ISA-67.01.01-2002 (R2007) - Transducer and Transmitter Installation For Nuclear Safety Applications
ISA-67.01.01-2002 (R2007) - Transducer and Transmitter Installation For Nuclear Safety Applications
01–2002 (R2007)
Transducer and Transmitter
Installation for Nuclear Safety Applications
ISBN: 978-1-934394-47-2
Copyright ©2007 by ISA. All rights reserved. Not for resale. Printed in the United States of America. No
part of this publication may be reproduced, stored in a retrieval system, or transmitted in any form or by
any means (electronic mechanical, photocopying, recording, or otherwise), without the prior written
permission of the Publisher.
ISA
67 Alexander Drive
P.O. Box 12277
Research Triangle Park, North Carolina 27709
Preface
This preface, as well as all footnotes and annexes, is included for information purposes and is not part of
ISA–67.01.01–2002 (R2007).
This document has been prepared as part of the service of ISA toward a goal of uniformity in the field of
instrumentation. To be of real value, this document should not be static but should be subject to periodic
review. Toward this end, the Society welcomes all comments and criticisms and asks that they be
addressed to the Secretary, Standards and Practices Board; ISA; 67 Alexander Drive; P. O. Box 12277;
Research Triangle Park, NC 27709; Telephone (919) 549-8411; Fax (919) 549-8288; E-mail:
[email protected].
The ISA Standards and Practices Department is aware of the growing need for attention to the metric
system of units in general, and the International System of Units (SI) in particular, in the preparation of
instrumentation standards. The Department is further aware of the benefits to USA users of ISA
standards of incorporating suitable references to the SI (and the metric system) in their business and
professional dealings with other countries. Toward this end, this Department will endeavor to introduce
SI-acceptable metric units in all new and revised standards, recommended practices, and technical
reports to the greatest extent possible. Standard for Use of the International System of Units (SI): The
Modern Metric System, published by the American Society for Testing & Materials as IEEE/ASTM SI 10-
97, and future revisions, will be the reference guide for definitions, symbols, abbreviations, and
conversion factors.
It is the policy of ISA to encourage and welcome the participation of all concerned individuals and
interests in the development of ISA standards, recommended practices, and technical reports.
Participation in the ISA standards-making process by an individual in no way constitutes endorsement by
the employer of that individual, of ISA, or of any of the standards, recommended practices, and technical
reports that ISA develops.
EVEN IF ISA IS UNAWARE OF ANY PATENT COVERING THIS DOCUMENT, THE USER IS
CAUTIONED THAT IMPLEMENTATION OF THE DOCUMENT MAY REQUIRE USE OF TECHNIQUES,
PROCESSES, OR MATERIALS COVERED BY PATENT RIGHTS. ISA TAKES NO POSITION ON THE
EXISTENCE OR VALIDITY OF ANY PATENT RIGHTS THAT MAY BE INVOLVED IN IMPLEMENTING
THE DOCUMENT. ISA IS NOT RESPONSIBLE FOR IDENTIFYING ALL PATENTS THAT MAY
REQUIRE A LICENSE BEFORE IMPLEMENTATION OF THE DOCUMENT OR FOR INVESTIGATING
THE VALIDITY OR SCOPE OF ANY PATENTS BROUGHT TO ITS ATTENTION. THE USER SHOULD
CAREFULLY INVESTIGATE RELEVANT PATENTS BEFORE USING THE DOCUMENT FOR THE
USER’S INTENDED APPLICATION.
HOWEVER, ISA ASKS THAT ANYONE REVIEWING THIS DOCUMENT WHO IS AWARE OF ANY
PATENTS THAT MAY IMPACT IMPLEMENTATION OF THE DOCUMENT NOTIFY THE ISA
STANDARDS AND PRACTICES DEPARTMENT OF THE PATENT AND ITS OWNER.
PROFESSIONAL JUDGMENT CONCERNING ITS USE AND APPLICABILITY UNDER THE USER’S
PARTICULAR CIRCUMSTANCES. THE USER MUST ALSO CONSIDER THE APPLICABILITY OF
ANY GOVERNMENTAL REGULATORY LIMITATIONS AND ESTABLISHED SAFETY AND HEALTH
PRACTICES BEFORE IMPLEMENTING THIS DOCUMENT.
THE USER OF THIS DOCUMENT SHOULD BE AWARE THAT THIS DOCUMENT MAY BE IMPACTED
BY ELECTRONIC SECURITY ISSUES. THE COMMITTEE HAS NOT YET ADDRESSED THE
POTENTIAL ISSUES IN THIS VERSION.
The following people served as members of the ISA67.01 Subcommittee and approved this document in
1994:
NAME COMPANY
The following people served as members of the ISA67 Committee and approved the document in 1994:
NAME COMPANY
This standard was approved for publication by the ISA Standards and Practices Board on 15 November
1994.
NAME COMPANY
The following people served as voting members of the ISA67 Committee and reaffirmed ISA–67.01.01–
2002 (R2007):
NAME COMPANY
This standard was approved for reaffirmation by the ISA Standards and Practices Board on 1 April 2008.
NAME COMPANY
Contents
1 Scope ..................................................................................................................................................... 9
2 Purpose.................................................................................................................................................. 9
6 Location of equipment.......................................................................................................................... 14
7 Environmental considerations.............................................................................................................. 15
8 Interface connections........................................................................................................................... 16
10 Quality assurance............................................................................................................................. 19
1 Scope
This document covers the installation of transducers for nuclear safety-related applications.
2 Purpose
This document establishes requirements and recommendations for the installation of transducers and
auxiliary equipment for nuclear applications outside of the main reactor vessel.
3.2 code:
refers to the ASME Boiler and Pressure Vessel Code, Section III* and other sections required to
implement the requirements of Section III.
3.4 in-line:
transducers exposed directly to the process fluid in piping, vessels, equipment, or the main flow paths of
fluid systems.
b) containment isolation
g) providing reasonable assurance that a nuclear power plant can be operated without undue risk to
health and safety of the public.
3.6 off-line:
transducers that are either connected to the process fluid via sensing lines with one or more isolation
valves or are not exposed to the process fluid.
3.8 qualified:
demonstrated to be acceptable for the design requirements.
4 Safety classification
4.1 Code applicability
The reason that a transducer is classified as safety-related is important in determining which of the criteria
in this document shall be applicable. In general, transducers are classified as safety-related for one or
more of the following reasons:
b) Mounting
The transducer must be mounted in a manner that prevents it from affecting the performance of other
safety-related equipment, such as following a seismic event.
c) Electrical connection
The transducer must be electrically installed in a manner that prevents it from affecting the
performance of other safety-related equipment.
d) Function
If the reason that a transducer is classified as safety-related is its function, then all of the criteria of this
document should be considered for applicability. However, if a transducer is safety-related due to one of
the other three reasons, only certain criteria within this document need to be considered for applicability.
Consider, for example, a transducer whose only safety-related function is its pressure boundary. Those
criteria within this document relative to ensuring that the transducer maintains the pressure boundary
would be applicable to the transducer. Criteria associated with electrical connections, separation,
calibration, testing, etc. may not be relevant to such a transducer. Similarly, the user of a transducer
whose only safety-related function is its electrical connection would find the criteria of this standard
associated with maintaining that electrical connection to be applicable. Criteria associated with process-
fluid connections, environmental considerations, accessibility, etc. may not be applicable for such a
transducer.
It is the responsibility of the user to determine the reasons that a transducer is classified as safety-related
and to apply the criteria of this document that will maintain these safety-related functions.
Installations of transducers in Code piping, vessels, or equipment shall comply with the Code.
Transducers for nuclear safety-related applications may be installed in or connected to non-Code piping,
vessels, or equipment, as necessary to obtain measurements from non-Code systems. The Code shall
not apply to these installations.
The Code shall not apply to off-line transducers. Sensing lines for off-line transducers shall be installed in
accordance with ANSI/ISA-67.02.01-1999.*
Mounting structures that support Code equipment shall comply with the Code (subsection NF).
5 Equipment mounting
5.1 Mounting of in-line transducers
To facilitate replacement and periodic inspections, flow-through transducers, such as differential pressure
meters (orifice plates, flow nozzles, venturi tubes, etc.), electromagnetic flowmeters, mass flowmeters,
vortex flowmeters, positive displacement flowmeters, turbine flowmeters, ultrasonic flowmeters, variable
area flowmeters, and certain radiation monitors should be flange-mounted to the piping, except in ASME
Code Class 1 installations.
The piping shall not impose unacceptable loads on the instrument. Auxiliary supports shall be provided to
restrain the instrument where the mass of the instrument puts unacceptable stress on the piping.
Flow-past devices (such as protective wells, differential pressure meters [pitot tubes], insertion-type
electromagnetic vortex, target, and turbine flowmeters) designed to be inserted into the flow path through
the wall of the pipe or vessel, shall be installed and mounted through a piping penetration specifically
designed to accommodate the transducer.
Where removal is required for service, one of the following alternatives to permanent welding of the
transducer shall be used:
b) For insertion shank diameters of 25 mm OD (1 in.) or less, mounting with a flareless fitting (see 8.2.3)
Mating fittings shall be welded into the pipe boss or fitting. The mating bodies, nuts, and ferrules shall
be obtained from the same manufacturer or shall otherwise be qualified to perform their intended
function.
They shall provide positive nonfriction restraint in both the inserted and the withdrawn position.
d) Straight threads with resilient seals, and conical or spherical seat unions.
The mounting structure shall not induce stresses greater than the allowable stresses on the transducer or
on the sensing lines, signal lines, and electrical cables serving the transducer.
The structure shall be designed to support the transducer in the physical orientation(s) for which it is
qualified. Only qualified mounting hardware shall be used. Preference should be given to use of hardware
furnished and qualified as part of the transducer.
Mounting structures and their attachments shall have a load capacity not less than that required by any of
the supported transducers or auxiliary equipment.
5.2.2 Fasteners
Bolts, screws, or other fasteners used for mounting shall be chemically and metallurgically compatible
with the equipment, the structure, and the environment. Fasteners shall be qualified to withstand all loads
including normal loads, structural vibrations, and seismic stresses.
5.2.3 Materials
The materials selected for the mounting structures shall be resistant to or protected against the design
environment; for example, aluminum may be prohibited in caustic spray environments.
Protective coatings shall be resistant to both normal and (where applicable) accident environments, and
the coatings shall be chemically and metallurgically compatible with the materials to be protected. Paints
or paint-type coatings used on mounting structures shall be fire-retardant.
a) Wall bracket
The addition of flat plate side panels or cross-bracing is permitted to obtain satisfactory stiffness.
Bracing to the wall or other structures is permitted.
Unless cabinets are designed specifically to control the transducer environment, they shall be
designed to allow natural air circulation. Where a controlled environment is essential to the accuracy
or continued function of the enclosed equipment, the auxiliary equipment for controlling the
environment shall be designed and installed to the same requirements as the enclosed equipment.
Monitoring of the controlled environment parameters shall be provided.
d) Panels (flat plates attached to open racks, wall brackets, or cabinets, as defined in 5.2.4.(c))
e) Pipe stands or stanchions (a single length or assembly of pipe or structural shapes that is mounted to
the floor, wall, or structural steel)
Friction mounting of the bracket (such as that provided by U-bolt clamps around a pipe) may be used
when qualified.
If welding is specified for non-Code attachment or assembly, the weld shall be shown to have a stressed
cross section sufficient to support the maximum design loads. Tack welding shall not be used as a
structural weld.
Other assembly methods (such as bonding or adhesives) shall be qualified for all structural,
environmental, and design-life conditions.
The mounting structure shall be attached to its supporting structure by bolting or welding in place.
Plates connected to embedded anchors, expansion bolts, cement, or other means of attachment in
concrete are acceptable.
Inspection of the final assembly shall be performed and documented to verify that:
a) fasteners used are the size, type, and material specified and have been properly tightened
b) welding is as specified
c) paint and other protective coatings have been applied as specified to corrodible materials, and that
the coating remains intact or has been repaired
d) transducers and auxiliary equipment items are installed in the orientation appropriate for seismic
qualification, and the designated mounting brackets or supports shown on the approved design
drawings have been properly installed
e) piping, tubing, fittings, valves, and electrical connections have been installed and tested in
accordance with the drawings or specifications, and
f) nondestructive examination, if specified on the drawings or other documents, has been completed.
Impingement barriers shall be used where required to protect against damage from postulated missiles,
fluid jets, and other identified moving objects. The barriers may also serve to separate redundant
transducers and auxiliary equipment. The barriers shall be designed consistent with the seismic
qualification requirements for the protected devices.
Unless otherwise justified, the requirements of 5.2 and 5.3 shall apply to auxiliary equipment.
6 Location of equipment
6.1 Selecting a location
Transducers shall not be installed in locations with environments that may exceed the qualified
capabilities of the transducer, except when it can be shown that a potentially adverse environment will
exist only after the transducer's function is no longer required. For instance, transducers with no post-
accident requirements may be located in the reactor containment without being qualified for post-accident
environments, so long as their failure will not degrade the availability of other equipment that is required
to be operable. Selection of locations for transducers should consider the availability of transducers
qualified to operate in the various design environments.
Transducers shall be located or enclosed as necessary to protect them against physical damage,
radiation, freezing, and changes or rates-of-change in ambient conditions in excess of that for which they
have been qualified.
Transducers shall be located so that no credible single event can prevent the required nuclear safety-
related functions. Piping, tubing, and wiring associated with the transducers shall be placed with similar
attention to separation of locations. A minimum of 450 mm (18 in.) separation shall be provided between
surfaces of redundant transducers. Where analysis shows that specific postulated events, including but
not limited to fires, missiles, and fluid jets, could circumvent the protection afforded by this separation,
additional spacing or protective barriers shall be provided. Protective barriers may also be used in lieu of
separation where it is impractical to maintain the required spacing. If barriers are used, a minimum of 25
mm (1 in.) of free space shall be provided on each side between transducers and the barrier.
Where redundant transducers must be included on the same structure, service access to the transducers,
or to the subassemblies of one transducer, shall be separated from access to components or
subassemblies of their redundant counterpart(s). (For instance, with cabinet construction, separate
access doors should be provided.)
The transducers should be located in an accessible place for ease of periodic testing, servicing, removal,
and replacement. Adequate lighting, electrical outlets, water, compressed air, and similar utility services
should be provided to support testing and surveillance requirements.
Placement of equipment (with respect to the mounting structures, impingement barriers, and adjacent
equipment) shall allow clearance for the removal of covers and normal use of hand tools for mounting,
calibration, and servicing. Placement shall allow removal and replacement of a complete device without
disturbing equipment not functionally associated with the instrument loop being serviced. (That is, it shall
not be necessary to shut down one instrument loop to facilitate replacement or service of a transducer or
auxiliary equipment in another instrument loop.)
Unless otherwise justified, the requirements of 6.1, 6.2, and 6.3 shall also apply to auxiliary equipment.
7 Environmental considerations
7.1 Seismic considerations
The design of nuclear safety-related transducer installations shall accommodate seismic disturbances
such that the transducers are not subjected to seismic shock or vibration in excess of that for which they
are qualified. Addition, deletion, or relocation of equipment on mounting structures (beyond the original
design considerations) shall require re-verification of the seismic suitability.
Exposure to vibrational excitation due to pumps, turbines, or other sources should be avoided. Where
high vibration is unavoidable, the equipment should be mounted on an adjoining nonvibrating surface, or,
if no other reasonable alternative exists, the equipment should be isolated by shock mounting for the
expected vibratory motion.
The design of a nuclear safety-related transducer installation shall accommodate normal and abnormal
ambient operating and accident conditions. As a minimum, limits of the following parameters shall be
determined and documented:
a) Temperature
b) Pressure
c) Humidity
d) Radiation.
When chemicals are transported in the lines being measured, the wetted materials of the transducer
installation shall be compatible with the chemical. When the environment includes a chemical component,
the installation shall be qualified for the environment.
If the installation is exposed to ambient temperatures below the freezing, condensation, or precipitation
point of fluids, the transducer, lines, and other parts shall be heated by steam studs, electrical heat
tracing, a radiant electric housing, or another suitable means. Conversely, insulation or cooling of
instruments may be required in high temperature environments. Such provisions shall be treated as
auxiliary equipment. (See 5.2.4 also.)
Unless otherwise justified, the requirements of 7.1 to 7.4 also apply to auxiliary equipment.
8 Interface connections
8.1 Process fluid connections
Valves, fittings, attaching bosses, adapters, tubing, and piping used to connect transducers to process
piping shall be installed per ANSI/ISA-67.02.01-1999.*
Interface connection methods that do not involve the use of thermowells between the measurand and the
transducer (that is, in-line installation) shall be used wherever necessary to achieve the response
required by the system design. The designer of the installation should consider sources of error in
accordance with ASME Performance Test Code, PTC19.3, "Temperature Measurement,"* as applicable
to the measurand and selected transducer.
Designers of the installation should consider the performance guides and sources of error given in ASME
Performance Test Code, PTC19.2, "Pressure Measurement,"* as applicable to the measurand and
method of measurement.
Designers of the installation should consider the general requirements, recommendations, conditions for
proper installation and operation, errors, and other characteristics of the primary element or flowmeter,
given in the ASME publication on "Fluid Meters"* and ASME-MFC standards.*
The effect of valves, fittings, tubing, and the volumetric displacement of the transducer shall be included
in determining the response of the installation.
Each type of connection selected shall be qualified to the design conditions at the connection. Materials
employed for valves, fittings, adapters, tubing, piping, thread lubricants, and seals shall be selected to
meet the particular conditions of service required by the design, including material compatibility for
welding, compatibility with the fluid chemistry, and material hardness requirements of mechanical joint
fittings.
8.2.1 Flanges
Proprietary flange designs (usually two-bolt manifold adapters) are permitted as disassembly joints for the
sensing lines at the transducer, when qualified for use with the transducer. Other flanges shall comply
with ANSI B16.5.* Due to their bulk, installation of other flanges in the immediate area of off-line
transducers is not recommended.
Tapered pipe threads shall not be used as take-down joints when repeated disassembly and reassembly
are planned. Straight thread fittings with metal-to-metal or resilient seals are permitted.
Disassembly joints, in tubing with diameters of 25 mm OD (1 in.) or less, may be made using flareless
couplings. The joints shall be made in accordance with the manufacturer's specification and shall be
visually inspectable.
These systems include all filled capillary systems, such as chemical-seal diaphragms with capillary
tubing, pressure-sensitive bellows with capillary tubing, temperature bulbs with capillary tubing, and so
forth. Whether factory-filled or field-filled, the capillary tubing is an extension of the transducer but shall be
routed, separated, supported, and protected per ANSI/ISA-67.02.01-1999. Armor provided as part of the
capillary tubing is for protection during normal installation and use; it alone shall not be considered to
meet separation or protective barrier requirements.
Shut-off and calibration valves in a sealed capillary line may seriously compromise the functional
capability of the transducer and shall not be provided. Valves provided for capillary field-filling operations
shall not be capable of interrupting the pressure-sensing path and shall have the capability of being totally
sealed against external leakage by welding after the capillary lines are filled. Where an all-welded
capillary tubing (that is, no mechanical joints or seals) is provided and qualified, a double leakage barrier
for the process fluid or containment atmosphere inherently exists in the design. Therefore, reactor
containment penetrations, if any, shall not require additional valving in the capillary.
For piping design purposes, the connection interface shall be defined as the remote bellows, diaphragm,
or bulb. The remote bellows, diaphragm, or bulb shall be part of the transducer; the housing for the
remote bellows, diaphragm, or bulb and its connections to the process shall be part of the piping and shall
meet applicable codes and other design criteria.
Materials at connection boxes shall be compatible with the expected environment. Where electrical
connections must be protected from the environment, such as would be experienced in post-accident
service, the connection box design shall be qualified for the design conditions. Tapered pipe thread
connections for use with conduit or cable adapters are permitted. Connection boxes furnished as part of
qualified transducers shall be installed in the same configurations for which they were qualified.
When screw terminals on terminal boards or strips are used, they shall be qualified and shall have ratings
of at least twice the instrument signal voltage (or power supply voltage as applicable).
When splices are used, provide a single insulated splice for each wire. The complete splicing system
shall be qualified for the design conditions.
Where quick connectors are used, the connector and cable system design shall consider size (conductor
size and overall cable size), cable retention, strain relief, and requirements for cable flexibility, pull space,
and other applicable factors. Solid wire shall not be used with the removable half of quick connectors.
Connectors shall be mechanically retained in the connected configuration by screw threads with a
minimum of 1¼ turns or mechanical detent. Both halves of each connector shall be furnished by the same
manufacturer or shall otherwise be qualified to mate properly and to provide an adequate electrical
connection. The connector and cable combination shall be qualified for the design conditions.
Cables and wire furnished with racks, or special interconnecting cables furnished for connection between
transducers and auxiliary equipment, shall be flame-retardant and qualified for the design conditions.
8.3.5 Shielding
Shielding shall be insulated against grounding, except at the points specified by the design documents.
Shielding continuity shall be carried ungrounded through all other connection boxes, penetrations, and
connectors. Braided or spiral exterior armor provided for mechanical protection should not be considered
shielding.
Test connections shall be provided in each sensing line for the calibration and test of equipment in place.
Test connections shall be capable of being isolated from the process pressure. Test connections shall be
located to permit access, testing, and accurate calibration. Connections provided at or near the
transducer for the use of portable test and calibration equipment shall be provided with a plugged or
capped connection designed for repeated assembly and disassembly.
Capability for venting, draining, and flushing the transducer installation shall be provided where required.
In addition, methods for capture and disposal of the drained, vented, or flushed process fluid from
radioactive systems shall be included as part of this capability.
Test connections provided for test and calibration of transducers and auxiliary equipment shall not
adversely affect the transducer during those periods when it is required to function. Test connections shall
not interfere with the normal operation of any transducer not being tested.
9.4 Communications
Communication methods, for purposes of transducer calibration and service, should be coordinated with
(and may be a part of) the overall plant communication network and systems. Due to the possibility of
electromagnetic interference, portable radio transceivers shall not be the only method available for
transducer calibration and service.
9.5 Labeling
Permanent labels shall be provided to facilitate identification of the installation, for warning purposes, and
as guides to service and calibration. As a minimum, each transducer location shall be labeled with the
transducer tag number. Where redundant groups or sets of transducers are identified by color coding,
transducer and auxiliary equipment mounting labels shall be similarly color coded. Labels for non-nuclear
safety transducer and warning labels or service and calibration guide labels that are not unique to a
redundant group or protection set shall be of a different color.
Removable service panels or other features that may compromise the internal environment shall bear
clear and permanent warning labels that explain the effects of their improper use. An example follows:
10 Quality assurance
The installation of nuclear safety-related transducers in nuclear facilities shall be in accordance with the
requirements of the owner's quality assurance program.
A.1 References
AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI)
MFC-3M Measurement of Fluid Flow in Pipes Using Orifice, Nozzle, and Venturi,
1989
MFC-6M Measurement of Fluid Flow in Pipes Using Vortex Flow Meters, 1987
Boiler and Pressure Vessel Code, Section III, Nuclear Power Plant Components,1992
ISA
A.2 Bibliography
The following documents may provide additional information, guidance, or requirements for various
aspects of the installation of transducers:
383 Standard for Type Test of Class 1E Electric Cables, Field Splices, and
Connections for Nuclear Power Generating Stations, 1974
603 Standard Criteria for Safety Systems for Nuclear Power Generating
Stations, 1998
622 Recommended Practice for the Design and Installation of Electrical Heat
Tracing Systems for Nuclear Power Generating Stations, 1987
ISA is an American National Standards Institute (ANSI) accredited organization. ISA administers United
States Technical Advisory Groups (USTAGs) and provides secretariat support for International
Electrotechnical Commission (IEC) and International Organization for Standardization (ISO) committees
that develop process measurement and control standards. To obtain additional information on the
Society’s standards program, please write:
ISA
Attn: Standards Department
67 Alexander Drive
P.O. Box 12277
Research Triangle Park, NC 27709
ISBN: 978-1-934394-47-2