Single Phase Transformers
Single Phase Transformers
UNIT-4
Single phase Transformer
Transformer is a static device which transfers the electrical energy from one circuit to
another circuit, without changing its frequency. The voltage can be raised or lowered in a circuit,
but with a proportional increase or decrease in the current ratings.
Construction of a Transformer:
Basically a transformer consists of two inductive windings and a laminated steel core.
Windings:
There are two windings in a transformer. Which winding is connected to supply is called primary
winding and which winding is connected to load is called secondary winding. Windings are made
up of copper. The windings are insulated from each other as well as from the steel core.
Iron Core:
In all types of transformers, core is constructed by assembling laminated sheets of steel,
with minimum air-gap between them (to achieve continuous magnetic path). The steel used is
having high silicon content and sometimes heat treated, to provide high permeability and low
hysteresis loss. Laminated sheets of steel are used to reduce eddy current loss. The sheets are cut in
the shape as E,I, C and L.
The main principle of operation of a transformer is mutual inductance between two circuits
which is linked by a common magnetic flux. A basic transformer consists of two coils that are
electrically separate and inductive, but are magnetically linked through a path of reluctance.
When the supply is given to the primary winding then an alternating flux produced due to
alternating current. This flux is linked to the secondary winding through the magnetic core. An emf
will be induced in the secondary winding from the principle of faradays law of electromagnetic
induction. This emf is caused to flow current when the circuit is in closed path.
Let,
N1 = Number of turns in the primary winding
N2 = Number of turns in the secondary winding
ϕm = Maximum flux in the core in webers = Bmax * A
f = Frequency of alternating current input in hertz (Hz)
The general equation for induced EMF, e is expressed as
d
e N
dt
A sinusoidal varying flux is represented as
Φ= ϕm sinꞷt
Then,
d (m sin t )
e N
dt
e= -Nϕmꞷcosꞷt
e= -N ϕmꞷ[-sin(ꞷt-π/2)]
e= N ϕmꞷsin(ꞷt-900)
this equation of e, is of the form e= Em sin (ꞷt-90)
Em N
Em N 2f
E 4.44m fN Volts
Now, r.m.s value of induced e.m.f in the whole of primary winding= (induced e.m.f./turn) X
Number of primary turns
Therefore,
E1 = 4.44f N1ϕm = 4.44fN1BmA
Similarly, r.m.s value of induced e.m.f in secondary is
E2 = 4.44f N2 ϕm = 4.44fN2BmA
In an ideal transformer on no load,
V1 = E1 and V2 = E2
Voltage Transformation Ratio (K):
It is defined as the ratio of secondary voltage to the primary voltage.
N 2 V2 E2 I1
K
N1 V1 E1 I 2
Types of Transformers:
1. Based on construction, transformers can be classified into two types as;
(i) Core type transformer
(ii) Shell type transformer
Copper loss is due to ohmic resistance of the transformer windings. Copper loss for the
primary winding is I12R1 and for secondary winding is I22R2. Where, I1 and I2 are current in primary
and secondary winding respectively, R1 and R2 are the resistances of primary and secondary
winding respectively. It is clear that Cu loss is proportional to square of the current, and current
depends on the load. Hence copper loss in transformer varies with the load.
Efficiency of a Transformer:
Efficiency of a transformer can be defined as the ration of output power to the input power.
Efficiency = output / input
Transformers are the most highly efficient electrical devices. Most of the transformers have full
load efficiency between 95% to 98.5%.
Efficiency = (input - losses) / input = 1 - (losses / input).
Condition for Maximum Efficiency:
Let,
Copper loss = I12R1
Iron loss = Wi
I12R1= Wi
Hence, efficiency of a transformer will be maximum when copper loss and iron losses are equal.
Copper loss = Iron loss
Another formula for efficiency of a transformer is
X * KVARating * Cos
Efficiency( )
X * KVARating * Cos Pi X 2 Pcu
The applied voltage to the primary is V1 and voltage across the primary winding is E1. Total
current supplied to primary is I1. So the voltage V1 applied to the primary is partly dropped by I1Z1
or I1R1 + j.I1X1 before it appears across primary winding.
The voltage appeared across winding is countered by primary induced EMF E1. So voltage
equation of this portion of the transformer can be written as,
Total primary current I1 has two components, one is no – load component Io and the other is
load component I2′. As this primary current have two components or branches, so there must be a
parallel path with primary winding of transformer.
This parallel path of current is known as excitation branch of equivalent circuit of
transformer. The resistive and reactive branches of the excitation circuit can be represented as
The load component I2′ flows through the primary winding of transformer and induced
voltage across the winding is E1. This induced voltage E1 transforms to secondary and it is E2 and
load component of primary current I2′ is transformed to secondary as secondary current I2. Current
of secondary is I2. So the voltage E2 across secondary winding is partly dropped by I2Z2 or I2R2 +
j.I2X2 before it appears across load. The load voltage is V2.
Now if we see the voltage drop in secondary from primary side, then it would be ′1/K′ times greater
and would be written as Z2.I2/K.
Z2
Z2 '
K2
R2 X
Hence, R2 ' 2
andX 2 22
K K
So, the complete equivalent circuit of transformer referred to primary is shown in the figure below:
Since Io is very small compared to I1, it is less than 5% of full load primary current, Io
changes the voltage drop insignificantly. Hence, it is good approximation to ignore the excitation
circuit in approximate equivalent circuit of transformer. The winding resistance and reactance
being in series can now be combined into equivalent resistance and reactance of transformer,
referred to primary side.
V
V2 ' 2
K
Z1 ' K 2 Z1
Therfore, R1 ' K 2 R1
X1' K 2 X1
Here,V1 ' KV1
8. From the phasor diagram drawn above, the following conclusions are made:
Usually high voltage (HV) winding is kept open and the low voltage (LV) winding is
connected to its normal supply. A wattmeter (W), ammeter (A) and voltmeter (V) are connected to
the LV winding as shown in the figure. Now, applied voltage is slowly increased from zero to
normal rated value of the LV side with the help of a variac. When the applied voltage reaches to the
rated value of the LV winding, readings from all the three instruments are taken.
The ammeter reading gives the no load current I0. As I0 itself is very small, the voltage
drops due to this current can be neglected.
The input power is indicated by the wattmeter (W). And as the other side of transformer is
open circuited, there is no output power. Hence, this input power only consists of core losses and
copper losses. As described above, no-load current is so small that these copper losses can be
neglected. Hence, now the input power is almost equal to the core losses. Thus, the wattmeter
reading gives the core losses of the transformer.
Sometimes, a high resistance voltmeter is connected across the HV winding. Though, a
voltmeter is connected, HV winding can be treated as open circuit as the current through the
voltmeter is negligibly small. This helps in to find voltage transformation ratio (K).
The two components of no load current can be given as,
Iμ = I0sinΦ0 and Iw = I0cosΦ0.
cosΦ0 (no load power factor) = W / (V1I0). ... (W = wattmeter reading)
From this, shunt parameters of equivalent circuit of transformer (X0 and R0) can be calculated as
X0 = V1/Iμ and R0 = V1/Iw
Hence, it is seen that open circuit test gives core losses of transformer and shunt parameters of the
equivalent circuit.
The ammeter reading gives primary equivalent of full load current (Isc).
The voltage applied for full load current is very small as compared to rated voltage. Hence, core
loss due to small applied voltage can be neglected. Thus, the wattmeter reading can be taken as
copper loss in the transformer.
The suitable load which absorbs the full load power of a large transformer will not easily be
available. Hence a large amount of energy will be wasted. The back-to-back test determines the
maximum temperature rise in a transformer, and hence the load is chosen according to the
capability of the transformer.
Back to Back Test Circuit
The two identical transformer is used for the back to back test. Consider the T r1 and Tr2 are
the primary windings of the transformer connects parallel to each other. The nominal rated voltage
and frequency is supplied to their primary winding. The voltmeter and ammeter are connected on
their primary side for the measurement of the input voltage and current.
The secondary winding of the transformer is connected in series with the each other but
with opposite polarity. The voltmeter V2 is connected to the terminal of the secondary winding for
the measurement of the voltage.
The series opposition of the secondary winding is determined by connecting there any two
terminals; the voltmeter is connected across their remaining terminals. If it is connected in series
opposition, the voltmeter gives the zero reading. The open terminal is used for measuring the
parameter of the transformer.
The above figure shows that the terminal B and C are connected to each other, and the voltage is
measured across the terminal A and D.
Determination of Temperature Rise
The temperature rise of the transformer is determined by measuring the temperature of their
oil after every particular interval of time. The transformer is operating back to back for the long
time which increases their oil temperature. By measuring the temperature of their oil the withstand
capacity of the transformer under high temperature is determined.
The copper loss of the transformer is determined when the full load current flows through
their primary and secondary windings. The additional regulating transformer is used for exciting
the secondary windings. The full load current flows from the secondary to the primary winding.
The wattmeter W2 measures the full load copper loss of the two transformers.
Parallel Operation of a Single Phase Transformer
Parallel Operation of a Single Phase Transformer means that the two or more transformers
having the same polarities, same turn ratios, same phase sequence and the same voltage ratio are
connected in parallel with each other.
The circuit diagram of two single-phase transformers A and B connected in parallel are shown
below:
Let,
a1 is the turn ratio of the transformer A
a2 is the turn ratio of transformer B
ZA is the equivalent impedance of the transformer A referred to secondary
ZB is the equivalent impedance of the transformer B referred to secondary
ZL is the load impedance across the secondary
IA is the current supplied to the load by the secondary of the transformer A
IB is the current supplied to the load by the secondary of the transformer B
VL is the secondary load voltage
IL is the load current
Now putting the value of IB from the equation (1) in equation (3) we will get,
The current IA and IB have two components. The first component represents the
transformers share of the load currents and the second component is a circulating current in the
secondary windings of the single-phase transformer.
The undesirable effects of the circulating currents are as follows
They increase the copper loss.
The circulating current overloads the one transformer and reduces the permissible load
kVA.
Equal Voltage Ratio
In order to eliminate circulating currents, the voltage ratios must be identical. That is a1=a2
Under this condition,
From the above equation (9), it is clear that the transformer currents are inversely
proportional to the transformer impedance. Thus, for the efficient parallel operation of the two
single-phase transformers, the potential differences at full load across the transformer internal
impedance should be equal.
This condition ensures that the load sharing between the two single-phase transformer is
according to the rating of each transformer. If the per-unit equivalent impedance are not equal, then
the transformer will not share the load in proportion to their kVA ratings. As a result, the overall
rating of the transformer bank will be reduced.
Equation (9) can also be written as
The current in the equations (7) and (8) is changed into volt-amperes by multiplying the two
equations by the common load voltage VL.
Therefore, we know that,
The total load in volt-ampere (VA) is
Equation (13) tells that the volt-ampere load on each single-phase transformer is inversely
proportional to its impedance.
Hence, to share the load in proportion to their ratings, the transformers should have the
impedance which is inversely proportional to their ratings.
Applications:
o It is used to increase or decrease the alternating voltages in electric power applications.
o The transformer used in voltmeter, ammeters, protective relay etc.
o The transformer used for step up low voltage in case of measurement.
o The transformer used for step down high voltage for safety.
o The transformer used in rectifier.
o It is used in voltage regulators, voltage stabilizers, power supplies etc.
where,
E2 – secondary terminal voltage at no load
V2 – secondary terminal voltage at full load
The voltage regulation by considering the primary terminal voltage of the transformer is expressed
as,
If the transformer is fully loaded, i.e., the load is connected to their secondary terminal, the
voltage drops appear across it. The value of the voltage regulation should always be less for the
better performance of the transformer.
From the circuit diagram shown above, the following conclusions are made
The primary voltage of the transformer is always greater than the induced emf on the
primary side. V1>E1
The secondary terminal voltage at no load is always greater than the voltage at full load
condition. E2>V2
By considering the above circuit diagram, the following equations are drawn
The approximate expression for the no-load secondary voltage for the different types of the load is
1. For inductive load
Where,
Exercise Problems: