0% found this document useful (0 votes)
134 views

Monitoring Card Type VT 13 477: Series 2X

Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
134 views

Monitoring Card Type VT 13 477: Series 2X

Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 8

RE 29 782/06.

96
Replaces: 01.95

Monitoring Card
Type VT 13 477

Series 2X

HA 3694/93
Type VT 13 477-2X

Table of contents Features

Contents Page The VT 13 477 card is used to monitor the correct functioning of two
Features 1 amplifier cards for controlling proportional or servo valves.
Technical data 2 It consists of two monitoring systems which operate inde-pendently
Block circuit diagram / pin allocation 3 of one another.
Function 3
Circuit example 4-7 Card holder:
– Type VT 3002-2X/32, see RE 29 928
Projecting notes / maintenance instructions /
Single card holder without power pack
additional information 8
Ordering code 8 Power pack:
– Type VT 19 083-1X, see RE 29 929
Unit dimensions 8
Power pack NE30; 115/230 VAC - 24 VDC, 70 VA

© 2003
by Bosch Rexroth AG, Industrial Hydraulics, D-97813 Lohr am Main
All rights reserved. No part of this document may be reproduced or stored, processed, duplicated or circulated using
electronic systems, in any form or by any means, without the prior written authorisation of Bosch Rexroth AG.
In the event of contravention of the above provisions, the contravening party is obliged to pay compensation.

VT 13 477 1/8 RE 29 782/06.96


Technical data (For applications outside these stated values, please consult us!)

Operating voltage UB + 24 VDC + 40 % – 5 %; smoothed

Operating range:
– upper limit value uB(t)max + 35 V
– lower limit value uB(t)min + 22 V
Power consumption I 300 mA (unloaded)
Fuse IS 0,5 A T
Internally controlled voltage UM ± 9 V with raised zero (M0)
Input signals (4 differential inputs) U ± 10 V
Relay contact load U UB; Imax = 3 A
Type of connection 32-pin blade connector, DIN 41 612, form D
Card dimensions Eurocard 100 x 160 mm, DIN 41 494
Front plate dimensions:
– Height 3 HE (128,4 mm)
– Width conductor side 1 TE (5,08 mm)
– Width connector side 5 TE
Permitted ambient temperature ϑ 0 to + 50 oC
Storage temperature ϑ – 20 to + 70 oC
Weight m 0,15 kg

RE 29 782/06.96 2/8 VT 13 477


Block circuit diagram / pin allocation

1
Differential inputs:
30c
± 10 V u
Command 30a
u
Reference potential
value 1
2
3
28c
Σ
22ac
± 10 V u
Actual 28a H1
Reference potential u
value 1
K1
8a
External reset + 24 V
ϑ

24ac

4 Reset
Differential inputs: (internal)
6c
± 10 V u
Command 6a
u
Reference potential
value 2
5
6
4c
Actual
± 10 V
4a
u Σ H2
14ac

Reference potential u
value 2
K2
10a
Reference potential
ϑ

7 8 16ac
Reset
(internal)
M0 M0 Internal
voltages:
2c
2a +9V
+ 24 V 20ac
Operating voltage 32a M0
0V 32c
–9V

Test point 1: Command value 1 (max. ± 6 V) Test point 4: Command value 2 (max. ± 6 V)
Test point 2: Command value – Actual value 1 (max. ± 6 V) Test point 5: Command value 2 (max. ± 6 V)
Test point 3: Actual value 1 (max. ± 6 V) Test point 6: Command value 2 (max. ± 6 V)
Test point 7: Measured potential Test point 8: Measured potential
NB: Measured zero is raised by + 9 V against an operating voltage of 0 V.

Function

On amplifier cards for valves without electrical feedback the valve The VT 13477 permits a maximum error of 10 %.The delay time
command value is compared with the solenoid current ; on amplifier applicable for the error signal is geared to the amplifiers in the rele-
cards for valves with electrical feedback the command value for the vant valve group. The error signal can either be reset via an external
valve is compared with its actual value. Where there is an inadmissibly 24V signal (200 ms) or internally by means of a switch on the front
large deviation one of the relay contacts assigned to the relevant plate.
monitoring system opens. A safety function may be triggered by the
open relay e.g. 'Switch off supply voltage' on proportional valves or
'Switch off torque motor coils' on servo valves.

VT 13 477 3/8 RE 29 782/06.96


RE 29 782/06.96

In the cause of fault the power supply to the proportional amplifier is switched off!

VT 3000; VT 3006; VT 3013; VT 3014; VT 3017; VT 3018; VT 3024


Circuit example of monitoring for the following amplifier cards:
20a 30a Solenoid "A"
Channel 1
18a 24ac
0…±6V 30c
24a
1R u
+ 24 V 32a Command value M0 30a u
0V 26a 28a Solenoid "B" 22ac

22a
1R 28a
i
VT 30xx Actual value 28c u

Channel 2 14ac
0…±6V 6c
Solenoid "A" u
20a 30a Command value M0 6a u
4/8

18a 16ac
24a
+ 24 V 1R
32a
0V 26a 28a Solenoid "B" 4a 10a Reset external
i + 24 V; 200 ms
22a Actual value 4c u
1R

VT 30xx 2c
+9V
0 V (L0) 32a 20ac For
M0
+ 24 V (UB) 2a 32c testing
–9V

VT 13477-2X

0V
110 V

24 V + 24 V
220 V
VT 13 477

External
power supply
VT 13 477

In the cause of fault the power supply to the proportional amplifier is switched off!

VT 5001 to VT 5004; VT 5010 to VT 5018; VT 5036


Circuit example of monitoring for the following amplifier cards:
Channel 1
30c 24ac
28a Command value 0…+6V
u
18ac M0 30a u
+ 24 V 6ac 22ac
0V 10ac
18ac M0 28a
i
32a Actual value 0…–6V 28c u

VT 50xx

Channel 2 14ac
28a Command value 0…+6V 6c
u
+ 24 V 6ac
18ac M0 6a u
16ac
5/8

0V 10ac
18ac M0 4a
10a Reset external
i
32a Actual value 0…–6V 4c u + 24 V; 200 ms

VT 50xx
2c
+9V
0 V (L0) 32a 20ac
M0 For
+ 24 V (UB) 2a 32c testing
–9V

VT 13477-2X

0V
110 V
RE 29 782/06.96

24 V + 24 V
220 V

External
power supply
RE 29 782/06.96

In the cause of fault the power supply to the proportional amplifier is switched off!

VT 5005 to VT 5008; VT 5024; VT 5025; VT 5035


Circuit example of monitoring for the following amplifier cards:
Channel 1 24ac
4a Command value 0…±6V 30c
u
26c M0 30a u
+ 24 V 22ac 22ac
0V 28ac
26c M0 28a
i
4c Actual value ±
0… 6V 28c u

VT 50xx

Channel 2 14ac
4a Command value 0…±6V 6c
u
+ 24 V 22ac
26c M0 6a u
16ac
6/8

0V 28ac
26c M0 4a
10a Reset external
i
4c Actual value ±
0… 6V 4c u + 24 V; 200 ms

VT 50xx
2c
+9V
0 V (L0) 32a 20ac
M0 For
+ 24 V (UB) 2a 32c testing
–9V

VT 13477-2X

0V
110 V

24 V + 24 V
220 V
VT 13 477

External
power supply
VT 13 477

In the cause of fault the enable is withdrawn!

SR 1; SR 7; SR 30 to SR 39
Circuit example of monitoring for the following amplifier cards:
Channel 1
Customer command value 30c 24ac
+ 24 V 6a Enable of valve 0 … ± 10 V
0V 16a u
18c M0 30a u
22ac

18c M0 28a
i
32a Actual value ±
0 … 10 V 28c u

SR xx

Channel 2 14ac
+ 24 V 6a Enable of valve Customer command value 0 … ± 10 V 6c
0V 16a
u
18c M0 6a u
16ac
7/8

18c M0 4a
10a Reset external
i
32a Actual value ±
0 … 10 V 4c u + 24 V; 200 ms

SR xx
2c
+9V
0 V (L0) 32a 20ac
M0 For
+ 24 V (UB) 2a 32c testing
–9V

VT 13477-2X

0V
110 V
RE 29 782/06.96

24 V + 24 V
220 V

External
power supply
Projecting / maintenance notes / additional information
– Ensure that the card is not connected to a voltage supply before plugging it in or unplugging it.
– Measurements should only be conducted with instruments conforming to Ri > 100 kW.
– Do not connect measured zero (M0) to 0V operating voltage.
– Do not route signals which are to be screened through a common cable.
– Apply command and actual value lines to the control side.
– Do not lay supply and discharge signal lines in the vicinity of power lines.
– Warning : The posistor on the plate may reach a temperature of 70 °C.
Note: Electrical signals (e.g. actual value ) routed via an electronic control or monitoring system may not be used
for switching off machine safety functions.
(See also European standard "Safety Requirements for Hydraulic Installations and Components - Hydraulics", prEN 982.)

Ordering code

VT 13 477 – 2X / *
Monitoring card Further details in clear text
Series 20 to 29 = 2X 1= Monitoring of amplifier cards
(20 to 29: technical data and pin allocation VT 3000, VT 3006 and VT 3024
unchanged) for the control of proportional valves
2= Monitoring of amplifier cards VT 3013,
VT 3014, VT 3017 and VT 3018
for the control of proportional valves
3= Monitoring of amplifier cards VT 5001 to VT 5008,
and VT 5010 to VT 5036
for the control of proportional valves
4= Monitoring of amplifier cards SR1 and SR7
and SR 30 to SR 39
for the control of servo valves
Unit dimensions (dimensions in mm)

1 4
2 5
3HE (128,4)

3 6
M0 M0
100
89

H2
Reset
H1

VT
15

13477
7

6TE (30,1) 2
7 165
186

Bosch Rexroth AG The data specified above only serves to describe


Industrial Hydraulics the product. No statements concerning a certain
D-97813 Lohr am Main condition or suitability for a certain application
Zum Eisengießer 1 • D-97816 Lohr am Main can be derived from our information.The details
Telefon 0 93 52 / 18-0 stated do not release you from the responsibility
Telefax 0 93 52 / 18-23 58 • Telex 6 89 418-0 for carrying out your own assessment and
eMail [email protected] verification. It must be remembered that our
Internet www.boschrexroth.de products are subject to a natural process of
wear and ageing.

RE 29 782/06.96 8/8 VT 13 477

You might also like