CPO-RL2 - ComfortPoint Open - Room Controller
CPO-RL2 - ComfortPoint Open - Room Controller
BACnet IP
BACnet Wi-Fi
ADAPTER
TR42 TR42 TR42 TR42 TR42 TR42
RL3 24 VAC 2 6 4 4 16 --
RL4 230 VAC 6 10 4 4 24 72-hr data retention
RL5 24 VAC 6 10 4 4 24 72-hr data retention; removable terminals
RL6 24 VAC 6 10 4 4 24 72-hr data retention
RL7U 24 VAC 6 10 4(C 4 23 72-hr data retention; with watchdog relay
RL8 230 VAC 6 10(D 4 4 24 with lighting support
RS1 230 VAC 3 3 0 0 6 --
(162 x 110 x 57.5
small housing
EN0B-0732GE51 R0717 2
CPO-Rxx ROOM CONTROLLERS – DATA SHEET
Housings 54 59
The controller is available in two housing sizes, both IRM-RLC
conforming to IP20: (BULK PACK, 10 pcs.)
▪ RLxx (large housing):
W x L x H = 110 x 198 x 59 mm and
58.325
▪ RSxx (small housing):
W x L x H = 110 x 162 x 59 mm
See also Fig. 3 and Fig. 4.
161.65
198 RLx RLx
57 59
58.325
REMOVABLE
TERMINALS
54
10
162
53.5
110
45
52
54 59
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25
IRM-RSC
L N 24V~ 24V0 24V~ 24V0 TN T~ T01 TN T02 T03 TN T04 RC4 RO4 IN4 RN RN IN1 RO1 IN2 RO2 IN3 RO3
230-V 10
3.5 MODELS
24-V
MODELS
58.325
Fig. 3. RLxx dimensions (in mm)
NOTE: In the case of the RL5, all of the terminal blocks are
removable.
161.65
RSx RSx
162
58.325
57 59
REMOVABLE
TERMINALS
54
59
53.5 TERMINAL ASSIGNMENT
110
45
52 General
1
L
2
N
3 4
24V~ 24V0
5
TN
6
T~
7
T01 TN
8 9
T02
10 11 12 13 14 15 16 17 18 19
RO4 IN4 RN RN IN1 RO1 IN2 RO2 IN3 RO3 For a complete list of all terminals and a description of their
functions, see Table 2 and Table 6.
230-V 10
3.5 MODELS
24-V
MODELS
Communication Interfaces
Fig. 4. RSxx dimensions (in mm) All models of the controller features the following communi-
The unit is suitable for mounting on a standard rail, on walls, cation interfaces:
as well as in wiring cabinets or fuse boxes. ▪ A Sylk Bus interface for connection to TR40x/42x Wall
Modules;
▪ A BACnet MS/TP interface;
Terminal Protection Covers for IP30
▪ An RJ45 connector for connection of the BACnet WiFi
In the case of controllers mounted outside of a cabinet, before Adapter.
applying power to the device, Terminal Protection Covers (10-
pc. bulk packs, order no.: IRM-RLC for large housings and
IRM-RSC for small housings) must be mounted so as to
provide IP30.
3 EN0B-0732GE51 R0717
CPO-Rxx ROOM CONTROLLERS – DATA SHEET
Table 2. RSxx Room Controllers: Overview of terminals and functions (by model)
term. printing function RS1 RS2 RS3 RS4 RS5 RS6
1, 2 "L", "N" 230-V power supply X X X X -- --
3, 4 "24V~", "24V0" Removable 24-V power supply input -- -- -- -- X X
3, 4 "24V~", "24V0" Aux. output voltage (24 VAC) for all triacs X X X X X --
Aux. term. for triac neutral wiring
5 "TN" -- X X X X X
(internally connected with terminal 8)
Triac input voltage (24 VAC / 230 VAC)
6 "T~" -- X X X X X
for all triacs; triac-switched
7 "T01" Triac-switched output -- X X X X X
Aux. term. for triac neutral wiring
8 "TN" -- X X X X X
(internally connected with terminal 5)
9 "T02" Triac-switched output -- X X X X X
10, 11 "RO4", "IN4" Output of Relay 4, Input for Relay 4 -- -- -- type 2 type 2 --
12, 13 "RN", "RN" Aux. terminals for relay neutral wiring -- -- -- X X --
14, 15 "IN1", "RO1" Input for Relay 1, Output of Relay 1 -- -- type 1 type 1 type 1 --
16, 17 "IN2", "RO2" Input for Relay 2, Output of Relay 2 -- -- type 1 type 1 type 1 --
18, 19 "IN3", "RO3" Input for Relay 3, Output of Relay 3 -- -- type 1 type 1 type 1 --
20, 21 "WM1", "WM2" Removable interface for Sylk Bus X X X X X X
22, 23, "24V~", "C2+", Aux. power (24 VAC 20%, 50/60 Hz) +
-- -- -- -- -- --
24, 25 "C2-", "24V0" RS485 Modbus interface + corresp. GND
26 "AO1" Analog Output 1 type 2 type 2 -- type 2 type 2 type 2
27 "24V~" 24 VAC power for field devices X X -- X X X
28 "GND" Ground for AOs X X -- X X X
29 "AO2" Analog Output 2 type 1 -- -- type 1 type 1 --
30 "AO3" Analog Output 3 type 1 -- -- type 1 type 1 --
31 "24V~" 24 VAC power for field devices X -- -- X X --
32 "GND" Ground for AOs X -- -- X X --
33 "AO4" Analog Output 4 -- -- -- type 1 type 1 --
34 "UI1" Universal Input 1 type 1 type 1 type 1 type 1 type 1 type 1
35 "GND" Ground for UIs X X X X X X
36 "UI2" Universal Input 2 type 1 type 1 type 1 type 1 type 1 type 1
37 "UI3" Universal Input 3 type 1 type 1 type 1 type 1 type 1 type 1
38 "GND" Ground for UIs X X X X X X
39 "UI4" Universal Input 4 -- -- -- type 1 type 1 --
40, 41, "C1+", "C1-", Removable BACnet MS/TP interface and
X X X X X X
42 "GND" corresponding GND
Relay output types: See Table 3. Universal input types: Table 4. Analog output types: See Table 5.
EN0B-0732GE51 R0717 4
CPO-Rxx ROOM CONTROLLERS – DATA SHEET
5 EN0B-0732GE51 R0717
CPO-Rxx ROOM CONTROLLERS – DATA SHEET
Table 6. RLxx Room Controllers: Overview of terminals and functions (by model)
term. printing function RL1 RL2 RL3 RL4 RL5 RL6 RL7U RL8
1, 2 "L", "N" 230-V power supply X X -- X -- -- -- X
3, 4 "24V~", "24V0" Removable 24-V power supply input -- -- X -- X X X --
5, 6 "24V~", "24V0" Aux. output voltage (24 VAC) for all triacs X X X X X X X X
Aux. terminal for triac neutral wiring (internally
7 "TN"
connected with terminals 10 + 13) X X X X X X X X
Triac input voltage (24 VAC / 230 VAC) for all triacs;
8 "T~"
triac-switched X X X X X X X X
9 "T01" Triac-switched output X X X X X X X X
Aux. terminal for triac neutral wiring (internally
10 "TN"
connected with terminals 7 + 13) X X X X X X X X
11 "T02" Triac-switched output X X X X X X X X
12 "T03" Triac-switched output -- X X X X X X X
Aux. terminal for triac neutral wiring (internally
13 "TN"
connected with terminals 7 + 10) -- X X X X X X X
14 "T04" Triac-switched output -- X X X X X X X
15 "RC4" N.C. contact (watchdog) of Relay 4 -- -- -- -- -- -- type 3 --
16, 17 "RO4", "IN4" Output of Relay 4, Input for Relay 4 type 2 type 2 type 2 type 2 type 2 type 2 type 2 type 2
18 "RN" Aux. terminal for relay neutral wiring X X X X X X X X
19 "RN" Aux. terminal for relay neutral wiring -- X X X X X X X
20, 21 "IN1", "RO1" Input for Relay 1, Output of Relay 1 -- type 2 type 2 type 2 type 2 type 2 type 2 type 2
22, 23 "IN2", "RO2" Input for Relay 2, Output of Relay 2 -- type 1 type 1 type 1 type 1 type 1 type 1 type 1
24, 25 "IN3", "RO3" Input for Relay 3, Output of Relay 3 -- type 1 type 1 type 1 type 1 type 1 type 1 type 1
26, 27, 28, "C2+", "C2-", RS485 Modbus interface, corr. GND, + aux. power
29 "24V0", "24V~" (24 VAC 20%, 50/60 Hz) -- -- -- -- -- -- -- --
30, 31 "WM1", "WM2" Removable interface for Sylk Bus X X X X X X X X
32 "AO1" Analog Output 1 type 3 type 3 type 3 type 3 type 3 type 3 type 3 type 4
33 "GND" Ground for AOs X X X X X X X X
34 "AO2" Analog Output 2 type 3 type 3 type 3 type 3 type 3 type 3 type 3 type 3
35 "24V~" 24 VAC power for field devices X X X X X X X X
36 "AO3" Analog Output 3 -- -- -- type 1 type 1 type 1 type 1 type 5
37 "GND" Ground for AOs -- -- -- X X X X X
38 "AO4" Analog Output 4 -- -- -- type 1 type 1 type 1 type 1 type 5
39 "24V~" 24 VAC power for field devices -- -- -- X X X X X
40 "AO5" Analog Output 5 -- -- -- type 1 type 1 type 1 type 1 type 1
41 "GND" Ground for AOs -- -- -- X X X X X
42 "AO6" Analog Output 6 -- -- -- type 1 type 1 type 1 type 1 type 1
43 "24V~" 24 VAC power for field devices -- -- -- X X X X X
44 "24V~" 24 VAC power for field devices X X X -- -- -- -- X
45 "LED" Output to LED of T7460C,E,F X X X -- -- -- -- X
46 "GND" Ground for UIs X X X X X X X X
47 "UI1" Universal Input 1 type 1 type 1 type 1 type 1 type 1 type 1 type 1 type 3 (BI)
48 "UI2" Universal Input 2 type 1 type 1 type 1 type 1 type 1 type 1 type 1 type 3 (BI)
49 "GND" Ground for UIs X X X X X X X X
50 "UI3" Universal Input 3 type 1 type 1 type 1 type 1 type 1 type 1 type 1 type 3 (BI)
51 "UI4" Universal Input 4 type 1 type 1 type 1 type 1 type 1 type 1 type 1 type 3 (BI)
52 "GND" Ground for UIs X X X X X X X X
53 "UI5" Universal Input 5 type 1 type 1 type 1 type 1 type 1 type 1 type 1 type 1
54 "UI6" Universal Input 6 type 1 type 1 type 1 type 1 type 1 type 1 type 1 type 1
55 "GND" Ground for UIs X X X X X X X X
56 "UI7" Universal Input 7 -- -- -- type 2 type 2 type 2 type 2 type 2
57 "UI8" Universal Input 8 -- -- -- type 2 type 2 type 2 type 2 type 2
58 "GND" Ground for UIs -- -- -- X X X X X
59 "UI9" Universal Input 9 -- -- -- type 2 type 2 type 2 type 2 type 2
60 "UI10" Universal Input 10 -- -- -- type 2 type 2 type 2 type 2 type 2
61 "GND" Ground for UIs -- -- -- X X X X X
"C1+", "C1-", Removable BACnet MS/TP interface and
62, 63, 64
"GND" corresponding GND X X X X X X X X
Relay output types: See Table 3. Universal input types: Table 4. Analog output types: See Table 5.
EN0B-0732GE51 R0717 6
CPO-Rxx ROOM CONTROLLERS – DATA SHEET
*OPTIONAL FUSE (TO PROTECT CONTROLLER‘S INTERNAL commissioning app BACnet WiFi
TRANSFORMER, WHICH HAS ONLY A NON-RESETTABLE FUSE). T7460B1009 WALL MODULE on smart device ADAPTER
TR40x/TR42x 1 2 3
WALL MODULE PROP. PROP. TEMP SETP COM
COOL HEAT
22 °C
OCCUPANCY CONTACT RJ45
PLUG
BACnet MS/TP
20 21 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42
WM1 WM2 AO1 24V~ 24V0 AO2 AO3 24V~ GND AO4 UI1 GND UI2 UI3 GND UI4 C1+ C1- GND 87654321
RJ45 INTERFACE
7 8 2,3,
5,6 4
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19
L N 24V~ 24V0 TN T~ T01 TN T02 RO4 IN4 RN RN IN1 RO1 IN2 RO2 IN3 RO3
*OPTIONAL FUSE (TO PROTECT CONTROLLER‘S INTERNAL commissioning app BACnet WiFi
TRANSFORMER, WHICH HAS ONLY A NON-RESETTABLE FUSE). T7460C,E,F WALL MODULE on smart device ADAPTER
TR40x/TR42x 1 2 3 4 5 6 7
WALL MODULE PROP. PROP. COM TEMP SETP BYP LED NC NC
COOL HEAT
22 °C
OCC. CONTACT RJ45
Pt1000 PLUG
BACnet MS/TP
30 31 32 34 36 38 40 42 44 46 48 50 52 54 56 58 60 62 63 64
WM1 WM2 AO1 AO2 AO3 AO4 AO5 AO6 24V~ GND UI2 UI3 GND UI6 UI7 GND UI10 C1+ C1- GND 87654321
33 35 37 39 41 43 45 47 49 51 53 55 57 59 61 RJ45 INTERFACE
GND 24V~ GND 24V~ GND 24V~ LED UI1 GND UI4 UI5 GND UI8 UI9 GND
7 8 2,3,
5,6 4
1 2 5 6 7 8 9 10 11 12 13 14 16 17 18 19 20 21 22 23 24 25
L N 24V~ 24V0 TN T~ T01 TN T02 T03 TN T04 RO4 IN4 RN RN IN1 RO1 IN2 RO2 IN3 RO3
7 EN0B-0732GE51 R0717
CPO-Rxx ROOM CONTROLLERS – DATA SHEET
ELECTRICAL DATA cooling (incl. fan interlock). It supports PID and, optionally,
cascade control as well as min. temperature limitation.
RL1, RL2, RL4, RL8, RS1, RS2, RS3, RS4 (230 VAC) This application type may be used in combination with
Power via terminals 1 + 2: 230 VAC +10% / -15%, 50/60 Hz. other types (see following).
Max. power consumption (when unloaded): 8 W. ▪ The chilled/heated ceiling application type uses PID
Max. power consumption (when loaded): 18 W. with dewpoint protection (2-pipe or 4-pipe). It also
supports 6-way valve on AO.
A 230-VAC model is "unloaded" when it has no external load.
Thus, the only load on the controller is the inherent load (8 W) ▪ The radiator heating application type uses PID and,
of the electronics, themselves. The heat dissipation then optionally, min. temperature limitation.
amounts to 8 W. The controller is "loaded" when – besides ▪ The underfloor heating application type uses PID and,
the inherent load – an additional sum load resulting from max. optionally, max. temperature limitation.
300 mA (irrespective as to whether it is supplied by the ▪ The intake air / air quality control application type
controller's internal transformer or by an external source) is uses PID and, optionally, min. temperature limitation and
applied to the 24 VAC output terminals. The max. unloaded air quality control.
output voltage at terminals 3 and 4 is 33 VAC (typically: 29.5 ▪ Those inputs/outputs not needed by the configurable
VAC). application are available for use as free I/Os (like the I/Os
of an I/O module) by the plant controller – see also CPO-
Rxx Room Controller – Inst. & Comm. Instr. (EN1B-
RL3, RL5, RL6, RL7U, RS5, RS6 (24 VAC) 0591GE51).
Power via terminals 3+4: 24 VAC 20%, 50/60 Hz. The use of different application types is limited by the number
Max. current consumption (when unloaded): 300 mA. of I/Os supported by the given model.
Max. current consumption (when loaded): 900 mA.
The controller is "loaded" when – besides the inherent load Supported Actuators
(300 mA) – an additional sum load resulting from max. 600
The application supports a variety of actuators.
mA is applied to the 24 VAC output terminals. The max.
unloaded output voltage at terminals 3 and 4 (24 VAC RSxx) / Table 7. Supported actuators
at terminals 5 and 6 (24 VAC RLxx) is identical with the output
voltage of the external supplying transformer.
6-way valve
0(2)…10 V
Stage 1+2
ON / OFF
Floating
Stage 2,
0…10 V
Stage 1
Analog
PWM
Supported actuators /
Application
COMMISSIONING
The controller can be used with freely programmable
applications or with a configurable application.
FCU Cooling X X X -- -- -- --
FCU Heating X X X -- -- -- --
Freely Programmable Applications FCU DX-Cooling -- -- X X X -- --
All models can be used with applications which the application FCU E-Heating -- -- X X X -- --
engineer can freely program for each controller. This process Ceiling Cooling X X X -- -- X --
is performed on a PC on which the CPO Studio software Ceiling Heating X X X -- -- X --
program has been installed (see also Table 10 on pg. 14).
Ceiling Switch over 2-
-- -- -- -- -- -- X
way Cooling
Library Application Ceiling Switch over 2-
-- -- -- -- -- -- X
way Heating
All models can be used with the library application already
included in CPO Studio. Ceiling Switch over 3-
-- -- -- -- -- -- X
way
The library application has the advantage that it is proven and Radiator Heating X X X -- -- -- --
quickly configured using the wizard available in CPO Studio
Underfloor Heating X X X -- -- -- --
and then commissioned using the commissioning tool running
Intake Air X X -- X -- -- --
on an Android Smart device.
FreeAO X X X X X -- --
NOTE: Before configuring, if as yet no WLAN is present, the
FreeBO -- -- -- -- -- -- X
commissioning engineer will require a BACnet WiFi
Adapter (order no.: BACA-A) to establish wireless
communication between his Android Smart device Supported Sensors
and the controller. A variety of sensors (e.g., room temperature sensors, supply
temperature sensors, condensation switch, window sensors,
occupancy sensors, card readers, etc.) may be used to
Example Application Types
optimize control quality.
The library application supports the following application
types:
▪ The FCU application type supports 1-, 2-, and 3-stage or Supported Operating Modes
variable-speed fan. It also supports water cooling, water The application supports a variety of different operating
heating (2-pipe or 4-pipe), electric re-heating, and dx- modes (e.g., occupied, standby, unoccupied, building pro-
EN0B-0732GE51 R0717 8
CPO-Rxx ROOM CONTROLLERS – DATA SHEET
tection, fan automatic/manual/fan, only [FCU application type, ▪ A key card will be detected if one of the key card sensors
only], night purge [intake air application type, only]). detects a key card.
