Using ControlLogix in SIL 2 Applications
Using ControlLogix in SIL 2 Applications
SIL 2 Applications
ControlLogix 5560 and 5570 Controllers
Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required to
be carried out by suitably trained personnel in accordance with applicable code of practice.
If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be
impaired.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use
or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and
requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for
actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software
described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is
prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment,
which may lead to personal injury or death, property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property
damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.
IMPORTANT Identifies information that is critical for successful application and understanding of the product.
SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous
voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may
reach dangerous temperatures.
ARC FLASH HAZARD: Labels may be on or inside the equipment, for example, a motor control center, to alert people to
potential Arc Flash. Arc Flash will cause severe injury or death. Wear proper Personal Protective Equipment (PPE). Follow ALL
Regulatory requirements for safe work practices and for Personal Protective Equipment (PPE).
Chapter 1
SIL Policy Introduction to Safety Integrity Level (SIL) . . . . . . . . . . . . . . . . . . . . . . . . . 9
Programming and Debugging Tool (PADT) . . . . . . . . . . . . . . . . . . . . 10
About the ControlLogix System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Gas and Fire Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Boiler and Combustion Considerations . . . . . . . . . . . . . . . . . . . . . . . . 11
Typical SIL 2 Configurations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Simplex Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Duplex Logic-Solver Configurations . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Duplex System Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Proof Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Proof Testing with Redundancy Systems. . . . . . . . . . . . . . . . . . . . . . . 27
Reaction Times . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Reaction Times in Redundancy Systems. . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Safety Watchdog . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Safety Certifications and Compliance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Chapter 2
Features of the ControlLogix SIL Module Fault Reporting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
2 System Data Echo Communication Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Pulse Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Communication Ports . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
ControlNet Network . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
EtherNet/IP Network . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Electronic Keying of Modules in SIL 2 Applications. . . . . . . . . . . . . . . . . 35
Chapter 3
ControlLogix Controllers, ControlLogix Controllers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Chassis, and Power Supplies Operating Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Requirements for Use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
ControlLogix Chassis . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
ControlLogix Power Supplies. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Redundant Power Supplies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Recommendations for Using Power Supplies. . . . . . . . . . . . . . . . . . . 39
Chapter 5
ControlLogix I/O Modules Overview of ControlLogix I/O Modules. . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Using 1756 Digital Input Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Requirements When Using Any ControlLogix Digital Input Module . . . 47
Wiring ControlLogix Digital Input Modules. . . . . . . . . . . . . . . . . . . . 47
Using 1756 Digital Output Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Requirements When Using ControlLogix Digital Output Modules. . . . . 49
Wiring ControlLogix Digital Output Modules . . . . . . . . . . . . . . . . . . 50
Using 1756 Analog Input Modules. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Conduct Proof Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Calibrate Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Use the Floating Point Data Format . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Program to Respond to Faults Appropriately . . . . . . . . . . . . . . . . . . . 54
Program to Compare Analog Input Data . . . . . . . . . . . . . . . . . . . . . . . 55
Configure Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Specify the Same Controller as the Owner. . . . . . . . . . . . . . . . . . . . . . 56
Wiring ControlLogix Analog Input Modules. . . . . . . . . . . . . . . . . . . . 56
Using 1756 HART Analog Input Modules. . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Wiring the HART Analog Input Modules . . . . . . . . . . . . . . . . . . . . . . . 61
Using 1756 Analog Output Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Considerations for Using Analog Output Modules . . . . . . . . . . . . . . 62
Wiring ControlLogix Analog Output Modules . . . . . . . . . . . . . . . . . . 64
Using 1756 HART Analog Output Modules . . . . . . . . . . . . . . . . . . . . . . . . . 66
Wiring the HART Analog Output Modules . . . . . . . . . . . . . . . . . . . . . 66
Chapter 6
FLEX I/O Modules Overview of FLEX I/O Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Using 1794 Digital Input Modules. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Requirements When Using FLEX I/O Digital Input Modules. . . . . 67
Wiring FLEX I/O Digital Input Modules . . . . . . . . . . . . . . . . . . . . . . . 68
Using 1794 Digital Output Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Considerations When Using FLEX I/O Digital Output Modules . . 69
Wiring FLEX I/O Digital Output Modules . . . . . . . . . . . . . . . . . . . . . . 70
Chapter 7
Requirements for Application Software for SIL 2-Related Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
Development SIL 2 Programming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
Programming Languages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
Programming Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Security . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Basics of Application Program Development and Testing . . . . . . . . . . . 83
Functional Specification Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Sensors (digital or analog) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
Actuators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
Creating the Application Program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
Logic and Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
Program Language . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
Program Identification. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
SIL Task/Program Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Forcing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Checking the Application Program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Verify Download and Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
Commissioning Lifecycle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Changing Your Application Program. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Chapter 8
Faults in the . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .91
ControlLogix System
Chapter 9
Use of Human-to-Machine Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
Interfaces Accessing Safety-related Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
Reading Parameters in Safety-related Systems . . . . . . . . . . . . . . . . . 95
Changing Safety-related Parameters in SIL-rated Systems . . . . . . 96
Appendix A
Reaction Times of the Local Chassis Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
ControlLogix System Remote Chassis Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
Calculating Worst-case Reaction Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
For Digital Modules. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
For Analog Modules. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
Appendix B
SIL 2-certified ControlLogix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .101
System Components
Rockwell Automation Publication 1756-RM001Q-EN-P - August 2021 5
Appendix C
PFD and PFH Calculations About PFD and PFH Calculations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
for a SIL 2 System Determine Which Values To Use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
About the Calculations in This Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
1-Year PFD Calculations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
2-Year PFD Calculations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
5-year PFD Calculations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120
Using Component Values to Calculate System PFD. . . . . . . . . . . . . . . . 126
Example: 1-year PFD Calculation for a ControlLogix System
(1oo1 Configuration) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 126
Example: 1-year PFD Calculation for a ControlLogix System
(1oo2 Configuration) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 126
Appendix D
Using ControlLogix and FLEX I/O . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .127
Modules in SIL 1 Applications
Appendix E
Checklists Checklist for the ControlLogix System . . . . . . . . . . . . . . . . . . . . . . . . . . . 131
Checklist for SIL Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 132
Checklist for SIL Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 133
Checklist for the Creation of an Application Program. . . . . . . . . . . . . . 134
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .135
About This Publication This safety reference manual describes the ControlLogix® Control System
components that are suitable for use in low demand and high demand (no
more than 10 demands per year) safety-related control, up to and including
SIL 2 applications. The manual also provides safety-related information, such
as PFD calculations, system configurations, programming, and
implementation.
IMPORTANT This manual describes typical SIL 2 implementations using ControlLogix equipment. Keep in mind that the
descriptions presented in this manual do not preclude other methods of implementing a SIL 2-compliant system
by using ControlLogix equipment.
Make sure that other methods are reviewed and approved by a recognized certifying body, such as TÜV Rheinland
Group.
Download Firmware, AOP, Download firmware, associated files (such as AOP, EDS, and DTM), and access
EDS, and Other Files product release notes from the Product Compatibility and Download Center at
rok.auto/pcdc.
Summary of Changes This publication contains the following new or updated information. This list
includes substantive updates only and is not intended to reflect all changes.
Topic Page
Added PFD and PFH calculations for series B modules 110…123
Terminology This table defines abbreviations that are used in this manual.
SIL Policy
Introduction to Safety Certain catalog numbers of the ControlLogix® system (listed in Appendix B)
Integrity Level (SIL) are type-approved and certified for use in SIL 2 applications according to these
standards:
• IEC 61508, edition 2, 2010 (this manual describes architectures that are
required to achieve edition 2)
• IEC 61511
The TÜV Rheinland Group has approved the ControlLogix system for use in up
to, and including, SIL 2 safety-related applications in which the de-energized
state is typically considered to be the safe state.
IMPORTANT Keep in mind that a demand is an event where the safety function is
executed. A ControlLogix system can be configured to execute standard
control and safety functions. The demand rate is determined by how
often the safety function is executed and not how often the control
function is executed.
When used in accordance with the information in this manual and the
relevant safety standards, the ControlLogix system is suitable for
applications up to and including SIL 2, where the demand rate is no
more than 10 times per year.
These are the measures and modifications that are related to the use of the
ControlLogix system in Gas and Fire applications.
• The use of a manual override is necessary to make sure that the operator
can maintain the desired control in the event of a controller failure. This
is similar in concept to the function of the external relay or redundant
outputs that are required to make sure that a de-energized state is
achieved for an ESD system when a failure occurs (for example, a shorted
output driver) that prevents this from normally occurring. The system
knows that it has a failure, but the failure state requires an independent
means to maintain control and either remove power or provide an
alternate path to maintain power to the end actuator.
• If the application cannot tolerate an output that can fail shorted
(energized), then an external means such as a relay or other output must
be wired in series to remove power when the fail shorted condition
occurs. See Wiring ControlLogix Digital Output Modules on page 50 for
more information.
• If the application cannot tolerate an output that fails open (de-
energized), then an external means such as a manual override or output
must be wired in parallel. See Figure 1. You must supply alternative
means and develop the application program to initiate the alternate
means to remove or continue to supply power in the event the main
output fails.
Manual Override
Actuator
L2 or Ground 43379
Fault
Alarm to Operator
To comply with the requirements of IEC 61508, the safety demand rate must be
no more than 10 demands per year.
If your system must meet standard EN 50156, then you must also meet the
requirements that are identified in the current version of EN 50156. To use
FLEX™ I/O or 1756-series I/O modules in SIL 2 EN50156 applications, you must
use a GuardLogix® controller. See the GuardLogix Safety Reference Manual,
publication 1756-RM093.
IMPORTANT When using a GuardLogix controller with SIL 2-rated 1756 or 1794 I/O,
you must also follow the requirements defined in this manual.
Typical SIL 2 Configurations SIL 2-certified ControlLogix systems can be used in standard (simplex) or
high-availability (duplex) configurations. For the purposes of documentation,
the various levels of availability that can be achieved by using various
ControlLogix system configurations are referred to as simplex or duplex.
When using a duplex ControlLogix configuration, the ControlLogix controller
remains simplex (1oo1) from a safety perspective.
This table lists each system configuration and the hardware that is part of the
safety loop.
IMPORTANT The system operator is responsible for the following tasks when any of
the ControlLogix SIL 2 system configurations are used:
• The setup, SIL rating, and validation of any sensors or actuators that are
connected to the ControlLogix control system
• Project Management and functional testing
• Programming the application software and the module configuration
according to the descriptions in this manual
The SIL 2 portion of the certified system excludes the development
tools and display/human machine interface (HMI) devices; these tools
and devices must not be part of the safety loop.
Simplex Configuration
Figures 2 …9 each show typical simplex SIL loops for limited high demand
applications with up to 10 demands per year. The figures show the following:
• Overall safety loop
• ControlLogix portion of the overall safety loop
SIL 2 I/O modules in the safety loop must meet the requirements that are
specified in Chapter 5, ControlLogix I/O Modules and Chapter 6, FLEX I/O
Modules. Chassis can have modules within SIL 2 certified ControlLogix safety
loop that are not being used within SIL safety functions, if these modules are
listed in the SIL 2-certified ControlLogix System Components on page 101.
Table 1 defines the module abbreviations used in the graphics in this section.
ST 0 1 2 3 4 5 6 7 O ST 0 1 2 3 4 5 6 7 O ST 0 1 2 3 4 5 6 7 O ST 0 1 2 3 4 5 6 7 O ST
ST
ST 000111222333444555666777OOO
ST 8 9 10 1112131415 K ST 8 9 10 1112131415 K ST 8 9 10 1112131415 K ST 8 9 10 1112131415 K ST
ST
ST 88899910
10
10
1112131415
1112131415KKK
1112131415
Sensor
I I O M O Actuator
N N U O U
E T N T
N
2 1 1 2 I 2
T A B A N B
Monitoring input
module
Non-isolated digital output modules
Standard Communication
1756 SIL 2 I/O module pairs can be in the same chassis because only SIL 2
capable hardware is within the controller chassis. The number on the label
indicates a module pair in a 1oo2 configuration; Module A and Module B. For
example, Input 1A and Input 1B are a 1oo2 duplex module pair. For more
information on how to wire field devices, see Figure 6 on page 18.
Chassis within the 'SIL 2 certified ControlLogix Safety Loop' can have modules
that are not being used within SIL 2 safety functions, if these modules are listed
in the SIL 2-certified ControlLogix System Components on page 101.
ST 0 1 2 3 4 5 6 7 O ST 0 1 2 3 4 5 6 7 O ST 0 1 2 3 4 5 6 7 O ST 0 1 2 3 4 5 6 7 O ST
ST
ST 000111222333444555666777OOO ST 0 1 2 3 4 5 6 7 O ST 0 1 2 3 4 5 6 7 O
ST 8 9 10 1112131415 K ST 8 9 10 1112131415 K ST 8 9 10 1112131415 K ST 8 9 10 1112131415 K ST
ST
ST 88899910
10
10
1112131415
1112131415KKK
1112131415 ST 8 9 10 1112131415 K ST 8 9 10 1112131415 K
Sensor I I D O Actuator
N N I U
E EE E A
N N T
N N G
2 22 2 O
T TT 1 1 2
T A B 2 B
RR R A
ST 0 1 2 3 4 5 6 7 O ST 0 1 2 3 4 5 6 7 O ST
ST 0 11
1 22
2 33
3 44
4 55
5 66
6 77
7O ST 0 1 2 3 4 5 6 7 O ST
ST
ST 000111222333444555666777OOO ST 0 1 2 3 4 5 6 7 O
ST 00 O
O
ST 8 9 10 1112131415 K ST 8 9 10 1112131415 K ST
ST 8 99
9 10
101112131415 K
1112131415 KK ST 8 9 10 1112131415 K ST
ST
ST 88899910
10
10
1112131415
1112131415KKK
1112131415 ST 8 9 10 1112131415 K
ST 88 10 1112131415
I I O M O
N N U O U
E T N T
N
2 3 3 4 I 4
EtherNet/IP T A B A N B
R
1756 SIL 2 I/O module pairs can be in same chassis because non SIL 2 hardware is on a separate
network. For more information on how to wire field devices, see Figure 6 on page 18.
Figure 4 - Fail-safe ControlLogix ControlNet Configuration (Safety and Standard Connections on the Same Network)
ST 0 1 2 3 4 5 6 7 O
ST 0 1 2 3 4 5 6 7 O ST 0 1 2 3 4 5 6 7 O ST
ST
ST 000111222333444555666777OOO ST 0 1 2 3 4 5 6 7 O ST 0 1 2 3 4 5 6 7 O ST 0 1 2 3 4 5 6 7 O
ST 8 9 10 1112131415 K
ST 8 9 10 11121314 15 K ST 8 9 10 11121314 15 K ST
ST
ST 888999
10
10
10
11121314
11121314
11121314
15
15KKK
15 ST 8 9 10 11121314 15 K ST 8 9 10 11121314 15 K ST 8 9 10 11121314 15 K
DIAGNOSTIC
DIAGNOSTIC DIAGNOSTIC DIAGNOSTIC
DIAGNOSTIC
DIAGNOSTIC DIAGNOSTIC DIAGNOSTIC DIAGNOSTIC
I O M
C C C N U O
N N N T N
2 2 2
R R 1 2 I
A A N
ControlNet
Standard Communication
Remote I/O Chassis
DC INTPUT DC
DC
DCOUTPUT
OUTPUT
OUTPUT DC INTPUT
ST 0 1 2 3 4 5 6 7 O ST
ST
ST 000111222333444555666777OOO ST 0 1 2 3 4 5 6 7 O
ST 8 9 10 11121314 15 K ST
ST
ST 888999
10
10
10
11121314
11121314
11121314
15
15KKK
15 ST 8 9 10 11121314 15 K
DIAGNOSTIC DIAGNOSTIC
DIAGNOSTIC
DIAGNOSTIC DIAGNOSTIC
I O
N U
C
N T
2
1 2
B B
Dual networks are required because one of the two networks includes non-SIL 2 hardware.
The 1756 SIL 2 I/O module pairs must be split over two networks. For more information on
how to wire field devices, see Figure 6 on page 18.
Figure 5 - Fail-safe ControlLogix ControlNet Configuration with Non-SIL 2 Communication (Safety and Standard Connections on Separate Networks)
ST 0 1 2 3 4 5 6 7 O ST 0 1 2 3 4 5 6 7 O ST 0 1 2 3 4 5 6 7 O ST 0 1 2 3 4 5 6 7 O ST
ST
ST 000111222333444555666777OOO ST 0 1 2 3 4 5 6 7 O ST 0 1 2 3 4 5 6 7 O
I I D O
N N I U
E C C A
N T
N N G
2 2 2 O
1 1 2
T A B 2 B
A
Standard Communication
ControlNet
ST 0 1 2 3 4 5 6 7 O ST 0 1 2 3 4 5 6 7 O ST 0 1 2 3 4 5 6 7 O ST 0 1 2 3 4 5 6 7 O ST
ST
ST 000111222333444555666777OOO ST 0 1 2 3 4 5 6 7 O
ST 8 9 10 1112131415 K ST 8 9 10 1112131415 K ST 8 9 10 1112131415 K ST 8 9 10 1112131415 K ST
ST
ST 88899910
10
10
1112131415
1112131415KKK
1112131415 ST 8 9 10 1112131415 K
I I O M O
N N U O U
C
N T N T
2
3 3 4 I 4
A B A N B
ControlNet
1756 SIL 2 I/O module pairs can be in the same chassis because the non-SIL 2
hardware is on a separate network. For more information on how to wire field
devices, see Figure 6 on page 18.
Figure 6 - Fail-safe ControlLogix EtherNet/IP Configuration: Single DLR Loop for Safety and Standard Communication
ST 0 1 2 3 4 5 6 7 O ST 0 1 2 3 4 5 6 7 O ST 0 1 2 3 4 5 6 7 O ST 0 1 2 3 4 5 6 7 O ST
ST
ST 000111222333444555666777OOO ST
ST 00 11 22 33 44 55 66 77OO ST 0 1 2 3 4 5 6 7 O
ST 8 9 10 11121314 15 K ST 8 9 10 11121314 15 K ST 8 9 10 11121314 15 K ST 8 9 10 1112131415 K ST
ST
ST 888999
10
10
10
11121314
11121314
11121314
15
15KKK
15 ST
ST 88 9910
1011121314 15KK
1112131415 ST 8 9 10 11121314 15 K
I O O
N U U
E EE E T T
N N
N N
2 22 2
TT 1 2 3
T T
R R A A A
R R
Standard EtherNet/IP +V
Communication DLR
Relay +V
Input Device
ST 0 1 2 3 4 5 6 7 O ST 0 1 2 3 4 5 6 7 O ST
ST 00
ST 0 11
1 22
2 33
3 44
4 55
5 66
6 77
7O ST
ST 00 11 22 33 44 55 66 77OO ST 0 1 2 3 4 5 6 7 O
O
O
ST 8 9 10 11121314 15 K ST 8 9 10 11121314 15 K ST
ST 8 99
ST 88 9 10
1011121314
10 1112131415
11121314 15
K
15 KK ST
ST 88 9910
1011121314 15KK
1112131415 ST 8 9 10 11121314 15 K
I I O M
N S U O EtherNet/IP
Remote I/O Chassis O T N E
L N
1 O 3 I 2
B 2 B N T
B R
Actuator
Actuator
Standard
Communication DLR
DLR mixes SIL 2 and non-SIL 2 hardware. Independent paths are required to the SIL 2 I/O module pairs. The
1756 adapters and I/O module pairs can be placed into one chassis or split among two. Splitting them over
two chassis is shown.
Unused channels on a SIL 2 input module pair can be used as the monitoring input. There is no need for the
monitoring input to be wired to both input modules in a SIL 2 module pair. A separate monitoring input
module is not required.
Figure 7 - Fail-safe ControlLogix EtherNet/IP Configuration with FLEX I/O Modules: Single DLR Loop for Safety and Standard Communication
Controller Chassis
Logix5570 EtherNet/IP™ EtherNet/IP™
EtherNet/IP™
EtherNet/IP™ DC OUTPUT
ST 0 1 2 3 4 5 6 7 O
ST 8 9 10 1112131415 K
DIAGNOSTIC
E EE
N N
N
2 22
T TT 1794-AENTR
R RR MOD IN 1A OUT 2A OUT 3A
Standard LINK 1 LINK 2
REDUNDANY MEDIA
ADAPTER
1794-AENTR
Communication
DLR +V
EtherNet/IP
Input Relay +V
Device
1794-AENTR
1794-IOW8
Standard EtherNet/IP
Communication
DLR
Actuator Actuator
DLR mixes SIL 2 and non-SIL2 hardware. Independent paths are required to the SIL 2 I/O
module pairs. FLEX SIL 2 I/O module pairs must always be split over different nodes.
Unused channels on a SIL 2 input module pair can be used as the monitoring input. There is
no need for the monitoring input to be wired to both input modules in a SIL 2 module pair. A
separate monitoring input module is not required.
IMPORTANT As shown in Figure 6 and Figure 7, standard devices can reside within an EtherNet/IP™ SIL 2 subnet provided the
following requirements are met:
• The EtherNet/IP™ subnet topology must be DLR.
• The ControlLogix chassis must have two 1756-EN2TR modules.
• Independent connection paths must be established for channels A and B I/O through each ControlLogix chassis bridge.
• Channel A and Channel B I/O must reside in separate chassis or connected to separate adapters.
• Direct Internet connectivity must be limited to EtherNet/IP bridges listed in Appendix B of this manual.
Direct Internet connections via other standard devices are not allowed.
Figure 8 - Fail-safe ControlLogix Configuration with FLEX I/O Modules on the ControlNet Network
HMI
Programming Software
For Diagnostics and Visualization
For SIL applications, a programming
(see special instructions in Chapter 9 for
terminal is not normally connected.
writing to safety-related controllers in the
safety loop).
Plant-wide Ethernet/Serial
Overall Safety Loop
ST 0 1 2 3 4 5 6 7 O
ST 8 9 10 1112131415 K
E
N C
B N
T 2
R
To other safety-related ControlLogix or FLEX
ControlNet
I/O remote I/O chassis.
1794-IOW8
1794-ACN15 IN 1B OUT 2B
ControlNet
Non-SIL 2 hardware is on separate networks. FLEX I/O module pairs must always be split over
different nodes. For more information on how to wire field devices, see Figure 7 on page 19
Figure 9 - Fail-safe ControlLogix Configuration with FLEX I/O Modules the EtherNet/IP Network
HMI
Programming Software
For Diagnostics and Visualization
For SIL applications, a programming
(see special instructions in Chapter for
terminal is not normally connected.
writing to safety-related controllers in the
safety loop).
Plant-wide Ethernet/Serial
ST 0 1 2 3 4 5 6 7 O
1794 FLEX I/O
ST 8 9 10 1112131415 K
DIAGNOSTIC
E EE LINK 1 LINK 2
REDUNDANY MEDIA
N N
ADAPTER
N
1794-AENTR
B 22
T TT
RR
EtherNet/IP
1794-AENTR
1794-IOW8
MOD IN 1B OUT 2B
LINK 1 LINK 2
REDUNDANY MEDIA
ADAPTER
1794-AENTR
EtherNet/IP
Non-SIL 2 hardware is on separate networks. FLEX I/O module pairs must always be split over
different nodes. For more information on how to wire field devices, see Figure 7 on page 19.
Figure 10 shows a typical duplex SIL loop. The figure also shows the following:
• Overall safety loop
• ControlLogix portion of the overall safety loop
• How other devices (for example, HMI) connect to the loop, while
operating outside the loop
Plant-wide Ethernet/Serial
ST 0 1 2 3 4 5 6 7 O ST 0 1 2 3 4 5 6 7 O
ST 0 1 2 3 4 5 6 7 O ST 0 1 2 3 4 5 6 7 O ST 0 1 2 3 4 5 6 7 O ST
ST
ST 000111222333444555666777OOO ST 0 1 2 3 4 5 6 7 O ST 0 1 2 3 4 5 6 7 O
ST 8 9 10 1112131415 K ST 8 9 10 11121314 15 K
ST 8 9 10 11121314 15 K ST 8 9 10 11121314 15 K ST 8 9 10 1112131415 K ST
ST
ST 888999
10
10
10
1112131415
1112131415KKK
1112131415 ST 8 9 10 11121314 15 K ST 8 9 10 1112131415 K
PRI COM OK
DIAGNOSTIC DIAGNOSTIC
DIAGNOSTIC DIAGNOSTIC DIAGNOSTIC DIAGNOSTIC
DIAGNOSTIC
DIAGNOSTIC DIAGNOSTIC DIAGNOSTIC
I I D O
N N I U
E C C R A C
N N N T
M G N
2 2 2 O 2
T 1 1 2
A B 2 B
A
ControlNet ControlNet
ST 0 1 2 3 4 5 6 7 O ST 0 1 2 3 4 5 6 7 O ST 0 1 2 3 4 5 6 7 O ST
ST
ST 000111222333444555666777OOO ST 0 1 2 3 4 5 6 7 O ST 0 1 2 3 4 5 6 7 O ST 0 1 2 3 4 5 6 7 O ST 0 1 2 3 4 5 6 7 O
ST 8 9 10 1112131415 K ST 8 9 10 11121314 15 K ST 8 9 10 11121314 15 K ST
ST
ST 888999
10
10
10
1112131415
1112131415KKK
1112131415 ST 8 9 10 11121314 15 K ST 8 9 10 1112131415 K ST 8 9 10 11121314 15 K ST 8 9 10 11121314 15 K
PRI COM OK
DIAGNOSTIC DIAGNOSTIC DIAGNOSTIC DIAGNOSTIC
DIAGNOSTIC
DIAGNOSTIC DIAGNOSTIC DIAGNOSTIC DIAGNOSTIC DIAGNOSTIC
O M O I I
U O U N N
E C C R C
T N T
N N N M N
2 2 2 2
3 I 3 4 4
T N
A B A B
ControlNet ControlNet
1756 SIL 2 I/O module pairs can be in same chassis because non-SIL 2 hardware
is on separate networks. SIL 2 I/O modules in the safety loop must meet the
requirements that are specified in Chapter 5, ControlLogix I/O Modules.
For more information on how to wire field devices, see Figure 6 on page 18.
IMPORTANT You can also access a remote I/O chassis via an EtherNet/IP network if
you use ControlLogix Enhanced Redundancy System, Revision 20.54 or
later.
ST 0 1 2 3 4 5 6 7 O ST 0 1 2 3 4 5 6 7 O
ST 0 1 2 3 4 5 6 7 O ST 0 1 2 3 4 5 6 7 O
ST 8 9 10 1112131415 K ST 8 9 10 1112131415 K
ST 8 9 10 1112131415 K ST 8 9 10 1112131415 K
PRI COM OK
PRI COM OK
DIAGNOSTIC DIAGNOSTIC
DIAGNOSTIC DIAGNOSTIC
E E R E E R
N N M N N M
2 2 2 2
T T T T
R R R R
1783-ETAP1F
MOD
LINK 1
LINK 2
DEVICE
PORT
1783-ETAP1F
MOD
LINK 1
LINK 2
DEVICE
PORT
Fiber Fiber
I/O Chassis A1
1 2
(front) (rear)
I/O Chassis B1 1 2
(front) (rear)
1783-ETAP2F I M
LINK 2
I O I
DEVICE
PORT
N U N S O
1783-ETAP E E O
N T N
1 3 1783-ETAP1F MOD
N 1 L
2
LINK 1
2
LINK 2
A 3 I
DEVICE
A B
PORT
T 1783-ETAP2F T B
1
(front)
2
(rear)
R N
R
1 2
I/O Chassis A2
MOD (front) (rear)
ST 0 1 2 3 4 5 6 7 O ST 0 1 2 3 4 5 6 7 O ST 0 1 2 3 4 5 6 7 O
ST 0 1 2 3 4 5 6 7 O ST 0 1 2 3 4 5 6 7 O ST 0 1 2 3 4 5 6 7 O
ST 8 9 10 1112131415 K ST 8 9 10 1112131415 K ST 8 9 10 1112131415 K
ST 8 9 10 1112131415 K ST 8 9 10 1112131415 K ST 8 9 10 1112131415 K
I O I I M
N U N S O
E E
1 2
O N
(front) (rear)
T
MOD
N LINK 1
N L
1783-ETAP 2
LINK 2
2 4
DEVICE
2
PORT
2 4 I
T A A B
T B N
MOD
R R
LINK 1
LINK 2
DEVICE
PORT
1783-ETAP 1
(front)
2
(rear)
1 2
Note: All SIL 2 guidelines for 1756 or FLEX I/O modules remain the same.
(front) (rear)
ST 0 1 2 3 4 5 6 7 O ST 0 1 2 3 4 5 6 7 O
ST 0 1 2 3 4 5 6 7 O ST 0 1 2 3 4 5 6 7 O
ST 8 9 10 1112131415 K ST 8 9 10 1112131415 K
ST 8 9 10 1112131415 K ST 8 9 10 1112131415 K
PRI COM OK
PRI COM OK
DIAGNOSTIC DIAGNOSTIC
DIAGNOSTIC DIAGNOSTIC
E E R E E R
N N M N N M
2 2 2 2
T T T T
R R R R
Chassis 1A Chassis 1B
EtherNet/IP™ DC INTPUT DC OUTPUT DC INTPUT EtherNet/IP™ DC INTPUT DC OUTPUT DC INTPUT
ST 0 1 2 3 4 5 6 7 O ST 0 1 2 3 4 5 6 7 O ST 0 1 2 3 4 5 6 7 O
ST 0 1 2 3 4 5 6 7 O ST 0 1 2 3 4 5 6 7 O ST 0 1 2 3 4 5 6 7 O
ST 8 9 10 1112131415 K ST 8 9 10 1112131415 K ST 8 9 10 1112131415 K
ST 8 9 10 1112131415 K ST 8 9 10 1112131415 K ST 8 9 10 1112131415 K
I O I I M
N U N S O
E E O N
N T N
1 3 1 L
2 2 3 I
T A A B
T B N
R R
Chassis 2A Chassis 2B
EtherNet/IP™ DC INTPUT DC OUTPUT DC INTPUT EtherNet/IP™ DC INTPUT DC INTPUT
DC OUTPUT
ST 0 1 2 3 4 5 6 7 O ST 0 1 2 3 4 5 6 7 O ST 0 1 2 3 4 5 6 7 O ST 0 1 2 3 4 5 6 7 O ST 0 1 2 3 4 5 6 7 O ST 0 1 2 3 4 5 6 7 O
ST 8 9 10 1112131415 K ST 8 9 10 1112131415 K ST 8 9 10 1112131415 K ST 8 9 10 1112131415 K ST 8 9 10 1112131415 K ST 8 9 10 1112131415 K
I O I I M
N U N S O
E E O N
N T N
2 4 2 L
2 2 4 I
T A A B
T B N
R R
ST 0 1 2 3 4 5 6 7 O ST 0 1 2 3 4 5 6 7 O
ST 0 1 2 3 4 5 6 7 O ST 0 1 2 3 4 5 6 7 O
ST 8 9 10 1112131415 K ST 8 9 10 1112131415 K
ST 8 9 10 1112131415 K ST 8 9 10 1112131415 K
PRI COM OK
DIAGNOSTIC DIAGNOSTIC PRI COM OK
DIAGNOSTIC DIAGNOSTIC
E E R E E R
N N M N N M
2 2 2 2
T T T T
R R R R
ST 0 1 2 3 4 5 6 7 O ST 0 1 2 3 4 5 6 7 O ST 0 1 2 3 4 5 6 7 O ST 0 1 2 3 4 5 6 7 O ST 0 1 2 3 4 5 6 7 O ST 0 1 2 3 4 5 6 7 O ST 0 1 2 3 4 5 6 7 O ST 0 1 2 3 4 5 6 7 O ST 0 1 2 3 4 5 6 7 O ST 0 1 2 3 4 5 6 7 O ST 0 1 2 3 4 5 6 7 O ST 0 1 2 3 4 5 6 7 O
ST 8 9 10 1112131415 K ST 8 9 10 1112131415 K ST 8 9 10 1112131415 K ST 8 9 10 1112131415 K ST 8 9 10 1112131415 K ST 8 9 10 1112131415 K ST 8 9 10 1112131415 K ST 8 9 10 1112131415 K ST 8 9 10 1112131415 K ST 8 9 10 1112131415 K ST 8 9 10 1112131415 K ST 8 9 10 1112131415 K
DIAGNOSTIC DIAGNOSTIC DIAGNOSTIC DIAGNOSTIC DIAGNOSTIC DIAGNOSTIC DIAGNOSTIC DIAGNOSTIC DIAGNOSTIC DIAGNOSTIC DIAGNOSTIC DIAGNOSTIC
I O I O I O I O
B B F U B B F U
E 3 1 1 T E 3 1 1 T
N 2 6 6 2 N 6 6 2
2
2 D 3 2 D 3
1 1
T 2 A T 2 B
A B
R A R B
Analog Input Termination Board Digital Input Termination Board Digital Output Termination Board
For more information about this SIL 2 application solution, see the
ControlLogix SIL 2 System Configuration Using SIL 2 Add-On Instructions,
publication 1756-AT012.This publication explains how to configure a
SIL 2-certified system by using Add-On Instructions and hardware
termination boards.
ST 0 1 2 3 4 5 6 7 O ST 0 1 2 3 4 5 6 7 O
ST 8 9 10 1112131415 K ST 8 9 10 1112131415 K ST 0 1 2 3 4 5 6 7 O ST 0 1 2 3 4 5 6 7 O
ST 8 9 10 1112131415 K ST 8 9 10 1112131415 K
PRI COM OK
DIAGNOSTIC DIAGNOSTIC PRI COM OK
DIAGNOSTIC DIAGNOSTIC
C E R E R
N C
N M
N N M
2 2 2
T 2
R R T
R R
O
DIAGNOSTIC DIAGNOSTIC DIAGNOSTIC DIAGNOSTIC
I I O I O I O
B B F U B B F U
C 3 1 1 T 3 1 1 T
C
N 2 6 6 2 2 6 6 2
N
2 1 D 3 2 1 D 3
R A 2 A R B 2 B
A B
The duplex system configuration uses safety and programming principles that
are described in this manual, and programming and hardware that is
described in the application technique manuals.
Proof Tests IEC 61508 requires that you perform various proof tests of the equipment that
is used in the system. Proof tests are performed at user-defined times (for
example, proof test intervals can be once a year, once every 2 years or whatever
time frame is appropriate based on the SIL verification calculation) and could
include some of the following tests:
• Test all safety application-fault routines to verify that process parameters
are monitored properly and the system reacts properly when a fault
condition arises.
• Test all digital input or output channels to verify that they are not stuck
in the ON or OFF state.
- Manually cycle inputs to make sure that all inputs are operational and
not stuck in the ON state.
- Manually test outputs that do not support runtime pulse testing.
- You can automatically perform proof tests by switching ground open
on input modules and check to make sure that all input points go to
zero (turn OFF.).
• The relays in the redundant power supplies must be tested to make sure
that they are not stuck in the closed state.
• Calibrate analog input and output modules to verify that accurate data is
obtained from and used on the modules.
IMPORTANT Each specific application has its own time frame for the proof test
interval.
The switchover can be monitored so that the system notifies the user when it
has occurred. In this case (that is, when a switchover takes place), we
recommend that you replace the failed controller within the mean time to
restoration (MTTR) for your application.
If you are concerned about the availability of the secondary controller if the
primary controller fails, it is good engineering practice to implement a switchover
periodically (for example, once per proof test interval).
Reaction Times The response time of the system is defined as the amount of time it takes for a
change in an input condition to be recognized and processed by the
controller’s logic program, and then to initiate the appropriate output signal to
an actuator.
Each of the times listed is variably dependent on factors such as the type of I/O
module and instructions used in the logic program. For examples of how to
perform these calculations, see Appendix A, Reaction Times of the
ControlLogix System.
For more information on the available instructions and for a full description of
logic operation and execution, see the following publications:
• Logix 5000™ Controllers General Instruction Set Reference Manual,
publication 1756-RM003
• ControlLogix System User Manual, publication 1756-UM001
Reaction Times in The worst-case reaction time of a duplex system is different than a simplex
Redundancy Systems system. The redundancy system has a longer reaction time because of the
following:
• There are a series of crossloading operations that continuously occur
between the primary and secondary controllers. Crossloading fresh data
at the end of each program scan increases scan time.
IMPORTANT To avoid nuisance trips, you must account for the additional cross
checking time of a duplex system when setting the watchdog time.
Safety Watchdog Configure the properties of the SIL 2 safety task correctly for your application.
• Priority: must be the highest-priority task in the application (lowest
number)
• Watchdog: the value that is entered for the SIL 2 safety task must be large
enough for all logic in the task to be scanned
If the task execution time exceeds the watchdog time, a major fault occurs on
the controller. You must monitor the watchdog and program the system
outputs to transition to the safe state (typically the OFF state) in the event of a
major fault occurring on the controller. For more information on faults, see
Chapter 8, Faults in the ControlLogix System.
For more information about setting the watchdog, see the ControlLogix
System User Manual, publication 1756-UM001.
Safety Certifications and Diagnostic hardware and firmware functions, and how you apply
Compliance ControlLogix components, enable the system to achieve CL SIL 2 compliance.
ControlLogix products that are referenced in this manual can have safety
certifications and the SIL certification. If a product has achieved agency
certification, the product label is not necessarily marked as certified. To view
safety certifications for products, go to http://www.ab.com and click the
Product Certifications link or on the certificate’s revision release list.
Notes:
The diagnostic methods and techniques that are used in the ControlLogix®
platform let you configure and program ControlLogix controllers to perform
checks on the total system. The checks include configuration, wiring, and
performance, monitoring input sensors and output devices. Timestamping of
I/O and diagnostic data also aid in diagnostics.
Module Fault Reporting Every module in the system is ‘owned’ by one controller. Multiple controllers
can share data, and consume data from non-owned modules. When a
controller ‘owns’ an I/O module, that controller stores the module’s
configuration data, which you define; this data dictates how the module
behaves in the system. Inherent in this configuration and ownership is the
establishment of a ‘heartbeat’ between the controller and module, which is
known as the requested packet interval (RPI).
The RPI defines a time interval in which the controller and I/O module must
communicate with each other. If, communication cannot be established or
maintained, for example, the I/O module has failed, the communication path
is unavailable, the system can be programmed to run specialized routines.
These specialized routines can determine whether the system can continue
functioning or whether the fault condition warrants a shutdown of the
application. For example, the system can be programmed to retrieve the fault
code of the failed module. It can also make a determination, which is based on
the type of fault, whether to continue operating.
The controller can monitor the health of I/O modules in the system. The
controller can take appropriate action that is based on the severity of a fault
condition and gives you complete control of the application. It is your
responsibility to establish the course of action appropriate to your safety
application.
Data Echo Communication Output data echo allows you to verify that the correct output module received
Check the ON/OFF command from the controller was received and that the module
attempts to execute the command to the field device.
When used with standard ControlLogix output modules, the data echo
validates the integrity of communication up to the system-side of the module,
but not to the field-side. When you use this feature with diagnostic output
modules, you can verify the integrity from the controller to the output terminal
on the module.
When using non-diagnostic output modules, you must verify the ON and OFF
state. This verification must be accomplished by monitoring the output
command from the non-diagnostic output module in an input module or
validation by alternative methods. Approve all methods according to IEC
61508. A separate input module is required for a non-diagnostic output
module.
Actuator
Pulse Test Discrete diagnostic output modules contain a feature called a pulse test. A
pulse test can verify the output circuit functionality without actually changing
the state of the actuator connected to the output. A short-duration pulse is
directed to a particular output on the module. The output circuitry
momentarily changes its state long enough to verify that it can change state on
demand. The test pulse is fast (milliseconds), and typically does not affect
actuators. Some actuators can have electronic front ends and can detect these
fast pulses. You can disable pulse testing, if necessary.
Software The location, ownership, and configuration of I/O modules and controllers is
performed by using RSLogix 5000® software or the Studio 5000 Logix
Designer® application. Use the software to create, test, and debug application
logic.
When using the programming software, you must remember these points:
• During normal control program (controller in Run mode):
- Disconnect the programming terminal.
- Set the keyswitch to the RUN position.
- Remove the controller key from the keyswitch.
• Authorized personnel can change an application program, but only by
using one of the processes that are described in Changing Your
Application Program on page 88.
Communication Several communication options are available for connecting with the
ControlLogix SIL 2 system and for the exchange of data within the SIL 2
system.
Communication Ports
A built-in USB port is available for program upload and download on 1756-L7x
controllers.
ControlNet Network
IMPORTANT In SIL 2 applications, all I/O and produce/consume tags that are
associated with safety data must use scheduled connections on the
ControlNet network.
EtherNet/IP Network
Electronic Keying of Modules If a module in your SIL 2-certified ControlLogix system is replaced, Exact
in SIL 2 Applications Match keying is recommended.
Exact Match keying requires all keying attributes of the physical module and
the module that is created in the software to match precisely before
establishing communication. The keying attributes are Vendor, Product Type,
Product Code (catalog number), Major Revision, and Minor Revision.
If any attribute does not match precisely, I/O communication is not permitted
with the module or with modules connected through it, as in the case of a
communication module.
For more information about electronic keying, see the ControlLogix Digital
I/O Modules User Manual, publication 1756-UM058.
Notes:
Operating Modes
The controller performs power-up and runtime functional tests. The tests are
used with user-supplied application programs to verify proper controller
operation.
RUN FORCE SD OK
REM PR
RUN OG
1756-L6x 1756-L7x
ControlLogix Chassis The ControlLogix 1756-Axx chassis provide the physical connections between
controllers and I/O modules. The chassis is passive and is not relevant to the
safety discussion because any physical failure would be unlikely under normal
environmental conditions and would be manifested and detected as a failure
within one or more of the active components.
ControlLogix Power Supplies ControlLogix power supplies are certified for use in SIL 2 applications. No
extra configuration or wiring is required for SIL 2 operation of the
ControlLogix power supplies. If an anomaly occurs in the supplied voltages,
the power supply immediately shuts down. For this reason, the power supply is
not part of the safety calculation.
IMPORTANT If you are using any of the 1756-Px75 (non-redundant) power supplies,
with a 1756-L6x/B or 1756-L7x/B controller, you must use the Series B
version of the power supply, that is, 1756-Px75/B power supplies.
The power supplies share the current load that the chassis requires and an
internal solid-state relay that can annunciate a fault. Upon detection of a
failure in one supply, the other redundant power supply automatically
assumes the full current load that the chassis requires without disruption to
installed devices.
For more information about how to install ControlLogix chassis and power
supplies, see the publications that are listed in Additional Resources on page 8.
Notes:
ControlNet Modules and ControlNet modules provide communication between any nodes that are
Components properly scheduled on the ControlNet network.
IMPORTANT In SIL 2 applications, all I/O and produce/consume tags that are
associated with safety data must use scheduled connections on the
ControlNet network.
ControlNet Cabling
For remote racks, one RG6 coax cable is required for ControlNet
communication. Although it is not a requirement to use redundant media with
the 1756-CNBR or 1756-CN2R modules, it does provide higher system
reliability. Redundant media is not required for SIL 2 operation.
ControlNet Repeater
The following ControlNet repeater modules are approved for use in safety
applications up to and including SIL 2:
• 1786-RPCD, ControlNet Hub Repeater Module
• 1786-RPFS, Short-distance Fiber Repeater Module
• 1786-RPFM, Medium-distance Fiber Repeater Module
• 1786-RPFRL, Long-distance Fiber Repeater Module
• 1786-RPFRXL, Extra-long-distance Fiber Repeater Module
Use of the 1786-RPA adapter is required with the repeater modules listed.
All communication over the passive ControlNet media occurs via CIP™. CIP
verifies that at least one valid packet is seen during the greater of either 100 ms
or 4 times the requested packet interval (RPI). If a valid packet is not seen
during this period, data transitions to the safe state.
See the examples in Figure 5 on page 17, Figure 6 on page 18, and Figure 11 on
page 23.
DeviceNet Scanner The 1756-DNB scanner connects the controller to devices on a DeviceNet
network. You can use the 1756-DNB module to communicate only nonsafety
data to devices outside of the safety loop.
Data Highway Plus - Remote The 1756-DHRIO module supports both Data Highway Plus and the
I/O Module (1756-DHRIO) Remote I/O network of communication. You can use the 1756-DHRIO module
to communicate only nonsafety data to devices outside of the safety loop. For
example, it can be used to communicate alarms to the Distributed Control
System (DCS).
SynchLink Module The SynchLink module (catalog number 1756-SYNCH) is used for CST time
propagation between multiple chassis for event recording. The module can be
used only outside of the safety loop. It must not be used for any safety-related
activity in a SIL 2-certified ControlLogix system.
General Requirements for Follow these requirements when using SIL 2-certified communication
Communication Networks modules:
• When installing ControlLogix communication modules, carefully follow
the information that is provided in the installation instructions.
• DH+™ can be used for communication to Human-to-Machine Interfaces
(HMI) and for communicating with the nonsafety portion of the system.
For more information on how to use HMI, see Chapter 9, Use of Human-
to-Machine Interfaces on page 95.
• For controllers that are not part of the SIL 2 safety function, use listen-
only connections to monitor SIL 2 I/O modules.
• You must not use the Quick Connect feature when using an Ethernet
communication for SIL 2 safety I/O.
• Only SIL 2 devices or other devices that provide non-interference write to
SIL 2 controllers. The only exception is the use of HMI devices. For more
information on how to use HMI in the safety loop, see Chapter 9, Use of
Human-to-Machine Interfaces on page 95.
Additional Resources This table lists additional resources specific to the ControlLogix
communication modules.
IMPORTANT The programming information and examples in this chapter are provided to illustrate diagnostic and other
logic-related principles that must be demonstrated in SIL 2 application programs.
• The principles and logic that is shown in this chapter can be encased in Add-On Instructions for easier use.
• The wiring diagrams are provided to illustrate SIL 2 concepts. For wiring information, see the I/O module
users manual listings in Additional Resources on page 8.
• If you are using a duplex configuration and certain I/O termination boards, the programming that is
explained in this chapter is available in Add-On Instructions. These Add-On Instructions are certified by TÜV.
See the ControlLogix SIL 2 System Configuration Using SIL 2 Add-On Instructions, publication 1756-AT012.
Overview of ControlLogix At the most basic level, there are two types of SIL 2-certified ControlLogix® I/O
I/O Modules modules:
• Digital I/O modules
• Analog I/O modules
With each type, however, there are differences between specific modules.
Because the differences propagate to varying levels in each module type, a
graphical representation can best provide an overview of the many
SIL 2-certified ControlLogix I/O modules.
The 1756-IF8I provides the current and voltage input option, the 1756-IRT8I
covers the RTD and Thermocouple temperature options while the 1756-OF8I
covers current and voltage outputs. The 8-channel modules can emulate the
6-channel modules and are SIL 1, Systematic Capability 2 type certified.
IMPORTANT: Some catalog numbers have a K suffix that indicates a version of the product that has conformal coating. These K versions have the same SIL 2
certification as the non-K versions. For more information on which products have conformal coating go to: http://ab.com.rockwellautomation.com/
For SIL 2 compliance when installing ControlLogix I/O modules, follow the
procedures that are provided in the installation instructions. For a full list of
installation instructions for SIL 2-certified modules, see Appendix B.
Using 1756 Digital To achieve SIL 2, two digital input modules must be used, with field sensors
Input Modules wired to channels on each module. The software must compare the two
channels before reconciling the data.
Regardless of the type of ControlLogix input module that is used, you must
follow these general application requirements when applying these modules in
a SIL 2 application:
• Ownership – The same controller must own both modules.
• Direct connection – Always use a direct connection with any SIL 2 CL
modules. You must not use rack-optimized connections in a SIL 2
application.
• Separate input points – Wire sensors to separate input points on two
separate modules. The use of two digital input modules is required,
regardless of the number of field sensors.
• Field device testing – Test field devices by cycling them. The closer you
can get to the device being monitored to perform the test, the more
comprehensive the test is.
• Proof tests – Periodically perform a system validation test. Manually or
automatically test all inputs to make sure that they are operational and
not stuck in the ON or OFF state. Inputs must be cycled from ON to OFF
or OFF to ON. For more information, see Proof Tests on page 27.
This diagram shows two examples of wiring digital inputs. In either case, the
type of sensors being used determines whether the use of 1 or 2 sensors is
appropriate to fulfill SIL 2 requirements.
Input A2 Input B2
Sensor
43366
Actuator
The user program must also contain rungs to annunciate a fault in the event of
a sustained miscompare between two points.
Timer
Timer Done
Fault
Fault
Alarm to Operator
Using 1756 Digital ControlLogix digital output modules are divided into two categories:
Output Modules • Diagnostic output modules
• Standard output modules
Wiring the two types of digital output modules differs, depending on your
application requirements (these wiring methods are explained in detail in later
sections). However, regardless of the type of ControlLogix output module
used, you must follow these general application requirements when applying
these modules in a SIL 2 application:
• Proof tests - Periodically perform a system validation test. Manually or
automatically test all outputs to make sure that they are operational and
not stuck in the ON or OFF state. Outputs must be cycled from ON to OFF
or OFF to ON. For more information, see Proof Tests on page 27.
• Examination of output data echoes signal in application logic – The
application logic must examine the Data Echo value that is associated
with each output point to make sure that the requested ON/OFF
command from the controller was received and acted upon by the
module.
Actuator
Timer
Fault
Secondary
Output
Timer Done
Fault
Fault
Alarm to Operator
• Test outputs at specific times to make sure that they are operating
properly. The method and frequency of testing is determined by the
requirements of the safety application. For more information on how to
test diagnostic module outputs, see page 50. For more information on
how to test standard module outputs, see page 51.
• For typical emergency shutdown (ESD) application outputs must be
configured to de-energize: When configuring any ControlLogix output
module, each output must be configured to de-energize in the event of a
fault and in the event of the controller going into Program mode. For
exceptions to the typical ESD applications, see Chapter 1, SIL Policy on
page 9.
• When wiring two digital output modules in series so that one can break
source voltage (as shown in Figure 26 on page 53), one controller must
own both modules.
For more information on performing the pulse test, see the ControlLogix
Digital I/O Modules User Manual, publication 1756-UM058.
Actuator
Timer
Fault
Secondary
Output
Timer Done
Fault
Fault
Alarm to
Operator
When using standard (non-diagnostic) output modules, you must wire each
output to its field device and also to a system input to monitor the
performance. To verify output performance, use one of these methods:
• Write logic to test the ability of the output to turn ON and OFF at
power-up.
• At the proof test interval, force the output ON and OFF and use a
voltmeter to verify output performance.
For limited high demand applications, test the output modules (that is, you
turn the outputs ON and OFF to verify proper operation) once every 8 hours.
High demand applications are limited to 10 demands per year for ControlLogix
SIL 2 systems.
Actuator
Fault
Secondary
Output
Timer Done
Fault
Fault
Alarm to
Operator
You can also wire two standard outputs in series to critical actuators. If a
failure is detected, the outputs from each of the output modules must be set to
OFF to make sure that the field devices de-energize. Figure 26 shows how to
wire two isolated, standard outputs in series to critical actuators.
43364
Using 1756 Analog There are a number of general application considerations that you must make
Input Modules when using analog input modules in a SIL 2 application. The following section
describes those considerations specific to the use of analog input modules.
To achieve SIL 2, two analog input modules are required. Field sensors must be
wired to channels on each module and compared within a deadband. Whether
one or two field sensors are required is dependent on the Probability of Failure
on Demand (PFD) value of the sensor.
Calibrate Inputs
When programming the SIL 2 system, verify that your program examines the
appropriate module fault, channel fault, and channel status bits and responds
by initiating the appropriate fault routine.
When wiring sensors to two input channels on different modules, the values
from those channels must be compared to each other within the program for
concurrence within an acceptable range for the application, before an output is
actuated. Any miscompare between the two inputs outside the programmed
acceptable range must be annunciated as a fault.
Timer
LIM
Low Limit
Inputs OK
Input 2
High Limit
Timer Done
Analog Inputs
Faulted
Alarm to Operator
Configure Modules
When using identical modules, configure the modules identically, that is, by
using the same RPI, filter values, and so on.
When using different modules for improved diversity, make sure the module’s
scaling of data does not introduce error or fault conditions.
The wiring diagrams that are shown in this section apply to applications that
require two transmitters. The type of transmitter along with the application
requirements determine whether one or two transmitters are required.
Good design practice dictates that each of the two transmitters must be wired
to input terminals on separate modules such that the channel values can be
validated by comparing the two within an acceptable range. Special
consideration must be given when you apply this technique, depending on the
type of module being used.
Figure 28 shows how to wire an analog input for use in Voltage mode.
(+)
Voltage
Transmitter B
(–)
43368
Figure 29 shows how to wire a SIL 2 transmitter to two analog input modules
configured for voltage mode.
Figure 30 and Figure 31 show how to wire an analog input for use in Current
mode.
Ch0 + Ch0 +
Current
Source A
Ch0 – Ch0 –
Current
Source B
43369
Figure 31 - ControlLogix Analog Input Module Wiring for Isolated Channels (in Current mode)
Ch0 + Ch0 +
SIL 2 Transmitter-Current
Output Source
Ch0 – Ch0 –
All configured for 0...5V operation. All configured for 0...5V operation.
Reference Voltages
Module B
DIP Switch for Sensor
Wiring
Precision 249
Resistor*
*4-20mA converted to 0-5Vdc
(1) See ControlLogix SIL 2 System Configuration Using RSLogix 5000® Subroutines, publication 1756-AT012 for more information.
Ch0 + Ch0 +
Thermocouple A
RTN RTN
Thermocouple B
43370
Ch0 A Ch0 A
RTD A
Ch0 B Ch0 B
RTN RTN
RTD B
43371
Using 1756 HART Analog The Highway Addressable Remote Transducer (HART) analog modules must
Input Modules be used according to the same considerations as other analog input modules.
Ch0 + Ch0 +
Sensor
Ch0 -
Ch0 -
Sensor
Using 1756 Analog Output There are a number of general application considerations that you must make
Modules when using analog output modules in a SIL 2 application. An analog output
module, along with an analog input module is required to monitor to achieve
SIL 2. The following sections describe those considerations specific to the use
of analog output modules.
Calibrate Outputs
Calibrate the analog output modules periodically, as their use and application
requires. ControlLogix I/O modules ship from the factory with a highly
accurate level of calibration. However, because each application is different,
you are responsible for making sure your ControlLogix I/O modules are
properly calibrated for your specific application.
When programming the SIL 2 system, verify that your program examines the
appropriate module fault, channel fault, and channel status bits and responds
by initiating the appropriate fault routine.
You must wire each analog output to an actuator and then back to an analog
input to monitor the performance of the output, as shown in Figure 37. The
application logic must examine the analog input (feedback value) associated
with each analog output to make sure that the output from the controller was
received correctly at the actuator. The analog output value must be compared
to the analog input that is monitoring the output to make sure that the value is
within an acceptable range for the application.
Timer
LIM
Low Limit
Outputs OK
Output Echo
High Limit
Fault
Secondary
Output
Timer Done
Outputs Faulted
Outputs Faulted
Alarm to Operator
In general, good design practice dictates that each analog output must be
wired to a separate input terminal to make sure that the output is functioning
properly.
Figure 37 shows how to wire the 1756-OF8 module for use in Voltage mode.
43377
Figure 38 shows how to wire the 1756-OF8 module for use in Current mode.
43376
Using 1756 HART Analog Use the Highway Addressable Remote Transducer (HART) analog modules
Output Modules according to the same considerations as other analog output modules. For an
illustration of how to wire the HART analog output modules, see Wiring the
HART Analog Output Modules on page 66.
Secondary
Output
Ch0+ Ch0+
Actuator
Ch0- Ch0-
Ch1+ This normally open relay is controlled by the status of the rest of the ControlLogix system.
If a short-circuit or fault occurs on the module, the relay can disconnect power to the
module. The module that is used to control this relay must follow SIL 2 output guidelines.
This module must also be considered during PFD analysis for each safety function.
Use a signal-grade relay using bifurcated or similar grade contacts. The relay can be
Ch1-
located in a position to remove power to an actuator, or can remove power to multiple
actuators depending on the granularity needed.
Overview of FLEX I/O There are two types of SIL 2-certified FLEX™ I/O modules:
Modules • Digital I/O modules
• Analog I/O modules
FLEX I/O modules are designed with inherent features that allow them to
comply with the requirements of the 61508 Standard. For example, the
modules all have a common backplane interface, execute power-up and
runtime diagnostics, and offer electronic keying.
Using 1794 Digital To achieve SIL 2, two digital input modules must be used, with field sensors
Input Modules wired to channels on each module. The two digital modules must be on
separate 1794 rails. Use the software to compare the two channels before you
reconcile the data.
Regardless of the type of FLEX I/O input module that is used, there are a
number of general application considerations that you must follow when
applying these modules in a SIL 2 application:
• Proof tests—Periodically a system validation test must be performed.
Manually, or automatically, test inputs to make sure that all inputs are
operational and not stuck in the ON or OFF state. Inputs must be cycled
from ON to OFF or OFF to ON.
• Configuration parameters (for example, RPI, filter values) must be
identical between the two modules.
• The same controller must own both modules.
• Monitor the network status bits for the associated module and make sure
that appropriate action is invoked via the application logic by these
status bits.
The wiring diagrams in Figure 40 show two methods of wiring the digital
input module. In either case, you must determine whether the use of 1 or 2
sensors is appropriate to fulfill SIL 2 requirements.
1794-IB16 1794-IB16
24VDC SINK INPUT 24VDC SINK INPUT
Input
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
1
SENSOR
COM
+24V
1
Note 1: Both sensors are monitoring the same safety application. SENSOR 43366
The user program must also contain rungs to annunciate a fault if there is a
sustained miscompare between two points.
Timer
Input A Input B
Timer preset in milliseconds to
compensate for filter time and
hardware delay differences.
Timer Done
Fault
Fault
Alarm to Operator
Using 1794 Digital To achieve SIL 2, the output module must be wired back to an input module for
Output Module monitoring.
Regardless of the type of FLEX I/O output module that is used, there are a
number of general application considerations that you must follow when
applying these modules in a SIL 2 application:
• Proof tests- Periodically a System Validation test must be performed.
Manually, or automatically, test outputs to make sure that all outputs are
operational and not stuck in the ON or OFF state. Outputs must be cycled
from ON to OFF or OFF to ON.
Figure 43 - Testing Outputs
Application Logic
Application Logic Output
Output Fault
Fault
Actuator
Actuator
Output Bit
Output Bit Monitoring Input
Monitoring Input
Timer
Timer
Output Bit
Output Bit Monitoring Input
Monitoring Input
Timerdone
Timer Done
Fault
Fault
Fault
Fault
Alarm
Alarmto Operator
to Operator
When using standard output modules, you must wire an output to an actuator
and then back to an input to monitor the performance of the output.
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
A
COM
24V DC
Output B
Actuator
43363
IMPORTANT: Other configurations are possible as long they are SIL 2 approved.
Install a relay in position A or B. This relay is controlled by another output in the ControlLogix/FLEX I/O system. If a short circuit or fault occurs on output modules, the relay can
disconnect power to the modules. An isolated relay output module (1794-OW8) can be used for this purpose when it is connected to a different 1794-ACN15 or 1794-ACNR15 ControlNet®
adapter module.
You can also wire a standard-digital output module in series with an isolated
relay output module in series with a critical actuator. If a failure is detected,
the output from both output modules must be set to OFF to make sure the
Output Loads de-energize.
See Figure 45 on page 71 for detailed information about how to wire an output
module with an isolated relay module.
Figure 45 - ControlLogix/FLEX I/O Standard Output Module Wiring with an Isolated Relay Module
Standard Digital Isolated Relay Output Standard Digital
Output Module Module Input Module
COM +24V Wire output point to
input point to verify the
24VDC SOURCE OUTPUT
1794-OB16
24VDC SOURCE OUTPUT
1794-OB16
correct state of the 24VDC SINK INPUT
1794-IB16
output.
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
COM
Output +24V
Output Actuator
43364
Note 1: An external relay can be replaced with an isolated relay module that is mounted in another FLEX I/O rail.
Using 1794 Analog To achieve SIL 2, two analog input modules are required. Field sensors must be
Input Modules wired to channels on each module and compared within a deadband. Whether
one or two field sensors are required is dependent on the Probability of Failure
on Demand (PFD) value of the sensor.
You must follow these general application considerations when applying these
modules in a SIL 2 application:
• Proof tests. Periodically a System Validation test must be performed.
Manually, or automatically, test inputs to make sure that all inputs are
operational. Vary the field signal levels over the full operating range to
make sure that the corresponding channel data varies accordingly.
• Calibrate inputs periodically, as necessary. FLEX I/O modules ship from
the factory with a highly accurate level of calibration. However, because
each application is different, you are responsible for making sure their
FLEX I/O modules are properly calibrated for their specific application.
Timer
LIM
Low Limit
Inputs OK
Input 2
High Limit
Timer Done
Inputs Faulted
Inputs Faulted
Alarm to Operator
The wiring diagrams in this section show two methods of wiring the analog
input module. In either case, you must determine whether the use of one or
two sensors is appropriate to fulfill SIL 2 requirements.
Input 1 Input 2
Input 1
SENSOR
COM
+24V
1
SENSOR
43366A
Note 1: Both sensors are monitoring the same safety application.
Along with following the Considerations When Using FLEX I/O Analog Input
Modules on page 71, make sure that you use the correct documentation to wire
the module.
1794-TB3 + - 1794-TB3
+ -
Voltage Voltage
Transmitter A Transmitter B
1794-TB3 + - 1794-TB3
+ -
Voltage Voltage
Transmitter A Transmitter B
Along with following the Considerations When Using FLEX I/O Analog Input
Modules on page 71, before wiring the module, consider the following
application guideline:
Place other devices in current loop. You can locate other devices in a current
loop of an input channel anywhere as long as the current source can provide
sufficient voltage to accommodate all voltage drops (each module input is 250
).
1794-TB3 1794-TB3
1794-TB3 1794-TB3
Along with following the Considerations When Using FLEX I/O Analog Input
Modules on page 71 and before wiring the module, consider the following
application guideline:
Thermocouple Thermocouple
1794-IT8 1794-IT8
Input Module Input Module
1794-TB3T 1794-TB3T
+ +
- -
Thermocouple/ Thermocouple/
RTD/mV 1794-IRT8 RTD/mV 1794-IRT8
Input Module Input Module
1794-TB3G 1794-TB3G
+ +
- -
Along with following the Considerations When Using FLEX I/O Analog Input
Modules on page 71 and before wiring the module, consider the following
application guideline:
1794-TB3T 1794-TB3T
3-wire RTD
Thermocouple/ Thermocouple/
RTD/mV RTD/mV
1794-IRT8 1794-IRT8
Input Module Input Module
1794-TB3G 1794-TB3G
4-wire RTD
Two-, three-, or four-wire RTDs can be used as applicable to the associated RTD input module.
Using 1794 Analog An analog output module, along with an analog input module for monitoring
Output Modules is required to achieve SIL 2.
Then you can measure output values on multiple channels and compare
those values to acceptable values within the tolerance band. Based on the
differences in the comparison, you could then determine whether
recalibration is necessary.
The OK bit precondition for the output is a Timer run that is preset to
accommodate an acceptable fault response time, any communication
filtering, or output, and lags in the system. If the monitoring input value
and the Output Feedback miscompare are longer than the preset value, a
fault is registered with a corresponding alarm.
Rockwell Automation Publication 1756-RM001Q-EN-P - August 2021 77
Chapter 6 FLEX I/O Modules
Timer
LIM
Low Limit
Output Feedback Outputs OK
High Limit
Timer Done
Outputs Faulted
Outputs Faulted
Alarm to Operator
In general, good design practice dictates that each analog output must be
wired to a separate input terminal to make sure that the output is functioning
properly.
You must wire analog outputs to an actuator and then back to an analog input
to monitor the output performance.
1794-TB3 1794-TB3
V RET Secondary
Output
Actuator
1794-OF4I 1794-IF4I
1794-TB3 1794-TB3
V RET Secondary
Output
Actuator
This normally open relay is controlled by the status of the rest of the ControlLogix system. If a short-circuit or fault occurs on
the module, the relay can disconnect power to the module. The module that is used to control this relay must follow SIL 2 output
guidelines. This module must also be considered during PFD analysis for each safety function.
Use a signal-grade relay using bifurcated or similar grade contacts. The relay can be located in a position to remove power to
an actuator, or can remove power to multiple actuators depending on the granularity needed.
Along with following the Requirements When Using FLEX I/O Analog Output
Modules on page 77, consider the following application guideline before wiring
the module in Current mode:
Place other devices in current loop. You can locate other devices in a current
loop for the output channel anywhere as long as the current source can provide
sufficient voltage to accommodate all voltage drops.
1794-TB3 1794-TB3
Actuator
Secondary
Output
1794-OF4I 1794-IF4I
1794-TB3 1794-TB3
Secondary
Output
Actuator
This normally open relay is controlled by the status of the rest of the ControlLogix system. If a short-circuit or fault occurs on the module,
the relay can disconnect power to the module. The module that is used to control this relay must follow SIL 2 output guidelines. This
module must also be considered during PFD analysis for each safety function.
Use a signal-grade relay using bifurcated or similar grade contacts. The relay can be located in a position to remove power to an actuator,
or can remove power to multiple actuators depending on the granularity needed.
Software for The application software for the SIL 2-related automation system is created
SIL 2-Related Systems using the programming tool, that is, RSLogix 5000® software or the Studio
5000 Logix Designer® application, according to IEC 61131-3.
The application program has to be created by using the programming tool and
contains the specific equipment functions that the ControlLogix® system
implements. Parameters for the operating function are also entered into the
system with the programming software.
SIL 2 Programming The safety concept of the SIL 2 ControlLogix system assumes the following:
• The user who is responsible for creating, operating, and maintaining the
application is fully qualified, specially trained, and experienced in safety
systems.
• The programming software is installed correctly.
• Control system hardware is installed in accordance with product
installation guidelines.
• User application code (user program) uses common and good design
practices.
• A test plan is documented and adhered to, including well-understood
proof test requirements and procedures.
• A well-designed validation process is defined and implemented.
For more information on how you handle changes to the application program,
see Changing Your Application Program on page 88.
Programming Languages It is good engineering practice to keep safety-related logic as simple and easy
to understand as possible. The preferred language for safety-related functions
is ladder logic, followed by function block. Structured text and sequential
function chart are not recommended for safety-related functions. Use of the
SequenceManager™ feature is not recommended for safety-related functions.
Programming Options Pre-programmed SIL 2 I/O Add-On Instructions can be used in RSLogix 5000
software or the Studio 5000 Logix Designer application, version 20 or later. If
you choose to use Add-On Instructions, see the ControlLogix SIL 2 System
Configuration Using SIL 2 Add-On Instructions, publication 1756-AT012.
SIL 2 Add-On Instructions simplify the programming that is required for a SIL
2 system. However, these instructions are not necessarily suitable for use in all
SIL 2 applications and system configurations. Yo must evaluate the suitability
of a SIL 2 Add-On Instruction that is used in a safety-related function.
RUN FORCE SD OK
REM PR
RUN OG
1756-L6x 1756-L7x
• In RSLogix 5000 software, V18 and later, and in the Studio 5000 Logix
Designer application, tags have two attributes: External Access and
Constant. External Access controls access from external applications like
HMIs. It can have values of Read/Write, Read Only, or None. All SIL 2
safety-related tags should be set to Read Only. The Constant attribute is
either on or off. When enabled, it helps prevent programmatic changes
of a tag's value. Where possible, it is highly recommended to configure
SIL 2 safety-related tags as Constant.
Basics of Application A system integrator develops the application program. The developer must
Program Development consider general procedures for programming ControlLogix SIL 2
applications. (does not require independent third-party review).
and Testing
• Specification of the SIL 2 safety control function, including the
following:
- Specifications
- Flow and timing charts
- Engineering diagrams
- Sequence charts
- Program description
- Program review process
• Writing the application program
• Checking by independent reviewer
• Verification and validation
Functional Specification You must create a specification for your control function. Use this
Guidelines specification to verify that program logic correctly and fully addresses the
functional and safety control requirements of your application. The
specification can be in various formats, depending on your application. The
specification must include a detailed description of the following (if applicable):
• Sequence of operations
• Flow and timing diagrams
• Sequence charts
• Program description
• Program print-out
• Written descriptions of the steps with step conditions and actuators to
be controlled, including the following:
- Input definitions
- Output definitions
- I/O wiring diagrams and references
- Theory of operation
• Matrix- or table form of stepped conditions and the actuators to be
controlled, including the sequence and timing diagrams
• Definition of marginal conditions, for example, operating modes,
EMERGENCY STOP, and others
The I/O-portion of the specification must contain the analysis of field circuits,
that is, the type of sensors and actuators.
Actuators
• Position and activation in standard operation (normally OFF)
• Safe reaction or positions when switching OFF
• Discrepancy monitoring and visualization, including diagnostic logic
Creating the Consider the following when developing the application program logic.
Application Program
Logic and Instructions
The logic and instructions for programming the application must have these
features:
• Easy to understand
• Easy to trace
• Easy to change
• Easy to test
• Well-documented
Program Language
You must implement simple, easy to understand program language with these
features:
• Ladder
• Other IEC 61131-3-compliant language
• Function blocks with specified characteristics
We use ladder, for example, because it is easier to visualize and make partial
program changes with this format.
Program Identification
Include a single SIL task composed of programs and routines in the user
application. The SIL 2 task must be the top priority task of the controller and
the user-defined watchdog must be set to accommodate the SIL 2 task.
IMPORTANT You must dedicate a specific task for safety-related functions and set
that task to the highest priority (1). SIL 2 safety logic and logic that is
intended for use in non-SIL 2 functions must be separate, or everything
in the task containing safety must be treated as safety-related.
IMPORTANT Forcing must not be used during normal operation, during final system
test, and validation.
Checking the Application To check safety-related application logic for adherence to specific safety
Program functions, you must generate a suitable set of test cases that cover the safety
specification. The set of test cases must be well-written and filed as the test
specification.
Suitable tests must also be generated for the numeric evaluation of formulas.
Equivalent range tests are acceptable. Suitable tests are tests within defined
value ranges, at the limits, and outside the defined value ranges. The test cases
must be selected to prove the correctness of the calculation. The necessary
number of test cases depends on the formula that is used and must comprise
critical value pairs.
Verify Download Verify the download of the application program and its proper operation. A
and Operation typical technique is to upload the completed program file and perform a
compare of that file against what is stored in the programming terminal.
IMPORTANT If the controller has a USB port, it is intended for temporary local-
programming purposes only and not intended for permanent
connection.
Commissioning Lifecycle Figure 56 shows the steps that are required to develop, debug, and commission
an application program.
Create Flow
Diagram
Create Timing
Diagrams
Establish Sequence
of Operations
Perform Validation
Testing on all Logic
Yes Tests
Pass?
No
Verification
okay? Make more online edits & accept
edits or make more offline edits
and download to CTR
Begin Normal No
Determine what logic has
Project Operation
been Changed or Affected
Finish the
Validation Test1
Secure PADT
1
You must periodically repeat the validation test (also known as proof tests) to make sure that module inputs and outputs are functioning properly and as commanded by the
application programming. For more information on proof tests for I/O modules, see Chapter 1, SIL Policy on page 9.
Changing Your The following rules apply when you change your application program in
Application Program RSLogix 5000 software or the Studio 5000 Logix Designer application:
IMPORTANT You cannot make program edits while the program is online if the
changes prevent the system from executing the safety function or if
alternative protection methods are not in place.
• Program edits are not recommended and must be limited. For example,
minor changes such as changing a timer preset or analog setpoint are
allowed.
• Only authorized, specially trained personnel can make program edits.
These personnel must use all supervisory methods available, for example,
use the controller keyswitch and software password protections.
• Anyone making data or programming edits to an operational system
assumes the central safety responsibility while the changes are in
progress. These personnel must also maintain safe application
operation.
• Before you make any program edits, perform an impact analysis by
following the safety specification and other lifecycle steps that are
described in Figure 56 on page 87 as if the edits were an entirely
new program.
• Sufficiently document all program edits, including:
- Authorization.
- Impact analysis.
- Execution.
- Test information.
- Revision information.
• Multiple programmers cannot edit a program from multiple
programming terminals simultaneously.
• Changes to the safety application software–in this case, RSLogix 5000
software or the Studio 5000 Logix Designer application– must comply
with IEC 61511 standard on process safety section 11.7.1 Operator
Interface requirements.
• When the ControlLogix controller keyswitch is in the RUN position
(controller is in Run mode), you cannot make online edits.
• Use one of the following methods that are described in Table 3 on page 89
to edit the relay ladder logic portion of the safety program.
Notes:
Detect and React to Faults The ControlLogix architecture provides many ways to detect and react to faults
in the system.
• Various device objects can be interrogated to determine the current
operating status.
• Modules provide runtime status of their operation and of the process
that is executing.
• You can configure a ControlLogix system to identify and handle faults,
including such tasks as:
- Developing a fault routine.
- Creating a user-defined major fault.
- Monitoring minor faults.
- Developing a power-up routine.
See the Logix 5000™ Controllers Common Procedures Programming Manual,
publication 1756-PM001, for more information.
To help handle faults, make sure that you have completed the input (see Checklist
for SIL Inputs on page 132) and output (see Checklist for SIL Outputs on page 133)
checklists for their application.
Module Fault Reporting for You must verify that all components in the system are operating properly.
Verification can be accomplished in ladder logic by using the Get System Value
Any ControlLogix or FLEX I/O instruction (GSV) and an examination of the MODULE Object Entry Status
Module attribute for a running condition.
For more information on the GSV instruction, monitor the SlotStatusBits for
the Input tag of the associated adapter. The lower 8 bits of this tag correspond
to the associated slot. For example, the tag “Node3:I.Slot1StatusBits” is defined
as follows:
• Node 3 is the name that is given to the adapter, in this example, a
1794-ACNR15.
• I indicates the Input file.
• SlotStatusBits is a 32-bit value, where the lower 8 bits correspond to a
FLEX™ I/O module, as shown.
Check Keyswitch Position The following rungs generate a fault if the keyswitch on the front of the
controller is switched from the RUN position.
with GSV Instruction
Figure 58 - Keyswitch State (Operation mode) Change Logic
GSV
Class: CONTROLLERDEVICE
Attribute: STATUS
Destination: KEYSTATE
KEYSTATE.13
Fault
Fault
Alarm to Operator
In Figure 58 on page 92, the Get System Value (GSV) instruction interrogates
the STATUS attribute of the CONTROLLERDEVICE object and stores the
result in a word that is called KEYSTATE, where bits 12 and 13 define the state
of the keyswitch as shown in Table 4.
If bit 13 is ever ON, then the keyswitch is not in the RUN position. Examine bit
13 of KEYSTATE for an ON state generates a fault.
For more information on the accessing the CTROLLERDEVICE object, see the
Logix 5000 Controllers General Instructions RefeONrence Manual,
publication 1756-RM003.
Examine a 1756 Analog Input ControlLogix analog modules process and compare field data values right on
the module, which allows easy examination of status bits to initiate a fault.
Module’s High Alarm
For example, the 1756-IF8 module can be configured with user-defined alarm
values that, when exceeded, sets a status bit on the module, which is then sent
back to the controller. You can examine the state of these bits to initiate a fault
as shown in Figure 59.
Fault
Alarm to
Operator
In the example above, the High Alarm bits for channels 1 and 2 are being
examined for a condition to initiate a fault. During operation, as the analog
input module processes analog signals from the field sensors, if the value
exceeds the user-defined value for High Alarm, the alarm bit is set and a fault is
declared.
The ControlLogix architecture provides for the detecting and reacting to faults
in the system. Various device objects can be interrogated to determine the
current operating status. Additionally, modules provide runtime status of their
operation and of the process.
Additional Resources
Resource Description
Logix 5000 Controllers General Instructions Reference Manual, publication 1756-RM003 Provides information on how to use specific instructions to get and set controller system data
that is stored in device objects
Logix 5000 Controllers Common Procedures Programming Manual, publication 1756-PM001 Provides information on controller fault codes, including major and minor codes and on
creating fault and power-up routines
ControlLogix Analog I/O Modules User Manual, publication 1756-UM009 Provides information on how to access the runtime operational and process status of a
ControlLogix Digital I/O Modules User Manual, publication 1756-UM058 module.
Precautions You must exercise precautions and implement specific techniques on HMI
devices. These precautions include, but are not restricted to the following:
• Limited access and security
• Specifications, testing, and validation
• Restrictions on data and access
• Limits on data and parameters
For more information on how HMI devices fit into a typical SIL loop, see
Figure 10 on page 22.
Use sound techniques in the application software within the HMI and
controller.
IMPORTANT If any changes are needed to the program in the safety loop, they must be done in accordance with IEC 61511-1,
paragraph 11.7.1.5, which states:
‘The Safety Instrumentation System (SIS) operator interface design shall be such as to prevent changes to SIS
application software. Where safety information needs to be transmitted from the basic process control system (BPCS)
to the SIS then systems should be used that can selectively allow writing from the BPCS to specific SIS variables.
Equipment or procedures should be applied to confirm the proper selection has been transmitted and received by the
SIS and does not compromise the safety function of the SIS.’
Accessing Safety-related HMI- related functions consist of two primary activities: reading and
Systems writing data.
A parameter change in a safety-related loop via an external (that is, outside the
safety loop) device (for example, an HMI) is allowed only with the following
restrictions:
• Only authorized, specially trained personnel (operators) can change the
parameters in safety-related systems via HMIs.
• The operator who changes a safety-related system via an HMI is
responsible for the effect of those changes on the safety loop.
• You must clearly document variables that need changed.
• You must use a clear, comprehensive, and explicit operator procedure to
make safety-related changes via an HMI.
• Changes can only be accepted in a safety-related system if the following
sequence of events occurs.
a. The new variable must be sent twice to two different tags; that is, both
values must not be written to with one command.
b. Safety-related code that executes in the controller, must check both
tags for equivalency and make sure that they are within range
(boundary checks).
c. Both new variables must be read back and displayed on the HMI
device.
d. Trained operators must visually check that both variables are the same
and are the correct value.
e. Trained operators must manually acknowledge that the values are
correct on the HMI screen that sends a command to the safety logic,
which allows the new values to be used in the safety function.
In every case, the operator must confirm the validity of the change before
they are accepted and applied in the safety loop.
• Test all changes as part of the safety validation procedure.
• Sufficiently document all safety-related changes that are made via HMI,
including the following:
- Authorization
- Impact analysis
- Execution
- Test information
- Revision information
• Changes to the safety-related system, must comply with IEC 61511
standard on process safety section 11.7.1 Operator Interface
requirements.
• The developer must follow the same sound development techniques and
procedures that are used for other application software development,
including the verification and testing of the operator interface and its
access to other parts of the program. The controller application software
builds a table that is accessible by the HMI and limits access to required
data points only.
• Similar to the controller program, you must secure and maintain the
HMI software for SIL-level compliance after the system has been
validated and tested.
IMPORTANT The High Speed Jog function is not allowed and must not be used in the
entire project.
The calculation formulas in this chapter can be used to calculate the worst-case
reaction times for a given change in input or fault condition and the
corresponding output action.
Local Chassis Configuration Figure 60 shows an example system with digital or analog modules where the
following occurs:
• Field signal changes state.
• The data is transmitted to the controller.
• The controller runs its program scan and reacts to the data change.
• The controller transmits data to the output module.
• The output module processes data from the controller and turns the
output device on or off.
Figure 60 - Local Chassis Configuration of Digital or Analog Modules
Input Module Controller Output Module
Remote Chassis Figure 61 shows an example system where the following occurs:
Configuration • Input data changes on the input module.
• The data is transmitted to the controller via the network communication
modules.
• The controller runs its program scan and reacts to the data change,
including new data sent to the output module via the network
communication modules.
• The output module behavior changes based on the new data that is
received from the controller.
Calculating Worst-case The formulas for calculating worst-case reaction times with no system faults
Reaction Time or errors differ slightly for digital or analog I/O modules, as shown in the
following sections.
Use this formula to determine worst-case reaction time for digital modules in
local or remote configurations:
Worst-Case Reaction Time with no faults or errors =
(Input Module Delay + Input Filter Time) + (Input Module RPI x 4/8/16… 100 ms)(1) +
(SIL 2 Task Period + SIL 2 Task Watchdog) + (Output Module RPI x 4/8/16… 100 ms)(1) +
(Output Module Delay).
Module delay times are listed in the ControlLogix® I/O Modules Specifications
Technical Data, publication 1756-TD002.
Input filter time is configurable via the Configuration tab on the Module
Properties dialog box in the programming software.
• If the safe state in your application is low, use the On -> Off Input Filter
Time.
• If the safe state in your application is high, use the Off -> On Input Filter
Time.
(1) Multiply the module RPI by 4, then 8, then 16, and so on, until the result is at least 100 ms.
Use this formula to determine worst-case reaction time for analog modules in
local or remote configurations:
Worst-Case Reaction Time with no faults or errors =
(Real Time Sample (RTS) Rate) +
(Input Module RPI x 4/8/16… 100 ms)(1) + (SIL 2 Task Period + SIL 2 Task Watchdog) +
(Output Module RPI x 4/8/16… 100 ms)(1) + (Output Module Delay).
For this calculation for the 1756-IRT8I or IF8I the RPI should be used in place of the
RTS.
Filter time and RTS are configurable via the Configuration tab on the Module
Properties dialog box in the programming software. Module RPI is
configurable via the Connection tab.
(1) Multiply the module RPI by 4, then 8, then 16, and so on, until the result is at least 100 ms.
This calculation for the 1756-IRT8I or 1756-IF8I modules, the RPI should be
used in place of the RTS.
System components that are listed here are certified according to IEC 61508
2010 Edition 2, unless noted in the following tables.
Use only the series versions that are listed in Appendix C. These tables list
publications that are related to these components. Publications are available
from Rockwell Automation by visiting http://www.rockwellautomation.com/
literature.
Table 5 - SIL 2-certified ControlLogix® Components - Hardware
Cat. No.(1) Description Related Documentation
1756-A4, 1756-A7 1756-A10, 1756-A13, 1756-A17 ControlLogix chassis
1756-PA75(2) ControlLogix AC power supply
1756-PB75(2) ControlLogix DC power supply
1756-PA75R ControlLogix AC redundant power supply
1756-PB75R ControlLogix DC redundant power supply
1756-PA72 ControlLogix AC power supply
1756-IN005
1756-PB72 ControlLogix DC power supply
1756-PC75 ControlLogix DC power supply
1756-PH75 ControlLogix DC power supply
ControlLogix redundant power supply chassis adapter
1756-PSCA(3) module
ControlLogix redundant power supply chassis adapter
1756-PSCA2(3) module
(1) Some catalog numbers have a K suffix. This indicates a version of the product that has conformal coating. These K versions have the same SIL 2 certification as the non-K versions. For
more information on which products have conformal coating go to http://ab.com.rockwellautomation.com/
(2) The 1756-PA75/A and 1756-PB75/A power supplies are no longer available. However, if your existing SIL 2 application uses these power supplies, they are SIL 2 certified.
(3) Existing systems that use the 1756-PSCA and 1756-PSCA2 are SIL 2-certified. However, when implementing new SIL 2-certified systems or upgrading existing systems, we recommend that
you use the 1756-PSCA2 module if possible.
Table 6 - SIL 2-certified ControlLogix Components - 1756 Non-redundant Controllers, I/O, and Communication Modules
Cat. No.(1) Description Related Documentation
1756-L61(2) (3) ControlLogix 2 MB controller
1756-L62(2) (3) ControlLogix 4 MB controller
1756-L63(2) (3) ControlLogix 8 MB controller
1756-L71(2) ControlLogix 2 MB controller
1756-UM001
1756-L72(2) ControlLogix 4 MB controller
1756-L73(2) ControlLogix 8 MB controller
1756-L74(2) ControlLogix 16 MB controller
1756-L75(2) ControlLogix 32 MB controller
1756-L61S(2)(3) GuardLogix® controller, 2 MB standard
(2)(3) GuardLogix controller, 4 MB standard
1756-L62S
1756-L63S(2)(3) GuardLogix controller, 8 MB standard
1756-L71S(2) GuardLogix controller, 2 MB standard 1756-UM022
1756-L72S(2) GuardLogix controller, 4 MB standard
1756-L73S(2) GuardLogix controller, 8 MB standard
1756-L73SXT(2) GuardLogix-XT™ controller, 8 MB standard
1756-IA16I ControlLogix AC isolated input module
1756-IA8D ControlLogix AC diagnostic input module
1756-IB16D ControlLogix DC diagnostic input module 1756-UM058
1756-IB16I ControlLogix DC isolated input module
1756-IB32 ControlLogix DC input module
1756-IB16ISOE ControlLogix Sequence of Events module
1756-UM528
1756-IH16ISOE ControlLogix Sequence of Events module
1756-OA16I ControlLogix AC isolated output module
1756-OA8D ControlLogix AC diagnostic input module
1756-OB16D ControlLogix DC diagnostic output module
1756-OB16E ControlLogix DC electronically fused output module
1756-OB16I ControlLogix DC isolated output module 1756-UM058
1756-OB32 ControlLogix DC output module
1756-OB8EI ControlLogix DC isolated output module
1756-OW16I ControlLogix isolated relay output module
1756-OX8I ControlLogix isolated relay output module
1756-IF8 ControlLogix analog input module
1756-IF16 ControlLogix analog input module
1756-UM009
1756-IF6I ControlLogix isolated analog input module
1756-IF6CIS ControlLogix isolated analog input module
1756-IF8H ControlLogix HART analog input module
1756-UM533
1756-IF16H ControlLogix HART analog input module
1756-IF8I ControlLogix isolated analog input module
ControlLogix isolated analog RTD thermocouple input
1756-IRT8I 1756-UM540
module
1756-OF8I ControlLogix isolated analog output module
Table 6 - SIL 2-certified ControlLogix Components - 1756 Non-redundant Controllers, I/O, and Communication Modules (Continued)
Cat. No.(1) Description Related Documentation
1756-IR6I ControlLogix RTD input module
1756-IT6I ControlLogix Thermocouple input module
1756-IT6I2 ControlLogix enhanced Thermocouple input module
1756-UM009
1756-OF8 ControlLogix analog output module
1756-OF6CI ControlLogix isolated analog output module
1756-OF6VI ControlLogix isolated analog output module
1756-OF8H ControlLogix HART analog output module 1756-UM533
1756-CNB(4) ControlLogix ControlNet® communication module
1756-CN2 ControlLogix ControlNet communication module CNET-IN005
CNET-UM001
ControlLogix redundant media ControlNet
1756-CN2R communication module
1786-RPFS ControlNet short-distance fiber repeater module 1786-IN012
1786-RPFM ControlNet medium-distance fiber repeater module 1786-IN011
1786-RPFRL ControlNet long-distance fiber repeater module
1786-IN003
1786-RPFRXL ControlNet extra-long-distance fiber repeater module
1786-RPA ControlNet repeater adapter 1786-IN013
1786-RPCD ControlNet Hub repeater module 1786-IN001
ControlLogix redundant media EtherNet/IP™
1756-EN2TR Series B communication module
ENET-IN002
ControlLogix redundant media EtherNet/IP
1756-EN2TR Series C ENET-UM001
communication module
1756-EN2T Series C ControlLogix EtherNet/IP communication module
(1) Some catalog numbers have a K suffix. This indicates a version of the product that has conformal coating. These K versions have the same SIL 2 certification as the non-K versions. For
more information on which products have conformal coating go to http://ab.com.rockwellautomation.com/
(2) Use of any series B controller requires the use of the series B versions of the 1756-Px75 power supplies.
(3) Certified according to IEC 61508 1999 Edition 1.
(4) Specified ControlNet repeaters may be used in SIL 2 applications. See Chapter 4, ControlLogix Communication Modules for more information.
IMPORTANT ControlLogix-XT modules use the same firmware as traditional ControlLogix components. When obtaining firmware
for ControlLogix-XT modules, download and use the firmware specific to each module.
For example, if you are using a 1756-EN2TXT module in your system, use SIL 2-certified firmware for the 1756-EN2T
module.
For more information about ControlLogix-XT module firmware revisions, see the firmware release notes specific to
the module. ControlLogix-XT module release notes are available at:
http://www.rockwellautomation.com/literature or http://www.rockwellautomation.com/support/.
Table 9 - FLEX™ I/O Components For Use in the SIL 2 System (Continued)
Cat. No.(1) Description Related Documentation(2)
1794-IN039
1794-IF2XOF2I FLEX I/O isolated analog input/output module
1794-UM008
1794-IN129
1794-IF2XOF2IXT FLEX I/O-XT isolated analog input/output module
1794-UM008
1794-IN100
1794-OE4 FLEX I/O analog output module 1794-UM002
1794-IN037
1794-OF4I FLEX I/O isolated analog output module 1794-UM008
1794-IN021
1794-IT8 FLEX I/O Thermocouple input module 1794-UM007
1794-IR8 FLEX I/O RTD input module 1794-IN021
1794-IR8XT FLEX I/O-XT RTD input module 1794-UM004
1794-IRT8 FLEX I/O Thermocouple/RTD input module 1794-IN050
1794-IRT8XT FLEX I/O-XT Thermocouple/RTD analog input module 1794-UM012
1794-IJ2 FLEX I/O counter module 1794-IN049
1794-IJ2XT FLEX I/O-XT counter module 1794-UM011
1794-IN064
1794-IP4 FLEX I/O counter module
1794-UM016
1794-IE4XOE2XT FLEX I/O-XT analog input/output module 1794-IN125
1794-IE8XT FLEX I/O-XT analog input module 1794-IN125
1794-OE4XT FLEX I/O-XT analog output module 1794-IN125
1794-IN129
1794-OF4IXT FLEX I/O-XT isolated analog output module
1794-UM008
1794-TB3 FLEX I/O terminal base unit
1794-TB3S FLEX I/O terminal base unit
1794-TB3T FLEX I/O temperature terminal base unit
1794-TB3TS FLEX I/O spring-clamp temperature terminal base unit
1794-IN092
1794-TB3G FLEX I/O cage-clamp generic terminal base unit
1794-TB3GS FLEX I/O spring-clamp generic terminal base unit
1794-TBN FLEX I/O NEMA terminal base unit
1794-TBNF FLEX I/O NEMA fused terminal base unit
(1) Some catalog numbers have a K suffix. This indicates a version of the product that has conformal coating. These K versions have the same SIL 2 certification as the non-K versions. For
more information on which products have conformal coating go to http://ab.com.rockwellautomation.com/
(2) These publications are available from Rockwell Automation by visiting http://www.rockwellautomation.com/literature.
Notes:
About PFD and PFH The probability of failure on demand (PFD) is the SIL value for a safety-related
Calculations system as related directly to order-of-magnitude ranges of its average
probability of failure to satisfactorily perform its safety function on demand.
IEC 61508 quantifies this classification by stating that the frequency of
demands for operation of the safety system is no greater than once per year in
the Low Demand mode.
PFD calculations are commonly used for process safety applications and
applications where emergency stop devices (ESDs) are used.
Although PFD values are associated with each of the three elements that
constitute a safety-related system (the sensors, the actuators, and the logic
element), they can be associated with each component of the logic element,
that is, each module of a programmable controller.
Tables in this chapter present PFD and PFH values for ControlLogix and
ControlLogix-XT™ components that TÜV evaluates.
Each of the PFD and PFH calculated values that are provided in this manual is
based on the configuration that the module can be used in, that is 1oo1 or 1oo2.
• Controllers only have a 1oo1 configuration, even when used in a 1756-RM
module redundancy architecture.
• You can architect communication modules in a 1oo1 or 1oo2
configuration. Use 1oo2 if the I/O module pair is split among two
separate chassis; thus a separate path to each module via a unique
communications module.
• Input or output modules have PFD values typically for use in a 1oo2
configuration. But 1oo1 values are provided in the event diversity is used
for input modules, or the output module that controls the actuator and
secondary relay are diverse.
About the Calculations in For the example calculations presented in this chapter, these values were used
This Manual as the two application-dependent variables:
• Mean time to restoration (MTTR) is ten hours.
• Mean repair time (MRT) is ten hours.
• Proof test interval (T1) is listed for each table.
Both the common cause failure rate (ß) and common cause failure rate
dangerous (ßd) values used in the calculations presented in this chapter are
5%.
Common Terms
= failure rate = 1/MTBF
s = rate of safe failures = x 50%
d = rate of dangerous failures = x 50%
dd= dangerous, detected failure rate = /2 x DC
du= dangerous, undetected failure rate = /2 x (1-DC)
SFF = safe failure fraction =(s +dd)/
TCE1oo1 = channel equivalent down time = du/d x (T1/2 + MRT) + (dd/d x MTTR)
DC = diagnostic coverage
ß = common cause failure rate
ßd = common cause failure rate, dangerous
1oo1 Configuration
STR1oo1 = spurious trip rate = s + dd
PFD1oo1 = (dd + du) x TCE
PFH1oo1 = du
1oo2 Configuration
STR1oo2 = spurious trip rate = 2 x (s + dd)
TGE1oo2 = system equivalent down time = du/d x (T1/3 + MRT) + (dd/d x MTTR)
PFD1oo2= 2 x [(1-ßD) x dd + (1-ß) x du]2 x TCE x TGE + (ßD x dd x MTTR) + ß x du x (T1/2 + MRT)
PFH1oo2 = 2 x [(1-ßD) x dd + (1-ß) x du] x (1-ß) x du x TCE + ß x du
The PFD and PFH values in this manual are calculated with formulas that are
explained in IEC 61508, Part 6, Annex B. See IEC 61508, Part 6, for more
information about how to calculate PFD values for your system.
1-Year PFD Calculations The PFD calculations in this table are calculated for a 1-year proof test interval
(8760 hours) and are specific to ControlLogix system components.
Table 10 - 1- Year PFD Calculations
Common Terms(3) 1oo1 Configuration 1oo2 Configuration
Mean Time
between Safe
Cat No.(1)(2) Description Failure Spurious Spurious
s, d Failure TCE1oo1 Trip Rate PFH(5)
(4) Fraction du
dd PFD Trip Rate TGE PFH(5) PFD
(MTBF)(2)
Series
STR STR
(SFF) %
1756-AXX(6) C ControlLogix chassis 22,652,010 4.41E-08 2.21E-08 95% 2.21E-09 1.99E-08 448 4.19E-08 2.21E-09 9.89E-06
B 4-slot ControlLogix-XT
1756-A4LXT 1,069,120 9.35E-07 4.68E-07 95% 4.68E-08 4.21E-07 448 8.89E-07 4.68E-08 2.10E-04
chassis
C 5-slot ControlLogix-XT
1756-A5XT 734,420 1.36E-06 6.81E-07 95% 6.81E-08 6.13E-07 448 1.29E-06 6.81E-08 3.05E-04
chassis
B 7-slot ControlLogix-XT
1756-A7LXT 27,628,178 3.62E-08 1.81E-08 95% 1.81E-09 1.63E-08 448 3.44E-08 1.81E-09 8.11E-06
chassis
C 7-slot ControlLogix-XT
1756-A7XT 1,081,600 9.25E-07 4.62E-07 95% 4.62E-08 4.16E-07 448 8.78E-07 4.62E-08 2.07E-04
chassis
C 85-265V AC 10 A
1756-PA72 18,336,146 5.45E-08 2.73E-08 95% 2.73E-09 2.45E-08 448 5.18E-08 2.73E-09 1.22E-05
ControlLogix power supply
85-265V AC 13 A
1756-PA75 B ControlLogix power supply 18,693,044 5.35E-08 2.67E-08 95% 2.67E-09 2.41E-08 448 5.08E-08 2.67E-09 1.20E-05
(75 W)
A 85-265V AC 13 A redundant
1756-PA75R 1,412,877 7.08E-07 3.54E-07 95% 3.54E-08 3.18E-07 448 6.72E-07 3.54E-08 1.59E-04
ControlLogix power supply
A 18-32V DC 13 A redundant
1756-PB75R 1,736,020 5.76E-07 2.88E-07 95% 2.88E-08 2.59E-07 448 5.47E-07 2.88E-08 1.29E-04
ControlLogix power supply
Not applicable
B ControlLogix-XT AC power
1756-PAXT 18,693,044 5.35E-08 2.67E-08 95% 2.67E-09 2.41E-08 448 5.08E-08 2.67E-09 1.20E-05
supply
B ControlLogix-XT DC power
1756-PBXT 1,855,360 5.39E-07 2.69E-07 95% 2.69E-08 2.43E-07 448 5.12E-07 2.69E-08 1.21E-04
supply
B 90-143V DC 13 A
1756-PH75 2,119,520 4.72E-07 2.36E-07 95% 2.36E-08 2.12E-07 448 4.48E-07 2.36E-08 1.06E-04
ControlLogix power supply
Series
STR STR
(SFF) %
1756-L61(7) B ControlLogix controller, 2 MB 1,000,053 1.00E-06 5.00E-07 95% 5.00E-08 4.50E-07 448 9.50E-07 5.00E-08 2.24E-04
1756-L62(7) B ControlLogix controller, 4 MB 1,034,830 9.66E-07 4.83E-07 95% 4.83E-08 4.35E-07 448 9.18E-07 4.83E-08 2.16E-04
1756-L63(7) B ControlLogix controller, 8 MB 1,055,910 9.47E-07 4.74E-07 95% 4.74E-08 4.26E-07 448 9.00E-07 4.74E-08 2.12E-04
B ControlLogix-XT controller,
1756-L63XT(7) 8 MB 357760 2.80E-06 1.40E-06 95% 1.40E-07 1.26E-06 448 2.66E-06 1.40E-07 6.26E-04
1756-L71(8) B ControlLogix controller, 2 MB 2.69E-06 1.34E-06 96% 1.01E-07 1.25E-06 340 2.91E-06 1.01E-07 4.50E-04
1756-L72(8) B ControlLogix controller, 4 MB 2.69E-06 1.34E-06 96% 1.01E-07 1.25E-06 340 2.91E-06 1.01E-07 4.50E-04
1756-L73(8) B ControlLogix controller, 8 MB
Calculated
2.69E-06 1.34E-06 96% 1.01E-07 1.25E-06 340 2.91E-06 1.01E-07 4.50E-04
MTBF and
B ControlLogix-XT controller,
1756-L73XT(8) 8 MB PFD via 2.69E-06 1.34E-06 96% 1.01E-07 1.25E-06 340 2.91E-06 1.01E-07 4.50E-04
FMEA
B ControlLogix controller,
1756-L74(8) 16 MB 2.69E-06 1.34E-06 96% 1.01E-07 1.25E-06 340 2.91E-06 1.01E-07 4.50E-04
B GuardLogix controller, 4 MB
1756-L62S(7) standard 1,034,830 9.66E-07 4.83E-07 95% 4.83E-08 4.35E-07 448 9.18E-07 4.83E-08 2.16E-04
B GuardLogix controller, 2 B
1756-L71S(8) standard 2.69E-06 1.34E-06 96% 1.01E-07 1.25E-06 340 2.91E-06 1.01E-07 4.50E-04
B GuardLogix-XT™ controller,
1756-L73SXT(8) 8 MB standard 2.69E-06 1.34E-06 96% 1.01E-07 1.25E-06 340 2.91E-06 1.01E-07 4.50E-04
ControlLogix ControlNet
1756-CNB E 1,786,977 5.60E-07 2.80E-07 95% 2.80E-08 2.52E-07 448 5.32E-07 2.80E-08 1.25E-04
communication module
ControlLogix ControlNet
1756-CNBR E redundant communication 2,608,543 3.83E-07 1.92E-07 95% 1.92E-08 1.73E-07 448 3.64E-07 1.92E-08 8.59E-05
module
B ControlLogix ControlNet
1756-CN2 1,096,299 9.12E-07 4.56E-07 95% 4.56E-08 4.10E-07 448 8.67E-07 4.56E-08 2.04E-04
communication module
Calculated
C ControlLogix ControlNet MTBF and
1756-CN2(8) communication module PFD via 1.97E-06 9.87E-07 96.6% 6.62E-08 9.21E-07 303.63 1.91E-06 6.62E-08 3.0E-04
FMEA
ControlLogix ControlNet
1756-CN2R B redundant communication 1,096,299 9.12E-07 4.56E-07 95% 4.56E-08 4.10E-07 448 8.67E-07 4.56E-08 2.04E-04 Not applicable
module
Calculated
ControlLogix ControlNet MTBF and
1756-CN2R(8) C redundant communication PFD via 1.97E-06 9.87E-07 96.6% 6.62E-08 9.21E-07 303.63 1.91E-06 6.62E-08 3.0E-04
module FMEA
ControlLogix-XT ControlNet
1756-CN2RXT B redundant communication 1,980,160 5.05E-07 2.53E-07 95% 2.53E-08 2.27E-07 448 4.80E-07 2.53E-08 1.13E-04
module
Calculated
ControlLogix-XT ControlNet MTBF and
1756-CN2RXT(8) C redundant communication PFD via 1.97E-06 9.87E-07 96.6% 6.62E-08 9.21E-07 303.63 1.91E-06 6.62E-08 3.0E-04
module FMEA
ControlLogix Data Highway
1756-DHRIO(9) E Plus™ remote I/O module 2,503,396 2.90E-07 5.79E-07
ControlLogix-XT Data
1756-DHRIOXT(9) E Highway Plus remote I/O 2,503,396 2.90E-07 5.79E-07
module Non-interference only Not applicable Not applicable
D ControlLogix
(9) DeviceNet®
1756-DNB 2,192,202 3.31E-07 6.61E-07
communication module
A ControlLogix EtherNet/IP™
1756-ENBT(9) communication module 2,088,198 3.47E-07 6.94E-07
C ControlLogix EtherNet/IP™
1756-EN2T 1,312,712 7.62E-07 3.81E-07 95% 3.81E-08 3.43E-07 448 7.24E-07 3.81E-08 1.71E-04
communication module
D ControlLogix EtherNet/IP
1756-EN2T(9) communication module 269,774 Non-interference only 3.71E-06 Not applicable Not applicable
ControlLogix EtherNet/IP
1756-EN2TR B communication module with 3,664,960 2.73E-07 1.36E-07 95% 1.36E-08 1.23E-07 448 2.59E-07 1.36E-08 6.11E-05
fault tolerance
Series
STR STR
(SFF) %
ControlLogix EtherNet/IP
1756-EN2TR(8) C communication module with Calculated 1.97E-06 9.87E-07 96.6% 6.62E-08 9.21E-07 303.63 1.91E-06 6.62E-08 3.0E-04 3.82E-06 258.2 1.36E-09 6.11E-06
fault tolerance MTBF and
ControlLogix EtherNet/IP PFD via
1756-EN2TRXT(8) C communication module with FMEA 1.97E-06 9.87E-07 96.6% 6.62E-08 9.21E-07 303.63 1.91E-06 6.62E-08 3.0E-04 3.82E-06 258.2 1.36E-09 6.11E-06
fault tolerance
ControlLogix EtherNet/IP
1756-EN3TR(9) B communication module with 269,774 3.71E-06
fault tolerance
B ControlLogix redundancy
1756-RM(9) module 1,373,840 7.28E-07
Not applicable
A ControlLogix enhanced Non-interference only
1756-RM2(9) redundancy module 250,182 4.00E-06
A ControlLogix-XT enhanced
1756-RM2XT(9) redundancy module 250,182 4.00E-06
ControlLogix-XT redundancy
1756-RMXT(9) B module 980,096 1.02E-06
A ControlLogix SynchLink™
1756-SYNCH(9) Module 6,932,640 1.05E-07 Not applicable 2.09E-07 Not applicable
A ControlLogix isolated V AC
1756-IA16I 20,801,920 4.81E-08 2.40E-08 80% 9.61E-09 1.44E-08 1762 3.85E-08 9.61E-09 4.24E-05 7.69E-08 1178 4.81E-10 2.12E-06
input module
A ControlLogix diagnostic
1756-IA8D 15,966,080 6.26E-08 3.13E-08 80% 1.25E-08 1.88E-08 1762 5.01E-08 1.25E-08 5.52E-05 1.00E-07 1178 6.28E-10 2.76E-06
V AC input module
A ControlLogix diagnostic
1756-IB16D 30,228,640 3.31E-08 1.65E-08 80% 6.62E-09 9.92E-09 1762 2.65E-08 6.62E-09 2.91E-05 5.29E-08 1178 3.31E-10 1.46E-06
V DC input module
A ControlLogix isolated V DC
1756-IB16I 81,443,094 1.23E-08 6.14E-09 80% 2.46E-09 3.68E-09 1762 9.82E-09 2.46E-09 1.08E-05 1.96E-08 1178 1.23E-10 5.41E-07
input module
ControlLogix isolated V DC
1756-IB16ISOE A Sequence Of Events input 11,537,760 8.67E-08 4.33E-08 80% 1.73E-08 2.60E-08 1762 6.93E-08 1.73E-08 7.64E-05 1.39E-07 1178 8.69E-10 3.82E-06
module
B ControlLogix V DC input
1756-IB32 10,462,329 9.56E-08 4.78E-08 80% 1.91E-08 2.87E-08 1762 7.65E-08 1.91E-08 8.42E-05 1.53E-07 1178 9.59E-10 4.22E-06
module
Calculated
B ControlLogix isolated analog MTBF and
1756-IF8I(8) input module PFD via 5.83E-07 2.92E-07 78% 1.26E-07 1.66E-07 1897 4.58E-07 1.26E-07 5.56E-04 9.15E-07 1268 2.65E-09 1.15E-05
FMEA
Calculated
B ControlLogix isolated RTD / MTBF and
1756-IRT8I(8) thermocouple input module PFD via 6.11E-07 3.06E-07 80% 1.24E-07 1.82E-07 1783 Not allowed for 1oo1 9.75E-07 1192 2.61E-09 1.13E-05
configurations
FMEA
A ControlLogix isolated
1756-IT6I thermocouple input module 3,957,824 2.53E-07 1.26E-07 80% 5.05E-08 7.58E-08 1762 4.04E-07 1178 2.55E-09 1.12E-05
ControlLogix isolated
1756-IT6I2 A enhanced thermocouple 2,720,046 3.68E-07 1.84E-07 80% 7.35E-08 1.10E-07 1762 5.88E-07 1178 3.72E-09 1.63E-05
input module
A ControlLogix V AC output
1756-OA16I 32,891,456 3.04E-08 1.52E-08 80% 6.08E-09 9.12E-09 1762 2.43E-08 6.08E-09 2.68E-05 4.86E-08 1178 3.04E-10 1.34E-06
module
A ControlLogix V AC
1756-OA8D 11,311,040 8.84E-08 4.42E-08 80% 1.77E-08 2.65E-08 1762 7.07E-08 1.77E-08 7.79E-05 1.41E-07 1178 8.87E-10 3.90E-06
diagnostic output module
Series
STR STR
(SFF) %
A ControlLogix V DC
1756-OB16D 8,884,374 1.13E-07 5.63E-08 80% 2.25E-08 3.38E-08 1762 9.00E-08 2.25E-08 9.92E-05 1.80E-07 1178 1.13E-09 4.97E-06
diagnostic output module
ControlLogix V DC
1756-OB16E A electronically fused output 14,997,714 6.67E-08 3.33E-08 80% 1.33E-08 2.00E-08 1762 5.33E-08 1.33E-08 5.87E-05 1.07E-07 1178 6.68E-10 2.94E-06
module
A ControlLogix V DC isolated
1756-OB16I 7,388,160 1.35E-07 6.77E-08 80% 2.71E-08 4.06E-08 1762 1.08E-07 2.71E-08 1.19E-04 2.17E-07 1178 1.36E-09 5.98E-06
output module
A ControlLogix V DC output
1756-OB32 2,681,316 3.73E-07 1.86E-07 80% 7.46E-08 1.12E-07 1762 2.98E-07 7.46E-08 3.29E-04 5.97E-07 1178 3.77E-09 1.66E-05
module
ControlLogix V DC isolated
1756-OB8EI A electronic ally fused output 14,019,200 7.13E-08 3.57E-08 80% 1.43E-08 2.14E-08 1762 5.71E-08 1.43E-08 6.28E-05 1.14E-07 1178 7.15E-10 3.15E-06
module
Calculated
B ControlLogix isolated analog MTBF and
1756-OF8I(8) output module PFD via 6.08E-07 3.04E-07 78% 1.37E-07 1.67E-07 1982 4.71E-07 1.37E-07 6.03E-04 9.42E-07 1325 2.90E-09 1.25E-05
FMEA
A FLEX I/O-XT™
1794-IB16XT 35,587,189 2.81E-08 1.40E-08 80% 5.62E-09 8.43E-09 1762 4.50E-08 1178 2.81E-10 1.24E-06
24V DC input module
1794-IJ2 A FLEX I/O counter module 55,344,640 1.81E-08 9.03E-09 80% 3.61E-09 5.42E-09 1762 2.89E-08 1178 1.81E-10 7.96E-07
1794-IJ2XT A FLEX I/O-XT counter module 11,714,128 8.54E-08 4.27E-08 80% 1.71E-08 2.56E-08 1762 Not allowed for 1oo1 1.37E-07 1178 8.56E-10 3.77E-06
configurations
1794-IP4 B FLEX I/O counter module 22,027,200 4.54E-08 2.27E-08 80% 9.08E-09 1.36E-08 1762 7.26E-08 1178 4.55E-10 2.00E-06
A FLEX I/O-XT
1794-IB10XOB6XT 24V DC input/output module 22,202,487 4.50E-08 2.25E-08 80% 9.01E-09 1.35E-08 1762 7.21E-08 1178 4.51E-10 1.99E-06
Series
STR STR
(SFF) %
2-Year PFD Calculations The PFD calculations in this table are calculated for a 2-year proof test interval
(17,520 hours) and are specific to ControlLogix system components.
Table 11 - 2-Year PFD Calculations
Common Terms(3) 1oo1 Configuration 1oo2 Configuration
Mean Time
between Safe
Cat No.(1)(2) Description Failure Spurious Spurious
s, d Failure TCE1oo1
(4) Fraction du
dd Trip Rate PFH(5) PFD Trip Rate TGE PFH(5) PFD
(MTBF)(2)
Series
STR STR
(SFF) %
1756-AXX(6) C ControlLogix chassis 22,652,010 4.41E-08 2.21E-08 95% 2.21E-09 1.99E-08 886 4.19E-08 2.21E-09 1.96E-05
4-slot ControlLogix-XT
1756-A4LXT B 1,069,120 9.35E-07 4.68E-07 95% 4.68E-08 4.21E-07 886 8.89E-07 4.68E-08 4.14E-04
chassis
5-slot ControlLogix-XT
1756-A5XT C 734,420 1.36E-06 6.81E-07 95% 6.81E-08 6.13E-07 886 1.29E-06 6.81E-08 6.03E-04
chassis
7-slot ControlLogix-XT
1756-A7LXT B 27,628,178 3.62E-08 1.81E-08 95% 1.81E-09 1.63E-08 886 3.44E-08 1.81E-09 1.60E-05
chassis
7-slot ControlLogix-XT
1756-A7XT C 1,081,600 9.25E-07 4.62E-07 95% 4.62E-08 4.16E-07 886 8.78E-07 4.62E-08 4.10E-04
chassis
18-32V DC 10 A ControlLogix
1756-PB72 C 31,561,095 3.17E-08 1.58E-08 95% 1.58E-09 1.43E-08 886 3.01E-08 1.58E-09 1.40E-05
power supply
85-265V AC 10 A ControlLogix 18,336,146
1756-PA72 C 5.45E-08 2.73E-08 95% 2.73E-09 2.45E-08 886 5.18E-08 2.73E-09 2.42E-05
power supply
85-265V AC 13 A ControlLogix 18,693,044
1756-PA75 B 5.35E-08 2.67E-08 95% 2.67E-09 2.41E-08 886 5.08E-08 2.67E-09 2.37E-05
power supply (75 W)
85-265V AC 13 A Redundant
1756-PA75R A 1,412,877 7.08E-07 3.54E-07 95% 3.54E-08 3.18E-07 886 6.72E-07 3.54E-08 3.14E-04
ControlLogix power supply
18-32V DC 13 A ControlLogix
1756-PB75 B 15,675,475 6.38E-08 3.19E-08 95% 3.19E-09 2.87E-08 886 6.06E-08 3.19E-09 2.83E-05
power supply
18-32V DC 13 A Redundant
1756-PB75R A 1,736,020 5.76E-07 2.88E-07 95% 2.88E-08 2.59E-07 886 5.47E-07 2.88E-08 2.55E-04
ControlLogix power supply
ControlLogix-XT AC power Not applicable
1756-PAXT B 18,693,044 5.35E-08 2.67E-08 95% 2.67E-09 2.41E-08 886 5.08E-08 2.67E-09 2.37E-05
supply
ControlLogix-XT DC power
1756-PBXT B 1,855,360 5.39E-07 2.69E-07 95% 2.69E-08 2.43E-07 886 5.12E-07 2.69E-08 2.39E-04
supply
30-60V DC 13 A ControlLogix 5,894,836
1756-PC75 B 1.70E-07 8.48E-08 95% 8.48E-09 7.63E-08 886 1.61E-07 8.48E-09 7.52E-05
power supply
90-143V DC 13 A ControlLogix 2,119,520
1756-PH75 B 4.72E-07 2.36E-07 95% 2.36E-08 2.12E-07 886 4.48E-07 2.36E-08 2.09E-04
power supply
Redundant power supply
1756-PSCA A 45,146,727 2.21E-08 1.11E-08 95% 1.11E-09 9.97E-09 886 2.10E-08 1.11E-09 9.81E-06
adapter
Redundant power supply
1756-PSCA2 A 38,461,280 2.60E-08 1.30E-08 95% 1.30E-09 1.17E-08 886 2.47E-08 1.30E-09 1.15E-05
adapter
ControlNet Fiber repeater -
1786-RPFS A 26,461,760 3.78E-08 1.89E-08 95% 1.89E-09 1.70E-08 886 3.59E-08 1.89E-09 1.67E-05
short
ControlNet Fiber repeater -
1786-RPFM A 16,697,862 5.99E-08 2.99E-08 95% 2.99E-09 2.69E-08 886 5.69E-08 2.99E-09 2.65E-05
medium
ControlNet Fiber repeater -
1786-RPFRL A 5,717,227 1.75E-07 8.75E-08 95% 8.75E-09 7.87E-08 886 1.66E-07 8.75E-09 7.75E-05
long
1786-RPCD A ControlNet Hub repeater 28,654,080 3.49E-08 1.74E-08 95% 1.74E-09 1.57E-08 886 3.32E-08 1.74E-09 1.55E-05
1786-RPA B ControlNet repeater adapter 11,826,146 8.46E-08 4.23E-08 95% 4.23E-09 3.81E-08 886 8.03E-08 4.23E-09 3.75E-05
ControlNet Fiber repeater -
1786-RPFRXL B 11,373,440 8.79E-08 4.40E-08 95% 4.40E-09 3.96E-08 886 8.35E-08 4.40E-09 3.90E-05
extra long
Series
STR STR
(SFF) %
1756-L61(7) B ControlLogix controller, 2 MB 1,000,053 1.00E-06 5.00E-07 95% 5.00E-08 4.50E-07 886 9.50E-07 5.00E-08 4.43E-04
(7) B ControlLogix controller, 4 MB 1,034,830 9.66E-07 4.83E-07 95% 4.83E-08 4.35E-07 886 9.18E-07 4.83E-08 4.28E-04
1756-L62
1756-L63(7) B ControlLogix controller, 8 MB 1,055,910 9.47E-07 4.74E-07 95% 4.74E-08 4.26E-07 886 9.00E-07 4.74E-08 4.20E-04
ControlLogix-XT controller,
1756-L63XT(7) B 8 MB 357,760 2.80E-06 1.40E-06 95% 1.40E-07 1.26E-06 886 2.66E-06 1.40E-07 1.24E-03
1756-L71(8) B ControlLogix controller, 2 MB 2.69E-06 1.34E-06 96% 1.01E-07 1.25E-06 670 2.91E-06 1.01E-07 8.90E-04
1756-L72(8) B ControlLogix controller, 4 MB 2.69E-06 1.34E-06 96% 1.01E-07 1.25E-06 670 2.91E-06 1.01E-07 8.90E-04
1756-L73(8) B ControlLogix controller, 8 MB Calculated 2.69E-06 1.34E-06 96% 1.01E-07 1.25E-06 670 2.91E-06 1.01E-07 8.90E-04
MTBF and
ControlLogix-XT controller, PFD via
1756-L73XT(8) B 8 MB 2.69E-06 1.34E-06 96% 1.01E-07 1.25E-06 670 2.91E-06 1.01E-07 8.90E-04
FMEA
1756-L74(8) B ControlLogix controller, 16 MB 2.69E-06 1.34E-06 96% 1.01E-07 1.25E-06 670 2.91E-06 1.01E-07 8.90E-04
ControlLogix controller,
1756-L75(8) B 32 MB 2.69E-06 1.34E-06 96% 1.01E-07 1.25E-06 670 2.91E-06 1.01E-07 8.90E-04 Not applicable
GuardLogix controller, 2 MB
1756-L61S(7) B standard 1,000,053 1.00E-06 5.00E-07 95% 5.00E-08 4.50E-07 886 9.50E-07 5.00E-08 4.43E-04
GuardLogix controller, 4 MB
1756-L62S(7) B standard 1,034,830 9.66E-07 4.83E-07 95% 4.83E-08 4.35E-07 886 9.18E-07 4.83E-08 4.28E-04
GuardLogix controller, 8 MB
1756-L63S(7) B standard 1,055,910 9.47E-07 4.74E-07 95% 4.74E-08 4.26E-07 886 9.00E-07 4.74E-08 4.20E-04
GuardLogix controller, 2 MB
1756-L71S(8) B standard 2.69E-06 1.34E-06 96% 1.01E-07 1.25E-06 670 2.91E-06 1.01E-07 8.90E-04
GuardLogix-XT controller,
1756-L73SXT(8) B 8 MB standard 2.69E-06 1.34E-06 96% 1.01E-07 1.25E-06 670 2.91E-06 1.01E-07 8.90E-04
ControlLogix ControlNet
1756-CNB E 1,786,977 5.60E-07 2.80E-07 95% 2.80E-08 2.52E-07 886 5.32E-07 2.80E-08 2.48E-04
communication module
ControlLogix ControlNet
1756-CNBR E redundant communication 2,608,543 3.83E-07 1.92E-07 95% 1.92E-08 1.73E-07 886 3.64E-07 1.92E-08 1.70E-04
module
ControlLogix ControlNet
1756-CN2 B 1,096,299 9.12E-07 4.56E-07 95% 4.56E-08 4.10E-07 886 8.67E-07 4.56E-08 4.04E-04
communication module
Calculated
ControlLogix ControlNet MTBF and
1756-CN2(8) C communication module PFD via 1.97E-06 9.87E-07 96.6% 6.62E-08 9.21E-07 597.25 1.91E-06 6.62E-08 5.90E-04
FMEA
ControlLogix ControlNet
1756-CN2R B redundant communication 1,096,299 9.12E-07 4.56E-07 95% 4.56E-08 4.10E-07 886 8.67E-07 4.56E-08 4.04E-04 Not applicable
module
Calculated
ControlLogix ControlNet MTBF and
1756-CN2R(8) C redundant communication PFD via 1.97E-06 9.87E-07 96.6% 6.62E-08 9.21E-07 597.25 1.91E-06 6.62E-08 5.90E-04
module FMEA
ControlLogix-XT ControlNet
1756-CN2RXT B redundant communication 1,980,160 5.05E-07 2.53E-07 95% 2.53E-08 2.27E-07 886 4.80E-07 2.53E-08 2.24E-04
module
Calculated
ControlLogix-XT ControlNet MTBF and
1756-CN2RXT(8) C redundant communication PFD via 1.97E-06 9.87E-07 96.6% 6.62E-08 9.21E-07 597.25 1.91E-06 6.62E-08 5.90E-04
module FMEA
ControlLogix Data Highway
1756-DHRIO(9) E Plus remote I/O module 2,503,396 3.79E-07 7.59E-07
ControlLogix-XT Data
1756-DHRIOXT(9) E Highway Plus remote I/O 2,503,396 3.79E-07 7.59E-07
module Non-interference only Not applicable Not applicable
ControlLogix DeviceNet
1756-DNB(9) D communication module 2,192,202 4.33E-07 8.67E-07
ControlLogix EtherNet/IP
1756-ENBT(9) A communication module 2,088,198 4.55E-07 9.10E-07
ControlLogix EtherNet/IP
1756-EN2T C 1,312,712 7.62E-07 3.81E-07 95% 3.81E-08 3.43E-07 886 7.24E-07 3.81E-08 3.37E-04
communication module
ControlLogix EtherNet/IP
1756-EN2T(9) D communication module 269,774 Non-interference only 3.71E-06 Not applicable Not applicable
ControlLogix EtherNet/IP
1756-EN2TR B communication module with 3,664,960 2.73E-07 1.36E-07 95% 1.36E-08 1.23E-07 886 2.59E-07 1.36E-08 1.21E-04
fault tolerance
Series
STR STR
(SFF) %
ControlLogix EtherNet/IP
1756-EN2TR(8) C communication module with Calculated 1.97E-06 9.87E-07 96.6% 6.62E-08 9.21E-07 597.25 1.91E-06 6.62E-08 5.90E-04 3.82E-06 401.50 1.40E-09 1.22E-05
fault tolerance MTBF and
ControlLogix EtherNet/IP PFD via
1756-EN2TRXT(8) C communication module with FMEA 1.97E-06 9.87E-07 96.6% 6.62E-08 9.21E-07 597.25 1.91E-06 6.62E-08 5.90E-04 3.82E-06 401.50 1.40E-09 1.22E-05
fault tolerance
ControlLogix-XT EtherNet/IP 1,300,000
1756-EN2TXT C 7.69E-07 3.85E-07 95% 3.85E-08 3.46E-07 886 7.31E-07 3.85E-08 3.41E-04 Not applicable
communication module
ControlLogix-XT EtherNet/IP 269,774
1756-EN2TXT(9) D communication module 3.71E-06
ControlLogix EtherNet/IP
1756-EN3TR(9) B communication module with 269,774 3.71E-06
fault tolerance
ControlLogix redundancy
1756-RM(9) B module 1,373,840 6.91E-07
Not applicable
ControlLogix enhanced Non-interference only
1756-RM2(9) A redundancy module 250,182 4.00E-06
ControlLogix-XT enhanced
1756-RM2XT(9) A redundancy module 250,182 4.00E-06
ControlLogix-XT redundancy
1756-RMXT(9) B module 980,096 9.69E-07
ControlLogix SynchLink
1756-SYNCH(9) A Module 6,932,640 1.37E-07 Not applicable 2.74E-07 Not applicable
ControlLogix isolated V AC
1756-IA16I A 20,801,920 4.81E-08 2.40E-08 80% 9.61E-09 1.44E-08 3514 3.85E-08 9.61E-09 8.45E-05 7.69E-08 2346 4.82E-10 4.23E-06
input module
ControlLogix diagnostic V AC 15,966,080
1756-IA8D A 6.26E-08 3.13E-08 80% 1.25E-08 1.88E-08 3514 5.01E-08 1.25E-08 1.10E-04 1.00E-07 2346 6.29E-10 5.52E-06
input module
ControlLogix diagnostic V DC 30,228,640
1756-IB16D A 3.31E-08 1.65E-08 80% 6.62E-09 9.92E-09 3514 2.65E-08 6.62E-09 5.81E-05 5.29E-08 2346 3.32E-10 2.91E-06
input module
ControlLogix isolated V DC
1756-IB16I A 81,443,094 1.23E-08 6.14E-09 80% 2.46E-09 3.68E-09 3514 9.82E-09 2.46E-09 2.16E-05 1.96E-08 2346 1.23E-10 1.08E-06
input module
ControlLogix isolated V DC
1756-IB16ISOE A Sequence Of Events input 11,537,760 8.67E-08 4.33E-08 80% 1.73E-08 2.60E-08 3514 6.93E-08 1.73E-08 1.52E-04 1.39E-07 2346 8.71E-10 7.64E-06
module
ControlLogix V DC input
1756-IB32 B 10,462,329 9.56E-08 4.78E-08 80% 1.91E-08 2.87E-08 3514 7.65E-08 1.91E-08 1.68E-04 1.53E-07 2346 9.62E-10 8.43E-06
module
ControlLogix analog input
1756-IF8 A 8,699,254 1.15E-07 5.75E-08 80% 2.30E-08 3.45E-08 3514 9.20E-08 2.30E-08 2.02E-04 1.84E-07 2346 1.16E-09 1.01E-05
module
ControlLogix isolated analog 2,337,541
1756-IF8I(8) A input module 4.28E-07 2.139E-07 77% 9.81E-08 1.16E-07 4028 3.3E-07 9.81E-08 8.61E-04 6.59E-07 2688 2.12E-09 1.82E-05
Calculated
ControlLogix isolated analog MTBF and
1756-IF8I(8) B input module PFD via 5.83E-07 2.92E-07 78% 1.26E-07 1.66E-07 3784 4.58E-07 1.26E-07 1.11E-03 9.15E-07 2526 2.79E-09 2.37E-05
FMEA
ControlLogix HART analog
1756-IF8H A 1,291,978 7.74E-07 3.87E-07 80% 1.55E-07 2.32E-07 3514 6.19E-07 1.55E-07 1.36E-03 1.24E-06 2346 8.12E-09 7.02E-05
input module
ControlLogix analog input
1756-IF16 A 4,592,506 2.18E-07 1.09E-07 80% 4.35E-08 6.53E-08 3514 1.74E-07 4.35E-08 3.83E-04 3.48E-07 2346 2.21E-09 1.93E-05
module
ControlLogix HART analog
1756-IF16H A 442,914 2.26E-06 1.13E-06 80% 4.52E-07 6.77E-07 3514 1.81E-06 4.52E-07 3.97E-03 3.61E-06 2346 2.58E-08 2.17E-04
input module
ControlLogix isolated analog 2,654,080
1756-IF6CIS A 3.77E-07 1.88E-07 80% 7.54E-08 1.13E-07 3514 3.01E-07 7.54E-08 6.62E-04 6.03E-07 2346 3.86E-09 3.36E-05
input module
ControlLogix isolated analog 4,176,185
1756-IF6I A 2.39E-07 1.20E-07 80% 4.79E-08 7.18E-08 3514 1.92E-07 4.79E-08 4.21E-04 3.83E-07 2346 2.43E-09 2.12E-05
input module
ControlLogix V DC Sequence 2,150,720
1756-IH16ISOE A 4.65E-07 2.32E-07 80% 9.30E-08 1.39E-07 3514 3.72E-07 9.30E-08 8.17E-04 7.44E-07 2346 4.79E-09 4.17E-05
Of Events input module
ControlLogix isolated RTD
1756-IR6I A 4,268,525 2.34E-07 1.17E-07 80% 4.69E-08 7.03E-08 3514 3.75E-07 2346 2.38E-09 2.08E-05
input module
ControlLogix isolated RTD /
1756-IRT8I(8) A thermocouple input module 1,896,813 5.272E-07 2.636E-07 76% 1.27E-07 1.36E-07 4244 8.00E-07 2833 2.82E-09 2.40E-05
Calculated
ControlLogix isolated RTD / MTBF and
1756-IRT8I(8) B thermocouple input module PFD via 6.11E-07 3.06E-07 80% 1.24E-07 1.82E-07 3556 Not allowed for 1oo1 9.75E-07 2374 2.74E-09 2.33E-05
configurations
FMEA
ControlLogix isolated
1756-IT6I A 3,957,824 2.53E-07 1.26E-07 80% 5.05E-08 7.58E-08 3514 4.04E-07 2346 2.57E-09 2.24E-05
thermocouple input module
ControlLogix isolated
1756-IT6I2 A enhanced thermocouple 2,720,046 3.68E-07 1.84E-07 80% 7.35E-08 1.10E-07 3514 5.88E-07 2346 3.76E-09 3.28E-05
input module
ControlLogix V AC output
1756-OA16I A 32,891,456 3.04E-08 1.52E-08 80% 6.08E-09 9.12E-09 3514 2.43E-08 6.08E-09 5.34E-05 4.86E-08 2346 3.05E-10 2.67E-06
module
ControlLogix V AC diagnostic 11,311,040
1756-OA8D A 8.84E-08 4.42E-08 80% 1.77E-08 2.65E-08 3514 7.07E-08 1.77E-08 1.55E-04 1.41E-07 2346 8.89E-10 7.80E-06
output module
Series
STR STR
(SFF) %
ControlLogix V DC diagnostic 8,884,374
1756-OB16D A 1.13E-07 5.63E-08 80% 2.25E-08 3.38E-08 3514 9.00E-08 2.25E-08 1.98E-04 1.80E-07 2346 1.13E-09 9.94E-06
output module
ControlLogix V DC
1756-OB16E A electronically fused output 14,997,714 6.67E-08 3.33E-08 80% 1.33E-08 2.00E-08 3514 5.33E-08 1.33E-08 1.17E-04 1.07E-07 2346 6.70E-10 5.87E-06
module
ControlLogix V DC isolated
1756-OB16I A 7,388,160 1.35E-07 6.77E-08 80% 2.71E-08 4.06E-08 3514 1.08E-07 2.71E-08 2.38E-04 2.17E-07 2346 1.37E-09 1.20E-05
output module
ControlLogix V DC output
1756-OB32 A 2,681,316 3.73E-07 1.86E-07 80% 7.46E-08 1.12E-07 3514 2.98E-07 7.46E-08 6.55E-04 5.97E-07 2346 3.82E-09 3.33E-
module 05
ControlLogix V DC isolated
1756-OB8EI A electronic ally fused output 14,019,200 7.13E-08 3.57E-08 80% 1.43E-08 2.14E-08 3514 5.71E-08 1.43E-08 1.25E-04 1.14E-07 2346 7.17E-10 6.29E-06
module
ControlLogix isolated relay
1756-OX8I A 6,059,635 1.65E-07 8.25E-08 80% 3.30E-08 4.95E-08 3514 1.32E-07 3.30E-08 2.90E-04 2.64E-07 2346 1.67E-09 1.46E-05
output module
ControlLogix isolated relay
1756-OW16I A 13,695,899 7.30E-08 3.65E-08 80% 1.46E-08 2.19E-08 3514 5.84E-08 1.46E-08 1.28E-04 1.17E-07 2346 7.34E-10 6.43E-06
output module
ControlLogix analog output
1756-OF8 A 10,629,795 9.41E-08 4.70E-08 80% 1.88E-08 2.82E-08 3514 7.53E-08 1.88E-08 1.65E-04 1.51E-07 2346 9.46E-10 8.30E-06
module
ControlLogix isolated analog 2,213,369
1756-OF8I(8) A output module 4.52E-07 2.259E-07 76% 1.08E-07 1.18E-07 4202 3.44E-07 1.08E-07 9.49E-04 6.87E-07 2805 2.36E-09 2.01E-05
Calculated
ControlLogix isolated analog MTBF and
1756-OF8I(8) B output module PFD via 6.08E-07 3.04E-07 78% 1.37E-07 1.67E-07 3954 4.71E-07 1.37E-07 1.2E-03 9.42E-07 2639 3.06E-09 2.59E-05
FMEA
ControlLogix isolated analog 21,604,960
1756-OF6VI A 4.63E-08 2.31E-08 80% 9.26E-09 1.39E-08 3514 3.70E-08 9.26E-09 8.13E-05 7.41E-08 2346 4.64E-10 4.07E-06
output module
ControlLogix isolated analog 8,354,667
1756-OF6CI A 1.20E-07 5.98E-08 80% 2.39E-08 3.59E-08 3514 9.58E-08 2.39E-08 2.10E-04 1.92E-07 2346 1.21E-09 1.06E-05
output module
ControlLogix HART analog
1756-OF8H A 5,118,187 1.95E-07 9.77E-08 80% 3.91E-08 5.86E-08 3514 1.56E-07 3.91E-08 3.43E-04 3.13E-07 2346 1.98E-09 1.73E-05
output module
1794-ACN15 D FLEX I/O ControlNet adapter 8,223,684 1.22E-07 6.08E-08 80% 2.43E-08 3.65E-08 3514 1.95E-07 2346 1.23E-09 1.07E-05
FLEX I/O ControlNet
1794-ACNR15 D 8,223,684 1.22E-07 6.08E-08 80% 2.43E-08 3.65E-08 3514 1.95E-07 2346 1.23E-09 1.07E-05
redundant adapter
FLEX I/O-XT ControlNet
1794-ACNR15XT D 8,223,684 1.22E-07 6.08E-08 80% 2.43E-08 3.65E-08 3514 1.95E-07 2346 1.23E-09 1.07E-05
adapter Not allowed for 1oo1
1794-AENT B FLEX I/O EtherNet/IP adapter 1,779,827 5.62E-07 2.81E-07 80% 1.12E-07 1.69E-07 3514 configurations 8.99E-07 2346 5.82E-09 5.05E-05
FLEX I/O EtherNet/IP
1794-AENTR A 1,268,070 7.89E-07 3.94E-07 80% 1.58E-07 2.37E-07 3514 1.26E-06 2346 8.28E-09 7.16E-05
adapter, Ring media
FLEX I/O EtherNet/IP
1794-AENTRXT A 1,268,070 7.89E-07 3.94E-07 80% 1.58E-07 2.37E-07 3514 1.26E-06 2346 8.28E-09 7.16E-05
adapter, Ring media
FLEX I/O 24V DC input
1794-IB16 A 179,506,158 5.57E-09 2.79E-09 80% 1.11E-09 1.67E-09 3514 8.91E-09 2346 5.57E-11 4.90E-07
module
