Control Valve Calibration (SIEMENS Positioner)
Control Valve Calibration (SIEMENS Positioner)
Start initialization by pressing the key for more than 5 s and the
following display will appears.
During the initialization process” RUN1” to” RUN5” appear one after the
other.
It will take almost 15 minutes to complete the initialization process
depending upon actuator.
When initialization completes the following display appears.
Then press the mode key briefly, the following display appears.
To exit Configuration mode press the mode key for more than 5 s. After
about 5 s, the software version is displayed. When mode key is released
the, the unit is in manual mode.
Then press the mode key briefly to go into auto mode.
Then give the positioner remote command of 0%, 25%, 50%, 75% and
100% from DCS and check its position feedback on DCS.
Then close the front cover of the positioner.
Ask the operator to close the drain valves and take the control valve back
in service.
Observe the control valve response in auto mode for 2, 3 minutes.