ACB Ace-MEC
ACB Ace-MEC
Ace-MEC
Air Circuit Breakers
Electric Equipment
Air Cicuit Breakers
LG“ATS with ACBs”interlocks the ACBs �Application: The place which require stable power
2
Characteristics 4
Features & internal structure 6
Ratings 8
Charging methods 10
Auxiliary devices 11
Electronic trip relay 12
Operating characteristics of trip relay 17
Characteristics curve 21
Optional accessories 25
ATS with ACBs 30
Control circuit 35
External dimensions 40
Technical information 50
Type selection 51
Ordering sheet for Ace-MEC ACB 53
Ordering sheet for ATS with ACBs 54
3
Characteristics
4
Safety and Convenience High functional digital type trip relay
�OCR terminals are located in front �Easy inspection by LCD
�Modulized mechanical part and accessories - Load current value
�for easy maintenance and inspection Improved draw-out rail - Setting values of each trip characteristics
- Fault current(Max) value
for easy draw-out
- Tripping time
�Minimized arc space
�Self-diagnosis function
� Molded frame
- noEr : No error
※ The reverse connection of power source and load part is available but please use the normal - Err-1 : No MTD coil
connection for the safety in maintenance and inspection - Err-2 : Program error
- Err-4 : Configuration resister error
- Err-8 : Watch dog error
�Self-test function
- It is available to check whether OCR is operated normaly or
not by applying external power
�Pre-alarm function
�Contact output of the each tripping cause and LED indication
�OCR alarm contact (AL, 2a)
Variety of accessories
Optional accessories
�Interlock device
- Mechanical interlock, interlock unit,
- ATS, ATS controller
�Key interlock(K2, ON-Lock)
�Key lock(K0, K1)
�ON/OFF button lock(B, ON/OFF button lock)
�Door Frame(DF)
�Door Interlock(DI)
�UVT, UVT controller: Standard(1NO 1NC)
5
Features and internal structure
2 1
15
13 11 10 12 14
6
4 3 2 1 13
�
21
14
5
15
7
8 16
22
6 17
11
10 12 20 19 18
1 Control circuit terminal block 9 Charging mechanism 17 Main conductor of load part
2 Control terminal 10 Closing spring 18 Contact spring
3 Auxiliary switches 11 Draw-out mechanism 19 CT for power
4 Shunt trip device, closing coil 12 Insulated base 20 Coil for current detection
5 Electronic trip relay 13 Arc extinguishing chamber 12
21 Cradle
1
6 Front cover 14 Main movable contact
12 22 Main circuit junction
7 Closing mechanism 15 Main fixed contact
8 Tripping mechanism 16 Main conductor of line part
7
Ratings
ATS with Mechanical Without maintenance 10000 10000 10000 10000 10000
(time)
ACBs Note 4) Electrical Without maintenance 3000 3000 3000 3000 3000
Main body Motor charging type 66/80 67/81 67/81 67/81 67/81
Draw-out
(with cradle) Manual charging type 63/77 64/78 64/78 64/78 64/78
Weight type
(kg) Cradle only 26/30 26/30 26/30 26/30 26/30
(3P/4P)
Motor charging type 43/53 44/54 44/54 44/54 44/54
Fixed type
Manual charging type 40/50 41/51 41/51 41/51 41/51
Horizontal type Note5) Standard Standard Standard Standard Standard
Bus-bar Connection type
Vertical type Option Option Option Option Option
Motor charging type Standard Standard Standard Standard Standard
Closing type
Manual charging type Option Option Option Option Option
External Draw-out type (mm) H: 435, D: 479 W(3P/4P) 350/435 350/435 350/435 350/435 350/435
dimension Fixed type (mm) H: 410, D: 375 W(3P/4P) 345/430 345/430 345/430 345/430 345/430
Certificate & Approval KERI, CECI, CCC
8
Type LBA-20���C LBA-25���C LBA-32���C LBA-40���C LBA-50���C
Note1)
Rated current (In max) (A) 2000 2500 3150(3200) 4000 5000
Rated operating voltage (Ue) (V) 690 690 690 690 690
Rated insulation voltage (Ui) (V) 1000 1000 1000 1000 1000
Frequency Note2) (Hz) 50/60 50/60 50/60 50/60 50/60
Number of poles (P) 3,4 3,4 3,4 3,4 3,4
OCR-II For industry In max. ×1.0-0.9-0.8-0.7-0.6-0.5-0.4(7 Steps) -
Setting current (In) (A) For industry In max. × 1.0-0.9-0.8-0.7-0.6-0.5-0.4(7 Steps)
OCR-III Note3)
For generator protection In max. ×1.0-0.9-0.8-0.7-0.6-0.5-0.4-0.3-0.2(9 Steps)
Rated current of neutral pole (A) 2000 2500 3150 2500 2500
690V 50 50 50 50 50
Rated breaking capacity (ICU)
(kA) IEC 60947-2 AC 600V 65 65 65 85 85
(Sym)
500V Under 85 85 85 100 100
Rated service breaking capacity (ICS) (kA) … % ×ICU 100% 100% 100% 100% 100%
690V 105 105 105 105 105
Rated making capacity (ICm)
(kA) IEC 60947-2 AC 600V 143 143 143 187 187
(peak)
500V Under 187 187 187 220 220
1 sec 65 65 65 85 85
Rated short-time capacity (ICW) (kA) 2 sec 65 65 65 - -
3 sec 65 65 65 - -
Maximum total breaking time 40 40 40 40 40
Operating time ( t) (ms)
Closing Time 80 80 80 80 80
Without maintenance 5000 5000 5000 2000 2000
Mechanical
With maintenance 20000 20000 20000 - -
ACB (time)
Without maintenance 3000 3000 3000 500 500
Life cycle Electrical
With maintenance 5000 5000 5000 - -
9
Charging method
10
Auxiliary devices
5 4 3
1 Pad lock(PL)
To fix a ACB into a position (Dis-connected, Test, Connected)
� Standard offer in the draw-out type
2 Position Indicator
Connected
To indicate the position (Dis-connected,Test, Connected) of a ACB Test
� Standard offer in the draw-out type Disconnected
4 Shunt coil(SHT)
�To open the breaker by remote control
�Use an auxiliary contact(INO) to prevent coil burning
�Pumping prevent circuit
�When the control power is ‘OFF’ at the ACB is ‘ON’ state, the ACB remains
‘ON’
Operational Inrush current Steady Closing
Rated voltage(V)
voltage(V) peak value(A) current(A) time(sec)
AC/DC 110 77~121 2 1
50/60Hz 220 154~242 3 1.3
125 88~138 2.3 1 0.04 under
DC 24 21~26V 30 3.5
48 41~53V 30 7
Note) The extent of operation voltage is 70~110% of the rated voltage. �Trip coil circuit
11
Electronic trip relay OCR-II
External configuration
No The name of knob Mode Setting step
(0.4-0.5-0.6-0.7-0.8-0.9-1.0) × In Max
�
1 Setting current In It blinks with OCR trip operation or when
it exceeds 115%, “Pick-up”LED blinks
Rated continuous
�
2 Ic (0.8 - 0.85 - 0.9 - 0.95 -1.0)×In
current
Long-time
�
3 LTD 15 - 30 - 60 -120 - 240 - 480 sec
delay tripping time
Short-time delay (2-3-4-6-8-10-OFF) × In
�
4 Is
tripping current In OCR trip operation, “STD” LED is turned ‘on’
Short-time delay
�
5 STD 0.05 - 0.1- 0.2 - 0.3 - 0.4 - 0.5 sec
tripping time
Instantaneous-time (4-6-8-10-12-16-OFF) × In
�
6 Ii
delay tripping current In OCR trip operation, “INST” LED is turned ‘on’
(0.7-0.8-0.9-0.95-1.0-OFF) × Ic
�
7 Pre-alarm Ip
In OCR trip operation, “PAL” LED is turned ‘on’
(0.1-0.2-0.3-0.4-0.5-0.6-OFF) × In Max 1
�
8 Ground fault current Ig
In OCR trip operation, “GTD” LED is turned ‘on’ 2
�
9 Ground fault time GTD 0.1 - 0.3 - 0.8 -1.5 - 3.0 sec 7
4
6
LED of the trip indicator and contact
LED Contact Kinds of tripping characteristics 8
LTD T1 - Long-time delay tripping indicator
STD T2 -
9
Short-time delay tripping indicator
INST T3 Instantaneous-time delay tripping indicator
GTD T4 Ground fault tipping indicator 3
PAL T5 Pre-alarm indicator
When the breaker closed(I,ON),“RUN”LED turn on and 5
RUN -
off continuously
- Over than 105% of the setting current(In)
PICK
- : LED turn on and off
UP
- Over than 120% of the setting current(In): LED turn off
12
Button operating procedures & explanation
Operating characteristics of trip Self-diagnosis check enforcement Indication of self-diagnosis and load condition
Button Button
Button LCD LCD LCD
Explanation operating Explanation operating Explanation
operating Indicate Indicate Indicate
order order
Press the Press the To indicate the result of
“MODE” To indicate “MODE” To indicate
self-diagnosis
button setting current(In) button setting current(In)
one time one time - noEr: No error
- Err-1: MTD coil does
Press
To indicate long- Press To indicate the Press the
“MODE” not exist
the “+” time delay tripping the “MODE” value of No trip button 4
button button - Err-2: Program error
time(LTD) (self-diagnosis mode) times
- Err-4: Configuration
Press To indicate Press To set the resister error
the “+” the “+” - Err-8: Watch dog
button continuous current(Ic) button value of No trip
error Note2
Press
To indicate short- To do self-diagnosis
the “+” time delay tripping test(Ip, In, TEST letter To indicate opreational
button Press current of the phase of
current(In) turn on and off)
the “+”
button
R-S-T-N in order by
Press To indicate short-time -After tripping, indicate the pressing “+” button
the “+”
button delay tripping time operating time of trip
Press
the “ENT” characteristics
Press
To indicate button
(“PAL” “LTD” LED turn on)
the “+” intantaneous-time
button - After 15~20sec, it
delay tripping current
changes to self-diagnosis
To indicate
Press display mode
the “+” ground fault
button automatically
tripping current
Press
To indicate Press the To reset “PAL”
the “+” ground fault “RESET”
button button “LTD” LED
tripping time
Note) 1. If - button pressed, the characteristics of trip displayed in the reversed order
2. In case of Watch dog error occurs, LCD indicates Error-8 during 15 seconds, then indicates maximum current value among R, S, T phases. At this moment, Run
LED is maintaining ON status when Error-8 occurs from the On and Off status in normal condition.
