Electrical Load-Phase-I
Electrical Load-Phase-I
TOWER A (G+3)
1 BHK - Lighting & Small Power
42 units @ 0.9 KW = 38 KW
1 (61 sq M @ 15 W/sqM = 0.92 KW)
1 BHK - AC Load @ 60% Diversity 42 units @ 2.3 KW = 95 KW
2 BHK - Lighting & Small Power
8 units @ 1.3 KW = 11 KW
2 (89 sq M @ 15 W/sqM = 1.34 KW)
2 BHK - AC Load @ 60% Diversity 8 units @ 3.4 KW = 27 KW
2 BHK (Club) - Lighting & Small Power
5 units @ 1.7 KW = 8 KW
3 (110 sq M @ 15 W/sqM = 1.65 KW)
Naturopathy Block
18 As per Annex - I @ 75% Overall Diversity = 235 KW
Activity Hall
4 units @ 1.0 KW = 4 KW
21 (67 sq M @ 15 W/sqM = 1.01 KW)
Activity Hall - AC Load 4 units @ 7.5 KW = 30 KW
26 STP = 25 KW
Recommended DG Sets (90% loading) = 1 nos. 750 KVA & 1 nos. 380 KVA