4.12.080-210-004-01 Clarified Water Storage tank-Layout1-A1

This document provides notes and specifications for construction dimensions, materials, and structural requirements for a water tank project. Key details include: - All dimensions are in centimeters and elevations in meters. - Structural requirements include loads in kilonewtons and structures designed to withstand pressure when full or empty. - Concrete specifications include 7 cm lean concrete and 30MPa characteristic strength. - Steel yield strength is 415MPa. - Tolerances include 2 mm/m flatness for plinths. - The document specifies responsibilities for excavation, piping, coatings, waterstops, and other materials.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
144 views1 page

4.12.080-210-004-01 Clarified Water Storage tank-Layout1-A1

This document provides notes and specifications for construction dimensions, materials, and structural requirements for a water tank project. Key details include: - All dimensions are in centimeters and elevations in meters. - Structural requirements include loads in kilonewtons and structures designed to withstand pressure when full or empty. - Concrete specifications include 7 cm lean concrete and 30MPa characteristic strength. - Steel yield strength is 415MPa. - Tolerances include 2 mm/m flatness for plinths. - The document specifies responsibilities for excavation, piping, coatings, waterstops, and other materials.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

A B C D E F G H

NOTE

General
All dimensions are in cm, levels are in meter
WL= Waterlevel (m)WC= Water column
TOC= Top Of Concrete
EOF= Emergency Overflow
Backfill with selected excaved material compacted in 30cm layers
Exact positions for concrete penetrations, bulkheads,...: see drawings piping and equipment
5 Dimensions of foundations for information only 5
TOP VIEW Structural requirements
All loads expressed in kN.
All structures are waterproof according to the best practice.
The thickness of the walls and slabs are given as indication and must be calculated in a structural study. All the
structural must be calculated to be stable and resistant when empty and under pressure independent of static or
dynamic charges due to what the structure contains, if the structure contains compartments that communicate with
eachother, the structural study shall take in the account the compartment could be empty while the other
compartment full
Lean concrete: 7 cm

Steel: 415MPa (yield strength)


Concrete: 30MPa (characteristics cubic strength)
Tolerances

Flatness of plinths: 2 mm/m.

Seals
The excavation and filling of the trenches for pipes that are found under the structure are the responsibility of the
Civil Contractor.
The bulkhead parts are supplied by Waterleau and place and sealed by the Civil Contractor.
The handrails, walkways, stairs and ladders are given indicatively and will be provided by Waterlleau and installed
by civil contractor.
te
concre VIEW Coating will be supplied by civil contractor
4 4
Waterstop will be supplied by civil contractor.
glass coated
A A
ext no
reinforc
ement zo
ne

+0.00

20
Total structural dead load: 24kN
3 3
Tank diameter int.
Sealer plate 1 per angle by WTL Mastic fillet by WTL
Galvanized foundation angle by WTL Floor sheets glass fused to steel by WTL
Shims 25 mm by WTL Polystyrene sheets to Kay-Cel EPS 150, 25mm thick

+0.00

Reinforcement by client Circumferential reinforcing

20
20 bar exclusion zone
200 x 200 mm by client

M20 chemical resin


foundation bolt by WTL

Note:
20 cm wide peripheral base area should be within
+/-5mm of specified level and should not vary
more than +/-3mm in any length.

SECTION A-A 01 Redraw SVL SVDH BL 05/12/2016


00 Initial issue SVL TB BL 31/10/12
2 Issue Description Drawn Checked Approved Date 2
CLIENT : SCOP

WC 350

MAIN CONTRACTOR :
Intra Ratbaa
430,4
350

Glass coated steel

Detail concrete SUPPLIER : WATERLEAU


base connection
Radioweg 18 - 3020 Herent - Belgium
+0.00 +0.00 Tel: +32(0)16 650 657 - Fax: +32(0)16 650 663
[email protected] - www.waterleau.com
20

20
20 This drawing is the confidential property of WATERLEAU Group N.V. Information and know how hereon are confidential and may not
1 be used, reproduces or revealed to others except in accord with contract or other written permissions of WATERLEAU Group N.V. 1
Any reproductions in whole or in part including shop drawings shall bear or refer to this stamp.
Status Format
WASTE WATER TREATMENT PLANT Preliminary A1

SCOP Page 1 of 1 1/50


AMARAH - IRAK

CIVIL GUIDE LINE


4.12.080
Issue
CLARIFIED WATER
STORAGE TANK 4.12.080-210-004 01