< Watch dog error Reset>
① If press mode button 4 times, LCD indicates Error-8 again. At this moment, press ENT button.
② After switch-OFF input power of over current relay, then switch-ON again.
Press Press
- “PAL” “LTD” LED turn on
Long-time
delay trip
the “-” the “+” - To indicate maximum current among
button button
the phase of R,S,T
�LCD: Press the - "STD" LED turn on
Press Press
Short-time
delay trip
the “-” the “+” “ENT” button - To indicate maximum current among
button button
the phase of R,S,T
Press Press
Ground
fault trip
the “-” the “+” - "GTD" LED turn on
button button
13
Electronic trip relay OCR-III
External configuration
1 Display LCD
�Display of normal condtion: In use current of R, S, T, N phases
�Fault display: Fault phases and kinds of fault EX)
- Long-time delay trip: L-INV FAULT : R
- Short-time delay trip: S-INV TYPE : L-INV
- Instantaneous-time delay trip: INST ⇒Long-time delay trip occuring in “R” phase
1
- Ground fault trip: GND ⇒ LCD reset method: Press “Func” button after “Ent”
Selection button
6 �Func: Mode selection button 7
RS232 Port
7 : OCR operation check port as connecting PC
TEST Port
8 : Connection button with OCR tester (OT-2000)
14
Button operation method in set-up modes
Set-up procedure of various set-up value
15
Electronic trip relay OCR-III
16
Operating characteristics of trip relay OCR-II
Ratings
17
Operating characteristics of trip relay OCR-III
Ratings
18
OCR-II
LGP, LTH
Characteristics of protection Standard functions
19
Operating characteristics of trip relay OCR-III
�6, P�
N� �6, N�
�5, P�
�5
Characteristics of protection Standard functions
�Setting the fixed current
�Setting the long-time delay tripping current�
Setting the long-time delay tripping time
�Setting the short-time delay tripping current
�Setting the short-time delay tripping time
�Setting the instantaneous-time delay
tripping current
�Setting the pre-alarm current
�Trip Indicator
�Communication
① RS232(Port)
① Long-time delay pick-up current - Setting the fixed value
② Long-time delay tripping time ③ Short- - Monitoring the fixed value
time delay pick-up current ④ Short- - Monitoring the operating tate of ACB
time delay tripping time OCR
⑤ Instantaneous pick-up current - Monitoring the load current of line
⑥ Pre-alarm pick-up current - Performing of calibration bility
⑦ Pre-alarm tripping time
�6, M�
C� �6, C�
�5, M�
�5
Characteristics of protection Standard functions
�Setting the fixed current
�Setting the long-time delay tripping current
�Setting the long-time delay tripping time
�Setting the short-time delay tripping current
�Setting the short-time delay tripping time
�Setting the instantaneous-time delay
tripping time
�Setting the ground fault tripping current
�Setting the ground fault tripping time
�Setting pre-alarm current
�Trip Indicator
�Communcation
① RS232(Port)
- setting the fixed value
① Long-time delay pick-up current
- Minitoring the fixed value
② Long-time delay tripping time
- Minitoring the load current of line
③ Short-time delay pick-up current
- Minitoring the operating state of ACB OCR
④ Short-time delay tripping time
- Performing of Calibration ability
⑤ Instantaneous pick-up current
② RS485(Port : 485+, 485-)
⑥ Pre-alarm pick-up current
- Setting the fixed value by remote
⑦ Pre-alarm tripping time
- Monitoring the fixed value
⑧ Ground fault pick-up current
- Monitoring the load current of line
⑨ Ground fault trip time
- Transmitting the failure information
(failure pole, failure factor)
- Transmitting the self-diagnosis information
20
Characteristics curve OCR-II
21
Characteristics curve OCR-II
22
OCR-III
�6, C�
N� �6, N�
�5, C�
�5 (For industry)
23
Characteristics curve OCR-III
�6, M�
P� �6, P�
�5, M�
�5 (For generator protection)
24
Optional accessories
OCR tester
Ratings
Name Key to initialize test current value (In, In Max)
OT-2000
and LED(trip, testing)
Rated voltage AC 100~240V
Frequency 50Hz, 60Hz (selection)
Key to start the test.
In max: (0-1) → If the value of In max is 1, the output
Output voltage is 200mV
Key to stop the operation of tester device
voltage In: (0-30)xIn max → It corresponds to the signal of
(Timer, stop output signal)
the OCR (Ex. If you set In to 30, 6V turns out.)
Type of output Key to initialize timer.
o, g, e Note1)
voltage (0 ms)
Stop signal OCR, a-contact, b-contact
Key that should be operated at first to revise test the
TC: Detect only the operation state of OCR
Trip time current value, and select type of the test current.
regardless of the timedelay characteristics.
Check
(Apply DC power) Key to shift the digit number of 7-segment,which
shows the test current value to right direction
Key to select frequency Key to increase 1digit by 1digit of 7-segment that shows
(50Hz, 60Hz) the test current value.
Key to select type of stop signal input voltage of the Key to decrease 1digit by 1digit of 7-segment that shows
OCR tester (OCR, a-contact, b-contact) the test current value.
Key to initialize the test current value when ED has been Key to set the test current value edited by →, ←, ↑, ↓ or
pressed one time. CL
Key to test whether OCR is operated normaly or not. Key to select operational characteristics of trip relay
Ⅱ
OCR-Ⅱ Ⅲ
OCR-Ⅲ
25
Optional accessories
Auxiliary contact(AX)
- To remote supervisory of the ON/OFF state of the ACB
Ratings
Standard type High capacity type
Type Resistive Inductive Resistive Inductive Remark
load load load load
460V 5A 2A 5A 2.5A
AC 250V 10A 10A 10A 10A
Contact 125V 10A 10A 10A 10A
capacity 250V 0.3A 0.3A 3A 1.5A
DC 125V 0.6A 0.6A 10A 6A
30V 10A 6A 10A 10A
AX 5a5b ‐ Standard
�Contact operating
Maximum HX ‐ 5a4b charging type
The condition of ACB a-contact b-contact
contact No. AC 5a5b ‐ High speed
HC ‐ 5a5b reclose ON ON OFF
charging type OFF OFF ON
Selection Standard offer Note) Option
Note) When you order the high capacity type auxiliary contact, the standard type auxiliary contact is not offered.
Cell switch(C)
kTo indicate the position (connected, test, dis-connected) of a
ACB
It is installed in the upper and back side of a cradle.
(Common use 630~5000A)
26
Undervoltage trip device(UVT)
To trip the ACB automatically when the voltage of main power or control power source
reduces below its normal value. It consists of UVT coil and UVT controller.
UVT is attached to the inside of main body and UVT controller left side of the main(Fixed
type) or cradle(Draw-out).
In addition, external output contact(1a1b),which can use UVT operation as external control
signal, is supplied.
�For control power use, please apply AC power only.
UVT ratings
Rated Operatin UVT out put Pick-up Drop-off
Type Name
voltage g time contact voltage voltage
V1 AC 110V
V2 AC 220V
V3 AC 380V
Instantaneous V4 AC 460V 0.2sec
1c
type E1 DC 24V under
E2 DC 48V
E3 DC 110V
E4 DC 125V Over Under
T1 AC 110V 85% 75%
T2 AC 220V
of the of the In case of resetting or testing UVT device,
T3 AC 380V please do not maintain ’ON’ status of push button for
rated rated
T4 AC 460V 0.5sec a long time, and besides do not operate often ON/OFF.
1c voltage voltage It can be cause of damage.
F1 DC 24V over (Maintenance duration of ’ON’ status : Under 1 second,
ON/OFF Cycle : Under 30 Seconds)
F2 DC 48V
Time delay type
F3 DC 110V
F4 DC 125V
D1 AC 110V
D2 AC 220V 3sec
-
D3 AC 380V over
D4 AC 460V
Ratings of UVT output contact �UVT circuit of instantaneous type and 0.5 sec time delay type
Type Resistance load Inductive load
AC 125V 5A 2.5A
Voltage
DC 30V 5A 2.5A
27
Optional accessories
Key interlock(K2)
It consists of 3 breakers to supply power stably and it is possible to
construct key interlock by using key lock attached to the inside of
Lifting hook (LH)
each breaker To move the ACB easily
�630~1600A: Optional offer
�2000~5000A: Standard offer
�Operational condition
ACB1 ACB2 ABC3
ON ON OFF
OFF ON ON
ON OFF ON
Door interlock(DI)
To prevent the panel door from opening when
the breaker is ON
28
Shorting b-contact (SBC) Condenser trip device (CTD)
It is the contact to maintain the external control circuit normal condition To trip the breaker electrically within regular time when the control
by disconnection of Axb of auxiliary contact when the position of air power source is off. It is used with Shunt Coil(SHT).
circuit breaker is moved from connected position to test position. If there isn’t DC power,it is possible to supply the power to ACB by
The number of shorting b contact is the same with the number(5b) of rectifying the AC power.
the auxiliary contact Axb of air circuit breaker.
