ACB Ace-MEC

This document provides information on Leader in Electrics & Automation Ace-MEC air circuit breakers. It discusses the compact and modular design, high breaking capacity up to 100kA, various certifications, safety features including the digital trip relay accessible by LCD, and optional accessories. The digital trip relay allows for inspection of load current, setting values, fault current, and tripping time along with self-diagnosis and testing functions.

Uploaded by

Alcindo Teixeira
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
353 views56 pages

ACB Ace-MEC

This document provides information on Leader in Electrics & Automation Ace-MEC air circuit breakers. It discusses the compact and modular design, high breaking capacity up to 100kA, various certifications, safety features including the digital trip relay accessible by LCD, and optional accessories. The digital trip relay allows for inspection of load current, setting values, fault current, and tripping time along with self-diagnosis and testing functions.

Uploaded by

Alcindo Teixeira
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 56

Leader in Electrics & Automation

Ace-MEC
Air Circuit Breakers

Electric Equipment
Air Cicuit Breakers

It is customer’s ACB that considers a customer’s convenience in the


use through the increase in the reliance of the operation characteristic
by digital type of trip relay and the easy checking of load
condition and fixed current value by LCD.

LG“ATS with ACBs”interlocks the ACBs �Application: The place which require stable power

by mechanically and electrically. supply (Hospital, Communication facility, Computer


room, Pump room, Office building)
It is more reliable in switching
�Comparing with the existing ATS, the LG“ATS with
operation and faster ACBs”has high breaking capacity and protects the
than existing ATS. loads from the over-current

The switching time is adjustable. and ground fault

2
Characteristics 4
Features & internal structure 6
Ratings 8
Charging methods 10
Auxiliary devices 11
Electronic trip relay 12
Operating characteristics of trip relay 17
Characteristics curve 21
Optional accessories 25
ATS with ACBs 30
Control circuit 35
External dimensions 40
Technical information 50
Type selection 51
Ordering sheet for Ace-MEC ACB 53
Ordering sheet for ATS with ACBs 54

3
Characteristics

Compact & Modular design


�More compact overall dimensions and light weights.
�LG Ace-MEC ACB have been made three types of modular
design creteria to facilitate their installation and integration in low
voltage switch boards.

High breaking capacity


�LG Ace-MEC ACE provides high breaking capacity upto lookA

Under 500V breaking


Upto 1600AF 1600AF service capacity
lcu[kA]

Upto 3150AF 3150AF

Upto 5000AF 5000AF

65kA 85kA 100kA

Various certification and approval


�LG Ace-MEC ACB is type-tested by IEC 60947 and
GB 14048-2-94 standard
�KEMA (Netherlands), ESI (Italy), CCC (China), KERI (Korea),
ISO 9001, ISO 14001

4
Safety and Convenience High functional digital type trip relay
�OCR terminals are located in front �Easy inspection by LCD
�Modulized mechanical part and accessories - Load current value
�for easy maintenance and inspection Improved draw-out rail - Setting values of each trip characteristics
- Fault current(Max) value
for easy draw-out
- Tripping time
�Minimized arc space
�Self-diagnosis function
� Molded frame
- noEr : No error
※ The reverse connection of power source and load part is available but please use the normal - Err-1 : No MTD coil
connection for the safety in maintenance and inspection - Err-2 : Program error
- Err-4 : Configuration resister error
- Err-8 : Watch dog error
�Self-test function
- It is available to check whether OCR is operated normaly or
not by applying external power
�Pre-alarm function
�Contact output of the each tripping cause and LED indication
�OCR alarm contact (AL, 2a)

Variety of accessories
Optional accessories
�Interlock device
- Mechanical interlock, interlock unit,
- ATS, ATS controller
�Key interlock(K2, ON-Lock)
�Key lock(K0, K1)
�ON/OFF button lock(B, ON/OFF button lock)
�Door Frame(DF)
�Door Interlock(DI)
�UVT, UVT controller: Standard(1NO 1NC)

Type Operating time Rated voltage


Instantaneous under AC 110, 220, 380, 460V
type 0.2sec DC 24, 48, 110, 125V
over AC 110, 220, 380, 460V
0.5sec DC 24, 48, 110, 125V
Delay type
over AC 110, 220, 380, 460V
3sec DC -
�Cell switch(4C, 8C)
�Shorting B. contact(SBC, 5b max)
�Safety shutter lock(SSL)
�Miss insertion prevent device(MIP)
�Condensor tripping device(CTD)
�OCR tester(OT)

Standard attachment of draw-out type


�Pad lock
�Position indicator (connected, test, disconnected)
�Counter(5-digit)
�Lifting hook
�Shorting b�contact
�Insulating barrier
�OCR alarm contact (AL, 2a)

5
Features and internal structure

2 1

15

13 11 10 12 14

1 Arc extinguishing chamber 6 OFF button 11 Pad lock


2 Control circuit terminal 7 ON button 12 Position indicator
3 Key lock 8 ON/ OFF indicator 13 Counter
4 Electronic trip relay 9 Charging indicator 14 Extension rail
5 Charging handle 10 Aperture for the draw-out handle 15 Lifting hook hole

6
4 3 2 1 13


21

14
5
15
7

8 16

22

6 17

11

10 12 20 19 18

1 Control circuit terminal block 9 Charging mechanism 17 Main conductor of load part
2 Control terminal 10 Closing spring 18 Contact spring
3 Auxiliary switches 11 Draw-out mechanism 19 CT for power
4 Shunt trip device, closing coil 12 Insulated base 20 Coil for current detection
5 Electronic trip relay 13 Arc extinguishing chamber 12
21 Cradle
1
6 Front cover 14 Main movable contact
12 22 Main circuit junction
7 Closing mechanism 15 Main fixed contact
8 Tripping mechanism 16 Main conductor of line part

7
Ratings

Type ���C LBA-08�


LBA-06� ���C LBA-10�
���C LBA-13�
���C LBA-16�
���C
Rated current (In max) (A) 630, 400, 250 800 1000 1250 1600
Rated operating voltage (Ue) (V) 690 690 690 690 690
Rated insulation voltage (Ui) (V) 1000 1000 1000 1000 1000
Frequency Note2) (Hz) 50/60 50/60 50/60 50/60 50/60
Number of poles (P) 3,4 3,4 3,4 3,4 3,4
OCR-II For industry In max. × 1.0-0.9-0.8-0.7-0.6-0.5-0.4(7 Steps)
Setting current (In) (A) For industry In max. × 1.0-0.9-0.8-0.7-0.6-0.5-0.4(7 Steps)
OCR-III Note3)
For generator protection In max. × 1.0-0.9-0.8-0.7-0.6-0.5-0.4-0.3-0.2(9 Steps)
Rated current of neutral pole (A) 630 800 1000 1250 1600
690V 50 50 50 50 50
Rated breaking capacity (ICU)
(kA) IEC 60947-2 AC 600V 50 50 50 50 50
(Sym)
500V Under 65 65 65 65 65
Rated service breaking capacity (ICS) (kA) … % × ICU 100% 100% 100% 100% 100%
690V 105 105 105 105 105
Rated making capacity (ICm)
(kA) IEC 60947-2 AC 600V 105 105 105 105 105
(peak)
500V Under 143 143 143 143 143
1 sec 65 65 65 65 65
Rated short-time capacity (ICW) (kA) 2 sec 40 40 40 40 60
3 sec 30 30 30 30 50
Maximum total breaking time 40 40 40 40 40
Operating time ( t) (ms)
Closing time 80 80 80 80 80
Without maintenance 10000 10000 10000 10000 10000
Mechanical
With maintenance 20000 20000 20000 20000 20000
ACB (time)
Without maintenance 3000 3000 3000 3000 3000
Life cycle Electrical
With maintenance 5000 5000 5000 5000 5000

ATS with Mechanical Without maintenance 10000 10000 10000 10000 10000
(time)
ACBs Note 4) Electrical Without maintenance 3000 3000 3000 3000 3000
Main body Motor charging type 66/80 67/81 67/81 67/81 67/81
Draw-out
(with cradle) Manual charging type 63/77 64/78 64/78 64/78 64/78
Weight type
(kg) Cradle only 26/30 26/30 26/30 26/30 26/30
(3P/4P)
Motor charging type 43/53 44/54 44/54 44/54 44/54
Fixed type
Manual charging type 40/50 41/51 41/51 41/51 41/51
Horizontal type Note5) Standard Standard Standard Standard Standard
Bus-bar Connection type
Vertical type Option Option Option Option Option
Motor charging type Standard Standard Standard Standard Standard
Closing type
Manual charging type Option Option Option Option Option
External Draw-out type (mm) H: 435, D: 479 W(3P/4P) 350/435 350/435 350/435 350/435 350/435
dimension Fixed type (mm) H: 410, D: 375 W(3P/4P) 345/430 345/430 345/430 345/430 345/430
Certificate & Approval KERI, CECI, CCC

Note) 1. Rated current of IEC standard


2. Trip relay is divided into 50Hz and 60Hz. Please be careful when you order it.
3. The generator protection relay is only available in OCR -III and the 4000/5000AF can only be built in OCR-III.
4. Ace-MEC ACB with interlock device can be a substitute for ATS (For order, refer to page 53)
5. For mainbody, only horizontal type is available. For cradle, vertical type is optional. In case of vertical type use of the horizontal type,
the user needs to apply the vertical adapter, The vertical type is atandard for 4000/500AF.
6. For 4000/5000AF, height is 455mm

8
Type LBA-20���C LBA-25���C LBA-32���C LBA-40���C LBA-50���C
Note1)
Rated current (In max) (A) 2000 2500 3150(3200) 4000 5000
Rated operating voltage (Ue) (V) 690 690 690 690 690
Rated insulation voltage (Ui) (V) 1000 1000 1000 1000 1000
Frequency Note2) (Hz) 50/60 50/60 50/60 50/60 50/60
Number of poles (P) 3,4 3,4 3,4 3,4 3,4
OCR-II For industry In max. ×1.0-0.9-0.8-0.7-0.6-0.5-0.4(7 Steps) -
Setting current (In) (A) For industry In max. × 1.0-0.9-0.8-0.7-0.6-0.5-0.4(7 Steps)
OCR-III Note3)
For generator protection In max. ×1.0-0.9-0.8-0.7-0.6-0.5-0.4-0.3-0.2(9 Steps)
Rated current of neutral pole (A) 2000 2500 3150 2500 2500
690V 50 50 50 50 50
Rated breaking capacity (ICU)
(kA) IEC 60947-2 AC 600V 65 65 65 85 85
(Sym)
500V Under 85 85 85 100 100
Rated service breaking capacity (ICS) (kA) … % ×ICU 100% 100% 100% 100% 100%
690V 105 105 105 105 105
Rated making capacity (ICm)
(kA) IEC 60947-2 AC 600V 143 143 143 187 187
(peak)
500V Under 187 187 187 220 220
1 sec 65 65 65 85 85
Rated short-time capacity (ICW) (kA) 2 sec 65 65 65 - -
3 sec 65 65 65 - -
Maximum total breaking time 40 40 40 40 40
Operating time ( t) (ms)
Closing Time 80 80 80 80 80
Without maintenance 5000 5000 5000 2000 2000
Mechanical
With maintenance 20000 20000 20000 - -
ACB (time)
Without maintenance 3000 3000 3000 500 500
Life cycle Electrical
With maintenance 5000 5000 5000 - -

ATS with Mechanical Without maintenance 10000 10000 10000 - -


(time)
ACBs Note 4) Electrical Without maintenance 3000 3000 3000 - -
Main body Motor charging type 95/116 96/117 98/119 244/267 244/267
Draw-out
(with cradle) Manual charging type 92/113 93/114 95/116 240/263 240/263
Weight type
(kg) Cradle only 35/43 35/43 36/44 125/140 125/140
(3P/4P)
Motor charging type 63/75 64/76 66/78 119/127 119/127
Fixed type
Manual charging type 60/72 61/73 63/75 115/123 115/123
Horizontal type Note5) Standard Standard Standard Standard offer in the fixed type
Bus-bar Connection type
Vertical type Option Option Option Standard offer in the draw-out type
Motor charging type Standard Standard Standard Standard Standard
Closing type
Manual charging type Option Option Option Option Option
External Draw-out type (mm) Note6)H: 435, D: 479 W(3P/4P) 485/615 485/615 485/615 960/1090 960/1090
dimension Fixed type (mm) H: 410, D: 375 W(3P/4P) 480/610 480/610 480/610 870/1000 870/1000
Certificate & Approval KERI, CECI, CCC KEMA

9
Charging method

Manual charging type


The closing coil is charged by manual charging handle.
For closing, first charge the spring by using the
charging handle, and then press the close button (I, ON) for
closing, the open button(O, OFF) for opening
�When closing spring is completely charged, charge indicator
indicate “Charge” Charging Handle
�It is mechanically locked not to press the close button (I,ON) OFF button
and open button(O,OFF) simultaneously
�Contact condition of the main circuit is shown on the (O,OFF),
(I,ON) indicator. ON button

Motor charging type


The closing spring is charged by a motor ON charging
ON, OFF Indicator Charging Indicator
method or OFF charging method is available
selectively.
- OFF charging method: When the breaker opened, the closing
spring is charged automatically. It can change to ON charging
method by removing b(Axb) contact like beside circuit diagram
- ON charging method: The closing spring is charged
●Motor charging circuit
automatically when the breaker is closed. It can change to OFF
charging method by using b(Axb) contact There is a contact to
indicate the charging completion(TS+,TS-). Since the contact
signal of charging completion switch is connected to the external
terminal, It is easy to construct a circuit(ex. Automatic closing
circuit) by using that contact
�Manual charging is also available
�With the breaker closed(I,ON), only manual charging is
possible(motor charging cannot be performed)
�With the open button(O,OFF) pressed, closing cannot be
performed(electrical and mechanical lock)
�When OFF Lock device is in use, closing cannot be
worked.(electrical and mechanical lock)
�Opening should follow at least one second after completion of
charging
�Pumping prevent circuit is included with the closing
Note) 1. Since charging completion contact(TS+,TS-) terminal is for contact
coil(electrical lock) output power should not be allowed.
�Please note that pumping prevent circuit can be reset when the 2. Charging completion contact capacity is equal to that high
ofcapacity of auxiliary contact in page 26 .
voltage of input signal drops
●Motor ratings
Inrush current Steady Power Charging
Rated voltage
Voltage Reset voltage peak value(A) current(A) consumption(W) time(sec)

AC Rated voltage 85% under AC/DC 110 7 3.5 242


DC Rated voltage 85% under 50/60Hz 220 7 3.5 264
125 7 3.5 242 5 Under
DC 24 30 11 288
48 30 5.5 336
Note) The range of operating voltage: 85~110%

10
Auxiliary devices

5 4 3
1 Pad lock(PL)
To fix a ACB into a position (Dis-connected, Test, Connected)
� Standard offer in the draw-out type

2 Position Indicator
Connected
To indicate the position (Dis-connected,Test, Connected) of a ACB Test
� Standard offer in the draw-out type Disconnected

3 Closing Coil (CC)


�To close the breaker by remote control
�The coil only operates when the power is supplied continuously over 100ms
�Power should be supplied separately from the motor charging power.
�Electric pumping prevent circuit is built in it.
Operational Inrush current Steady Closing
Rated voltage(V)
voltage(V) peak value(A) current(A) time(sec)
AC/DC 110 94~121 2 1
50/60Hz 220 187~242 3 1.3
125 106~138 2.3 1 0.08 under
DC 24 21~26V 30 3.5
1 2
48 41~53V 30 7
Note) 1. Closing time is from coil excitation to contact closing
2. Steady current is the value at maximum rated voltage
3. Please be careful that the pumping prevention circuit is reset when its
voltage is under 85% of the rated voltage
4. The extent of operation voltage is 85~110% of the rated voltage

4 Shunt coil(SHT)
�To open the breaker by remote control
�Use an auxiliary contact(INO) to prevent coil burning
�Pumping prevent circuit
�When the control power is ‘OFF’ at the ACB is ‘ON’ state, the ACB remains
‘ON’
Operational Inrush current Steady Closing
Rated voltage(V)
voltage(V) peak value(A) current(A) time(sec)
AC/DC 110 77~121 2 1
50/60Hz 220 154~242 3 1.3
125 88~138 2.3 1 0.04 under
DC 24 21~26V 30 3.5
48 41~53V 30 7
Note) The extent of operation voltage is 70~110% of the rated voltage. �Trip coil circuit

5 OCR Alarm contact


�OCR alarm contact is fundamentally installed in only ACB with trip relay. When the
ACB is tripped by the OCR operation, electrical signal flows through the OCR alarm
contact for remote supervisory(INO)
�Contact type
Type OCR-II OCR-III
Momentary operation type
Operational type Magnetic maintenance type
(Under 15ms)
Formation of contact 2NO 2NO �Contact capacity
Type Capacity
�Operating condition of contact
AC 250V 5A
Condition of Condition of Ratings
Cause of trip DC 30V 5A
circuit breaker “a”
”contact
Rated current 5A
Long-time delay trip, Short-time delay trip, Instantaneous-time delay
ON AC 380V
TRIP trip, Groun fault trip Maximum contact voltage
Trip button, Shunt trip coil(SHT), Undervoltage trip(UVT) OFF DC 125V
ON OFF Maximum contact current 5A
OFF OFF Minimum applicable load DC 5V 10mA

11
Electronic trip relay OCR-II

External configuration
No The name of knob Mode Setting step
(0.4-0.5-0.6-0.7-0.8-0.9-1.0) × In Max

1 Setting current In It blinks with OCR trip operation or when
it exceeds 115%, “Pick-up”LED blinks
Rated continuous

2 Ic (0.8 - 0.85 - 0.9 - 0.95 -1.0)×In
current
Long-time

3 LTD 15 - 30 - 60 -120 - 240 - 480 sec
delay tripping time
Short-time delay (2-3-4-6-8-10-OFF) × In

4 Is
tripping current In OCR trip operation, “STD” LED is turned ‘on’
Short-time delay

5 STD 0.05 - 0.1- 0.2 - 0.3 - 0.4 - 0.5 sec
tripping time
Instantaneous-time (4-6-8-10-12-16-OFF) × In

6 Ii
delay tripping current In OCR trip operation, “INST” LED is turned ‘on’
(0.7-0.8-0.9-0.95-1.0-OFF) × Ic

7 Pre-alarm Ip
In OCR trip operation, “PAL” LED is turned ‘on’
(0.1-0.2-0.3-0.4-0.5-0.6-OFF) × In Max 1

8 Ground fault current Ig
In OCR trip operation, “GTD” LED is turned ‘on’ 2

9 Ground fault time GTD 0.1 - 0.3 - 0.8 -1.5 - 3.0 sec 7
4
6
LED of the trip indicator and contact
LED Contact Kinds of tripping characteristics 8
LTD T1 - Long-time delay tripping indicator
STD T2 -
9
Short-time delay tripping indicator
INST T3 Instantaneous-time delay tripping indicator
GTD T4 Ground fault tipping indicator 3
PAL T5 Pre-alarm indicator
When the breaker closed(I,ON),“RUN”LED turn on and 5
RUN -
off continuously
- Over than 105% of the setting current(In)
PICK
- : LED turn on and off
UP
- Over than 120% of the setting current(In): LED turn off

Formation of output terminal


Type of contact OCR-II
Common R+
Control
AC 110V R1�
power
AC 220V R2�
AL1+, AL1�
Pre-alarm
AL2+, AL2�
Common T0
Long-time T1�
Tripping Short-time T2�
type Instantaneous T3
Ground fault T4
Pre-alarm T5
Note) Only AC power can be used for input power to OCR-II

12
Button operating procedures & explanation
Operating characteristics of trip Self-diagnosis check enforcement Indication of self-diagnosis and load condition

Button Button
Button LCD LCD LCD
Explanation operating Explanation operating Explanation
operating Indicate Indicate Indicate
order order
Press the Press the To indicate the result of
“MODE” To indicate “MODE” To indicate
self-diagnosis
button setting current(In) button setting current(In)
one time one time - noEr: No error
- Err-1: MTD coil does
Press
To indicate long- Press To indicate the Press the
“MODE” not exist
the “+” time delay tripping the “MODE” value of No trip button 4
button button - Err-2: Program error
time(LTD) (self-diagnosis mode) times
- Err-4: Configuration
Press To indicate Press To set the resister error
the “+” the “+” - Err-8: Watch dog
button continuous current(Ic) button value of No trip
error Note2

Press Press Press To indicate maximum


To indicates To set the
the “+” the “MODE” the “MODE” current among the
button pre-alarm current(Ip) button value of trip button
phase of R, S, T, N

Press
To indicate short- To do self-diagnosis
the “+” time delay tripping test(Ip, In, TEST letter To indicate opreational
button Press current of the phase of
current(In) turn on and off)
the “+”
button
R-S-T-N in order by
Press To indicate short-time -After tripping, indicate the pressing “+” button
the “+”
button delay tripping time operating time of trip
Press
the “ENT” characteristics
Press
To indicate button
(“PAL” “LTD” LED turn on)
the “+” intantaneous-time
button - After 15~20sec, it
delay tripping current
changes to self-diagnosis
To indicate
Press display mode
the “+” ground fault
button automatically
tripping current

Press
To indicate Press the To reset “PAL”
the “+” ground fault “RESET”
button button “LTD” LED
tripping time
Note) 1. If - button pressed, the characteristics of trip displayed in the reversed order
2. In case of Watch dog error occurs, LCD indicates Error-8 during 15 seconds, then indicates maximum current value among R, S, T phases. At this moment, Run
LED is maintaining ON status when Error-8 occurs from the On and Off status in normal condition.
< Watch dog error Reset>
① If press mode button 4 times, LCD indicates Error-8 again. At this moment, press ENT button.
② After switch-OFF input power of over current relay, then switch-ON again.

The way to check tripping time


Button Button
LCD LCD LCD
operating operating Initialization Remark
Indicate Indicate Indicate
order order

Press Press
- “PAL” “LTD” LED turn on
Long-time
delay trip
the “-” the “+” - To indicate maximum current among
button button
the phase of R,S,T
�LCD: Press the - "STD" LED turn on
Press Press
Short-time
delay trip
the “-” the “+” “ENT” button - To indicate maximum current among
button button
the phase of R,S,T

Instantaneo Press Press


- "INST" LED turn on
us-time the “-” the “+” �LED : Press the - Instantaneous trip time is faster than LCD display time.
delaytrip button button
“RESET” button So, it is not available to display the values.

Press Press
Ground
fault trip
the “-” the “+” - "GTD" LED turn on
button button

13
Electronic trip relay OCR-III

External configuration
1 Display LCD
�Display of normal condtion: In use current of R, S, T, N phases
�Fault display: Fault phases and kinds of fault EX)
- Long-time delay trip: L-INV FAULT : R
- Short-time delay trip: S-INV TYPE : L-INV
- Instantaneous-time delay trip: INST ⇒Long-time delay trip occuring in “R” phase
1
- Ground fault trip: GND ⇒ LCD reset method: Press “Func” button after “Ent”

Condition display LED: “Run”


2 �The LED blinks with normal operation of OCR.
5
Over-current display LED 2
3 �“Pick-up”LED: In case of over default pre-alarm current flows the
“Pick-up” LED warning blinks and is turned off after 3
OCR operation.
�“Fault”
LED: The OCR operation of generating fault turns on “Fault” LED. 4

Communication display LED: “Rx, Tx”


4 �Blinks with normal communication of OCR.
6
Reset button
5 �Out-put contact signal reset and OCR over-current diaplay LED.

Selection button
6 �Func: Mode selection button 7

�Ent : Selection button of various set-up value 8


�▲, ▼: Set-up value input button

RS232 Port
7 : OCR operation check port as connecting PC

TEST Port
8 : Connection button with OCR tester (OT-2000)

Setting step Formation of output terminal


Operating characteristics Mode Setting step Type of contact Mark of contact
(0.4-0.5-0.6-0.7-0.8-0.9-1.0)×In max. - Industry Common “+”
R+( )
Setting current In Control
(0.2-0.3-0.4-0.5-0.6-0.7-0.8-0.9-1.0)×In max. - Generator protection AC/DC 100/220V
power “-”
R2-( )
Rated continuous current Ic (0.6-0.65-0.7-0.75-0.8-0.85-0.9-0.95-1.0)×In DC24/48V
Long-time delay 15-20-25-30~465-470-475-480sec(Step: 5sec) - Industry Alarm AL1+, AL1�
LTD (Holding type contact)
tripping time 1.5-2.0-2.5~47.0-47.5-48.0sec(Step: 0.5sec) - Generator protection AL2+, AL2�
Short-time delay Common T0
Is (2-3-4-5-6-7-8-9-10-no)×In
tripping current Time(Long, Short) T2-
Short-time delay STD 0.05-0.06-0.07~0.48-0.49-0.5sec(Step: 0.01sec) Tripping type Instantaneo trip T3
tripping time (4-5-6-7-8-9-10-11-12-13-14-15-16-no)×In - 4000AF under Ground trip T4
Iinst
Instantaneous-time delay (4-5-6-7-8-9-10-11-12-no)×In - 5000AF over Pre-alarm T5
tripping current Ip (0.7-0.8-0.9-1.0)×Ic Communication 485+, 485-
Pre-alam (0.3-0.4-0.5-0.6-0.7-0.8-no)×In max. - 3Pole Note) Only AC power can be used for input power to OCR-II
Ig
Ground fault current (0.1-0.2-0.3-0.4-0.5-0.6-0.7-0.8--no)×In max. - 4Pole
Ground fault time GTD 0.1-0.2-0.3~2.8-2.9-3.0sec (Step: 0.1sec)

14
Button operation method in set-up modes
Set-up procedure of various set-up value

Fault information method

Main formation method

15
Electronic trip relay OCR-III

Button operation method in set-up modes


Self diagnosis method Date and time set-up

OCR test method

Set-up value initializing method

16
Operating characteristics of trip relay OCR-II

Ratings

Classification Types and ratings of trip relays

Type 60Hz LPO LGP


50Hz LPH LTH
Application For industry For industry
Possible number of ACB poles 3, 4P 4P
Operting voltage AC 110V, 220V AC 110V, 220V
Communication - -
Long-time delay (L) � �
Short-time delay (S) � �
Operating characteristics Instantaneous time delay (I) � �
Ground fault (G) - �
Pre-alarm (P) � �
Setting current (A) In = … x In Max 0.4-0.5-0.6-0.7-0.8-0.9-1.0 0.4-0.5-0.6-0.7-0.8-0.9-1.0
Continuous current (A) Ic = … x In 0.8-0.85-0.9-0.95-1.0 0.8-0.85-0.9-0.95-1.0
Long-time delay(L) Trip current (A) IL = … x Ic 1.5 1.5
(Error tolerance : ±10%) Trip time (sec) LTD 15-30-60-120-240-480 15-30-60-120-240-480
Short-time delay(S) Trip current (A) Is = … x In 2-3-4-6-8-10-OFF 2-3-4-6-8-10-OFF
(Error tolerance : ±15%) Trip time (sec) STD 0.05-0.1-0.2-0.3-0.4-0.5 0.05-0.1-0.2-0.3-0.4-0.5
Instantaneous time delay(I) Trip current (A) li = … x In 4-6-8-10-12-16-OFF 4-6-8-10-12-16-OFF
(Error tolerance : ± 20%) Trip time (sec) INST 0.01 under 0.01 under
Ground fault(G) Trip current (A) Ig = … x In Max - 0.1-0.2-0.3-0.4-0.5-0.6-OFF
(Error tolerance : ±20%) Trip time (sec) GTD - 0.1-0.3-0.8-1.5-3.0
Pre-alarm(P) Trip current (A) Ip = … x Ic 0.7-0.8-0.9-0.95-1.0-OFF 0.7-0.8-0.9-0.95-1.0-OFF
(Error tolerance : ±10%) Trip time (sec) PAL = … x LTD 0.5(setting Ip 1.0) 0.5(setting Ip 1.0)
Note) It is impossible to install in 4000/5000AF ACB

�Power consumption of trip relay


Operational Voltage Ⅱ
OCR-Ⅱ
AC 110~220V 5VA

17
Operating characteristics of trip relay OCR-III

Ratings

Classification Types and ratings of trip relays

Type 60Hz N�6 C�6 P�6 M�6


50Hz N�5 C�5 P�5 M�5
Application For industry For industry For generator protection For generator protection
Possible number Of ACB poles 3, 4P 3, 4P 3, 4P 3, 4P
1 AC/DC 110V/220V AC/DC 110V/220V AC/DC 110V/220V AC/DC 110V/220V
Operting voltage 2 DC24V DC24V DC24V DC24V
4 DC48V DC48V DC48V DC48V
Communication - � - �
Communication protocol - RS 485 - RS 485
Protocol - DNP 3.0 - DNP 3.0
Transmission speed - 9600 bps - 9600 bps
Long-time delay(L) � � � �
Short-time delay(S) � � � �
Setting current Instantaneous time delay (I) � � � �
Ground fault (G) � � � �
Pre-alarm (P) � � � �
�For industry: 0.4-0.5-0.6-0.7-0.8-0.9-1.0
Setting current (A) In = … x In Max.
�For generator protection: 0.2-0.3-0.4-0.5-0.6-0.7-0.8-0.9-1.0
Continuous current (A) Ic = … x In 0.6-0.65-0.7-0.75-0.8-0.85-0.9-0.95-1.0
Trip current (A) IL = … x Ic 1.5
Long-time delay(L)
�For industry : 15-20-25-30~465-470-475-480(Steps: 5sec)
(Error tolerance : ±10%) Trip time (sec) LTD
�For generator protection: 1.5-2.0-2.5-3.0~46.5-47.0-47.5-48.0(Steps: 0.5sec)
Short-time delay(S) Trip current (A) Is = … x In 2-3-4-5-6-7-8-9-10-no
(Error tolerance: ±15%) Trip time (sec) STD 0.05-0.06~0.49-0.5(Steps: 0.01sec)
�4000A under: 4-5-6-7-8-9-10-11-12-13-14-15-16-no
Instantaneous time delay(I) Trip current (A) li = … x In
�5000A over: 4-5-6-7-8-9-10-11-12-no
(Error tolerance : ±15%)
Trip time (sec) INST 0.01under
�3 pole: 0.3-0.4-0.5-0.6-0.7-0.8-no
Ground fault(G) Trip current (A) Ig = … x In Max.
�4 pole: 0.1-0.2-0.3-0.4-0.5-0.6-0.7-0.8-no
(Error tolerance : ±20%)
Trip time (sec) GTD 0.1-0.2-0.3~2.8-2.9-3.0 (Step: 0.1sec)
Pre-alarm(P) Trip current (A) Ip = … x Ic 0.7-0.8-0.9-1.0
(Error tolerance : ±10%) Trip time (sec) PAL = … x LTD 0.5(setting Ip 1.0)

�Power consumption of trip relay �Trip relay type selection


Operational voltage OCR-III
AC/DC 110/220V 5VA N 1 6
DC 24V 5VA
DC 48V 5VA
Function Operational voltage Frequency
Communication function NO 1 AC/DC 110/220V 6 60Hz
N
(For industry) 2 DC 24V 5 50Hz
Communication function YES 4 DC 48V
C
(For industry)
Communication function NO
P
(For generator protection)
Communication function YES
M
(For generator protection)

18
OCR-II

LPO, LPH (Without ground fault trip unit)


Characteristics of protection Standard functions
�Setting the fixed current
�Setting the long-time delay tripping current
�Setting the long-time delay ripping time
�Setting the short-time delay tripping current
�Setting the short-time delay tripping time
�Setting the instantaneous-time delay
tripping current
�Setting pre-alarm current
�Trip Indicator

① Long-time delay pick-up current


② Long-time delay tripping time ③ Short-
time delay pick-up current ④ Short-
time delay tripping time
⑤ Instantaneous pick-up current
⑥ Pre-alarm pick-up current
⑦ Pre-alarm tripping time

LGP, LTH
Characteristics of protection Standard functions

�Setting the fixed current


�Setting the long-time delay tripping current
�Setting the long-time delay tripping time
�Setting the short-time delay tripping current
�Setting the short-time delay tripping time
�Setting the instantaneous-time delay
tripping current
�Setting the ground fault tripping current
�Setting the ground fault tripping time
�Setting pre-alarm current
�Trip Indicator
① Long-time delay pick-up current
② Long-time delay tripping time
③ Short-time delay pick-up current
④ Short-time delay tripping time
⑤ Instantaneous pick-up current
⑥ Pre-alarm pick-up current
⑦ Pre-alarm tripping time
⑧ Ground fault pick-up current
⑨ Ground fault trip time

Note) Ground fault trip is availble in 4pole type.

19
Operating characteristics of trip relay OCR-III

�6, P�
N� �6, N�
�5, P�
�5
Characteristics of protection Standard functions
�Setting the fixed current
�Setting the long-time delay tripping current�
Setting the long-time delay tripping time
�Setting the short-time delay tripping current
�Setting the short-time delay tripping time
�Setting the instantaneous-time delay
tripping current
�Setting the pre-alarm current
�Trip Indicator
�Communication
① RS232(Port)
① Long-time delay pick-up current - Setting the fixed value
② Long-time delay tripping time ③ Short- - Monitoring the fixed value
time delay pick-up current ④ Short- - Monitoring the operating tate of ACB
time delay tripping time OCR
⑤ Instantaneous pick-up current - Monitoring the load current of line
⑥ Pre-alarm pick-up current - Performing of calibration bility
⑦ Pre-alarm tripping time

�6, M�
C� �6, C�
�5, M�
�5
Characteristics of protection Standard functions
�Setting the fixed current
�Setting the long-time delay tripping current
�Setting the long-time delay tripping time
�Setting the short-time delay tripping current
�Setting the short-time delay tripping time
�Setting the instantaneous-time delay
tripping time
�Setting the ground fault tripping current
�Setting the ground fault tripping time
�Setting pre-alarm current
�Trip Indicator
�Communcation
① RS232(Port)
- setting the fixed value
① Long-time delay pick-up current
- Minitoring the fixed value
② Long-time delay tripping time
- Minitoring the load current of line
③ Short-time delay pick-up current
- Minitoring the operating state of ACB OCR
④ Short-time delay tripping time
- Performing of Calibration ability
⑤ Instantaneous pick-up current
② RS485(Port : 485+, 485-)
⑥ Pre-alarm pick-up current
- Setting the fixed value by remote
⑦ Pre-alarm tripping time
- Monitoring the fixed value
⑧ Ground fault pick-up current
- Monitoring the load current of line
⑨ Ground fault trip time
- Transmitting the failure information
(failure pole, failure factor)
- Transmitting the self-diagnosis information

20
Characteristics curve OCR-II

LPO, LPH(For industry)

21
Characteristics curve OCR-II

LGP, LTH(For industry)

22
OCR-III

�6, C�
N� �6, N�
�5, C�
�5 (For industry)

23
Characteristics curve OCR-III

�6, M�
P� �6, P�
�5, M�
�5 (For generator protection)

24
Optional accessories

OCR tester
Ratings
Name Key to initialize test current value (In, In Max)
OT-2000
and LED(trip, testing)
Rated voltage AC 100~240V
Frequency 50Hz, 60Hz (selection)
Key to start the test.
In max: (0-1) → If the value of In max is 1, the output
Output voltage is 200mV
Key to stop the operation of tester device
voltage In: (0-30)xIn max → It corresponds to the signal of
(Timer, stop output signal)
the OCR (Ex. If you set In to 30, 6V turns out.)
Type of output Key to initialize timer.
o, g, e Note1)
voltage (0 ms)
Stop signal OCR, a-contact, b-contact
Key that should be operated at first to revise test the
TC: Detect only the operation state of OCR
Trip time current value, and select type of the test current.
regardless of the timedelay characteristics.
Check
(Apply DC power) Key to shift the digit number of 7-segment,which
shows the test current value to right direction

Key to shift the digit number of 7-segment, which shows


Key operating explanation test current value to the left direction

Key to select frequency Key to increase 1digit by 1digit of 7-segment that shows
(50Hz, 60Hz) the test current value.

Key to select type of stop signal input voltage of the Key to decrease 1digit by 1digit of 7-segment that shows
OCR tester (OCR, a-contact, b-contact) the test current value.

Key to initialize the test current value when ED has been Key to set the test current value edited by →, ←, ↑, ↓ or
pressed one time. CL

Key to test whether OCR is operated normaly or not. Key to select operational characteristics of trip relay

Note) 1. - o: Pre-alarm, long-time delay, short-time delay, instantaneous-time


delay trip
- g: Ground fault trip
- e: Display output of contact except trip relay(Use to check the tester)
Connection method


OCR-Ⅱ Ⅲ
OCR-Ⅲ

25
Optional accessories

Auxiliary contact(AX)
- To remote supervisory of the ON/OFF state of the ACB

Ratings
Standard type High capacity type
Type Resistive Inductive Resistive Inductive Remark
load load load load
460V 5A 2A 5A 2.5A
AC 250V 10A 10A 10A 10A
Contact 125V 10A 10A 10A 10A
capacity 250V 0.3A 0.3A 3A 1.5A
DC 125V 0.6A 0.6A 10A 6A
30V 10A 6A 10A 10A
AX 5a5b ‐ Standard
�Contact operating
Maximum HX ‐ 5a4b charging type
The condition of ACB a-contact b-contact
contact No. AC 5a5b ‐ High speed
HC ‐ 5a5b reclose ON ON OFF
charging type OFF OFF ON
Selection Standard offer Note) Option
Note) When you order the high capacity type auxiliary contact, the standard type auxiliary contact is not offered.

Cell switch(C)
kTo indicate the position (connected, test, dis-connected) of a
ACB
It is installed in the upper and back side of a cradle.
(Common use 630~5000A)

Standard contact configuration


- 4C: 1 Disconnected 1 test 2 connected
- 8C: 2 Disconnected 2 test 4 connected(4C×2EA)
※ Please change contact configurations if you needed

Note) The number of maximum contact: 8C (if needed)

ON/OFF button lock(B) Miss insertion prevent device (MIP)


To protect mis-operation of the ON/OFF button When the ratings of ACB and cradle does not match, this device
of ACB (common use 630~5000A) mechanically prevent the ACB from being inserted into the cradle of ACB
(common use 630~5000A)

26
Undervoltage trip device(UVT)
To trip the ACB automatically when the voltage of main power or control power source
reduces below its normal value. It consists of UVT coil and UVT controller.
UVT is attached to the inside of main body and UVT controller left side of the main(Fixed
type) or cradle(Draw-out).
In addition, external output contact(1a1b),which can use UVT operation as external control
signal, is supplied.
�For control power use, please apply AC power only.

UVT ratings
Rated Operatin UVT out put Pick-up Drop-off
Type Name
voltage g time contact voltage voltage
V1 AC 110V
V2 AC 220V
V3 AC 380V
Instantaneous V4 AC 460V 0.2sec
1c
type E1 DC 24V under
E2 DC 48V
E3 DC 110V
E4 DC 125V Over Under
T1 AC 110V 85% 75%
T2 AC 220V
of the of the In case of resetting or testing UVT device,
T3 AC 380V please do not maintain ’ON’ status of push button for
rated rated
T4 AC 460V 0.5sec a long time, and besides do not operate often ON/OFF.
1c voltage voltage It can be cause of damage.
F1 DC 24V over (Maintenance duration of ’ON’ status : Under 1 second,
ON/OFF Cycle : Under 30 Seconds)
F2 DC 48V
Time delay type
F3 DC 110V
F4 DC 125V
D1 AC 110V
D2 AC 220V 3sec
-
D3 AC 380V over
D4 AC 460V

Ratings of UVT output contact �UVT circuit of instantaneous type and 0.5 sec time delay type
Type Resistance load Inductive load
AC 125V 5A 2.5A
Voltage
DC 30V 5A 2.5A

Dimension & Circuit diagram of UVT


�UVT controller outline dimension

�UVT circuit of 3 sec time delay type

27
Optional accessories

Key lock(K0, K1) Counter (C)


To compulsorily prevent specific breaker from charging(ON) or trip(OFF) To mechanically indicate the times of ON/OFF
when two or more breakers are used together by interlocking operation of breaker
-KO: Mechanical OFF protection
-K1: Mechanical ON protection

Key interlock(K2)
It consists of 3 breakers to supply power stably and it is possible to
construct key interlock by using key lock attached to the inside of
Lifting hook (LH)
each breaker To move the ACB easily
�630~1600A: Optional offer
�2000~5000A: Standard offer

�Operational condition
ACB1 ACB2 ABC3
ON ON OFF
OFF ON ON
ON OFF ON

Door interlock(DI)
To prevent the panel door from opening when
the breaker is ON

28
Shorting b-contact (SBC) Condenser trip device (CTD)
It is the contact to maintain the external control circuit normal condition To trip the breaker electrically within regular time when the control
by disconnection of Axb of auxiliary contact when the position of air power source is off. It is used with Shunt Coil(SHT).
circuit breaker is moved from connected position to test position. If there isn’t DC power,it is possible to supply the power to ACB by
The number of shorting b contact is the same with the number(5b) of rectifying the AC power.
the auxiliary contact Axb of air circuit breaker.
�Ratings
Ratings Specification
�Contacts(Linkage between Axb and short “b”) Type name CTD-100 CTD-200
ACB condition Rated input voltage(V) AC 100/110 AC 200/220
CLOSE OPEN
ACB position Frequency(Hz) 50/60 50/60
Connected position OFF OFF Rated charge voltage(V) 140/155 280/310
Shorting b contact
Test position ON ON Charging time Within 5sec Within 5sec
Auxiliary contacts Connected position OFF ON Tripping time over 3min over 2min
(Axb) Test position OFF ON Range of input voltage(%) 85~110 85~110
Condensor capacity 400㎌ 160㎌

�Circuit diagram
Safety shutter lock(STL)
To fix safety shutter for the safety during the operation in draw-out
state of a breaker.
For discharge of
electricity

�Outline dimension

Door frame (DF)


It is the device to look fine after the cut of a switchboard door when the
breaker is installed. It helps to check the front of a breaker from the
outside of a distributing board easily ※ Please refer
to door frame in 41, 42page.

<Side view>
Mechanical operated cell switch
(MOC)
The ACB mechanically operates, only in case of “connected” position
of its main board, so as to display its ON/OFF condition by contact
10a and 10b. Both Standard and large types are available. The
contact capacity is identical with the rated auxiliary contacts in page
26.

<Front view> <Rear view>

29
ATS with ACBs

Interlock can be composed only of an electric driven charge type circuit break and there are two kinds of bar type and wire
one. And in order to incorporate electric Interlock , ATS control is required separately. Electric Interlock charge closing
mode, voltage trip coil, closing coil, auxiliary contactor and charge complete contactor are elements for basic composition of
ACB.

ATS controller rating


As an operation voltage of ATS Controller it operates a motor of circuit breaker so an operation voltage of ATS controller and an operation of circuit
braker shall be used in the same way.

Model Name ATSC-110 ATSC-110-C ATSC-220 ATSC-220-C


Rated voltage AC110V AC220V
Usable voltage range AC 93.5(±5%)~126.5V(±5%) AC 187(±5%)~253V(±5%)
Frequency 50Hz/60Hz
Consumption power(wave phase) 15.4W
4-Position switch(stop,N, R, Auto) ■ ■ ■ ■
Test function ■ ■ ■ ■
Transmitter control function ■ ■ ■ ■
NRS function ■ ■ ■ ■
N power selection(Main phase/3phase) ■ ■ ■ ■
Time setting(T1~T6) ■ ■ ■ ■
Fault function(OCR/Circuit breaker trouble) ■ ■ ■ ■
Output contact(auto, load ) ■ ■ ■ ■
Communication function (RS-485) - ■ - ■

�T1 : At the time when EPCO UN is OFF the delayed time until Generation start-up signal is closed (t1 :
0.1, 0.5, 1, 2, 4, 8, 15, 30, 40, 50 seconds)

�T2 : At the time when EPCO UN is ON the delayed time until ACB2 is tripped (OFF) (t2 :
0.1, 1, 2, 4, 8, 15, 30, 60, 120, 240 seconds)

�T3 : At the time when ACB is tripped(OFF) the delayed time until ACB2 is inputted(ON)
(t3 : 0.5, 1, 2, 5, 10, 15, 20, 25, 30, 40 seconds)

�T4 : At the time when ACB2 is tripped(OFF) the delayed time until ACB2 is inputted(ON) (t4 :
0.5, 1, 2, 5, 10, 15, 20, 25, 30, 40 seconds)

�T5 : At the time when ACB2 is tripped(OFF) the delayed time until Generation start-up signal
contactor is opened (t5 : 60,
120, 180, 240, 300, 360, 420, 480, 540, 600 seconds)

�Stop-mode : In a state that UN (EPCO power) or UR(The Power , Station power) is usable a mode that ACB1(EPCO Circuit breaker) and ACB2
(The Power Station circuit breaker) are tripped (OFF).

�N-mode : In a state that UN (EPCO power) is usable a mode that ACB1(EPCO circuit braker) is inputted (ON) artificially -UR (The Power Station
power) is not related to ON or OFF state and if converting into N-mode during use of UR (The Power Station power) Generation start-
up signal is opened.

�R-mode : In a state that UN (EPCO power) is usable or not a mode that ACB2(The Power Station circuit breaker) is inputted (ON) artificially in a
state that UR(The Power Station power) is usable

�Auto-mode : A mode that unusable power (UN or UR) circuit braker is tripped (OFF) or usable power circuit breaker is inputted (ON) according
to unusability or usability of UN (EPCO power) or UR (The Power Station power).
Note) EPCO: Electric Power Co.

30
Operational condition
In case of using 2 ACBs
�If 1(One) of 2(two) connected ACBs is ON, the other is
not ON electrically and mechanically by interlock.
�Operational condition

ACB1 ACB2
OFF OFF
ON OFF
OFF ON

In case of using 3 ACBs


�If 2(two) of 3(three) connected ACBs are ON
simultaneously, the other is not ON electrically and
mechanically by interlock.
�Operational condition
ACB1 ACB2 ACB3
OFF OFF OFF
ON OFF OFF
ON ON OFF
OFF ON ON
OFF OFF ON
ON OFF ON

Interlock method
Bar type

Wire type
Interlock is possible regardless of the Ampere Frame sizes and the
number of poles. Standard length of wires are 2 meters

<Wire Type> <Bar Type>

31
32
Time chart
ATS with ACBs

�UN: Main power(normal power) �symbol explantion


�UR: Emergency power (standby power) ∙I position: circuit close
�Gs: Generator start-up signal ∙O position: circuit open
�Ls: Load shedding : there is no effect whether the condition is ON or OFF
�ACB1: N-side breaker(normal breaker)
�ACB2 : R-side breaker(stand-by breaker)
A flow chart of operation
STOP mode N mode R mode
Normal power ON Stand-by power ON
Un voltage R-mode and Un voltage

Stop Stop Generator Generator start-up signal

t < t6 UR recover
Stop generator
R side breaker open N side breaker open

N/R side breaker open t > t4 t > t3

N side breaker close R side breaker close


Reset

End reset
Normal power ON Stand-by power ON

Operate 4 position switch


Operate 4 position switch
Stop operation

AUTO mode

UN voltage recover
Normal power ON t > t2
UN voltage loss R side breaker open
t > t1

Operate generator t > t4

t < t6 UR recover N side breaker close

N side breaker open

t > t3 Generator running under


power ON condition

R side breaker close t > t5

Generator OFF

Stand-by power ON
UR voltage loss

33
ATS with ACBs

A flow chart of operation


NRS mode

Auto mode Auto mode Auto mode

NRS Mode NRS Mode NRS Mode


(D terminal) (D terminal) (D terminal)

Operate generator Operate generator Operate generator

t < t6 UR recover t ≥ t6 t ≥ t6

N side breaker open C terminal C terminal

t > t3 0 1

R side breaker close N side breaker open R side breaker open

t > t4

Stand-by power ON R side breaker open N side breaker close

Test mode

Auto mode

Test button

Operate generator

N side breaker open

t > t3

R side breaker close

180 sec

Note) If you want to stop the test under test mode, press test button again

34
OCR-II
Control circuit

Undervol-
tage trip Electric
device operating Charge complete Auxiliary switch
Main circuit Trip relay Cell switch
(UVT) circuit contact

Terminal code description Accessory code description

Note) 1. In case of auxiliary contact is high capacity, B10+ and B10- can not be used because contact composition is 5a4b.
2. Under voltage trip coil terminal such as U+ or U- shall put output power of UVT controller.
3. In case of 3poles, T4 terminal shall be removed.

35
4. Only alternating current power shall be put to trip relay power terminal such as R+ , R- and R2- .
5. Above circuit diagram shows ACB locates on "Connected" position and ACB status will be trip or motor charging completion.
36
OCR-III
Control circuit

Undervol-
tage trip Electric
device operating Charge complete Auxiliary switch
Main circuit Trip relay Cell switch
(UVT) circuit contact

Terminal code description Accessory code description

Note) 1. In case of auxiliary contact is high capacity, B10+ and B10- can not be used because contact composition is 5a4b.
2. Under voltage trip coil terminal such as U+ or U- shall put output power of UVT controller.
3. Only alternating current power shall be put to trip relay power terminal such as R+ and R2- .
4. Above circuit diagram shows ACB locates on "Connected" position and ACB status will be trip or motor charging completion.
ATS with ACBs (LG controller circuit)

(N, R Wiring Terminal)

Trip
relay
part

Trip
relay
part

Note) 1. part shows optional feature“N”and“R”distriduting wires are in same condition and applied OCR-II.
2. In case of connecting the trip relay (OCR-II) Control power R+/R1-: AC110V, R+/R2-: AC220V
3. In case of connecting the trip relay (OCR-III) Control power R+/R2-: AC/DC110V�220V common use, DC48V, DC24V (R1- contact is not provided)
4. Please compose“Self maintenance circuit”because alarm contact (AL1+/AL1-, AL2+/AL2-) is a instantaneous operating(under 15ms) type in case of using OCR-II.
You may not compose“Self maintenance circuit”, provided when OCR-III is using for a trip relay.
5. Please input power to the MCB1, MCB2 of controller from the primary power.
(If it is tripped OCR at the load part when power is connected, power will not be transfered automatically)
6. Please connect the control power of trip relay (OCR-II. III) at the primary power section.
7. According to this circuit drawing, ACB position is“connected”standard, and ACB status is motor charged and tripped.
37
Control circuit

ATS with ACBs (M/G controller circuit)

(N, R Wiring Terminal)

Trip
relay
part

Trip
relay
part

Note) 1. part shows optional feature“N”and“R”distriduting wires are in same condition and applied OCR-II.
2. In case of connecting the trip relay (OCR-II) Control power R+/R1-: AC110V, R+/R2-: AC220V
3. In case of connecting the trip relay (OCR-III) Control power R+/R2-: AC/DC110V�220V common use, DC48V, DC24V (R1- contact is not provided)
4. Please compose“Self maintenance circuit”because alarm contact (AL1+/AL1-, AL2+/AL2-) is a instantaneous operating (under 15ms) type in case of using OCR-II.
Youmay not compose“Self maintenance circuit”, provided when OCR-III is using for a trip relay.
5. Please input power to the MCB1, MCB2 of controller from the primary power.
(If it is tripped OCR at the load part when power is connected, power will not be tromsfered automatically)
6. Please connect the control power of trip relay (OCR-II. III) at the primary power section.
7. According to this circuit drawing, ACB position is“connected”standard, and ACB status is motor chargeed and tripped.

38
ATS with ACBs (Manual)
R21
MC2
R11

N21
MC1
N11
CAM S/W

CAM S/W

MC1

N11

N21
MC1

MC2

R11

R21
MC2

1. ATS Controller will be damaged when MC1 or MC2 is missing. Please compose it essentially.
2. If application of connection wire is required, please compose M+ and M- of Auto mode wiring which shall open when transfer
from Auto mode to manual mode.

Note) 1. Red part shows manual wiring.


2. Above wiring drawing is simplified, please refer to page 38.
3. CAM S/W specification : 2position 4contact (4a4b).
4. MC1, MC2 specification : AX 2b/Minimum contact capacity shall be 10A.
5. Wiring of Auto/Manual mode of "N", "R" circuit breaker is composed in same way. (When ship a ACB at factory)

39
External dimensions (Draw-out type)

Horizontal terminal type (630~1600A)


(Unit: mm)

339
423
67 162 162
67 162 246

5
27 27

UVT Controller UVT Controller


430

430
118

118
150

150
40

40
100 42.5 100 42.5
4-∅14 Mounting hole
200 Note 1) 285 Note 1) 4-∅14 Mounting hole

278 278

[Front view]

17 35 379

359
68 12
48

Cell S/W
25

Lifting hole

100
15
430

350

370
132
218
15
92
15

43

Note 1) 175 21
20

57 200 161 Note 2)

[Side view] [Rear view] [Connection conductor]


Note) 1. Size of mounting hole
2. Size of connection conductor of Ace-MEC ACB.

Door Frame (DF): (630~1600AF/3,4Pole)

[In case of using DF] [In case of not using DF]

Operating panel center Operating panel center nter Operating panel center
8
8- 5
367

367

352

371
392
335
352
417

195
195

295 280
280
320
345 Break Breaker mounting frame

External size Dimension of cutting panel Cutting panel


40
Horizontal terminal type (2000~3150A)
(Unit: mm)
473 603
67 252 206 67 252 336

5
27 27

UVT UVT
Controller Controller

430

430
118

118
150

150
40

40
100 42.5 100 42.5
4-∅14 4-∅14
200 Note 1) 278
278 300 Note 1)

[3Pole] [4Pole]
[Front view]

17 35 379
359
68 12
48

Cell S/W
25

Note 3)

100
430

350

370
132
218
92
15

43

Note 1) 175 21
20

57 200 161
Note 2)

[Side view] [Rear view] [Connection conductor]


Note) 1. Size of mounting hole
2. Size of connection conductor of Ace-MEC ACB.
3. Please refer to T dimension in 41 page.

Door frame (DF): (2000~3150AF/3,4Pole)

[In case of using DF] [In case of not using DF]


Operating Panel Center Operating panel center ter
8
8- 5
352
367

371
392
335

367
352
417

195(220)

195

295 280
280
320 Breaker mounting frame
345 Bre

External size Dimension of cutting panel Cutting panel


41
External dimensions (Draw-out type)

Vertical terminal type (630~1600A)

(Unit: mm)

68 12
48

Cell S/W

Note 1)
Note 2)
[Side view] [Rear view] [Connection conductor]

Vertical terminal type (2000~3150A)

Note 1)
Note 2)
[Side view] [Rear view] [Connection conductor]

�“T” Size
Rated current T
2000A, 2500A 20
3150A 25

Note) 1. Size of mounting hole


2. Size of connection conductor of Ace-MEC ACB.

42
Vertical terminal type (4000~5000A)
(Unit: mm)

67
Cell S/W
68 12

48
UVT
Controller

[Front view] [3Pole] [Side view]

67

UVT
Controller
118
175

48
58

[Front view] [4Pole] [Connection conductor]

[Rear view]

�Door Frame (DF): (4000~5000AF/3,4Pole): The 2000~3150A of page41 is common use.


43
External dimensions(Fixed type)

Horizontal terminal type (630~1600A)


(Unit: mm)

67 67

118
118

141
141

[3Pole] [4Pole]
[Front view]

[Side view] [Rear view] [Connection conductor]

Door Frame (DF) : (630~1600AF/3, 4Pole)

[In case of using DF] [In case of not using DF]


Operating panel center 8 Operating panel center
8-ф5
352
417

367
392
335

351
352
175

175

280 295
280 Breaker mounting frame
345 320

External size Dimension of cutting panel Cutting panel


44
Horizontal terminal type (2000~3150A)

20 430 20

UVT UVT
Controller 67 Controller 67
118

118
141

141

[3Pole] [4Pole]
[Front view]

[Side view] [Rear view] [Connection conductor]

Door Frame (DF) : (2000~3150A, 4000~5000A/3,4Pole)

[In case of using DF] [In case of not using DF]


Operating Panel Center
8 Operating Panel Center
8- 5
352
417

352
392
335

367

351
175
175

280 280 Breaker mounting frame


295
345 320

External size Dimension of cutting panel Cutting panel


45
External dimensions(Fixed type)

Horizontal terminal type (4000~5000A)

20 820 25

362 447
102 144

UVT
Controller 67

20
410
118

350
218
132
20
141

72
22
3.2
378 181 19
278 295 40 40

842
870

[Front view] [3Pole] [Side view]

20 950 25

362 577

UVT
Controller 67

40
17
410
118

25

95
25
141

25

378 4-13
3.2

278

972

1000

[Front view] [4Pole] [Connection conductor]

130 130 130 130 130 130 130 130 130 130 130

23 23
95 95
20

20

[Rear view]
46
External dimensions

Vertical adapter attachable type


In order to use as vertical type, user can attach the optional vertical adopter in the existing horizontal connection type ACB

Fixed type (630~1600A) Fixed type (2000~5000A)


(Unit: mm)
23 88 25
23 70 15 2000/2500,
4000/5000A:20t
3150A:25t

15t

125
50

307
57
40
197

40
97

125
50
57

39.5

B
�Needed units of vertical adopter �Size
Ampere Pole Top Lower Common Total Ampere A B
3pole - - 6 6 2000, 2500
630~1600A 52 9
4pole - - 8 8 4000, 5000

3pole 3 3 - 6 3150 47 4
2000~3150A
4pole 4 4 - 8
3pole 6 6 - 12
4000~5000A
4pole 7 7 - 14

Draw-out type (630~1600A) Draw-out type (2000~3150A)


25 70 15 25 88 25
125
50

307
57

40
197

40
97

125
50

59.5

A
77

�Needed units of vertical adopter �Size


Ampere Pole Top Lower Common Total Ampere A B
3pole - - 6 6 2000, 2500 72 29
630~1600A
4pole - - 8 8 3150 67 24
3pole 3 3 - 6
2000~3150A
4pole 4 4 - 8

47
External dimension

ATS with ACBs(630~1600A)

[3Pole type] [4Pole type] [Side view]

Note) Above size is the standard size of our company. If you need other size, Please contact to us.

48
ATS with ACBs(2000~3150A)

[3Pole type] [4Pole type] [Side view]

Note) Above size is the standard size of our company. �“T” Size
If you need other size, please contact to us.
Rated current T
2500A 20
3150A 25

49
Technical information

Deratings by ambient temperature


�Ambient temperature: -5℃~±40℃(Only applicable when the 24 hours average temperature is below ±35℃)
�Altitude: Below 2000m
�Environmental condition
-Below 85% in humidity with ±40℃ maximum temperature
-Within the flammable, ammonia and corrosive gas environment can not be used and stored
(H2S≤0.01ppm, SO2≤0.01ppm, NH3≤a few ppm)
�Safekeeping temperature: -20℃~±60℃ below ±35℃ degree of 24 hours average temperature

Applicable current of braker in temperature


In case of use of over 40℃ in ambient temperature, please refer to below table as adjusting the rated currents

Type Ambient temperayure LBA-06 LBA-08 LBA-10 LBA-13 LBA-16 LBA-20 LBA-25 LBA-32 LBA-40 LBA-50
40℃ 630 800 1,000 1,250 1,600 2,000 2,500 3,150 4,000 5,000
45℃ 630 800 1,000 1,250 1,600 2,000 2,500 3,150 4,000 5,000
IEC60947-2
50℃ 630 800 1,000 1,250 1,600 2,000 2,500 3,150 4,000 5,000
℃)
(Standarde temp: 40℃
55℃ 630 800 1,000 1,250 1,550 2,000 2,450 3,000 3,900 4,850
60℃ 630 800 1,000 1,200 1,500 2,000 2,350 2,900 3,750 4,700

Arc Space
When designing switchboard, please keep the distance more than the recommended insulation distance between Ace-MEC ACB and
switchboard.

(Unit: mm)
Type Fixed type Draw-out type
A 25 25
B 150 150
Note) The number of "A" shall be increased in proportion to the size when
attaching UVT, Mechanical Interlock, Door Interlock.

50
Type selection

Ace-MEC ACB

LBA-10S-3EC M1 D1 D1 AX LPO V1 B
C

Insertion type A power source of Trip Trip relay UVT


MA Manual charging D1 AC/DC 110V OCR-II OCR-III Non-attachment
00
Motor charging D2 AC/DC 220V protection type
Industry Option Industry Option
Operating power D3 DC 125V Motor Attachment type
sourceof the motor U1
D4 DC 24V 000 None 000 000 None
M1 AC/DC 110V D5 DC 48V LPO L,S,I,P AC110,220V 60Hz N16 P16 L,S,I,G,P Comm. NO AC/DC110/220V 60Hz
M2 AC/DC 220V Note) DC24, 48V is the LGP L,S,I,G,P N26 P26 L,S,I,G,P Comm. NO DC24V 60Hz
M3 DC 125V underdeveloped AC110,220V 60Hz N46 P46 L,S,I,G,P Comm. NO DC48V 60Hz
rating.
M4 DC 24V LPH L,S,I,P AC110,220V 50Hz C16 M16 L,S,I,G,P Comm. YES AC/DC110/220V 60Hz
M5 DC 48V C26 M26 L,S,I,G,P Comm. YES DC24V 60Hz
Note) DC24, 48V is the C46 M46 L,S,I,G,P Comm. YES DC48V 60Hz
underdeveloped N15 P15 L,S,I,G,P Comm. NO AC/DC110/220V 50Hz
rating.
N25 P25 L,S,I,G,P Comm. NO DC24V 50Hz
N45 P45 L,S,I,G,P Comm. NO DC48V 50Hz
C15 M15 L,S,I,G,P Comm. YES AC/DC110/220V 50Hz
Insertion power source Auxiliary contact and charging type C25 M25 L,S,I,G,P Comm. YES DC24V 50Hz
D1 AC/DC 110V Marking Auxiliary contact Charge Type C45 M45 L,S,I,G,P Comm. YES DC48V 50Hz
D2 AC/DC 220V AX Standard type 5a5b Standard type(OFF Charge)
D3 DC 125V HX High capacity 5a4b or manual charge method Optional accessories
D4 DC 24V AC Standard type 5a5b High speed reclose B On/Off button lock
D5 DC 48V charging type K1 Key lock (On-lock))
HC High capacity 5a5b K2 Key interlock
Note) DC24, 48V is the (ON Charge meathod)
underdeveloped DF Door frame
rating. SBC Shorting b-contac
CTD Condersor trip device
Separate
OT OCR tester
Type name of sale
1600A below Top, Lower
product Vertical
2000/2500A Top
(Individual
adapter code)
2000/2500A Lower
(Fixed
3150A Top
type)
3150A Lower
Note) Please refer to page 46 for needed units of
vertical adapters.

LBA 10 S 3 E C

Specific type Trip relay Installation method


LG ACB With triprelay E Draw-out type
S
(standard) P Fixed type
Without triprelay
E
(economic)

Rated current Numper of pole Disposal order of phase


06 630A 25 2500A 3 3Poles type C Ace-MEC standard type order (R,S,T,N)
08 800A 32 3150A 4 4Poles type X Ace-MEC reverse phase type order (N,R,S,T)
10 1000A 40 4000A
13 1250A 50 5000A
16 1600A
20 2000A

Note) Order procedure of Ace-MEC ACB refers to 52 page of Ace-MEC ACB order sheet.

51
Type selection

Ace-MEC ACB Cradle

LCL 16 3 S E C V1 DI

Specific type Bus-bar type Cardle type Reform order


LG ACB Cradle S Horizontal Safety shutter Standard type
C
V Vertical E non-attachment (R,S,T,N)
Note) Vertical type is type Reverse phase
basic for draw- X
Safety shutter type(N,R,S,T)
out type 4000, F
5000AF. attachment type Note) Only standard
Note ) Auto-connection type is available
type for 4000, 5000AF

Rated current Number of pole UVT Controller Optional accessories


06/16 630 ~ 1600A 3 3Poles type 00 Without UVT controller T1 AC 110V Delay, over 0.5sec 4C Cell switch (4c)
20/25 2000 ~ 2500A 4 4Poles type V1 AC 110V Instantaneous, under 0.15sec T2 AC 220V Delay, over 0.5sec 8C Cell switch (8c)
32 3150A V2 AC 220V Instantaneous, under 0.15sec T3 AC 380V Delay, over 0.5sec DI Door interlock
60 4000 ~ 6300A V3 AC380V Instantaneous, under 0.15sec T4 AC 460V Delay, over 0.5sec Mechanical operation indicating
MC1
Note) 6300AF is on V4 AC460V Instantaneous, under 0.15sec F1 DC 24V Delay, over 0.5sec contact(standard type)
developing Separate
E1 DC24V Instantaneous, under 0.15sec F2 DC 48V Delay, over 0.5sec Mechanical operation indicating
MC2 sale
E2 DC48V Instantaneous, under 0.15sec F3 DC 110V Delay, over 0.5sec contact(High capacity type)
(Individual
E3 DC110V Instantaneous, under 0.15sec F4 DC 125V Delay, over 0.5sec MIP Miss insertion prevent device
code)
E4 DC125V Instantaneous, under 0.15sec D1 AC 110V Delay, over 0.3sec STL Safety shutter lock
D2 AC 220V Delay, over 0.3sec 1600A below Top, Lower
Vertical
D3 AC 380V Delay, over 0.3sec 2000/2500A Top
adapter
D4 AC 460V Delay, over 0.3sec 2000/2500A Lower
(Draw-out
3150A Top
type)
3150A Lower
Note) Please refer to page 46 for needed units of
vertical adapters.

52
Ordering sheet for Ace-MEC ACB
If rating is different in each set, please fill out other ordering sheet. month date year
Reception LG Industrial Systems co., Ltd Team Esqr.
Dispatch Company name Name TEL. FAX.
Project Delivery data Delivery place
ACB Ratings � 630A EA � 800A EA � 1000A EA
Quantity � 1250A EA � 1600A EA � 2000A EA
� 2500A EA � 3150A EA � 4000A EA
� 5000A EA
Trip relay � No
� Yes
Application Operating characteristics Application Operating characteristics Remark
TYPE Long-time shot-time Instantaneous Ground Pre commu- Frequency TYPE Generator Long-time shot-time Pre commu- Frequency
Industry Generator
Instantaneous Ground
protection delay delay time delay fault -Alarm nication Industry protection delay delay time delay fault -Alarm nication
Marking method Operating Voltage

� LPO ● - ● ● ● - ● - 60Hz � LPH ● - ● ● ● - ● - 50Hz L,S,I,P AC110,220V


OCR-II
� LGP ● - ● ● ● ● ● - 60Hz � LTH ● - ● ● ● ● ● - 50Hz L,S,I,G,P AC110,220V
� N16 ● - ● ● ● ● ● - 60Hz � P16 - ● ● ● ● ● ● - 60Hz L,S,I,G,P AC/DC110/220V
� N26 ● - ● ● ● ● ● - 60Hz � P26 - ● ● ● ● ● ● - 60Hz L,S,I,G,P DC24V
� N46 ● - ● ● ● ● ● - 60Hz � P46 - ● ● ● ● ● ● - 60Hz L,S,I,G,P DC48V
� C16 ● - ● ● ● ● ● ● 60Hz � M16 - ● ● ● ● ● ● ● 60Hz L,S,I,G,P,C AC/DC110/220V
� C26 ● - ● ● ● ● ● ● 60Hz � M26 - ● ● ● ● ● ● ● 60Hz L,S,I,G,P,C DC24V
� C46 ● - ● ● ● ● ● ● 60Hz � M46 - ● ● ● ● ● ● ● 60Hz L,S,I,G,P,C DC48V
OCR-III
� N15 ● - ● ● ● ● ● - 50Hz � P15 - ● ● ● ● ● ● - 50Hz L,S,I,G,P AC/DC110/220V
� N25 ● - ● ● ● ● ● - 50Hz � P25 - ● ● ● ● ● ● - 50Hz L,S,I,G,P DC24V
� N45 ● - ● ● ● ● ● - 50Hz � P45 - ● ● ● ● ● ● - 50Hz L,S,I,G,P DC48V
� C15 ● - ● ● ● ● ● ● 50Hz � P15 - ● ● ● ● ● ● ● 50Hz L,S,I,G,P,C AC/DC110/220V
� C25 ● - ● ● ● ● ● ● 50Hz � P25 - ● ● ● ● ● ● ● 50Hz L,S,I,G,P,C DC24V
� C45 ● - ● ● ● ● ● ● 50Hz � P45 - ● ● ● ● ● ● ● 50Hz L,S,I,G,P,C DC48V
Note1) L: Long-time delay, S: Short-time delay, I: Instantaneous-time delay, G: Ground falult, P: Pre-Alarm 2) 3-poles no ground fault function 3) The 4000/5000AF can only be built in OCR-III
Number of pole � 3Pole type � 4Pole type
Installation type � Draw-out type � Fixed type
Diposal order Phase � Standard type (R, S, T, N) � Reverse phase type (N, R, S, T) Note1)
Input type � Manual charging
� Motor charging
�Charge type � Standard type (OFF Charge type)
� High speed (ON Charge type)
�Operating power source of the motor � AC/DC 110V � AC/DC 220V
� DC 125V � DC 48V � DC 48V
Insertion power � AC/DC 110V � AC/DC 220V � DC 125V � DC 48V � DC 24V
Trip power � AC/DC 110V � AC/DC 220V � DC 125V � DC 48V � DC 24V
ACB cradle Cradle type � Safety shutter non-attachment (E) � Safety shutter attachment(F)
Bus-bar type � Standard type (Horizontal) � Vertical type (Non-standard)
Accessory Main Standard ● Auxiliary contact (AX, 5a5b) � Standard type (attachment) � High capacity Note2)
body accessories ● Key Lock � ON- Lock (K1)
● Under voltage tripping device (UVT) � Non-attached type � Attached type
● Mechanical operating contact (MOC), Door Interlock (DI) � Non-attached type
Mechanical Interlock (MI) � Attached type
� Key Interlock (K2, ON-Lock)
� ON/OFF Button Lock (B)
Separate ● Shorting b-contact (SBC, 5b max.) � 1b � 2b � 3b � 4b � 5b
accessories � Door Frame (DF)
� Capacitor trip device (CTD)
� OCR tester (OT-2000)
ACB Separate ● UVT & UVT Controller
Cradle accessories � AC110V (V1) � AC220V (V2) � AC380V (V3) � AC460V (V4)
� Instantaneous type (Operation under 0.15sec)
� DC24V (E1) � DC48V (E2) � DC110V (E3) � DC125V (E4)
� AC110V (T1) � AC220V (T2) � AC380V (T3) � AC460V (T4)
� Delay type (Operation over 0.5sec)
� DC24V (F1) � DC48V (F2) � DC110V (F3) � DC125V (F4)
� Delay type (Operation over 3sec) � AC110V (D1) � AC220V (D2) � AC380V (V3) � AC460V (D4)
● Position switch (CL) � 4c � 8c (4c×2EA)
● Mechanical operating contact (MOC, 10a10b) � MC1 (Standard type) � MC2 (High capacity)
� Door Interlock (DI)
� Miss insertion prevent device (MIP)
� Safety shutte lock (STL)

Remark

Note) 1.In case of 4000/5000AF, producing reverse phase type of bus-bar phase configuration is not possible.
2.In case of motor charging(input)type, when charging type is standard (OFF Charging type) and high-capacity auxiliary contact is used, only 5a4b is possible.
Ordering sheet for ATS with ACBs
If rating is different in each set, please fill out other ordering sheet. month date year
Reception LG Industrial Systems co., Ltd Team Esqr.
Dispatch Company name Name TEL. FAX.
Project Delivery data Delivery place
Interlock Connection � WIRE type
meathod � Standard (WIRE length: 2000mm) � Non-standard (apply for further datails)
� BAR type
� Standard (BAR length: 675mm) � Non-standard (apply for further datails)
Interlock type � Mechancal and electrical type (Controller Yes) � Mechanical (Controller No)
ATS Controller � Communication function No � Communication function Yes
Angle (W×H×D) � Standard ∙630~1600AF: 600×1900×500mm � Non-standard (apply for further datails)
∙2000~3150AF: 800×1900×500mm
Main subatance ACB1 Rated (Main) ACB2 Rated (Emergency) � Same with ACB1 � Different fromACB1
of ACB Rated current AF AF
Trip relay � No � No
� Yes � Yes
OCR-II � LPO � LGP � LPH � LTH OCR-II � LPO � LGP � LPH � LTH
� N16 � N26 � N46 � C16 � C26 � C46 � N16 � N26 � N46 � C16 � C26 � C46
� P16 � P26 � P46 � M16 � M26 � M46 � P16 � P26 � P46 � M16 � M26 � M46
OCR-III OCR-III
� N15 � N25 � N45 � C15 � C25 � C45 � N15 � N25 � N45 � C15 � C25 � C45
� P15 � P25 � P45 � M15 � M25 � M45 � P15 � P25 � P45 � M15 � M25 � M45
Note1) L: Long-time delay, S: Short-time delay, I: Instantaneous-time delay, G: Ground falult, P: Pre-Alarm 2) 3-poles no ground fault function 3) The 4000/5000AF can only be built in OCR-III
Number of Pole � 3 Pole type � 4 Pole type � 3 Pole type � 4 Pole type
Installation type � Draw-out time � Fixed type � Draw-out time � Fixed type
Disposal order type � Standard (R,S,T,N) � Reverse phase type (N,R,S,T) Note1) � Standard (R,S,T,N) � Reverse phase type (N,R,S,T) Note1)
� Manual changing � Manual changing
Input type � Motor changing � Motor changing
� Standard (OFF-charge type) � Standard (OFF-charge type)
∙Charge type ∙Charge type
� High speed (ON-charge type) � High speed (ON-charge type)
Insertion power � AC/DC 110V � AC/DC 220V � AC/DC 110V � AC/DC 220V
Trip power � AC/DC 110V � AC/DC 220V � AC/DC 110V � AC/DC 220V
� Safety shutter non-attachment (E) � Safety shutter non-attachment (E)
ACB cradle Cradle type
� Safety shutter attachment (F) � Safety shutter attachment (F)
Bus-bar type � Standard type (Horizontal) � Vertical type (Non-standard) � Standard type (Horizontal) � Vertical type (Non-standard)
Accessory � Standard type (attachment) � Standard type (attachment)
Main Standard ● Auxiliary contact (AX, 5a5b) ● Auxiliary contact (AX, 5a5b)
body accessories � High capacity Note2 � High capacity Note2)
● Key Lock � ON-lock (K1) ● Key Lock � ON-lock (K1)
● Under voltage tripping device � Non-attached type ● Under voltage tripping device � Non-attached type
(UVT) � Attached type (UVT) � Attached type
� Key Interlock (K2) � Key Interlock (K2)
� ON/OFF Button Lock (B) � ON/OFF Button Lock
Separate � Door Frame (DF) � Door Frame (DF)
accessories � Shorting b-contact (SBC, 5b max.) - Contact: ( )b � Shorting b-contact (SBC, 5b max.) - Contact: ( )b
� Capacitor trip device (CTD) � Capacitor trip device (CTD)
� OCR tester (OT-2000) � OCR tester (OT-2000)
ACB Separate ● Under voltage tripping device (UVT and UVT Controller) ● Under voltage tripping device (UVT and UVT Controller)
cradle accessories � Instantaneous type (Operation under 0.15sec) � Instantaneous type (Operation under 0.15sec)
� AC110V (V1) � DC 24V (E1) � AC110V (V1) � DC 24V (E1)
� AC220V (V2) � DC 48V (E2) � AC220V (V2) � DC 48V (E2)
� AC380V (V3) � DC110V (E3) � AC380V (V3) � DC110V (E3)
� AC460V (V4) � DC125V (E4) � AC460V (V4) � DC125V (E4)
� Delay type (Operation over 0.5sec) � Delay type (Operation over 0.5sec)
� AC110V (T1) � DC 24V (F1) � AC110V (T1) � DC 24V (F1)
� AC220V (T2) � DC 48V (F2) � AC220V (T2) � DC 48V (F2)
� AC380V (T3) � DC110V (F3) � AC380V (T3) � DC110V (F3)
� AC460V (T4) � DC125V (F4) � AC460V (T4) � DC125V (F4)
� Delay type (Operation over 3sec) � Delay type (Operation over 3sec)
� AC110V (D1) � AC220V (D2) � AC110V (D1) � AC220V (D2)
� AC380V (D3) � AC460V (D4) � AC380V (D3) � AC460V (D4)
● Position switch (CL) � 4c � 8c (4c x 2EA) ● Position switch (CL) � 4c � 8c (4c x 2EA)
● Mechanical operating contact � Standard type (MC1) ● Mechanical operating contact � Standard type (MC1)
(MOC, 10a10b) � High capacity (MC2) (MOC, 10a10b) � High capacity(MC2)
� Door Interlock (DI) � Door Interlock (DI)
� Miss insertion prevent device (MIP) � Miss insertion prevent device (MIP)
� Safety shutter lock (STL) � Safety shutter lock (STL)

Remark

Note) 1.In case of 4000/5000AF, producing reverse phase type of bus-bar phase configuration is not possible.
2.In case of motor charging(input)type, when charging type is standard (OFF Charging type) and high-capacity auxiliary contact is used, only 5a4b is possible.
Memo
Leader in Electrics & Automation

� For your safety, please read user's manual thoroughly before operating.
� Contact the nearest authorized service facility for examination, repair, or adjustment.
� Please contact qualified service technician when you need maintenance.
Do not disassemble or repair by yourself!
Safety Instructions � Any maintenance and inspection shall be performed by the personnel having expertise concerned.

www.lgis.com

� HEAD OFFICE � Global Network


�Dalian LG Industrial Systems Co., Ltd China
LG TWIN TOWERS, 20 Yoido-dong, Youngdungpo-gu, Address: No. 15 Liaohexi 3 Road, economic and technical
development zone, Dalian, China
Seoul, 150-721, Korea Tel: 86-411-731-8210 Fax: 86-411-730-7560 e-mail: [email protected]
�LG-VINA Industrial Systems Co., Ltd Vietnam
Tel. (82-2)3777-4870 Address: LGIS VINA Congty che tao may dien Viet-Hung Dong Anh Hanoi, Vietnam
Tel: 84-4-882-0222 Fax: 84-4-882-0220 e-mail: [email protected]
Fax. (82-2)3777-4713
�LG Industrial Trading (Shanghai) Co., Ltd China
http://www.lgis.com Address: Room 1705-1707, 17th Floor Xinda Commerical Building No 318,
Xian Xia Road Shanahai, China
Tel: 86-21-6252-4291 Fax:86-21-6278-4372 e-mail: [email protected]
�LG Industrial Systems Beijing Office China
Address: Room 303, 3F North B/D, EAS 21 XIAO YUN ROAD,
Dong San Huan Bei Road, Chao Yang District, Beijing, China
Tel: 86-10-6462-3259/4 Fax: 86-10-6462-3236 e-mail: [email protected]
�LG Industrial Systems Shanghai Office China
Address: Room 1705-1707, 17th Floor Xinda Commerical Building
No 318, Xian Xia Road Shanahai, China
Tel: 86-21-6278-4370 Fax: 86-21-6278-4301 e-mail: [email protected]
�LG Industrial Systems Guangzhou Office China
Address: Room 303, 3F, Zheng Sheng Building, No 5-6, Tian He
Bei Road, Guangzhou, China
Tel: 86-20-8755-3410 Fax: 86-20-8755-3408
e-mail: [email protected]
�LG Industrial Systems New Jersey Office USA
Address: 1000 Sylvan Avenue, Englewood Cliffs, New Jersey 07632 USA
Tel: 1-201-816-2985 Fax: 1-201-816-2343 e-mail: [email protected]
�LG Industrial Systems Tokyo Office Japan
Address: 16F, Higashi-Kan, Akasaka Twin Towers 17-22, 2-chome,
Specifications in this catalog are subject to change without notice due to Akasaka, Minato-ku Tokyo 107-0052, Japan
continuous product development and improvement. Tel: 81-3-3582-9128 Fax: 81-3-3582-0065 e-mail: [email protected]

2003. 12 Ace-MEC ACB (E) 2003. 4/(03) 2003. 12 Printed in Korea STAFF