The document provides parameters for calculating wind loads on a building with a flat roof. It specifies the building has a 7.5m eave height and ridge height, is 8.3m long with a 0 degree roof slope. The basic wind speed is 45m/s for exposure category C. Using the specified coefficients, the velocity pressure is calculated as 0.739kPa but must be increased to the minimum of 1kPa. External pressure coefficients for the roof and walls are provided to be used in load calculations.
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0 ratings0% found this document useful (0 votes)
38 views
Wind Load Enclosed
The document provides parameters for calculating wind loads on a building with a flat roof. It specifies the building has a 7.5m eave height and ridge height, is 8.3m long with a 0 degree roof slope. The basic wind speed is 45m/s for exposure category C. Using the specified coefficients, the velocity pressure is calculated as 0.739kPa but must be increased to the minimum of 1kPa. External pressure coefficients for the roof and walls are provided to be used in load calculations.