Three Phase Transformer
Three Phase Transformer
UNIT-5
Auto Transformer
Autotransformer:
In an auto transformer, one single winding is used as primary winding as well as secondary
winding. But in two windings transformer two different windings are used for primary and
secondary purpose. A circuit diagram of auto transformer is shown below.
The winding AB of total turns N1 is considered as primary winding. This winding is tapped from
point ′C′ and the portion BC is considered as secondary. Let’s assume the number of turns in
between point’s ′B′ and ′C′ is N2.
If V1 voltage is applied across the winding i.e. in between ′A′ and ′B′. Voltage per turn in this
V
winding is 1 .
N1
Hence, the voltage across the portion BC of the winding, will be,
V1
V2 N2
N1
V2 V1
K
N 2 N1
Basis For
Autotransformer Conventional transformer
Differences
A transformer, having only one It is a static machine which transfers
Definition winding a part of which acts as a electrical energy from one end to
primary and the other as a secondary. another without changing frequency.
Number of Auto-transformer has only one It has two separate winding, i.e.,
Windings winding wound on a laminated core primary and secondary winding.
Symbol
The low windings are placed next to the core with suitable insulation between the core and
the low voltage windings. The high voltage windings are placed over the low voltage windings
with suitable insulation between them. The magnetic paths of the leg a and c are greater than that of
leg b, the construction is not symmetrical, and there is a resultant imbalance in the magnetising
current.
Shell type Three Phase Transformer
The shell type 3-phase transformer can be constructed by stacking three single phase shell
transformer as shown in the figure below. The winding direction of the central unit b is made
opposite to that of units a and c. If the system is balanced with phase sequence a-b-c, the flux will
also be balanced
The magnitude of this combined flux is equal to the magnitude of each of its components.
The cross section area of the combined yoke is same as that of the outer leg and top and bottom
section of the yoke. The imbalance in the magnetic path has very little effect on the performance of
the three shell-type transformers. The windings of the shell type three phase transformer are either
connected in delta or star as desired.
Three phase transformer connections
Star-star (Y-Y):
Star-star connection is generally used for small, high-voltage transformers. Because of star
connection, number of required turns/phase is reduced (as phase voltage in star connection
is 1/√3 times of line voltage only). Thus, the amount of insulation required is also reduced.
Line voltages on both sides are in phase with each other.
This connection can be used only if the connected load is balanced.
Delta-delta (Δ-Δ)
This connection is generally used for large, low-voltage transformers. Number of required
phase/turns is relatively greater than that for star-star connection.
The ratio of line voltages on the primary and the secondary side is equal to the
transformation ratio of the transformers.
This connection can be used even for unbalanced loading.
The primary winding is star (Y) connected with grounded neutral and the secondary
winding is delta connected.
This connection is mainly used in step down transformer at the substation end of the
transmission line.
The ratio of secondary to primary line voltage is 1/√3 times the transformation ratio.
The D divides the primary BC of the main transformers into two halves and hence the
number of turns in portion BD = the number of turns in portion DC = Tp/2.The voltage VBD and
VDC are equal, and they are in phase with VBC.
The teaser transformer has the primary voltage rating that is √3/2 or 0.866 of the voltage ratings of
the main transformer. Voltage VAD is applied to the primary of the teaser transformer and therefore
the secondary of the voltage V2t of the teaser transformer will lead the secondary terminal voltage
V2m of the main transformer by 90º as shown in the figure below.
Then,
For keeping the voltage per turn same in the primary of the main transformer and the
primary of the teaser transformer, the number of turns in the primary of the teaser transformer
should be equal to √3/2Tp.
Thus, the secondaries of both transformers should have equal voltage ratings. The V2t and
V2m are equal in magnitude and 90º apart in time; they result in the balanced 2-phase system.
Position of Neutral Point N
The primary of the two transformers may have a four wire connection to a 3-phase supply if
the tapping N is provided on the primary of the teaser transformer such that
The voltage across AN = VAN = phase voltage = Vl/√3.
Since, the voltage across the portion AD.
The same voltage turn in portion AN, ND and AD are shown by the equations,
The equation above shows that the neutral point N divides the primary of the teaser transformer in
ratio.
AN : ND = 2 : 1
Applications of Scott Connection
The following are the applications of the Scott-T connection.
1. The Scott-T connection is used in an electric furnace installation where it is desired to operate
two single-phase together and draw the balanced load from the three-phase supply.
2. It is used to supply the single phase loads such as electric train which are so scheduled as to
keep the load on the three phase system as nearly as possible.
3. The Scott-T connection is used to link a 3-phase system with a two–phase system with
the flow of power in either direction.
Exercise Problems