FLEX I/O-XT 24V DC input
1794-IB16XT A 35,587,189 2.81E-08 1.40E-08 80% 5.62E-09 8.43E-09 3514 4.50E-08 2346 2.82E-10 2.47E-06
module
1794-IJ2 A FLEX I/O counter module 55,344,640 1.81E-08 9.03E-09 80% 3.61E-09 5.42E-09 3514 2.89E-08 2346 1.81E-10 1.59E-06
1794-IJ2XT A FLEX I/O-XT counter module 11,714,128 8.54E-08 4.27E-08 80% 1.71E-08 2.56E-08 3514 Not allowed for 1oo1 1.37E-07 2346 8.58E-10 7.53E-06
configurations
1794-IP4 B FLEX I/O counter module 22,027,200 4.54E-08 2.27E-08 80% 9.08E-09 1.36E-08 3514 7.26E-08 2346 4.55E-10 4.00E-06
FLEX I/O 24V DC
1794-IB10XOB6 A 100,000,000 1.00E-08 5.00E-09 80% 2.00E-09 3.00E-09 3514 1.60E-08 2346 1.00E-10 8.79E-07
input/output module
FLEX I/O-XT 24V DC
1794-IB10XOB6XT A 22,202,487 4.50E-08 2.25E-08 80% 9.01E-09 1.35E-08 3514 7.21E-08 2346 4.52E-10 3.96E-06
input/output module
FLEX I/O 24V DC
1794-OB8EP A electronically fused output 100,000,000 1.00E-08 5.00E-09 80% 2.00E-09 3.00E-09 3514 1.60E-08 2346 1.00E-10 8.79E-07
module
FLEX I/O-XT 24V DC
1794-OB8EPXT A electronically fused output 14,771,049 6.77E-08 3.38E-08 80% 1.35E-08 2.03E-08 3514 1.08E-07 2346 6.80E-10 5.96E-06
module
FLEX I/O 24V DC output
1794-OB16 A 54,322,632 1.84E-08 9.20E-09 80% 3.68E-09 5.52E-09 3514 2.95E-08 2346 1.84E-10 1.62E-06
module
Not allowed for 1oo1
FLEX I/O 24V DC protected configurations
1794-OB16P A 100,000,000 1.00E-08 5.00E-09 80% 2.00E-09 3.00E-09 3514 1.60E-08 2346 1.00E-10 8.79E-07
output module
FLEX I/O-XT 24V DC
1794-OB16PXT A 26,709,401 3.74E-08 1.87E-08 80% 7.49E-09 1.12E-08 3514 5.99E-08 2346 3.75E-10 3.29E-06
protected output module
FLEX I/O isolated relay
1794-OW8 A 29,088,895 3.44E-08 1.72E-08 80% 6.88E-09 1.03E-08 3514 5.50E-08 2346 3.45E-10 3.02E-06
output module
FLEX I/O-XT isolated relay
1794-OW8XT A 18,518,519 5.40E-08 2.70E-08 80% 1.08E-08 1.62E-08 3514 8.64E-08 2346 5.42E-10 4.75E-06
output module
Series
STR STR
(SFF) %
1794-IE8 B FLEX I/O analog input module 18,914,770 5.29E-08 2.64E-08 80% 1.06E-08 1.59E-08 3514 8.46E-08 2346 5.30E-10 4.65E-06
FLEX I/O-XT analog input
1794-IE8XT B 14,041,000 7.12E-08 3.56E-08 80% 1.42E-08 2.14E-08 3514 1.14E-07 2346 7.15E-10 6.28E-06
module
FLEX I/O isolated analog
1794-IF4I A 9,885,959 1.01E-07 5.06E-08 80% 2.02E-08 3.03E-08 3514 1.62E-07 2346 1.02E-09 8.92E-06
input module
FLEX I/O-XT isolated analog
1794-IF4IXT A 7,297,140 1.37E-07 6.85E-08 80% 2.74E-08 4.11E-08 3514 2.19E-07 2346 1.38E-09 1.21E-05
input module
FLEX I/O-XT isolated analog
1794-IF4ICFXT A 7,297,140 1.37E-07 6.85E-08 80% 2.74E-08 4.11E-08 3514 2.19E-07 2346 1.38E-09 1.21E-05
input module
Flex, 8 Isolated HART Analog 926,808
1794-IF8IHNFXT A 1.08E-06 5.39E-07 80% 2.16E-07 3.24E-07 3514 1.73E-06 2346 1.15E-08 9.91E-05
Input, extended env
1794-IR8 A FLEX I/O RTD input module 5,016,231 1.99E-07 9.97E-08 80% 3.99E-08 5.98E-08 3514 3.19E-07 2346 2.02E-09 1.77E-05
FLEX I/O-XT RTD input Not allowed for 1oo1
1794-IR8XT A 9,585,890 1.04E-07 5.22E-08 80% 2.09E-08 3.13E-08 3514 configurations 1.67E-07 2346 1.05E-09 9.20E-06
module
FLEX I/O RTD/Thermocouple 1,407,269
1794-IRT8 B 7.11E-07 3.55E-07 80% 1.42E-07 2.13E-07 3514 1.14E-06 2346 7.43E-09 6.43E-05
input module
FLEX I/O-XT RTD/
1794-IRT8XT B Thermocouple input module 8,204,792 1.22E-07 6.09E-08 80% 2.44E-08 3.66E-08 3514 1.95E-07 2346 1.23E-09 1.08E-05
5-year PFD Calculations The PFD calculations in this table are calculated for a 5-year proof test interval
(43,800 hours) and are specific to ControlLogix system components.
Table 12 - 5-Year PFD Calculations
Common Terms(3) 1oo1 Configuration 1oo2 Configuration
Mean Time
between Safe
Cat No.(1)(2) Description Failure Spurious Spurious
s, d Failure TCE1oo1
(4) Fraction du
dd Trip Rate PFH(5) PFD Trip Rate TGE PFH(5) PFD
(MTBF)(2)
Series
STR STR
(SFF) %
1756-AXX(6) C ControlLogix chassis 22,652,010 4.41E-08 2.21E-08 95% 2.21E-09 1.99E-08 2200 4.19E-08 2.21E-09 4.86E-05
4-slot ControlLogix-XT
1756-A4LXT B 1,069,120 9.35E-07 4.68E-07 95% 4.68E-08 4.21E-07 2200 8.89E-07 4.68E-08 1.03E-03
chassis
5-slot ControlLogix-XT
1756-A5XT C 734,420 1.36E-06 6.81E-07 95% 6.81E-08 6.13E-07 2200 1.29E-06 6.81E-08 1.50E-03
chassis
7-slot ControlLogix-XT
1756-A7LXT B 27,628,178 3.62E-08 1.81E-08 95% 1.81E-09 1.63E-08 2200 3.44E-08 1.81E-09 3.98E-05
chassis
7-slot ControlLogix-XT
1756-A7XT C 1,081,600 9.25E-07 4.62E-07 95% 4.62E-08 4.16E-07 2200 8.78E-07 4.62E-08 1.02E-03
chassis
18-32V DC 10 A
1756-PB72 C ControlLogix power 31,561,095 3.17E-08 1.58E-08 95% 1.58E-09 1.43E-08 2200 3.01E-08 1.58E-09 3.49E-05
supply
85-265V AC 10 A
1756-PA72 C ControlLogix power 18,336,146 5.45E-08 2.73E-08 95% 2.73E-09 2.45E-08 2200 5.18E-08 2.73E-09 6.00E-05
supply
85-265V AC 13 A
1756-PA75 B ControlLogix power 18,693,044 5.35E-08 2.67E-08 95% 2.67E-09 2.41E-08 2200 5.08E-08 2.67E-09 5.88E-05
supply (75 W)
85-265V AC 13 A
1756-PA75R A Redundant ControlLogix 1,412,877 7.08E-07 3.54E-07 95% 3.54E-08 3.18E-07 2200 6.72E-07 3.54E-08 7.79E-04
power supply
18-32V DC 13 A
1756-PB75 B ControlLogix power 15,675,475 6.38E-08 3.19E-08 95% 3.19E-09 2.87E-08 2200 6.06E-08 3.19E-09 7.02E-05
supply
18-32V DC 13 A
1756-PB75R A Redundant ControlLogix 1,736,020 5.76E-07 2.88E-07 95% 2.88E-08 2.59E-07 2200 5.47E-07 2.88E-08 6.34E-04
power supply Not applicable
ControlLogix-XT AC
1756-PAXT B 18,693,044 5.35E-08 2.67E-08 95% 2.67E-09 2.41E-08 2200 5.08E-08 2.67E-09 5.88E-05
power supply
ControlLogix-XT DC
1756-PBXT B 1,855,360 5.39E-07 2.69E-07 95% 2.69E-08 2.43E-07 2200 5.12E-07 2.69E-08 5.93E-04
power supply
30-60V DC 13 A
1756-PC75 B ControlLogix power 5,894,836 1.70E-07 8.48E-08 95% 8.48E-09 7.63E-08 2200 1.61E-07 8.48E-09 1.87E-04
supply
90-143V DC 13 A
1756-PH75 B ControlLogix power 2,119,520 4.72E-07 2.36E-07 95% 2.36E-08 2.12E-07 2200 4.48E-07 2.36E-08 5.19E-04
supply
Redundant power supply 45,146,727
1756-PSCA A 2.21E-08 1.11E-08 95% 1.11E-09 9.97E-09 2200 2.10E-08 1.11E-09 2.44E-05
adapter
Redundant power supply 38,461,280
1756-PSCA2 A 2.60E-08 1.30E-08 95% 1.30E-09 1.17E-08 2200 2.47E-08 1.30E-09 2.86E-05
adapter
ControlNet Fiber repeater 26,461,760
1786-RPFS A 3.78E-08 1.89E-08 95% 1.89E-09 1.70E-08 2200 3.59E-08 1.89E-09 4.16E-05
- short
ControlNet Fiber repeater 16,697,862
1786-RPFM A 5.99E-08 2.99E-08 95% 2.99E-09 2.69E-08 2200 5.69E-08 2.99E-09 6.59E-05
- medium
ControlNet Fiber repeater 5,717,227
1786-RPFRL A 1.75E-07 8.75E-08 95% 8.75E-09 7.87E-08 2200 1.66E-07 8.75E-09 1.92E-04
- long
1786-RPCD A ControlNet Hub repeater 28,654,080 3.49E-08 1.74E-08 95% 1.74E-09 1.57E-08 2200 3.32E-08 1.74E-09 3.84E-05
ControlNet repeater
1786-RPA B 11,826,146 8.46E-08 4.23E-08 95% 4.23E-09 3.81E-08 2200 8.03E-08 4.23E-09 9.30E-05
adapter
ControlNet Fiber repeater 11,373,440
1786-RPFRXL B 8.79E-08 4.40E-08 95% 4.40E-09 3.96E-08 2200 8.35E-08 4.40E-09 9.67E-05
- extra long
Series
STR STR
(SFF) %
ControlLogix controller,
1756-L61(7) B 2 MB 1,000,053 1.00E-06 5.00E-07 95% 5.00E-08 4.50E-07 2200 9.50E-07 5.00E-08 1.10E-03
ControlLogix controller,
1756-L62(7) B 4 MB 1,034,830 9.66E-07 4.83E-07 95% 4.83E-08 4.35E-07 2200 9.18E-07 4.83E-08 1.06E-03
ControlLogix controller,
1756-L63(7) B 8 MB 1,055,910 9.47E-07 4.74E-07 95% 4.74E-08 4.26E-07 2200 9.00E-07 4.74E-08 1.04E-03
ControlLogix-XT
1756-L63XT(7) B controller, 8 MB 357,760 2.80E-06 1.40E-06 95% 1.40E-07 1.26E-06 2200 2.66E-06 1.40E-07 3.07E-03
ControlLogix controller,
1756-L71(8) B 2 MB
2.69E-06 1.34E-06 96% 1.01E-07 1.25E-06 1661 2.91E-06 1.01E-07 2.20E-03
ControlLogix controller,
1756-L72(8) B 4 MB 2.69E-06 1.34E-06 96% 1.01E-07 1.25E-06 1661 2.91E-06 1.01E-07 2.20E-03
ControlLogix controller,
1756-L74(8) B 16 MB 2.69E-06 1.34E-06 96% 1.01E-07 1.25E-06 1661 2.91E-06 1.01E-07 2.20E-03 Not applicable
ControlLogix controller,
1756-L75(8) B 32 MB 2.69E-06 1.34E-06 96% 1.01E-07 1.25E-06 1661 2.91E-06 1.01E-07 2.20E-03
GuardLogix controller,
1756-L61S(7) B 2 MB standard 1,000,053 1.00E-06 5.00E-07 95% 5.00E-08 4.50E-07 2200 9.50E-07 5.00E-08 1.10E-03
GuardLogix controller,
1756-L62S(7) B 4 MB standard 1,034,830 9.66E-07 4.83E-07 95% 4.83E-08 4.35E-07 2200 9.18E-07 4.83E-08 1.06E-03
GuardLogix controller,
1756-L63S(7) B 8 MB standard 1,055,910 9.47E-07 4.74E-07 95% 4.74E-08 4.26E-07 2200 9.00E-07 4.74E-08 1.04E-03
GuardLogix controller,
1756-L71S(8) B 2 MB standard 2.69E-06 1.34E-06 96% 1.01E-07 1.25E-06 1661 2.91E-06 1.01E-07 2.20E-03
GuardLogix-XT controller,
1756-L73SXT(8) B 8 MB standard 2.69E-06 1.34E-06 96% 1.01E-07 1.25E-06 1661 2.91E-06 1.01E-07 2.20E-03
ControlLogix ControlNet
1756-CNB E 1,786,977 5.60E-07 2.80E-07 95% 2.80E-08 2.52E-07 2200 5.32E-07 2.80E-08 6.16E-04
communication module
ControlLogix ControlNet
1756-CNBR E redundant 2,608,543 3.83E-07 1.92E-07 95% 1.92E-08 1.73E-07 2200 3.64E-07 1.92E-08 4.22E-04
communication module
ControlLogix ControlNet
1756-CN2 B 1,096,299 9.12E-07 4.56E-07 95% 4.56E-08 4.10E-07 2200 8.67E-07 4.56E-08 1.00E-03
communication module
Calculated
ControlLogix ControlNet MTBF and
1756-CN2(8) C communication module PFD via 1.97E-06 9.87E-07 96.6% 6.62E-08 9.21E-07 1478.14 1.91E-06 6.62E-08 1.50E-03
FMEA
ControlLogix ControlNet
1756-CN2R B redundant 1,096,299 9.12E-07 4.56E-07 95% 4.56E-08 4.10E-07 2200 8.67E-07 4.56E-08 1.00E-03 Not applicable
communication module
Calculated
ControlLogix ControlNet MTBF and
1756-CN2R(8) C redundant PFD via 1.97E-06 9.87E-07 96.6% 6.62E-08 9.21E-07 1478.14 1.91E-06 6.62E-08 1.50E-03
communication module FMEA
ControlLogix-XT
1756-CN2RXT B ControlNet redundant 1,980,160 5.05E-07 2.53E-07 95% 2.53E-08 2.27E-07 2200 4.80E-07 2.53E-08 5.56E-04
communication module
Calculated
ControlLogix-XT MTBF and
1756-CN2RXT(8) C ControlNet redundant PFD via 1.97E-06 9.87E-07 96.6% 6.62E-08 9.21E-07 1478.14 1.91E-06 6.62E-08 1.50E-03
communication module FMEA
ControlLogix Data
1756-DHRIO(9) E Highway Plus Remote I/O 2,503,396 3.79E-07 2.00E-08 7.59E-07
Module
ControlLogix-XT Data
1756-DHRIOXT(9) E Highway Plus remote I/O 2,503,396 3.79E-07 2.00E-08 Not 7.59E-07
module Non-interference only Not applicable
applicable
(9) ControlLogix DeviceNet
1756-DNB D 2,192,202 4.33E-07 2.28E-08 8.67E-07
communication module
ControlLogix EtherNet/IP 2,088,198
1756-ENBT(9) A communication module 4.55E-07 2.39E-08 9.10E-07
Series
STR STR
(SFF) %
ControlLogix EtherNet/IP 1,312,712
1756-EN2T C 7.62E-07 3.81E-07 95% 3.81E-08 3.43E-07 2200 7.24E-07 3.81E-08 8.38E-04
communication module
ControlLogix EtherNet/IP 269,774
1756-EN2T(9) D communication module Non-interference only 3.71E-06 Not applicable Not applicable
ControlLogix EtherNet/IP
1756-EN2TR B communication module 3,664,960 2.73E-07 1.36E-07 95% 1.36E-08 1.23E-07 2200 2.59E-07 1.36E-08 3.00E-04
with fault tolerance
ControlLogix EtherNet/IP
1756-EN2TR(8) C communication module Calculated 1.97E-06 9.87E-07 96.6% 6.62E-08 9.21E-07 1478.14 1.91E-06 6.62E-08 1.50E-03 3.82E-06 988.76 1.51E-09 3.19E-05
with fault tolerance MTBF and
ControlLogix EtherNet/IP PFD via
1756-EN2TRXT(8) C communication module FMEA 1.97E-06 9.87E-07 96.6% 6.62E-08 9.21E-07 1478.14 1.91E-06 6.62E-08 1.50E-03 3.82E-06 988.76 1.51E-09 3.19E-05
with fault tolerance
ControlLogix-XT
1756-EN2TXT C EtherNet/IP 1,300,000 7.69E-07 3.85E-07 95% 3.85E-08 3.46E-07 2200 7.31E-07 3.85E-08 8.46E-04 Not applicable
communication module
ControlLogix-XT
1756-EN2TXT(9) D EtherNet/IP 269,774 3.71E-06
communication module
ControlLogix EtherNet/IP
1756-EN3TR B communication module 269,774 3.71E-06
with fault tolerance
ControlLogix redundancy 1,373,840
1756-RM(9) B module 6.91E-07
Not applicable
ControlLogix enhanced Non-interference only
1756-RM2(9) A redundancy module 250,182 4.00E-06
ControlLogix-XT
1756-RM2XT(9) A enhanced redundancy 250,182 4.00E-06
module
ControlLogix-XT
1756-RMXT(9) B redundancy module 980,096 9.69E-07
ControlLogix SynchLink
1756-SYNCH(9) A Module 6,932,640 1.37E-07 Not applicable 2.74E-07 Not applicable
ControlLogix isolated V
1756-IA16I A 20,801,920 4.81E-08 2.40E-08 80% 9.61E-09 1.44E-08 8770 3.85E-08 9.61E-09 2.11E-04 7.69E-08 5850 4.84E-10 1.06E-05
AC input module
ControlLogix diagnostic V 15,966,080
1756-IA8D A 6.26E-08 3.13E-08 80% 1.25E-08 1.88E-08 8770 5.01E-08 1.25E-08 2.75E-04 1.00E-07 5850 6.33E-10 1.38E-05
AC input module
ControlLogix diagnostic V 30,228,640
1756-IB16D A 3.31E-08 1.65E-08 80% 6.62E-09 9.92E-09 8770 2.65E-08 6.62E-09 1.45E-04 5.29E-08 5850 3.33E-10 7.28E-06
DC input module
ControlLogix isolated V
1756-IB16I A 81,443,094 1.23E-08 6.14E-09 80% 2.46E-09 3.68E-09 8770 9.82E-09 2.46E-09 5.38E-05 1.96E-08 5850 1.23E-10 2.70E-06
DC input module
ControlLogix isolated V
1756-IB16ISOE A DC Sequence Of Events 11,537,760 8.67E-08 4.33E-08 80% 1.73E-08 2.60E-08 8770 6.93E-08 1.73E-08 3.80E-04 1.39E-07 5850 8.79E-10 1.92E-05
input module
ControlLogix V DC input
1756-IB32 B 10,462,329 9.56E-08 4.78E-08 80% 1.91E-08 2.87E-08 8770 7.65E-08 1.91E-08 4.19E-04 1.53E-07 5850 9.70E-10 2.12E-05
module
ControlLogix analog input 8,699,254
1756-IF8 A 1.15E-07 5.75E-08 80% 2.30E-08 3.45E-08 8770 9.20E-08 2.30E-08 5.04E-04 1.84E-07 5850 1.17E-09 2.55E-05
module
ControlLogix isolated
1756-IF8I(8) A analog input module 2,337,541 4.28E-07 2.139E-07 77% 9.81E-08 1.16E-07 10054 3.3E-07 9.81E-08 2.15E-03 6.59E-07 6706 2.37E-09 4.89E-05
Calculated
ControlLogix isolated MTBF and
1756-IF8I(8) B analog input module PFD via 5.83E-07 2.92E-07 78% 1.26E-07 1.66E-07 9445 4.58E-07 1.26E-07 2.77E-03 9.15E-07 6300 3.19E-09 6.51E-05
FMEA
ControlLogix HART analog 1,291,978
1756-IF8H A 7.74E-07 3.87E-07 80% 1.55E-07 2.32E-07 8770 6.19E-07 1.55E-07 3.39E-03 1.24E-06 5850 8.69E-09 1.84E-04
input module
ControlLogix analog input 4,592,506
1756-IF16 A 2.18E-07 1.09E-07 80% 4.35E-08 6.53E-08 3514 1.74E-07 4.35E-08 3.83E-04 3.48E-07 2346 2.21E-09 1.93E-05
module
ControlLogix HART analog 442,914
1756-IF16H A 2.26E-06 1.13E-06 80% 4.52E-07 6.77E-07 8770 1.81E-06 4.52E-07 9.90E-03 3.61E-06 5850 3.06E-08 6.13E-04
input module
ControlLogix isolated
1756-IF6CIS A 2,654,080 3.77E-07 1.88E-07 80% 7.54E-08 1.13E-07 8770 3.01E-07 7.54E-08 1.65E-03 6.03E-07 5850 3.99E-09 8.59E-05
analog input module
ControlLogix isolated
1756-IF6I A 4,176,185 2.39E-07 1.20E-07 80% 4.79E-08 7.18E-08 8770 1.92E-07 4.79E-08 1.05E-03 3.83E-07 5850 2.49E-09 5.38E-05
analog input module
ControlLogix V DC
1756-IH16ISOE A Sequence Of Events input 2,150,720 4.65E-07 2.32E-07 80% 9.30E-08 1.39E-07 8770 3.72E-07 9.30E-08 2.04E-03 7.44E-07 5850 4.99E-09 1.07E-04
module
Series
STR STR
(SFF) %
ControlLogix isolated RTD 4,268,525
1756-IR6I A 2.34E-07 1.17E-07 80% 4.69E-08 7.03E-08 8770 3.75E-07 5850 2.43E-09 5.26E-05
input module
ControlLogix isolated 2.636E-
1756-IRT8I(8) A RTD/thermocouple input 1,896,813 5.27E-07 07 76% 1.274E-07 1.362E-07 10594 8.00E-07 7066 3.23E-09 6.58E-05
module
Calculated
ControlLogix isolated MTBF and
1756-IRT8I(8) B RTD/thermocouple input PFD via 6.11E-07 3.06E-07 80% 1.24E-07 1.82E-07 8874 Not allowed for 1oo1 configurations 9.75E-07 5919 3.13E-09 6.39E-05
module FMEA
ControlLogix isolated
1756-IT6I A thermocouple input 3,957,824 2.53E-07 1.26E-07 80% 5.05E-08 7.58E-08 8770 4.04E-07 5850 2.63E-09 5.69E-05
module
ControlLogix isolated
1756-IT6I2 A enhanced thermocouple 2,720,046 3.68E-07 1.84E-07 80% 7.35E-08 1.10E-07 8770 5.88E-07 5850 3.89E-09 8.37E-05
input module
ControlLogix V AC output 32,891,456
1756-OA16I A 3.04E-08 1.52E-08 80% 6.08E-09 9.12E-09 8770 2.43E-08 6.08E-09 1.33E-04 4.86E-08 5850 3.05E-10 6.69E-06
module
ControlLogix V AC
1756-OA8D A diagnostic output module 11,311,040 8.84E-08 4.42E-08 80% 1.77E-08 2.65E-08 8770 7.07E-08 1.77E-08 3.88E-04 1.41E-07 5850 8.96E-10 1.96E-05
ControlLogix V DC
1756-OB16D A diagnostic output module 8,884,374 1.13E-07 5.63E-08 80% 2.25E-08 3.38E-08 8770 9.00E-08 2.25E-08 4.94E-04 1.80E-07 5850 1.15E-09 2.50E-05
ControlLogix V DC
1756-OB16E A electronically fused 14,997,714 6.67E-08 3.33E-08 80% 1.33E-08 2.00E-08 8770 5.33E-08 1.33E-08 2.92E-04 1.07E-07 5850 6.74E-10 1.47E-05
output module
ControlLogix V DC
1756-OB16I A 7,388,160 1.35E-07 6.77E-08 80% 2.71E-08 4.06E-08 8770 1.08E-07 2.71E-08 5.94E-04 2.17E-07 5850 1.38E-09 3.01E-05
isolated output module
ControlLogix V DC output 2,681,316
1756-OB32 A 3.73E-07 1.86E-07 80% 7.46E-08 1.12E-07 8770 2.98E-07 7.46E-08 1.64E-03 5.97E-07 5850 3.95E-09 8.50E-05
module
ControlLogix V DC
1756-OB8EI A isolated electronically 14,019,200 7.13E-08 3.57E-08 80% 1.43E-08 2.14E-08 8770 5.71E-08 1.43E-08 3.13E-04 1.14E-07 5850 7.21E-10 1.58E-05
fused output module
ControlLogix isolated
1756-OX8I A 6,059,635 1.65E-07 8.25E-08 80% 3.30E-08 4.95E-08 8770 1.32E-07 3.30E-08 7.24E-04 2.64E-07 5850 1.69E-09 3.68E-05
relay output module
ControlLogix isolated
1756-OW16I A 13,695,899 7.30E-08 3.65E-08 80% 1.46E-08 2.19E-08 8770 5.84E-08 1.46E-08 3.20E-04 1.17E-07 5850 7.39E-10 1.61E-05
relay output module
ControlLogix analog
1756-OF8 A 10,629,795 9.41E-08 4.70E-08 80% 1.88E-08 2.82E-08 8770 7.53E-08 1.88E-08 4.13E-04 1.51E-07 5850 9.55E-10 2.08E-05
output module
ControlLogix isolated
1756-OF8I(8) A analog output module 2,213,369 4.52E-07 2.259E-07 76% 1.08E-07 1.18E-07 10490 3.44E-07 1.08E-07 2.37E-03 6.87E-07 6997 2.65E-09 5.46E-05
Calculated MTBF
ControlLogix isolated
1756-OF8I(8) B analog output module and PFD via 6.08E-07 3.04E-07 78% 1.37E-07 1.67E-07 9869 4.71E-07 1.37E-07 3.0E-03 9.42E-07 6583 3.53E-09 7.16E-05
FMEA
ControlLogix isolated
1756-OF6VI A 21,604,960 4.63E-08 2.31E-08 80% 9.26E-09 1.39E-08 8770 3.70E-08 9.26E-09 2.03E-04 7.41E-08 5850 4.66E-10 1.02E-05
analog output module
ControlLogix isolated
1756-OF6CI A 8,354,667 1.20E-07 5.98E-08 80% 2.39E-08 3.59E-08 8770 9.58E-08 2.39E-08 5.25E-04 1.92E-07 5850 1.22E-09 2.66E-05
analog output module
ControlLogix HART analog 5,118,187
1756-OF8H A 1.95E-07 9.77E-08 80% 3.91E-08 5.86E-08 8770 1.56E-07 3.91E-08 8.57E-04 3.13E-07 5850 2.01E-09 4.37E-05
output module
FLEX I/O ControlNet
1794-ACN15 D 8,223,684 1.22E-07 6.08E-08 80% 2.43E-08 3.65E-08 8770 1.95E-07 5850 1.24E-09 2.70E-05
adapter
FLEX I/O ControlNet
1794-ACNR15 D 8,223,684 1.22E-07 6.08E-08 80% 2.43E-08 3.65E-08 8770 1.95E-07 5850 1.24E-09 2.70E-05
redundant adapter
FLEX I/O-XT ControlNet
1794-ACNR15XT D 8,223,684 1.22E-07 6.08E-08 80% 2.43E-08 3.65E-08 8770 1.95E-07 5850 1.24E-09 2.70E-05
adapter
Not allowed for 1oo1 configurations
FLEX I/O EtherNet/IP
1794-AENT B 1,779,827 5.62E-07 2.81E-07 80% 1.12E-07 1.69E-07 8770 8.99E-07 5850 6.12E-09 1.30E-04
adapter
FLEX I/O EtherNet/IP
1794-AENTR A 1,268,070 7.89E-07 3.94E-07 80% 1.58E-07 2.37E-07 8770 1.26E-06 5850 8.87E-09 1.87E-04
adapter, Ring media
FLEX I/O EtherNet/IP
1794-AENTRXT A 1,268,070 7.89E-07 3.94E-07 80% 1.58E-07 2.37E-07 8770 1.26E-06 5850 8.87E-09 1.87E-04
adapter, Ring media
FLEX I/O 24V DC input
1794-IB16 A 179,506,158 5.57E-09 2.79E-09 80% 1.11E-09 1.67E-09 8770 8.91E-09 5850 5.58E-11 1.22E-06
module
FLEX I/O-XT 24V DC input 35,587,189
1794-IB16XT A 2.81E-08 1.40E-08 80% 5.62E-09 8.43E-09 8770 4.50E-08 5850 2.82E-10 6.18E-06
module
1794-IJ2 A FLEX I/O counter module 55,344,640 1.81E-08 9.03E-09 80% 3.61E-09 5.42E-09 8770 2.89E-08 5850 1.81E-10 3.97E-06
FLEX I/O-XT counter
1794-IJ2XT A 11,714,128 8.54E-08 4.27E-08 80% 1.71E-08 2.56E-08 8770 Not allowed for 1oo1 configurations 1.37E-07 5850 8.65E-10 1.89E-05
module
1794-IP4 B FLEX I/O counter module 22,027,200 4.54E-08 2.27E-08 80% 9.08E-09 1.36E-08 8770 7.26E-08 5850 4.57E-10 1.00E-05
FLEX I/O 24V DC
1794-IB10XOB6 A 100,000,000 1.00E-08 5.00E-09 80% 2.00E-09 3.00E-09 8770 1.60E-08 5850 1.00E-10 2.19E-06
input/output module
FLEX I/O-XT 24V DC
1794-IB10XOB6XT A 22,202,487 4.50E-08 2.25E-08 80% 9.01E-09 1.35E-08 8770 7.21E-08 5850 4.54E-10 9.92E-06
input/output module
Series
STR STR
(SFF) %
FLEX I/O 24V DC
1794-OB8EP A electronically fused 100,000,000 1.00E-08 5.00E-09 80% 2.00E-09 3.00E-09 8770 1.60E-08 5850 1.00E-10 2.19E-06
output module
FLEX I/O-XT 24V DC
1794-OB8EPXT A electronically fused 14,771,049 6.77E-08 3.38E-08 80% 1.35E-08 2.03E-08 8770 1.08E-07 5850 6.84E-10 1.49E-05
output module
FLEX I/O 24V DC output
1794-OB16 A 54,322,632 1.84E-08 9.20E-09 80% 3.68E-09 5.52E-09 8770 2.95E-08 5850 1.85E-10 4.04E-06
module
FLEX I/O 24V DC Not allowed for 1oo1 configurations
1794-OB16P A protected output module 100,000,000 1.00E-08 5.00E-09 80% 2.00E-09 3.00E-09 8770 1.60E-08 5850 1.00E-10 2.19E-06
Series
STR STR
(SFF) %
FLEX I/O terminal base
1794-TB3 A 250,000,000 4.00E-09 2.00E-09 80% 8.00E-10 1.20E-09 8770 6.40E-09 5850 4.00E-11 8.77E-07
unit
FLEX I/O cage-clamp
1794-TB3G A generic terminal base 100,000,000 1.00E-08 5.00E-09 80% 2.00E-09 3.00E-09 8770 1.60E-08 5850 1.00E-10 2.19E-06
unit
FLEX I/O spring-clamp
1794-TB3GS A generic terminal base 100,000,000 1.00E-08 5.00E-09 80% 2.00E-09 3.00E-09 8770 1.60E-08 5850 1.00E-10 2.19E-06
unit
FLEX I/O terminal base
1794-TB3S A 100,000,000 1.00E-08 5.00E-09 80% 2.00E-09 3.00E-09 8770 1.60E-08 5850 1.00E-10 2.19E-06
unit Not allowed for 1oo1 configurations
FLEX I/O temperature
1794-TB3T A 100,000,000 1.00E-08 5.00E-09 80% 2.00E-09 3.00E-09 8770 1.60E-08 5850 1.00E-10 2.19E-06
terminal base unit
FLEX I/O spring-clamp
1794-TB3TS A temperature terminal 52,312,000 1.91E-08 9.56E-09 80% 3.82E-09 5.73E-09 8770 3.06E-08 5850 1.92E-10 4.20E-06
base unit
FLEX I/O NEMA terminal
1794-TBN A 100,000,000 1.00E-08 5.00E-09 80% 2.00E-09 3.00E-09 8770 1.60E-08 5850 1.00E-10 2.19E-06
base unit
FLEX I/O NEMA fused
1794-TBNF A 100,000,000 1.00E-08 5.00E-09 80% 2.00E-09 3.00E-09 8770 1.60E-08 5850 1.00E-10 2.19E-06
terminal base unit
DC input termination
1492-TIFM40F-F24A-2(9) A board 7,779,000 7.04E-08 1.03E-07
DC output termination
1492-TIFM4OF-24-2(9) A board 10,127,000 0.00E+00 0.00E+00
(1) Some catalog numbers have a K suffix. This indicates a version of the product that has conformal coating. These K versions have the same SIL 2 certification as the non-K versions. For more information on which
products have conformal coating go to http://ab.com.rockwellautomation.com/
(2) MTBF measured in hours unless calculated (as noted). Field return values – January 2012.
(3) Calculations performed on a per module basis.
(4) = Failure Rate = 1/MTBF.
(5) Demand rate must be less than 10 per year
(6) Average of 1756-A4, -A7, -A10, -A13, and -A17 chassis.
(7) Suitable for use only in applications requiring compliance to IEC 61508 1999 Edition 1
(8) Calculated MTBF and PFD by FMEA to 61508-2010.
(9) SIL 2-rated for non-interference in the chassis. Data not required within a safety function.
Using Component Values The system PFD value is calculated by totaling the PFD value of each
to Calculate System PFD component in the system. To calculate a system PFD value, use this equation:
modA PFD + modB PFD + modC PFD = system PFD
where modX PFD is the PFD value for one component or module in the system.
When calculating your system PFD, verify that all components that are used in
the system are totaled.
See Figure 6 on page 18 for a system diagram of the example calculation that is
shown here.
If you plan to use the 1756 I/O or the 1794 FLEX™ I/O modules in a SIL 1 1oo1
configuration, Table 13 guidelines must be implemented, including either the
use diagnostic modules or implementing appropriate field diagnostics as
defined here for limited high demand applications with up to 10 demands per
year.
• Field diagnostics must execute once every 8 hours for limited high
demand applications with up to 10 demands per year.
• An output or other sensing device must be used to provide field power
control to the digital inputs. See the SIL 2 output guidelines in Chapter ,
ControlLogix I/O Modules.
• You must consider the time that it takes a diagnostic to execute when
determining the safety reaction time because safety demands will not be
detectable if they occur during a diagnostic.
The diagnostic you implement must monitor the ability of all SIL 1 inputs
to detect a change of state. One example method would be to turn off the
output and monitor that all SIL 1 inputs detect the loss of signal within a
short period. Then, when the output turns back on, make sure that all SIL
1 inputs properly detect the change. You must consider and mitigate any
impact to your system while the diagnostic is executing.
Figure 64 - SIL 1 Digital Input Wiring Example for 1794 I/O Modules
Field Power
Field Devices
1
SIL 1 Output SIL 1 Input 1
2
SIL 1 Input 2
3
SIL 1 Input 3
Field diagnostics as described for 1794 I/O modules can also be used to meet the
requirements for periodic proof testing with either 1794 or 1756 I/O modules.
Reference Voltages
1492-CABLExxxUA() to 1756
Analog Input Module DIP Switch for Sensor
Wiring
Precision 249
Resistor
Reference Voltages
User-supplied cable
DIP Switch for Sensor
Wiring
Precision 249
Resistor
To make your own cable, follow the termination board pinout that is shown
here.
P1 Pins Description
3 Input 0
2 Input 1
1 Input 2
14 Input 3
15 Input 4
16 Input 5
17 Input 6
18 Input 7
12 Input 8
13 Input 9
25 Input 10
24 Input 11
23 Input 12
22 Input 13
20 Input 14
21 Input 15
P1 Pins Description
4 RTN
6 RTN
8 RTN
10 RTN
Checklists
Checklist for the The following checklist is required for planning, programming, and start up of
ControlLogix System a SIL 2-certified ControlLogix® system. It can be used as a planning guide and
during proof testing. If used as a planning guide, the checklist can be saved as
a record of the plan.
Checklist for SIL Inputs The following checklist is required for planning, programming, and startup of
SIL inputs. It can be used as a planning guide and during proof testing. If used
as a planning guide, the checklist can be saved as a record of the plan.
Checklist for SIL Outputs The following checklist is required for planning, programming, and startup of
SIL outputs. It can be used as a planning guide and during proof testing. If
used as a planning guide, the checklist can be saved as a record of the plan.
Checklist for the Creation of The following checklist is recommended to maintain safety technical aspects
an Application Program when programming, before and after loading the new or modified program.
Numerics communication
ControlNet components 42
1oo1 configuration 108 data echo 32
1oo2 configuration 108 Data Highway Plus - Remote I/O components
1-year PFD calculations 110 43
2-year PFD calculations 115 EtherNet/IP components 43
5-year PFD calculations 120 field-side output verification 32
network 34
requirements 43
A output data echo 49
SynchLink modules 43
actuators 84 compliances 29
Add-On Instructions 45, 82 components
alarms 1756 chassis 38
1756 analog input modules 54, 93 1756 power supply 38
analog input modules FLEX I/O 104 - 105
See ControlLogix analog input modules. configurations
See FLEX I/O analog input modules. fail-safe 13
analog output modules fault-tolerant 25
See ControlLogix analog output modules. high-availability 21
See FLEX I/O analog output modules. connections
application program direct 47
programming languages 81 rack-optimized 47
SIL task/program instructions 85 Control and Information Protocol (CIP) 7
applications control function
boiler 11 specification 83
combustion 11 CONTROLLERDEVICE object 93
gas and fire 10 controllers
requirements 38
ControlLogix
B analog input modules
boiler applications 11 alarms 54, 93
calibrate 54
ownership 56
C wiring 56
analog output modules
cable calibrate 62
ControlNet network 42 ownership 64
calculations wiring 64
1-year PFD 110 digital input modules
2-year PFD 115 requirements 47
5-year PFD 120 wiring 47
explanation of 109 digital output modules
PFD 107 requirements 49
calibrate wiring 50
1756 analog input modules 54 RTD input modules
1756 analog output modules 62 wiring 60
1794 analog input modules 71 thermocouple input modules
1794 analog output modules 77 wiring 59
certification 29 ControlNet communication modules
change parameters 96 diagnostic coverage 42
channel status ControlNet network 34
monitoring 54, 63 1756 communication modules 41
chassis 38 1756 components 42
cable 42
chassis adapter 39 repeater module 42
checklists 131 coordinated system time 43
CIP. See Control and Information Protocol.
CL SIL 2 29
combustion applications 11 D
commissioning life cycle 87 data echo 32, 49
E H
edit hardware
application program 88, 89 1756 chassis 38
emergency shutdown applications 10, 13, 50, 63 1756 power supply 38
EN 50156 12 HART analog input modules 61
ESD. See emergency shutdown (ESD) wiring 61
applications. HART analog output modules 66
EtherNet/IP network 34 wiring 66
1756 communication modules 41 high-availability configuration 21
components 43 HMI
changing parameters via 96
devices 12, 43, 95
F use and application 95 - 96
FactoryTalk Security 82 hold last state 10
fail-safe configuration
about 13
fault detection 93 I
fault handling I/O modules
additional resources 94 calibrate 54
detection of faults 91 - 93 fault reporting 92
fault reporting 31, 92 proof test
1794 analog input modules 72 1756 analog input modules 53
1794 analog output modules 77 1756 analog output modules 62
1794 digital input modules 68 1756 digital input modules 47
1794 digital output modules 69, 70 1756 digital output modules 49
additional resources 94 1794 analog output modules 77
detection of faults 91 - 93 1794 digital input modules 67
fault-tolerant configuration 25 1794 digital output modules 69
wiring
field devices 1756 analog input modules 56
testing 47 1756 analog output modules 64
field-side output verification 32 1756 digital input modules 47
fire 1756 digital output modules 50
considerations for 10 1756 RTD input modules 60
FLEX I/O 1756 thermocouple input modules 59
analog input modules 1794 analog input modules 73
calibrate 71 1794 analog output modules 79
wiring 73 1794 digital input modules 68
1794 digital output modules 70
T
terminal base units
FLEX I/O 105
tests
1756 analog input modules 53
1756 analog output modules 62
1756 digital output modules 49
application logic 85
field devices 47
proof 27
pulse 33
thermocouple input module
See ControlLogix thermocouple input
module.
See FLEX I/O thermocouple input module.
V
verify
download and operation 86
W
watchdog 29
Notes:
Documentation Feedback
Your comments help us serve your documentation needs better. If you have any suggestions on how to improve our
content, complete the form at rok.auto/docfeedback.
At the end of life, this equipment should be collected separately from any unsorted municipal waste.
Rockwell Automation maintains current product environmental compliance information on its website at rok.auto/pec.
Allen-Bradley, ControlLogix, ControlLogix-XT, Data Highway Plus, DH+, FactoryTalk, FLEX, FLEX I/O-XT, GuardLogix, GuardLogix-XT, Logix 5000, Rockwell Automation, Rockwell Software, RSLogix
5000, RSNetWorx, SequenceManager, Stratix, Studio 5000 Logix Designer, and SynchLink are trademarks of Rockwell Automation, Inc.
CIP, ControlNet, DeviceNet, and EtherNet/IP are trademarks of ODVA, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Rockwell Otomasyon Ticaret A.Ş. Kar Plaza İş Merkezi E Blok Kat:6 34752, İçerenköy, İstanbul, Tel: +90 (216) 5698400 EEE Yönetmeliğine Uygundur