1SBL371001R5111 A63 30 11 400 415v 50hz 480v 60hz
1SBL371001R5111 A63 30 11 400 415v 50hz 480v 60hz
General Information
Extended Product Type A63-30-11 400-415V 50Hz / 480V 60Hz
Product ID 1SBL371001R5111
EAN 3471522088512
Catalog Description A63-30-11 400-415V 50Hz / 480V 60Hz Contactor
A63 contactors are mainly used for controlling 3-phase motors and generally for
controlling power circuits up to 690 V AC / 1000 V AC or 220 V DC. The contactors can
also be used for many other applications such as isolation, capacitor switching,
Long Description lighting. The A... series 1-stack 3-pole contactors are of the block type design. - Main
poles and auxiliary contact blocks: 3 main poles and 2 built-in auxiliary contacts, front
and side-mounted add-on auxiliary contact blocks - Control circuit: AC operated with
laminated magnet circuit - Accessories: a wide range of accessories is available.
Ordering
Minimum Order Quantity 1 piece
Customs Tariff Number 85364900
Replacement Product ID 1SBL381001R5111
(NEW)
Popular Downloads
Data Sheet, Technical 1SBC100122C0202_Ch02
Information
Instructions and FPTC407700P0003
Manuals
A63-30-11 400-415V 50Hz / 480V 60Hz 2
Dimensions
Product Net Width 82 mm
Product Net Depth / 108 mm
Length
Product Net Height 110 mm
Product Net Weight 1.2 kg
Technical
Number of Main 3
Contacts NO
Number of Main 0
Contacts NC
Number of Auxiliary 1
Contacts NO
Number of Auxiliary 1
Contacts NC
Standards Devices complying with international standards IEC 947-1 / 947-4-1, and
European standards EN 60 947-1 / 60 947-4-1. Electromagnetic
compatibility (EMC) acc. to amendment A11 to IEC 947-1, EN 60 947-1 and
amendment 2 to IEC 947-4-1
Rated Operational Auxiliary Circuit 690 V
Voltage Main Circuit 1000 V
Rated Frequency (f) Supply Circuit 50 / 60 Hz
Conventional Free-air acc. to IEC 60947-4-1, Open Contactors q = 40 °C 125 A
Thermal Current (I th ) acc. to IEC 60947-5-1, q = 40 °C 16 A
Rated Operational (690 V) 40 °C 115 A
Current AC-1 (I e ) (690 V) 55 °C 95 A
(690 V) 70 °C 80 A
Rated Operational (415 V) 55 °C 65 A
Current AC-3 (I e ) (440 V) 55 °C 65 A
(500 V) 55 °C 55 A
(690 V) 55 °C 43 A
(1000 V) 55 °C 25 A
(380 / 400 V) 55 °C 65 A
(220 / 230 / 240 V) 55 °C 65
Rated Operational Power (415 V) 37 kW
AC-3 (P e ) (440 V) 37 kW
(500 V) 37 kW
(690 V) 37 kW
(1000 V) 33 kW
(380 / 400 V) 30 kW
(220 / 230 / 240 V) 18.5 kW
Rated Operational Power (230 / 240 V) 40 °C, 50 / 60 Hz 25 kvar
AC-6b (P e ) (230 / 240 V) 55 °C, 50 / 60 Hz 25 kvar
(230 / 240 V) 70 °C, 50 / 60 Hz 23 kvar
(400 / 415 V) 40 °C, 50 / 60 Hz 43 kvar
(400 / 415 V) 70 °C, 50 / 60 Hz 39 kvar
(400 / 415 V) 55 °C, 50 / 60 Hz 43 kvar
(440 V) 40 °C, 50 / 60 Hz 47 kvar
(440 V) 55 °C, 50 / 60 Hz 47 kvar
(440 V) 70 °C, 50 / 60 Hz 42.5 kvar
(500 / 550 V), 40 °C, 50 / 60 Hz 54 kvar
(500 / 550 V) 55 °C, 50 / 60 Hz 54 kvar
(500 / 550 V) 70 °C, 50 / 60 Hz 48.5 kvar
(690 V) 40 °C, 50 / 60 Hz 74 kvar
(690 V) 55 °C, 50 / 60 Hz 74 kvar
(690 V) 70 °C, 50 / 60 Hz 67 kvar
Rated Breaking Capacity 8 x Ie AC-3
AC-3
Rated Making Capacity 10 x Ie AC-3
AC-3
Rated Operational (500 V) 2 A
Current AC-15 (I e ) (690 V) 2 A
(24 / 127 V) 6 A
(220 / 240 V) 4 A
A63-30-11 400-415V 50Hz / 480V 60Hz 3
(380 / 400 V) 3 A
Short-Circuit Protective Auxiliary Circuit - gG Type Fuses 10 A
Devices gG Type Fuses 125 A
Rated Short-time at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 650 A
Withstand Current Low at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 135 A
Voltage (I cw ) at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 250 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1000 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 370 A
Maximum Breaking cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 1300 A
Capacity cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 630 A
Maximum Electrical (AC-1) 600 cycles per hour
Switching Frequency (AC-2 / AC-4) 150 cycles per hour
(AC-3) 600 cycles per hour
Rated Operational (24 V) 6 / 144 A
Current DC-13 (I e ) (48 V) 2.8 / 134 A
(72 V) 1 / 72 A
(125 V) 0.55 / 69 A
(250 V) 0.3 / 75 A
Rated Insulation Voltage acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V
(U i ) acc. to IEC 60947-5-1 and VDE 0110 (Gr. C) 690 V
acc. to UL/CSA 600 V
Rated Impulse 8 kV
Withstand Voltage (U imp
)
Mechanical Durability 10 million
Maximum Mechanical 3600 cycles per hour
Switching Frequency
Rated Control Circuit 50 Hz 400 ... 415 V
Voltage (U c ) 60 Hz 480 V
Coil Consumption Average Holding Value 50 Hz 18 V·A
Average Holding Value 60 Hz 18 V·A
Average Pull-in Value 50 Hz 180 V·A
Average Pull-in Value 60 Hz 210 V·A
Operate Time Between Coil De-energization and NC Contact Closing 7 ... 14 ms
Between Coil De-energization and NO Contact Opening 4 ... 11 ms
Between Coil Energization and NC Contact Opening 7 ... 22 ms
Between Coil Energization and NO Contact Closing 8 ... 27 ms
Mounting on DIN Rail TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
TH75-25 (75 x 25 mm Mounting Rail) acc. to IEC 60715
Mounting by Screws (not 2 x M6 screws placed diagonally
supplied)
Connecting Capacity Flexible with Cable End 6 ... 16 mm²
Main Circuit Rigid Cable 6 ... 25 mm²
Connecting Capacity Flexible with Cable End 0.75 ... 2.5 mm²
Auxiliary Circuit Rigid Cable 1 ... 4 mm²
Degree of Protection acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20
acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP10
Connecting Terminals M 6 (+,-) pozidriv 2 screws with 1x (13 x 10 mm) connector
(delivered in open
position) Main Poles
Terminal Type Screw Terminals
Technical UL/CSA
General Use Rating (600 V AC) 90 A
UL/CSA
Horsepower Rating (200 ... 208 V AC) Three Phase 20 hp
UL/CSA (220 ... 240 V AC) Three Phase 25 hp
(440 ... 480 V AC) Three Phase 60 hp
(550 ... 600 V AC) Three Phase 75 hp
Environmental
Ambient Air Close to Contactor Fitted with Thermal O/L Relay -25 ... 55 °C
A63-30-11 400-415V 50Hz / 480V 60Hz 4
Temperature Close to Contactor without Thermal O/L Relay (0.85 ... 1.1 Uc) -40 ... 55 °C
Close to Contactor without Thermal O/L Relay (Uc) -40 ... 70 °C
Close to Contactor for Storage -60 ... +80 °C
Climatic Withstand acc. to IEC 60068-2-30 and 60068-2-11 - UTE C 63-100 specification II
Maximum Operating Without Derating 3000 m
Altitude Permissible
RoHS Status Following EU Directive 2011/65/EU
Container Information
Package Level 1 Units 1 piece
Package Level 1 Width 140 mm
Package Level 1 Depth / 146 mm
Length
Package Level 1 Height 96 mm
Package Level 1 Gross 1.2 kg
Weight
Package Level 1 EAN 3471522088512
Package Level 2 Units box 63 piece
Package Level 2 Width 503 mm
Package Level 2 Depth / 153 mm
Length
Package Level 2 Height 307 mm
Package Level 2 Gross 75.6 kg
Weight
Package Level 3 Units 160 piece
Classifications
A63-30-11 400-415V 50Hz / 480V 60Hz 5
Object Classification Q
Code
ETIM 4 EC000066 - Magnet contactor, AC-switching
ETIM 5 EC000066 - Magnet contactor, AC-switching
ETIM 6 EC000066 - Power contactor, AC switching
ETIM 7 EC000066 - Power contactor, AC switching
ETIM 8 EC000066 - Power contactor, AC switching
eClass V11.0 : 27371003
UNSPSC 39121529
Categories
Low Voltage Products and Systems → Control Products → Contactors → Block Contactors