I/Os not used by the configurable application may be used by ▪ Occupancy override from one of the connected wall
a plant controller for monitoring or to switch an actuator (e.g., modules will trigger an occupancy override.
window actuator). ▪ The last setpoint change (temperature setpoint or fan
speed setpoint) on one of the wall modules (T7460x or
TR40x/TR42x) will define the setpoint (NOTE: All TR42x
Lighting Application wall modules will show the actual settings used by the
All BOs can be configured for lighting control. controllers. The T7460x and TR40x do not feature a
• When configured for lighting control, binary inputs are display and are thus unable to provide the actual setting,
automatically assigned for each binary output. nor does their setpoint wheel reflect setpoint changes
• Binary outputs are controlled directly by fast logic from the enacted using another wall module in the same group).
binary inputs without adding any control strategy. Outputs ▪ For such sensor values as temperature, CO2, and
are controlled within 50ms of button press and write to humidity, the commissioning engineer can configure the
priority table 15. use of the average, min., or max. value (thus improving
• Binary inputs can be configured as pulse ON / pulse OFF system robustness against failures of a single sensor.)
(two buttons per light output) or toggle (one button per ▪ The Master shares schedule, heat/cool mode, actuator
light output). positions, etc. with its Slave(s).
• Binary outputs configured for light control can also be
written from control strategy at any priority between 8 and
16. OPERATOR INTERFACES
The library application provides a single lighting control that LEDs
includes schedule control integrated with push button control The controller features the following LEDs:
that operates according to a "last wins" mechanism.
The available schedule operating modes are T2 R2 T1 R1 !
1 = Override OFF
2 = Repeated OFF
3 = OFF
4 = ON Fig. 9. Controller LEDs
5 = Repeated ON
6 = Override ON
NOTE: Before using lighting application, consider the relay Table 8. Description of LED behaviors
output types and characteristics in Table 3. symbol color function, description
T2 yellow Not used
R2 yellow Not used
Automatic MAC Addressing
LED indicating transmission of communication
In contrast to many other MS/TP controllers, the CPO-R T1 yellow
signals via the BACnet MS/TP interface
Controller features automatic MAC addressing. There is thus
LED indicating reception of communication
no need to manually set the MAC address. R1 yellow
signals via the BACnet MS/TP interface.
Status LED indicating firmware problems,
! yellow
hardware problems, etc.
BACnet MS/TP Master/Slave Functionality
Power LED indicating firmware problems,
During configuration, the commissioning engineer can identify green
hardware problems, etc.
which of the controllers located on a given BACnet MS/TP
red Watchdog (RL7U, only) has locked controller.
bus are so-called "Masters," and which are so-called "Slaves."
The commissioning engineer is not allowed to assign more
than a single Master to each Slave; this is the only action Watchdog Functionality (RL7U, only)
which the commissioning engineer is required to perform. The
The RL7U features a watchdog (relay 4) which enhances the
Slave controller will inform its Master that it has been
system's reliability.
assigned to be its Slave.
The watchdog indicates whether or not the controller's soft-
The given application in the Master controller defines how this
ware and processor are functioning properly. In the event that
group (consisting of the Master controller and its Slave
either the software or the processor is not functioning
controllers) reacts to sensor inputs.
properly, the watchdog will reboot the controller.
Examples:
If, after this reboot, the watchdog again detects a problem, the
▪ Activation of a window contact (indicating an opened watchdog will then lock the controller (i.e., permanent reset).
window) will cause the application to stop heating/cooling. The following will then occur: The watchdog will operate (i.e.,
▪ Each Master and each Slave needs to have its own ceiling terminal 15 will be connected with terminal 17), the power
cold water temperature sensor and its own condensation LED will light up RED, and the status LED will remain OFF
contact. (see Table 8).
▪ Occupancy will be detected if one of the occupancy Optionally, the user can connect an alarm (e.g., beeper) to
sensors detects occupancy. terminals 15 and 17.
9 EN0B-0732GE51 R0717
CPO-Rxx ROOM CONTROLLERS – DATA SHEET
The watchdog relay is not available for use by the application. with an Android Smart device so that the application engineer
See also Table 3 for technical details on the watchdog relay. can commission the controller.
NOTE: When the BACnet WiFi Adapter is connected to the
controller's RJ45 connection, it is powered by the
Service Button controller. It is then prohibited to simultaneously
The controller's Service Button is used to trigger dedicated power the BACnet WiFi Adapter via a wall adapter.
events. When, on the other hand, the BACnet WiFi Adapter
is instead connected to the controller's BACnet
MS/TP interface, it is prohibited to simultaneously
COMMUNICATION INTERFACES use an RJ45 plug; instead, the BACnet WiFi Adapter
BACnet MS/TP Interface must then be powered by a wall adapter (standard 5-
V USB wall adapter with micro USB connector).
The controller features an RS485 interface (RLx: terminals
62, 63, and 64; RSx: terminals 40, 41, and 42) suitable for See also corresponding Technical Literature listed in Table 10
BACnet MS/TP communication. The terminal block containing on pg. 14.
it is black. The cable length affects the baud rate. See Table
9.
Wall Modules
Table 9. Baud rate vs. max. cable length The T7460x and TR40x/TR42x Wall Modules can be used in
baud rate max. cable length (L) conjunction with the controller to perform room temperature
9.6, 19.2, 38.4, 57.6, and 76.8 kbps 1200 m sensing, setpoint adjustment, fan speed manual override, and
115.2 kbps 800 m occupancy override.
BACnet WiFi
ADAPTER
COMMISSIONING
APP ON SMART RJ45
DEVICE PLUG
CPO-RLx
(CPO-RSx) RJ45 CONNECTOR 1 = DETECT
BACnet MS/TP 2 = GND
87654321 3 = GND
62 63 64
4 = 24VAC
(40) (41) (42)
5 = GND
C1+ C1- GND
6 = GND
7 = C1+
8 = C1-
7 8 2,3,
5,6 4
INTERNAL
CONNECTIONS
CAUTION
It is permitted to connect only the BACnet WiFi
Adapter to this RJ45 connector. Do not connect IP!
A BACnet WiFi Adapter can be connected to the controller's
RJ45 connector in order to establish wireless communication
EN0B-0732GE51 R0717 10
CPO-Rxx ROOM CONTROLLERS – DATA SHEET
I/O TERMINALS 4 A per relay – even if two triacs are each simultaneously
loaded with max. 300 mA.
CAUTION If the triacs are supplied with current from an internal source,
a maximum of two relays may be loaded as follows: a max.
Failure to observe the following max. permissible load of 4 A for a relay serving a fan and a max. load of 10 A
current outputs of the power output terminals will for a relay serving a reheat – even if one triac is
result in damage to the device. simultaneously loaded with 300 mA.
11 EN0B-0732GE51 R0717
CPO-Rxx ROOM CONTROLLERS – DATA SHEET
Free Outputs
Max. 4 BACnet Analog Output Objects
Under the free I/O option, a maximum of four of the CPO-R
controller's unused outputs (analog or binary outputs) may be
used with BACnet Analog Output objects by the plant con-
troller. Possible characteristics are as follows:
▪ analog output: 0(2)..10 V outputs;
▪ floating output: triac or relay outputs;
▪ PWM: triac outputs;
▪ 1-, 2-, 3-stage output: triac / relay outputs.
EN0B-0732GE51 R0717 12
CPO-Rxx ROOM CONTROLLERS – DATA SHEET
13 EN0B-0732GE51 R0717
CPO-Rxx ROOM CONTROLLERS – DATA SHEET
Trademark Information
BACnetTM is a trademark of ASHRAE Inc.
ComfortPointTM Open is a trademark of Honeywell Inc.
Manufactured for and on behalf of the Environmental & Energy Solutions Division of Honeywell Technologies Sàrl, Rolle, Z.A. La Pièce 16, Switzerland by its Authorized Representative: