1.2 - Structural Loads and Loading System - Engineering LibreTexts
1.2 - Structural Loads and Loading System - Engineering LibreTexts
Example 1.2.1
The semi-gravity retaining wall shown in Figure 2.1 Figure 2.1 is made of mass concrete with a unit weight of 23.6
kN/m3. Determine the length of the wall’s weight per foot.
Example 1.2.1
The floor system of the classroom shown in Figure 2.2 consists of a 3-inch-thick reinforced concrete slab supported
by steel beams. If the weight of each steel beam is 62 lb/ft, determine the dead load in lb/ft supported by any
interior beam.
Fig. 2.2. Classroom floor system.
Solution
Dead load due to slab weight =
where
I = impact factor.
L = length in feet (or meters) of the span-loaded segment to cause maximum stress in the member under
consideration.
Table 2.3. Building live load impact factors, as specified in ASCE/SEI 7-16.
Loading Case I(%)
where
R = rain load on the undeflected roof, in psi or KN/m2.
ds = depth of water on the undeflected roof up to the inlet of the secondary drainage system (i.e. the static head), in
inches or mm.
dh = additional depth of water on the undeflected roof above the inlet of the secondary drainage system (i.e. the
hydraulic head), in inches or mm. It depends on the flow rate, the size of the drainage, and the area drained by each
drain.
The flow rate, Q, in gallons per minute, can be computed as follows:
Q (gpm) = 0.0104 Ai
where
A = roof area in square feet drained by the drainage system.
i = 100-yr., 1-hr. rainfall intensity in inches per hour for the building location specified in the plumbing code.
Fig. 2.3. Roof drainage system (Adapted from the International Code Council).
To determine the magnitude of wind velocity and its pressure at various elevations above ground level, the ASCE 7-16
modified equation 2.2 by introducing some factors to account for the height of the structure above ground level, the
importance of the structure in regard to human life and property, and the topography of its location, as follows:
where
Kz = the velocity pressure coefficient that depends on the height of the structure and the exposure condition. The values
of Kz are listed in Table 2.4.
Kzt = a topographic factor that accounts for an increase in wind velocity due to sudden changes in topography where
there are hills and escarpments. This factor is an equal unity for building on level ground and increases with elevation.
Kd = wind directionality factor. It accounts for the reduced probability of maximum wind coming from any given
direction and for the reduced probability of the maximum pressure developing on any wind direction most
unfavorable to the structure. For structures subjected to wind loads only, Kd = 1; for structures subjected to other loads,
in addition to a wind load, Kd values are tabulated in Table 2.5.
Ke = ground elevation factor. According to section 26.9 in ASCE 7-16, it is expressed as Ke = 1 for all elevations.
V = velocity of wind measured at a height z above ground level.
The three exposure conditions categorized as B, C, and D in Table 2.4 are defined in terms of surface roughness, as
follows:
Exposure B: The surface roughness for this category includes urban and suburban areas, wooden areas, or other terrain
with closely spaced obstructions. This category applies to buildings with mean roof heights of ≤ 30 ft (9.1 m) if the
surface extends in the upwind direction for a distance greater than 1,500 ft. For buildings with mean roof heights
greater than 30 ft (9.1 m), this category will apply if the surface roughness in the upwind direction is greater than 2,600
ft (792 m) or 20 times the height of the building, whichever is greater.
Exposure C: Exposure C applies where surface roughness C prevails. Surface roughness C includes open terrain with
scattered obstructions having heights less than 30 ft.
Exposure D: The surface roughness for this category includes flats, smooth mud flats, salt flats, unbroken ice,
unobstructed areas, and water surfaces. Exposure D applies where surface roughness D extends in the upwind
direction for a distance greater than 5,000 ft or 20 times the building height, whichever is greater. This also applies if
the surface roughness upwind is B or C, and the site is within 600 ft (183 m) or 20 times the building height, whichever
is greater.
Table 2.4. Velocity pressure exposure coefficient, Kz, as specified in ASCE 7-16.
Table 2.5. Wind directional factor, Kd, as specified in ASCE 7-16.
