LEXE0047-02 Data Sheet
LEXE0047-02 Data Sheet
Generator set ratings may seem complex, but maximum of 500 hours per year. The normal
their basic purpose is simple: fit the application standby rating is not for use in utility paralleling
needs at the optimum reliability, performance, applications.
and cost. An improper rating means either buying
For example, a 3 MW standby rated generator
more capacity than needed or risking shorter life
set will provide power for the duration of an
to overhaul, more repairs, and more downtime.
outage. It should be run for up to 500 hours per
Ratings have changed in recent years, and more year and have an average load factor of 2.1 MW.
sophisticated switchgear can be integrated with
generator sets. That means more flexibility to
Emergency Standby Power (ESP): The ESP
specify generating systems that closely match a
rating differs from the Standby rating only in the
specific installation requirement.
number of running hours allowed per year. ESP
The key to choosing the right rating is to ratings allow a maximum running time of 200
understand the application in detail. That means hours per year at a 70% average load factor with
not only knowing the type of duty but also varying load. An example of the Standby and
answering: ESP ratings are shown in Chart 1.
What is the average load factor? 3 .5
A ve rage Loa d o n G ene rato r
G ene rato r N am e pla te R ating
What is the maximum required load? 3
G ene rato r Loa d
Ratings Defined
Caterpillar defines five basic generator set 0 .5
Load (MW)
A verage Load on G enerator 2
3 .5
G enerator N am eplate R ating
1.5
G enerator Load
3
1 Load on Generator
2 .5 0.5 Average Load on Generators
Generator Nameplate Rating
0
Load (MW)
2 0 5 10 15 20 25 30
Time
1 .5 Chart 3: Example Load Profile: 2.7 MW Prime Rating
Load Management
0 .5 A Prime rated generator applied under load
management guidelines allows for a Prime rated
0
0 5 10 15
Tim e
20 25 30 generator set to be used in parallel with the
Chart 2: utility. A Prime rated generator set under load
Example Load Profile: 3MW Mission Critical Standby Rating management guidelines can run for a maximum
of 500 hours per year. This generator set has
the same nameplate rating as a Prime rated unit,
For example, a 3 MW mission critical standby
but allows for an average load factor of up to
rated generator set will provide power for the
100%. The Prime rating with load management
duration of an outage. It could be run for up to
guidelines does not allow for a 10% overload
500 hours per year and have an average load
capability.
factor of up to 2.55 MW.
For example, these guidelines state that a 2.7
Prime: In this application, the generator set is
MW unit (same nameplate rating as the Prime
capable of providing power to a varying load for
rated unit) can be run at 2.7 MW for a maximum
an unlimited number of hours per year. A Prime
of 500 hours.
rated generator set is capable of providing full
nameplate rating for a period of time, but must
Load management practices: There are two
have an average load factor of no more than
basic load management practices: base loading
70% of the Prime rating. Ten percent overload is
and peak shaving.
allowed for emergencies for a maximum of 1
hour in 12, and for no more than 25 hours per In base loading, the generator set operates at a
year. The standard prime rating is for use in fixed kW output, and the utility provides power for
either utility paralleling or isolated applications. any peaks above that level. In this scenario the
end user may export power to the grid if more
For example, a 2.7 MW rated unit may provide
power is being generated then is required by the
the full nameplate rating for a short duration, but
facility loads, and the appropriate agreements
should have a maximum average load of 1.89
with the utility are in place. An example of base
MW (not including generator set non-running
loading is shown in Chart 4.
time per ISO8528-1). The generator set can also
provide 3 MW of power in emergencies as 4
shown in Chart 3. 2 .5
Load (MW)
1 .5
U tility L o a d
1
0 .5
E x p o r t to U t ilit y
0
G e n e ra to r B a s e L o a d
1 5 9 13 17 21 25 29
T im e
3
Paralleling switchgear combined with the correct
2.5
prime rated units is required when operating
Load (MW)
2
under load management guidelines. The
1.5
switchgear controls provide increased system
1
flexibility allowing generator sets to operate in
0.5
parallel with the utility. The switchgear is able to
0
control the load on the generator sets and
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
T im e
17 18 19 20 21 22 23 24 25
monitor the power supplied from the utility. This
Chart 5: Example Load Profile –
ensures that the generator sets are providing the
2.7 MW Load Management (Peak Shaving) proper load and are not operating outside of their
rating guidelines.
Continuous: In this application, the generator
set is able to provide power to a non-varying load
Regardless of the application, generator set
for an unlimited number of hours per year. The
ratings help ensure that customers’ power needs
average power output of the generator set is 70 -
are met and that generating equipment is
100% of the rating. The rating is designed to
protected from premature wear. Choosing the
provide 100% of the rating for 100% of the
right rating means making the proper tradeoffs
operating hours.
between run hours, peak load, and average load.
Typical Continuous rating applications include The proper rating means the customer receives
base loading in parallel with the utility and co- the optimum combination of installed cost and
generation operations. An example of a long-term cost of ownership.
Continuous rated generator set is shown in Chart
6.
3
2 .5
2
Load (MW)
1 .5
L o a d o n G e n e ra to rs
0 .5
G e n e r a t o r N a m e p la t e
R a t in g
0
0 5 10 15 20 25 30
T im e
CAT, CATERPILLAR, their respective logos, “Caterpillar Yellow,” the “Power Edge” trade dress as well as corporate
and product identity used herein, are trademarks of Caterpillar and may not be used without permission.
www.Cat-ElectricPower.com
©2011 Caterpillar
All Rights Reserved.
LEXE0047-02
LEXE0047-02(04/11)
(04/11) Printed in U.S.A.
Page 3 of 4