What Is Leakage Current Testing and Measuring
What Is Leakage Current Testing and Measuring
Leakage current is the current that streams from either DC or AC circuit in an equipment to the ground or
framework and can be from the output or input. If the equipment is not properly grounded, the current flows
through other paths such as the human body. This mighty also occur if the ground is incompetent or
is disrupted unintentionally or intentionally.
The leakage current in an equipment flows when an unintentional electrical connection occurs between the ground
and an energized part or conductor. The ground may be the reference point of zero voltage, or the earth ground.
Ideally, the current leaking from the power supply unit should flow through the ground connection and into the
installations earth ground.
This measurement is done during the electrical safety test of a device. The currents flowing through the protective
conductor or metallic parts of the earth are measured.
Electrical system usually consists of a grounding technique that offers shield against a shock hazard if an insulation
fault occurs. The grounding system comprises of a grounding rod that connects the instrument to the earth. If ever a
disastrous failure of insulation between power line and conductive parts occur, the voltage will be pushed to ground.
The current that is created because of this event will flow, causing a circuit breaker to open or a fuse to blow thus
avoiding a shock hazard.
Clearly, a shock hazard prevails if the earth or ground connection is intruded, either accidentally or intentionally. The
possibility for a shock might be larger than assumed if there is case of leakage currents. Even in the scenario of no
insulation failure, intrusion of leakage currents streaming through the grounding rod still pose a threat of electric
shock to somebody meeting the ungrounded system and ground at the same time.
This is a huge concern when it comes to the field of medical applications, where a patient might be the receiver of
the electric shock. A shock can be even fatal if the patient is weak or unconscious, or if the current flows to internal
organs. The two-layered insulation offered in non-grounded equipment ensures protection. The security in this
scenario is made sure because both coats of insulation are not likely to collapse together. Nevertheless, the
situations that leads to leakage currents still exists and must be considered.
Hence, how can you eradicate or reduce the outcomes of leakage current? Measure the leakage current and
then recognize the cause. Purpose of the Test is to measure the amount of current that passes through a person
when that person touches an electrical product.
What is Done During Leakage Current Measurement?
The current streaming through the ground rod is quantified by attaching the meter in series with the
earthing connection.
The ground connection is unsealed and the current streaming to the neutral side of the power line is
measured, for data processing equipment.
The meter may also be connected between the outputs of the power supply and ground.
For very small leakage currents, the meter is substituted with a network comprising of either a resistor or a
resistor and capacitor grouping.
The voltage drop throughout the network is then quantified using an ac voltmeter.
Double-insulated equipment or ungrounded is verified by attaching the meter amid any touchable
conductive part and earth.
Direct Measurement
Leakage current clamp meter is the most popular device used to measure leakage current. They are like the clamp
meters utilized for finding load currents but gives considerably better results when quantifying currents less than
5mA. Generally, clamp meters wouldn’t register such small currents. After we position the jaws of a clamp meter
around a conducting rod or wire, the current reading is taken, and the value depends upon the intensity of the
alternating electromagnetic field around the conductor. The clamp meter will identify the magnetic field around
conductors like a wire armor cable, single core cable, a water pipe etc. The paired neutral and phase conductors of a
single-phase circuit, or all live conductors of a three-phase circuit.
If you performed an insulation test on a circuit that was powered down, the result would be in the range of
50MΩ or further, because the insulation tester utilizes s a dc voltage for checking, which do not consider the
capacitive effect.
If you measured the same circuit loaded with office equipment, the result would be significantly different
due to the capacitance of the input filters on these devices.
When a lot of parts of equipment are functioning on a circuit, the result will be collective, that is, the leakage
current will be greater and could well be in the range of milliamps. Adding new pieces of equipment to a
circuit protected by a GFCI could trip the GFCI. And as the value of leakage current differs based on how the
equipment is functioning, the GFCI may trip unintentionally.
When telecommunications equipment is present, the value of leakage indicated by a clamp meter may be
considerably more than that resulting from insulation impedance at 60 Hz because, telecommunications
system usually consists of filters that generate functional grounding currents and other gears that generates
harmonics, etc.
When the load is switched on, the leakage current measured includes leakage in load equipment. If the
leakage is adequately small with the load attached,
then circuit wiring leakage is even smaller. If circuit wiring leakage alone is required, disconnect the load.
If you test single-phase circuits by clamping the phase and neutral conductor, the obtained amount will be
any current streaming to ground.
Test 3 phase circuits by fastening a clamp around all 3 phase conductors. If a neutral is present, it must be
clamped along with the phase conductors and the measured amount will be any current flowing to ground.
To quantity the sum of leakage streaming to the proposed earth connection, position the clamp around the
ground rod.
This series of measurements identifies the overall leakage and the source. The first measurement can be
made on the main conductor to the panel.
The objective of the Leakage Current test is to verify that the electrical insulation used to protect the user from a
Risk of Shock is suitable for the application. Leakage Current testing is used to verify that the product does not leak
excessive current when contacted by the user. For medical equipment, the current flowing to ground is measured.
Excessive leakage current can cause the heart to go into ventricular fibrillation resulting in cardiac arrest
which can lead to death.
Leakage current measurement levels depend on the amount of capacitance in the products’ solid insulating
materials. Different types and number of layers of an electrical insulation results in varying amounts of
inherent capacitance through the insulation. This capacitance causes low amounts of current to “leak”
through the insulation.
Leakage current levels can be significantly elevated in products that are subject to EMI requirements (FCC,
CE-EMC). These products must incorporate EMI filters on their incoming mains power to provide clean
power to sensitive electronics while also protecting from radiating emissions back onto the power line.
These filters incorporate capacitors to ground, these capacitors can cause high leakage current when
operating normally. If the product is for professional use only, the standard may permit high leakage current
with warning markings for the user to insure the product is reliably grounded (so the user isn’t subjected to
the high leakage current). Otherwise, an isolation transformer must be added to power the product thereby
isolating the product from ground – which will almost eliminate leakage current to ground.
The HIPOT test also called Dielectric Withstand Test is a routine test that is performed in electrical
production industry. This is a high voltage test that stresses the insulation of an electrical product far 80 M.
If the insulation of product can withstand a much higher voltage for a given time, then it can withstand
normal voltage for its whole life.
The basic function of HIPOT tester is to monitor excessive leakage current to ground.
Hipot tester applies a high voltage across the insulation of device that is tested. This is generally higher
1400 Volts to test a device that is planned to be operated on 220 Volts.
Terminals A and B are connected to supply voltage of 220 or 110, terminal C is grounded, return lead is
floating as shown here.
One lead from winding is connected to HV out probe and return lead to motor body. This applies high
voltage across winding and case.
If winding is short or weak at any point a current will stream to return lead and meter will display that
current.
All HIPOT testers have an over-current trip to secure the tester itself. This is vital in case if device
is completely shorted to its body and extreme current flows upon application of high voltage from HIPOT
tester.
The device under test is not placed into service, and its polarity need not be reversed
Leakage current can be a sign of the inefficiency of insulation on conductors. It is achievable to trace the cause of
leakage current with the help of a low current leakage current clamp to interpret orderly measurements as needed.
If required, this allows you to re-allocate loads all around the installation in a better unbiased manner.