Structure Type Kd
To obtain the final external pressures for the design of structures, equation 2.3 is further modified, as follows:
where
Pz = design wind pressure on a face of the structure at height z above ground level. It increases with the height on
the windward wall, but it is constant with the height on the leeward and side walls.
G = gust effect factor. G = 0.85 for rigid structures with a natural frequency of ≥ 1 Hz. The gust factors for flexible
structures are calculated using the equations in ASCE 7-16.
Cp = external pressure coefficient. It is a fraction of the external pressure on the windward walls, leeward walls, side
walls, and roof. The values of Cp are presented in Tables 2.6 and 2.7.
To compute the wind load that will be used for member design, combine the external and internal wind pressures, as
follows:
where
GCpi = the internal pressure coefficient from ASCE 7-16.
Fig. 2.4. Typical wind distribution on a structureus walls and roof.
Table 2.6. Wall pressure coefficient, Cp, as specified in ASCE 7-16.
Notes:
1.Positive and negative signs are indicative of the wind pressures acting toward and away from the surfaces.
2.L is the dimension of the building normal to the wind direction, and B is the dimension parallel to the wind direction.
Table 2.7. Roof pressure coefficients, Cp, for use with qh, as specified in ASCE 7-16.
Example 1.2.1
The two-story building shown in Figure 2.5 is an elementary school located on a flat terrain in a suburban area,
with a wind speed of 102 mph and exposure category B. What is the wind velocity pressure at roof height for the
main wind force resisting system (MWFRS)?
where
рf = design flat roof snow load.
рs = design snow load for a sloped roof.
рg = ground snow load.
I = importance factor. See Table 2.9 for importance factor values, depending on the category of the building.
Ce = exposure factor. See Table 2.10 for exposure factor values, depending on the terrain category.
Ct = thermal factor. See Table 2.11 for typical values.
Cs = slope factor. Values of Cs are provided in section 7.4.1 through 7.4.4 of ASCE 7-16, depending on various
factors.
Table 2.8. Typical ground snow loads, as specified in ASCE 7-16.
Location Load (PSF)
Lancaster, PA 30
Yakutat, AK 150
New York City, NY 30
San Francisco, CA 5
Chicago, IL 25
Tallahassee, FL 0
Table 2.9. Importance factor for snow load, Is, as specified in ASCE 7-16.
Risk Category of Structure Importance Factor
I 0.8
II 1.0
III 1.1
IV 1.2
Structures kept just above freezing and others with cold, ventilated
roofs in which the thermal resistance (R-value) between the
1.1
ventilated space and the heated space exceeds 25° F × h × ft2/Btu
2
(4.4 K × m /W)
Unheated and open air structures 1.2
Structures intentionally kept below freezing 1.3
Continuously heated greenhouses with a roof having a thermal
0.85
resistance (R-value) less than 2.0 ° F × h × ft2/Btu
Example 2.4
A single-story heated residential building located in the suburban area of Lancaster, PA is considered partially
exposed. The roof of the building slopes at 1 on 20, and it is without overhanging eaves. What is the design snow load
on the roof?
Solution
According to Figure 7.2-1 in ASCE 7-16, the ground snow load for Lancaster, PA is
рg = 30 psf.
Since 30 psf > 20 psf, the rain-on-snow surcharge is not required.
Since 21 psf > 20Is = (20 psf)(1) = 20 psf. Therefore, the design flat roof snow load is 21 psf.
2.1.4.4 Seismic Loads
The ground motion caused by seismic forces in many geographic regions of the world can be quite significant and
often damages structures. This is particularly notable in regions near active geological faults. Thus, most building codes
and standards require that structures be designed for seismic forces in such areas where earthquakes are likely to
occur. The ASCE 7-16 standard provides numerous analytical methods for estimating the seismic forces when
designing structures. One of these methods of analysis, which will be described in this section, is referred to as the
equivalent lateral force (ELF) procedure. The lateral base shear V and the lateral seismic force at any level computed by
the ELF are shown in Figure 2.6. According to the procedure, the total static lateral base shear, V, in a specific direction
for a building is given by the following expression:
where
V = lateral base shear for the building. The estimated value of V must satisfy the following condition:
W = effective seismic weight of the building. It includes total dead load of the building and its permanent equipment
and partitions.
T = fundamental natural period of a building, which depends on the mass and the stiffness of the structure. It is
computed using the following empirical formula:
Ct = building period coefficient. The value of Ct = 0.028 for structural steel moment resisting frames, 0.016 for
reinforced concrete rigid frames, and 0.02 for most other structures (see Table 2.12).
ℎn = height of the highest level of the building, and x = 0.8 for steel rigid moment frames, 0.9 for reinforced concrete
rigid frames, and 0.75 for other systems.
Table 2.12. Ct values for various structural systems.
Structural System Ct x
SDI = design spectral acceleration. It is estimated by using a seismic map that provides an earthquake’s intensity of
design for structures at locations with T = 1 second.
SDs = design spectral acceleration. It is estimated by using a seismic map that provides an earthquake’s intensity of
design for structures with T = 0.2 second.
R = response modification coefficient. It accounts for the ability of a structural system to resist seismic forces. The
values of R for several common systems are presented in Table 2.13.
I = importance factor. This is a measure of the consequences to human life and damage to property in the event that the
structure fails. The value of the importance factor is 1 for office buildings, but equals 1.5 for hospitals, police stations,
and other public buildings where loss of more life or damages to property are anticipated should a structure fail.
Table 2.13. Response modification coefficient, R, as specified in ASCE 7-16.
Seismic Force-Resisting System R
where
Fx = lateral seismic force applied to level x.
Wi and Wx = effective seismic weights at levels i and x.
ℎi and ℎx = heights from the base of the structure to floors at levels i and x.
Determine the dead load at each level. Since the flat roof snow load given for the office building is greater than 30 psf,
20% of the snow load must be included in the seismic dead load computations.
The weight assigned to the roof level is as follows:
Wroof = (32 psf)(75 ft)(100 ft) + (20%)(40psf)(75 ft)(100 ft) = 300,000 lb
The weight assigned to all other levels is as follows:
Wi = (80 psf)(75ft)(100 ft) = 600,000 lb
The total dead load is as follows:
WTotal = 300,000 lb + (4)(600,000 lb) = 2700 k
Calculate the seismic response coefficient Cs.
Where
γ = unit weight of the retained material.
ℎ = distance from the surface of the retained material and the point under consideration.
2.1.4.6 Miscellaneous Loads
There are numerous other loads that may also be considered when designing structures, depending on specific cases.
Their inclusion in the load combinations will be based on a designer’s discretion if they are perceived to have a future
significant impact on structural integrity. These loads include thermal forces, centrifugal forces, forces due to
differential settlements, ice loads, flooding loads, blasting loads, and more.
2.2 Load Combinations for Structural Design
Structures are designed to satisfy both strength and serviceability requirements. The strength requirement ensures the
safety of life and property, while the serviceability requirement guarantees the comfortability of occupancy (people)
and the aesthetics of the structure. To meet the afore-stated requirements, structures are designed for the critical or the
largest load that would act on them. The critical load for a given structure is found by combining all the various
possible loads that a structure may carry during its lifetime. Sections 2.3.1 and 2.4.1 of ASCE 7-16 provide the following
load combinations for use when designing structures by the Load and Resistance Factor Design (LRFD) and the
Allowable Strength Design (ASD) methods.
For LRFD, the load combinations are as follows:
1.1.4D
2.1.2 D + 1.6L + 0.5(LrorS or R)
3.1.2D + 1.6(Lr or S or R) + (L or 0.5W)
4.1.2D + 1.0W + L + 0.5(Lr or S or R)
5.0.9D + 1.0W
For ASD, the load combinations are as follows:
1.D
2.D + L
3.D + (Lr or S or R)
4.D + 0.75L + 0.75(Lr or S or R)
5.D + (0.6W)
where
D = dead load.
L = live load due to occupancy.
Lr = roof live load.
S = snow load.
R = nominal load due to initial rainwater or ice, exclusive of the ponding contributions.
W = wind load.
E = earthquake load.
Example 2.6
A floor system consisting of wooden joists spaced 6 ft apart on the center and a tongue and groove wood boarding, as
shown in Figure 2.8, supports a dead load (including the weight of the beam and boarding) of 20 psf and a live load of
30 psf. Determine the maximum factored load in lb/ft that each floor joist must support using the LRFD load
combinations.
where
L = reduced design live load per ft2 (or m2).
≥ 0.50 Lo for structural members supporting one floor (e.g. beams, girders, slabs, etc.).
≥ 0.40 Lo for structural members supporting two or more floors (e.g. columns, etc.).
No reduction is permitted for floor live loads greater than 4.79 kN/m2(100 lb/ft2) or for floors of public assembly, such
as stadiums, auditoriums, movie theaters, etc., as there is a greater possibility of such floors being overloaded or used
as car garages.
Lo = unreduced design live load per ft2 (or m2) from Table 2.2 (Table 4.3-1 in ASCE 7-16).
AT = tributary area of member in ft2 (or m2).
KLL = AI/AT = live load element factor from Table 2.14 (see values tabulated in Table 4.7-1 in ASCE 7-16).
AI = KLLAT = influence area.
Table 2.14. Live load element factor.
Example 2.7
A four-story school building used for classrooms has its columns spaced as shown in Figure 2.10. The flat roof loading
of the structure is estimated to be 25 lb/ft2. Determine the reduced live load supported by an interior column at the
ground level.
According to Table 4.1 in ASCE 7-16, the reduced load as a fraction of the unreduced floor live load for a classroom is
Live loads: These are loads of varying magnitudes and positions. They include moveable loads and loads due to
occupancy.
Impact loads: Impact loads are sudden or rapid loads applied on a structure over a relatively short period of time
compared with other structural loads.
Rain loads: These are loads due to accumulation of water on a roof top after a rainstorm.
Wind loads: These are loads due to wind pressure exerted on structures.
Snow loads: These are loads exerted on a structure by accumulated snow on a rooftop.
Earthquake loads: These are loads exerted on a structure by the ground motion caused by seismic forces.
Hydrostatic and earth pressures: These are loads on retaining structures due to pressures developed by the retained
materials. They vary linearly with the height of the walls.
Load combinations: The two building design methods are the Load and Resistance Factor Design method (LRFD) and
the Allowable Strength Design method (ASD). Some of the load combinations for these methods are shown below.
LRFD:
1.1.4D
2.1.2 D + 1.6L + 0.5(LrorS or R)
3.1.2D + 1.6(Lr or S or R) + (L or 0.5W)
4.1.2D + 1.0W + L + 0.5(Lr or S or R)
5.0.9D + 1.0W
ASD:
1.D
2.D + L
3.D + (Lr or S or R)
4.D + 0.75L + 0.75(Lr or S or R)
5.D + (0.6W)
References
ACI (2016), Building Code Requirements for Structural Concrete (ACI 318-14), American Concrete Institute.
ASCE (2016), Minimum Design Loads for Buildings and Other Structures, ASCE 7-16, ASCE.
ICC (2012), International Building Code, International Code Council.
Practice Problems
2.1 Determine the maximum factored moment for a roof beam subjected to the following service load moments:
MD = 40 psf (dead load moment)
MLr = 36 psf (roof live load moment)
Ms = 16 psf (snow load moment)
2.2 Determine the maximum factored load sustained by a column subjected to the following service loads:
PD = 500 kips (dead load)
PL = 280 kips (floor live load)
PS = 200 kips (snow load)
PE = ±30 kips (earthquake load)
Pw = ±70 kips (wind load)
2.3 The typical layout of a steel-reinforced concrete composite floor system of a library building is shown in Figure
P2.1. Determine the dead load in lb/ft acting on a typical interior beam B1-B2 in the second floor. All beams are W12 ×
44, spaced at 10 ft o.c. The distributed loads on the second floor are as follows: