop line OUT (+) Loop positive output
Operating temperature range From -30 °C (min) to +70 °C (max) The VMC100 single channel
The location of modules should follow recognised 3 Loop line IN (-) Loop negative input
Humidity 95% RH (no condensation) supervised output module pro-
national or international installation codes of prac- 4 Loop line OUT (-) Loop negative output
Dimensions 87 x 87 x 32 mm (w/o gang box) VMC100 vides control, by closing contacts,
tice. Connections to the terminals are polarity sensi-
of auxiliary devices such as fire 5 Not used
tive thus, please, check them by referring to the Weight 200 grams 7 8 910 12
1 shutters.
wiring diagrams and tables for each model. Modules 6 Not used
Maximum wire gauge 2.5 mm2
are provided with female terminal blocks, a 27 Kohm 7 Load (+) Supervised output (+)
End of line resistor (Reol):27 Kohm.
end of line resistor and a 10 Kohm alarm resistor,
depending on the model. 8 Load (-) Supervised output (-)
*Product operates down to 15 V, but without LED indication. Relay contact ratings are:
**Check latest version of document TDS-VMXXX for further data, 9 Load power (+) Load’s power supply (+)
30 Vdc , 2 A or 30 Vac , 2 A
obtainable from your supplier. (resistive load). 10 Load power (-) Load’s power supply (-)

Load
Reol
+ 11 Not used
CAUTION CAUTION
Disconnect loop power before installing the Electrostatic Sensitive Device. 12 Not used
Load’s power
modules. Observe precautions when handling and making connections.

Module view WARNING


87 mm When switching an inductive CONTACT
OUTPUT relay module Terminal Description
load, in order to protect the
1 Loop line IN (+) Loop positive input
module from surges caused by
2 Loop line OUT (+) Loop positive output
counter-EMF, it is important to
The VMC120 single channel relay 3 Loop line IN (-) Loop negative input
protect the relay contacts. A s + Diode
output module provides pole

LOAD
VMxxxx
diode with a reverse breakdown
(DC
only) or changeover contacts for the 4 Loop line OUT (-) Loop negative output
60 mm VMC120
voltage of at least ten times the varistor
control of auxiliary devices such 5 Not used
1 7 8 9101112 as fire shutters. 6 Not used
circuit voltage (DC applications
only) or a varistor (AC or DC 7 Common 1 Relay contact terminal
Relay contact ratings are:
applications) should be connect- 30 Vdc , 2 A or 30 Vac , 2 A 8 Common 2 Relay contact terminal
Front Rear
ed in parallel to the load. (resistive load). 9 Normally open 1 Relay contact terminal
SETTING THE ADDRESS 11 10 Normally open 2 Relay contact terminal
7
Modules can be addressed by using a special hand-held programming unit or they can be auto-addressed by the control panel after 9 11 Normally closed 1 Relay contact terminal
they have been installed (the implementation of the auto-addressing feature depends on the control panel’s manufacturer). Address- 12 12 Normally closed 2 Relay contact terminal
es may be selected over the range from 1 to 240, although, of course, each device on the loop must have a unique address. 8
10
- Connect the programmer to the module using the proper cable (refer to the programmer’s instruction manual).
- After installing all modules and other loop devices, apply power to the loop in accordance with the panel’s installation instructions.
NOTE: The VMIC100 and VMIC120 input/output modules hold two addresses. The address assigned by the programmer Continues the following page
always relates to the input channel; the output channel is automatically assigned the consecutive address. WARNINGS AND LIMITATIONS
DEVICE’S MOUNTING Our devices use high quality electronic components and plastic materials that are highly resistant to environmental deterioration.
According to local electrical regulations, mount securely to a single gang box using the provided screws. However, after 10 years of continuous operation, it is advisable to replace the devices in order to minimize the risk of reduced perfor-
mance caused by external factors. Ensure that these modules are only used with compatible control panels. Detection systems must
MAINTENANCE be checked, serviced and maintained on a regular basis to confirm correct operation. Refer to and follow national codes of practice
Test the modules periodically according to local codes of practice. Those devices contain no serviceable part, so, should a fault and other internationally recognized fire engineering standards. Appropriate risk assessment should be carried out initially to deter-
develop, return them to your system supplier for exchange or disposal, according to warranty conditions. mine correct design criteria and updated periodically.

WARRANTY
All devices are supplied with the benefit of a limited 3 year warranty relating to faulty materials or manufacturing defects, effective
from the production date indicated on each product. This warranty is invalidated by mechanical or electrical damage caused in the
field by incorrect handling or usage. Product must be returned via your authorized supplier for repair or replacement together with full
information on any problem identified. Full details on our warranty and products returns policy can be obtained upon request.

ARGUS SECURITY S.R.L. - Via del Canneto, 14 - 34015 - Muggia (TS) - Italy www.argussecurity.it [email protected] SPNK-754431-078 (v2.2)
INPUT / OUTPUT supervised module Terminal Description
1 Loop line IN (+) Loop positive input
2 Loop line OUT (+) Loop positive output
The VMIC100 input and output
supervised module combine in a 3 Loop line IN (-) Loop negative input
VMIC100 single device supervised input and 4 Loop line OUT (-) Loop negative output
output characteristics. 5 Input (+) Supervised input (+)
1 5 6 7 8 910 12
6 Input (-) Supervised input (-)
End of line resistor (Reol):27 Kohm.
Alarm resistor (Rw):10 Kohm. 7 Load (+) Supervised output (+)

Load’s power
8 Load (-) Supervised output (-)
+ Relay contact ratings are:
9 Load power (+) Load’s power supply (+)
30 Vdc , 2 A or 30 Vac , 2 A
(resistive load). 10 Load power (-) Load’s power supply (-)
Rw 11 Not used
Reol Load 12 Not used
Reol

INPUT / OUTPUT relay module Terminal Description


1 Loop line IN (+) Loop positive input
The VMIC120 input and output 2 Loop line OUT (+) Loop positive output
relay module combine in a single 3 Loop line IN (-) Loop negative input
device supervised input and relay
VMIC120 4 Loop line OUT (-) Loop negative output
output characteristics.
5 6 7 8 9101112 5 Input (+) Supervised input (+)
1
End of line resistor (Reol):27 Kohm. 6 Input (-) Supervised input (-)
Alarm resistor (Rw):10 Kohm. 7 Common 1 Relay contact terminal
Relay contact ratings are: 8 Common 2 Relay contact terminal
30 Vdc , 2 A or 30 Vac , 2 A 9 Normally open 1 Relay contact terminal
11 (resistive load). 10 Normally open 2 Relay contact terminal
7
9
Rw 11 Normally closed 1 Relay contact terminal
12
Reol 8 12 Normally closed 2 Relay contact terminal
10

0786
ARGUS SECURITY S.R.L.
Via del Canneto, 14
34015 Muggia (TS)
Italy

12

VE0610CPR20130701

EN 54-17:2005 + AC:2007
EN 54-18:2005 + AC:2007

VMI100
VMC100
VMC120
VMIC100
VMIC120

For use in compatible fire


detection and alarm system

ARGUS SECURITY S.R.L. - Via del Canneto, 14 - 34015 - Muggia (TS) - Italy www.argussecurity.it [email protected] SPNK-754431-078 (v2.2)