�Ratings
Ratings Specification
�Contacts(Linkage between Axb and short “b”) Type name CTD-100 CTD-200
ACB condition Rated input voltage(V) AC 100/110 AC 200/220
CLOSE OPEN
ACB position Frequency(Hz) 50/60 50/60
Connected position OFF OFF Rated charge voltage(V) 140/155 280/310
Shorting b contact
Test position ON ON Charging time Within 5sec Within 5sec
Auxiliary contacts Connected position OFF ON Tripping time over 3min over 2min
(Axb) Test position OFF ON Range of input voltage(%) 85~110 85~110
Condensor capacity 400㎌ 160㎌
�Circuit diagram
Safety shutter lock(STL)
To fix safety shutter for the safety during the operation in draw-out
state of a breaker.
For discharge of
electricity
�Outline dimension
<Side view>
Mechanical operated cell switch
(MOC)
The ACB mechanically operates, only in case of “connected” position
of its main board, so as to display its ON/OFF condition by contact
10a and 10b. Both Standard and large types are available. The
contact capacity is identical with the rated auxiliary contacts in page
26.
29
ATS with ACBs
Interlock can be composed only of an electric driven charge type circuit break and there are two kinds of bar type and wire
one. And in order to incorporate electric Interlock , ATS control is required separately. Electric Interlock charge closing
mode, voltage trip coil, closing coil, auxiliary contactor and charge complete contactor are elements for basic composition of
ACB.
�T1 : At the time when EPCO UN is OFF the delayed time until Generation start-up signal is closed (t1 :
0.1, 0.5, 1, 2, 4, 8, 15, 30, 40, 50 seconds)
�T2 : At the time when EPCO UN is ON the delayed time until ACB2 is tripped (OFF) (t2 :
0.1, 1, 2, 4, 8, 15, 30, 60, 120, 240 seconds)
�T3 : At the time when ACB is tripped(OFF) the delayed time until ACB2 is inputted(ON)
(t3 : 0.5, 1, 2, 5, 10, 15, 20, 25, 30, 40 seconds)
�T4 : At the time when ACB2 is tripped(OFF) the delayed time until ACB2 is inputted(ON) (t4 :
0.5, 1, 2, 5, 10, 15, 20, 25, 30, 40 seconds)
�T5 : At the time when ACB2 is tripped(OFF) the delayed time until Generation start-up signal
contactor is opened (t5 : 60,
120, 180, 240, 300, 360, 420, 480, 540, 600 seconds)
�Stop-mode : In a state that UN (EPCO power) or UR(The Power , Station power) is usable a mode that ACB1(EPCO Circuit breaker) and ACB2
(The Power Station circuit breaker) are tripped (OFF).
�N-mode : In a state that UN (EPCO power) is usable a mode that ACB1(EPCO circuit braker) is inputted (ON) artificially -UR (The Power Station
power) is not related to ON or OFF state and if converting into N-mode during use of UR (The Power Station power) Generation start-
up signal is opened.
�R-mode : In a state that UN (EPCO power) is usable or not a mode that ACB2(The Power Station circuit breaker) is inputted (ON) artificially in a
state that UR(The Power Station power) is usable
�Auto-mode : A mode that unusable power (UN or UR) circuit braker is tripped (OFF) or usable power circuit breaker is inputted (ON) according
to unusability or usability of UN (EPCO power) or UR (The Power Station power).
Note) EPCO: Electric Power Co.
30
Operational condition
In case of using 2 ACBs
�If 1(One) of 2(two) connected ACBs is ON, the other is
not ON electrically and mechanically by interlock.
�Operational condition
ACB1 ACB2
OFF OFF
ON OFF
OFF ON
Interlock method
Bar type
Wire type
Interlock is possible regardless of the Ampere Frame sizes and the
number of poles. Standard length of wires are 2 meters
31
32
Time chart
ATS with ACBs
t < t6 UR recover
Stop generator
R side breaker open N side breaker open
End reset
Normal power ON Stand-by power ON
AUTO mode
UN voltage recover
Normal power ON t > t2
UN voltage loss R side breaker open
t > t1
Generator OFF
Stand-by power ON
UR voltage loss
33
ATS with ACBs
t < t6 UR recover t ≥ t6 t ≥ t6
t > t3 0 1
t > t4
Test mode
Auto mode
Test button
Operate generator
t > t3
180 sec
Note) If you want to stop the test under test mode, press test button again
34
OCR-II
Control circuit
Undervol-
tage trip Electric
device operating Charge complete Auxiliary switch
Main circuit Trip relay Cell switch
(UVT) circuit contact
Note) 1. In case of auxiliary contact is high capacity, B10+ and B10- can not be used because contact composition is 5a4b.
2. Under voltage trip coil terminal such as U+ or U- shall put output power of UVT controller.
3. In case of 3poles, T4 terminal shall be removed.
35
4. Only alternating current power shall be put to trip relay power terminal such as R+ , R- and R2- .
5. Above circuit diagram shows ACB locates on "Connected" position and ACB status will be trip or motor charging completion.
36
OCR-III
Control circuit
Undervol-
tage trip Electric
device operating Charge complete Auxiliary switch
Main circuit Trip relay Cell switch
(UVT) circuit contact
Note) 1. In case of auxiliary contact is high capacity, B10+ and B10- can not be used because contact composition is 5a4b.
2. Under voltage trip coil terminal such as U+ or U- shall put output power of UVT controller.
3. Only alternating current power shall be put to trip relay power terminal such as R+ and R2- .
4. Above circuit diagram shows ACB locates on "Connected" position and ACB status will be trip or motor charging completion.
ATS with ACBs (LG controller circuit)
Trip
relay
part
Trip
relay
part
Note) 1. part shows optional feature“N”and“R”distriduting wires are in same condition and applied OCR-II.
2. In case of connecting the trip relay (OCR-II) Control power R+/R1-: AC110V, R+/R2-: AC220V
3. In case of connecting the trip relay (OCR-III) Control power R+/R2-: AC/DC110V�220V common use, DC48V, DC24V (R1- contact is not provided)
4. Please compose“Self maintenance circuit”because alarm contact (AL1+/AL1-, AL2+/AL2-) is a instantaneous operating(under 15ms) type in case of using OCR-II.
You may not compose“Self maintenance circuit”, provided when OCR-III is using for a trip relay.
5. Please input power to the MCB1, MCB2 of controller from the primary power.
(If it is tripped OCR at the load part when power is connected, power will not be transfered automatically)
6. Please connect the control power of trip relay (OCR-II. III) at the primary power section.
7. According to this circuit drawing, ACB position is“connected”standard, and ACB status is motor charged and tripped.
37
Control circuit
Trip
relay
part
Trip
relay
part
Note) 1. part shows optional feature“N”and“R”distriduting wires are in same condition and applied OCR-II.
2. In case of connecting the trip relay (OCR-II) Control power R+/R1-: AC110V, R+/R2-: AC220V
3. In case of connecting the trip relay (OCR-III) Control power R+/R2-: AC/DC110V�220V common use, DC48V, DC24V (R1- contact is not provided)
4. Please compose“Self maintenance circuit”because alarm contact (AL1+/AL1-, AL2+/AL2-) is a instantaneous operating (under 15ms) type in case of using OCR-II.
Youmay not compose“Self maintenance circuit”, provided when OCR-III is using for a trip relay.
5. Please input power to the MCB1, MCB2 of controller from the primary power.
(If it is tripped OCR at the load part when power is connected, power will not be tromsfered automatically)
6. Please connect the control power of trip relay (OCR-II. III) at the primary power section.
7. According to this circuit drawing, ACB position is“connected”standard, and ACB status is motor chargeed and tripped.
38
ATS with ACBs (Manual)
R21
MC2
R11
N21
MC1
N11
CAM S/W
CAM S/W
MC1
N11
N21
MC1
MC2
R11
R21
MC2
1. ATS Controller will be damaged when MC1 or MC2 is missing. Please compose it essentially.
2. If application of connection wire is required, please compose M+ and M- of Auto mode wiring which shall open when transfer
from Auto mode to manual mode.
39
External dimensions (Draw-out type)
339
423
67 162 162
67 162 246
5
27 27
430
118
118
150
150
40
40
100 42.5 100 42.5
4-∅14 Mounting hole
200 Note 1) 285 Note 1) 4-∅14 Mounting hole
278 278
[Front view]
17 35 379
359
68 12
48
Cell S/W
25
Lifting hole
100
15
430
350
370
132
218
15
92
15
43
Note 1) 175 21
20
Operating panel center Operating panel center nter Operating panel center
8
8- 5
367
367
352
371
392
335
352
417
195
195
295 280
280
320
345 Break Breaker mounting frame
5
27 27
UVT UVT
Controller Controller
430
430
118
118
150
150
40
40
100 42.5 100 42.5
4-∅14 4-∅14
200 Note 1) 278
278 300 Note 1)
[3Pole] [4Pole]
[Front view]
17 35 379
359
68 12
48
Cell S/W
25
Note 3)
100
430
350
370
132
218
92
15
43
Note 1) 175 21
20
57 200 161
Note 2)
371
392
335
367
352
417
195(220)
195
295 280
280
320 Breaker mounting frame
345 Bre
(Unit: mm)
68 12
48
Cell S/W
Note 1)
Note 2)
[Side view] [Rear view] [Connection conductor]
Note 1)
Note 2)
[Side view] [Rear view] [Connection conductor]
�“T” Size
Rated current T
2000A, 2500A 20
3150A 25
42
Vertical terminal type (4000~5000A)
(Unit: mm)
67
Cell S/W
68 12
48
UVT
Controller
67
UVT
Controller
118
175
48
58
[Rear view]
67 67
118
118
141
141
[3Pole] [4Pole]
[Front view]
367
392
335
351
352
175
175
280 295
280 Breaker mounting frame
345 320
20 430 20
UVT UVT
Controller 67 Controller 67
118
118
141
141
[3Pole] [4Pole]
[Front view]
352
392
335
367
351
175
175
20 820 25
362 447
102 144
UVT
Controller 67
20
410
118
350
218
132
20
141
72
22
3.2
378 181 19
278 295 40 40
842
870
20 950 25
362 577
UVT
Controller 67
40
17
410
118
25
95
25
141
25
378 4-13
3.2
278
972
1000
130 130 130 130 130 130 130 130 130 130 130
23 23
95 95
20
20
[Rear view]
46
External dimensions
15t
125
50
307
57
40
197
40
97
125
50
57
39.5
B
�Needed units of vertical adopter �Size
Ampere Pole Top Lower Common Total Ampere A B
3pole - - 6 6 2000, 2500
630~1600A 52 9
4pole - - 8 8 4000, 5000
3pole 3 3 - 6 3150 47 4
2000~3150A
4pole 4 4 - 8
3pole 6 6 - 12
4000~5000A
4pole 7 7 - 14
307
57
40
197
40
97
125
50
59.5
A
77
47
External dimension
Note) Above size is the standard size of our company. If you need other size, Please contact to us.
48
ATS with ACBs(2000~3150A)
Note) Above size is the standard size of our company. �“T” Size
If you need other size, please contact to us.
Rated current T
2500A 20
3150A 25
49
Technical information
Type Ambient temperayure LBA-06 LBA-08 LBA-10 LBA-13 LBA-16 LBA-20 LBA-25 LBA-32 LBA-40 LBA-50
40℃ 630 800 1,000 1,250 1,600 2,000 2,500 3,150 4,000 5,000
45℃ 630 800 1,000 1,250 1,600 2,000 2,500 3,150 4,000 5,000
IEC60947-2
50℃ 630 800 1,000 1,250 1,600 2,000 2,500 3,150 4,000 5,000
℃)
(Standarde temp: 40℃
55℃ 630 800 1,000 1,250 1,550 2,000 2,450 3,000 3,900 4,850
60℃ 630 800 1,000 1,200 1,500 2,000 2,350 2,900 3,750 4,700
Arc Space
When designing switchboard, please keep the distance more than the recommended insulation distance between Ace-MEC ACB and
switchboard.
(Unit: mm)
Type Fixed type Draw-out type
A 25 25
B 150 150
Note) The number of "A" shall be increased in proportion to the size when
attaching UVT, Mechanical Interlock, Door Interlock.
50
Type selection
Ace-MEC ACB
LBA-10S-3EC M1 D1 D1 AX LPO V1 B
C
LBA 10 S 3 E C
Note) Order procedure of Ace-MEC ACB refers to 52 page of Ace-MEC ACB order sheet.
51
Type selection
LCL 16 3 S E C V1 DI
52
Ordering sheet for Ace-MEC ACB
If rating is different in each set, please fill out other ordering sheet. month date year
Reception LG Industrial Systems co., Ltd Team Esqr.
Dispatch Company name Name TEL. FAX.
Project Delivery data Delivery place
ACB Ratings � 630A EA � 800A EA � 1000A EA
Quantity � 1250A EA � 1600A EA � 2000A EA
� 2500A EA � 3150A EA � 4000A EA
� 5000A EA
Trip relay � No
� Yes
Application Operating characteristics Application Operating characteristics Remark
TYPE Long-time shot-time Instantaneous Ground Pre commu- Frequency TYPE Generator Long-time shot-time Pre commu- Frequency
Industry Generator
Instantaneous Ground
protection delay delay time delay fault -Alarm nication Industry protection delay delay time delay fault -Alarm nication
Marking method Operating Voltage
Remark
Note) 1.In case of 4000/5000AF, producing reverse phase type of bus-bar phase configuration is not possible.
2.In case of motor charging(input)type, when charging type is standard (OFF Charging type) and high-capacity auxiliary contact is used, only 5a4b is possible.
Ordering sheet for ATS with ACBs
If rating is different in each set, please fill out other ordering sheet. month date year
Reception LG Industrial Systems co., Ltd Team Esqr.
Dispatch Company name Name TEL. FAX.
Project Delivery data Delivery place
Interlock Connection � WIRE type
meathod � Standard (WIRE length: 2000mm) � Non-standard (apply for further datails)
� BAR type
� Standard (BAR length: 675mm) � Non-standard (apply for further datails)
Interlock type � Mechancal and electrical type (Controller Yes) � Mechanical (Controller No)
ATS Controller � Communication function No � Communication function Yes
Angle (W×H×D) � Standard ∙630~1600AF: 600×1900×500mm � Non-standard (apply for further datails)
∙2000~3150AF: 800×1900×500mm
Main subatance ACB1 Rated (Main) ACB2 Rated (Emergency) � Same with ACB1 � Different fromACB1
of ACB Rated current AF AF
Trip relay � No � No
� Yes � Yes
OCR-II � LPO � LGP � LPH � LTH OCR-II � LPO � LGP � LPH � LTH
� N16 � N26 � N46 � C16 � C26 � C46 � N16 � N26 � N46 � C16 � C26 � C46
� P16 � P26 � P46 � M16 � M26 � M46 � P16 � P26 � P46 � M16 � M26 � M46
OCR-III OCR-III
� N15 � N25 � N45 � C15 � C25 � C45 � N15 � N25 � N45 � C15 � C25 � C45
� P15 � P25 � P45 � M15 � M25 � M45 � P15 � P25 � P45 � M15 � M25 � M45
Note1) L: Long-time delay, S: Short-time delay, I: Instantaneous-time delay, G: Ground falult, P: Pre-Alarm 2) 3-poles no ground fault function 3) The 4000/5000AF can only be built in OCR-III
Number of Pole � 3 Pole type � 4 Pole type � 3 Pole type � 4 Pole type
Installation type � Draw-out time � Fixed type � Draw-out time � Fixed type
Disposal order type � Standard (R,S,T,N) � Reverse phase type (N,R,S,T) Note1) � Standard (R,S,T,N) � Reverse phase type (N,R,S,T) Note1)
� Manual changing � Manual changing
Input type � Motor changing � Motor changing
� Standard (OFF-charge type) � Standard (OFF-charge type)
∙Charge type ∙Charge type
� High speed (ON-charge type) � High speed (ON-charge type)
Insertion power � AC/DC 110V � AC/DC 220V � AC/DC 110V � AC/DC 220V
Trip power � AC/DC 110V � AC/DC 220V � AC/DC 110V � AC/DC 220V
� Safety shutter non-attachment (E) � Safety shutter non-attachment (E)
ACB cradle Cradle type
� Safety shutter attachment (F) � Safety shutter attachment (F)
Bus-bar type � Standard type (Horizontal) � Vertical type (Non-standard) � Standard type (Horizontal) � Vertical type (Non-standard)
Accessory � Standard type (attachment) � Standard type (attachment)
Main Standard ● Auxiliary contact (AX, 5a5b) ● Auxiliary contact (AX, 5a5b)
body accessories � High capacity Note2 � High capacity Note2)
● Key Lock � ON-lock (K1) ● Key Lock � ON-lock (K1)
● Under voltage tripping device � Non-attached type ● Under voltage tripping device � Non-attached type
(UVT) � Attached type (UVT) � Attached type
� Key Interlock (K2) � Key Interlock (K2)
� ON/OFF Button Lock (B) � ON/OFF Button Lock
Separate � Door Frame (DF) � Door Frame (DF)
accessories � Shorting b-contact (SBC, 5b max.) - Contact: ( )b � Shorting b-contact (SBC, 5b max.) - Contact: ( )b
� Capacitor trip device (CTD) � Capacitor trip device (CTD)
� OCR tester (OT-2000) � OCR tester (OT-2000)
ACB Separate ● Under voltage tripping device (UVT and UVT Controller) ● Under voltage tripping device (UVT and UVT Controller)
cradle accessories � Instantaneous type (Operation under 0.15sec) � Instantaneous type (Operation under 0.15sec)
� AC110V (V1) � DC 24V (E1) � AC110V (V1) � DC 24V (E1)
� AC220V (V2) � DC 48V (E2) � AC220V (V2) � DC 48V (E2)
� AC380V (V3) � DC110V (E3) � AC380V (V3) � DC110V (E3)
� AC460V (V4) � DC125V (E4) � AC460V (V4) � DC125V (E4)
� Delay type (Operation over 0.5sec) � Delay type (Operation over 0.5sec)
� AC110V (T1) � DC 24V (F1) � AC110V (T1) � DC 24V (F1)
� AC220V (T2) � DC 48V (F2) � AC220V (T2) � DC 48V (F2)
� AC380V (T3) � DC110V (F3) � AC380V (T3) � DC110V (F3)
� AC460V (T4) � DC125V (F4) � AC460V (T4) � DC125V (F4)
� Delay type (Operation over 3sec) � Delay type (Operation over 3sec)
� AC110V (D1) � AC220V (D2) � AC110V (D1) � AC220V (D2)
� AC380V (D3) � AC460V (D4) � AC380V (D3) � AC460V (D4)
● Position switch (CL) � 4c � 8c (4c x 2EA) ● Position switch (CL) � 4c � 8c (4c x 2EA)
● Mechanical operating contact � Standard type (MC1) ● Mechanical operating contact � Standard type (MC1)
(MOC, 10a10b) � High capacity (MC2) (MOC, 10a10b) � High capacity(MC2)
� Door Interlock (DI) � Door Interlock (DI)
� Miss insertion prevent device (MIP) � Miss insertion prevent device (MIP)
� Safety shutter lock (STL) � Safety shutter lock (STL)
Remark
Note) 1.In case of 4000/5000AF, producing reverse phase type of bus-bar phase configuration is not possible.
2.In case of motor charging(input)type, when charging type is standard (OFF Charging type) and high-capacity auxiliary contact is used, only 5a4b is possible.
Memo
Leader in Electrics & Automation
� For your safety, please read user's manual thoroughly before operating.
� Contact the nearest authorized service facility for examination, repair, or adjustment.
� Please contact qualified service technician when you need maintenance.
Do not disassemble or repair by yourself!
Safety Instructions � Any maintenance and inspection shall be performed by the personnel having expertise concerned.
www.lgis.com