Vertex VT26 MANUAL QIS - VT20V6
Vertex VT26 MANUAL QIS - VT20V6
Table of Contents
1. INTRODUCTION .......................................................................................................................2
2. IN A HURRY ? .............................................................................................................................2
3. INSTALLATION .........................................................................................................................3
3.1.PANELMOUNTING ......................................................................................................................................... 3
3.2.CONNECTION AND WIRING........................................................................................................................ 3
4. FRONT PANEL DESCRIPTION...............................................................................................5
4.1. CONTROLLER FACE INDICATIONS ......................................................................................................... 5
DISPLAY AND INDICATOR ........................................................................................................................ 5
PV (PROCESS VALUE) DISPLAY .............................................................................................................. 5
SV (SET VALUE) DISPLAY ......................................................................................................................... 5
4.2. KEY FUNCTION ....................................................................................................................................................................................... 5
This manual contains information for the installation, operation and tuning of your Vertex VT26 series
FUZZY ENHANCED auto-tuning microprocessor based controller. These controllers carry a two-year
factory warranty. The VERTEX microprocessor controllers are FUZZY ENHANCED “proportional +
integral + derivative” (PID) controllers that come in a variety of standard DIN sizes. The input is
configurable and allows selection of inputs between thermocouples and RTD’s. You can also have 4~20
and other linear inputs as an option to be specified when ordering the controller. When ordering your
controller you can choose between Relay, SSR, Heat / Cool, 4~20 mA or other output signals. They have
dual displays that show the input (measured temperature) in the top digital display and the required set
point in the lower. They all come standard with 2 alarm relay outputs. The controller boasts a
comprehensive range of other features that include a ramp, soft start with power limiting, auto/manual
function and comes standard with two configurable alarms. The controllers can be switched to manual and
can work as “time based ratio out-put controllers” in the event of thermocouple or input failures taking
place. There are other options you can choose including “retransmission” of either the PV or SV or RS485
communications. We have a simple data package (software) that you can use free of charge to link to and
monitor or record data.
2. IN A HURRY ?
Vertex temperature controllers, although quiet sophisticated, can be very simple to use as well. In
it’s simplest form, all you need to do is install it and get the wiring right, (YOU MUST READ
CONNECTIONS AND WIRING section 3.3, 3.4 + 3.5 BELOW) turn it on, check that the
thermocouple type it is correct, (during the self test it will display the input type), make sure it is
reading more or less the right temperature, that the heating elements actually get hot when the “C1”
light is on and away you go. No need for laboriously reading this manual and changing and setting
all the parameters….Just turn it on and when the system it is controlling has reached it’s operating
temperature, do an “auto-tune” as explained in the section “Tuning your VERTEX VT26 series
controller” You can also however explore all the parameters and set and use it in any way you may
wish. If you are not sure please contact Vertex and ask, we are always happy to help.
Panel Cutout
Model A B C D E a b c d
VT-4826 48 48 6 100 45 45+0.5 45+0.5 60 48
VT-4926 48 96 9 80 91 45+0.5 92+0.5 120 48
VT-7226 72 72 9 80 67 68+0.5 68+0.5 90 72
VT-9426 96 48 9 80 45 92+0.5 45+0.5 48 120
VT-9626 96 96 10 80 91 92+0.5 92+0.5 120 96
(Unit:mm)
Connections Explained
These are typical input connection drawing intended to explain the schematic symbols:
RTD Input looks like this Thermocouple input like this mA or mV looks like this
Relay output (10A/240VAC) This functions as a simple potential free switch. VT4826 use T11 + T12. VT4926
and VT9626 use T17 + T18
Solid State Relay output. (24Vdc pulsed) This supplies a 24 Vdc signal to switch SSR‟s requiring a DC 3 ~ 32
Vdc control signal. VT4826 use T11 (-ve) + T12 (+ve). VT4926 and VT9626 use T17 (+ve) + T18 (-ve)
Milli-amp output (4 ~ 20 mA). Max load 600 ohms This supplies a 24Vdc driven 4~20 or 0~20 signal. VT4826
use T11 (-ve) + T12 (+ve). VT4926 and VT9626 use T17 (+ve) + T18 (-ve)
1 ~ 50mV, 1 ~ 5V, 0 ~ 10V also available as an option.
SET key
Press once to access the next configurable parameter within the level you are in.
Press for 5 seconds to reset alarm timer if used.
SHIFT key
Shift digits to be adjusted by up/down key.
DOWN key
Press to decrease the set point or parameter value.
Press the SET and UP keys once to return the normal operation.
LEVEL key
Press the SET and SHIFT keys simultaneously for 5 seconds and then use the up and down keys to select the
programming level required. (ie: User, Soft, PID etc) Now press the SET key to enter that particular level and
access the first parameter.
All configurable parameters are user friendly and clearly structured in three levels. To change level from one to
the next, please press keys for at least 5 seconds to access level selection. Use UP/DOWN key to select
programming level.
Soft
Pid level. ( )
Option level. ( )
Scaling for Linear Input
5.1. USER LEVEL
The following parameters are listed in a default sequence. However any unused parameter can be removed
and the display sequence is configurable to simplify the operation.
: The ramp can be used separately from the “Soft Start” or in conjunction with as you please. With the Ramp
value set to 0 the ramp is disabled. When a value has been set in ℃/min each time a setpoint change is
made the setpoint will ramp at the set rate from the original value to the new setpoint value. This can be set
between the range of 0 ~ 9999 ℃/min (0.0 – 999.9)
: This is the temperature setpoint below which at startup, the output will be limited to the % value set in the
“out” parameter below. This value can be set anywhere between the LoLt - HiLt values of the range.
:Output percentage value to which the output will be limited at startup until the temperature has reached the
S.SP setpoint above at which the output will revert to full PID regulation.
5.3. PID LEVEL
: Proportional band value. Setting range from 0.0 to 300.0 % of controller„s Span. set to 0.0 for on/off control.
This value is automatically calculated by activating the auto tune function. It can also be set manually by
the user if so desired.
Ti : Integral (reset) time. This value is automatically calculated by activating the auto tune function. It can also
be set manually by the user if so desired.
When PB = 0.0, this parameter will be not available. When Ti is set to zero, make Pb & td ≠0 for PD
control.
: Derivative (rate) time. This value is automatically calculated by activating the auto tune function. It can also be
set manually by the user if so desired. When PB=0.0, this parameter will be not available. When td is set
to zero, Pb & ti ≠ 0 for PI control.
: Cycle time for the main control output. Setting range is from 0 to 100 seconds. Set to 1 for SSR output, set to 0
for 4 ~ 20 mA analog output and set to 15 for relay or contactor.
: Proportional band value for cooling control output when fitted. Set 0.0 for ON/OFF control.
: Integral time for cooling control output. When PB=0.0, this parameter will be not available. When set to zero,
Pb & td ≠ 0 for PD control.
: Derivative time for cooling control output. When Pb=0.0, this parameter will be not available. When set to zero,
VT26 MANUAL QIS 2 V6 7
Pb & ti ≠ 0 for PI control.
: Cycle time of second control output.
/ : Hysteresis (Dead Band) for on/off control on output 1 and output 2. Users can create a dead band
around the setpoint from 0.0 to 200.0 deg C. The temperature will continue to heat and rise above the
setpoint by the “HyS1” amount set, then cool until it has dropped below the setpoint by the same amount
before switching on again.
/ : Hysteresis for alarm 1 and alarm 2. The setting range is 0.0 to 200.0 and it works in the same way as
for the main Hysteresis setting.
: Dead band value. This defines the dead band between the heating and cooling outputs when used and can be
set from -100.0 to 100.0 deg C. If you are using proportional or PID control even though you set a dead
band you may get overlapping switching between the heating and cooling. This is a result of the control
algorithm action. If you make both the heating and cooling Pb = 0 however it will ensure that there is
nothing on between the two.
: Set point offset. Setting range is from -100.0 to 100.0 or –1000 to 1000. This value will be added to SV to
perform control. It mainly used to eliminate offset error between the SV and PV that may be experienced
during proportional only control.
: Process value offset. Setting range form -100.0 to 200.0 or –1000 to 2000 This parameter allows for manual
compensation of any process off-set that may exist between the measurement of the probe and the
reading on the controller PV display..
: Parameter lock. This security feature locks out selected levels or single parameters prohibiting tampering and
inadvertent programming changes. To change any “Lock” settings you must first make sure that gap “G1”
is soldered.
Setting Description
0000 All parameters are locked out.
0001 Only SP is adjustable
0010 Only USER level is adjustable
0011 USER and PID levels are adjustable.
0100 USER, PID, OPTI levels are adjustable.
0101 USER,SOFT,PID,OPTI levels are adjustable.
0101~0111 All parameters in all levels are opened.
1000=0000, 1001=0001, 1010=0010, 1011=0011, 1100=0100 but Output 2
1000 ~ 1111
is opened.
: Low limit of span or range. Set the low limit lower than the lowest expected SV and PV display.
Normally set at 0 deg C. If you make this setting above 0 deg C when the controller PV drops below this
setting it will be out of range and cease to operate.
: High limit of span or range. Note: If you have a PV retransmission output the Hilt and Lolt sets the
range that will equal your retransmission signal. Ie: 0~1000 / 4~20 mA or whatever.
: Software filters.
/ : Alarm function selection. See section 5.1 for detail.
/ : Alarm mode selection. See section 5.2 for detail.
: Address of the controller when communicating with a master device using RS485 comms.
Communication baud rate. 2.4k=2400 bps, 4.8k=4800 bps, 9.6k=9600 bps, 19.2k=19200 bps
Press the UP and DOWN keys simultaneously for 5 seconds to access “LnLo” parameter.
Adjust “LnLo” setting to correspond the low scale and after adjustment press key once to access
“LnHi” Parameter
Adjust “LnHi” setting to correspond the high scale and after adjustment press key once for normal
operation
6. OPERATION
6.1. HOW TO CHANGE THE INPUT TYPE
Press the SET and SHIFT keys simultaneously for 5 seconds until the display reads Level in the top
display. Then use the up and down keys to select the programming level required. (ie: User, Soft, PID
etc) In this case choose the Opti level. Now press the SET key to enter that particular level and access
the first parameter.
This should be the Type parameter. Use the up and down key to select the input type you wish to have
as listed in the table below
Now press the SET key a few times until you reach the parameter and leave this set at 0000 .
Press the SET key again and you will see the . Use the up and down to make this the nearest 100‟s
setting suitable. (ie a range of 0~200 or 0~400 or 0~600 etc etc)
Now Press the SET and UP keys once to return the normal operation.
Tuning is the process of setting the Proportional, Integral and Derivative terms of the controllers main output
VT26 MANUAL QIS 2 V6 10
to best suit your application and give the best possible control under your specific circumstances. (Note this
tuning will also tune the second cooling output should your controller have this option) If you are not happy
with the stability of control, and wish to have less over and undershoot around the setpoint, it is advisable to do
this procedure. It is also advisable always do this on commissioning new installations. The auto tune function
is used to “teach” the controller the main characteristics of the process. It “learns” by cycling the output on and
off around the setpoint. The results are measure and used to calculate optimum Pb, ti, td values, which are
automatically entered into nonvolatile memory.
The auto tune function is triggered manually and can be used during setup of the controller.
1. Firstly install the controller and get it controlling using the factory settings (As supplied)
2. Always set the setpoint at about half the eventual control temperature the first time you turn it on
after installing it during commissioning. This will allow the controller to start controlling and you will
easily see if there is something wrong.
3. If the controller is being used as a PID controller, the output will be on and stay on at first, and the
temperature will rise towards the setpoint. As it nears the setpoint it will begin to switch on and off.
You can monitor this by watching the “C1” light on the display. When the output is on and it is
heating, the light will be on.
4. Once the controller has stabilized at that setpoint and is working more or less ok, take the setpoint
up to the required temperature and let it re-stabilized there.
5. If you are then not happy with the control results you can make the controller set (tune) the PID
parameters itself. Should you wish to do this instruct the controller to do an “auto-tuning” calibration
of the parameters.
6. Make sure that the value of Pb is not zero (Pb = 0 forces on/off control). Set the “ ” parameter
to “ ” . (“ ” will force the tuning process at 10% below the required setpoint and is not
generally used.) The rightmost decimal (AT) on the PV display will blink during tuning process.
(See explanation of difference between “ ” and ” below)
7. After two oscillatory cycles of on/off control action around the setpoint (SV) the controller will use the
measurements learned to set the PID parameters. The controller performs PID control with these
“learned” PID values to verify the results. Finally the PID values will be entered into the memory.
The controller will now start controlling using fuzzy enhanced PID control.
8. To abort an auto tune process. Simply set the “ ” parameter to “ ”.
9. If initially the controller is oscillating badly you may need to perform this procedure a second time to
get the best results.
10. DO NOT CHANGE ANYTHING AT ALL IN THE PROCESS OR CONTROLLER WHILE DOING AN
AUTO TUNING PROCESS.
11. Do not change anything during this procedure, as it will result in erroneous settings that may not
control well at all. (Just leave the system for a few minutes while it does its thing.)
12. Also only do this at the full-required temperature, once the whole system has had a chance to warm
up and work for a while.
13. Once it has finished the auto tune light will stop flashing and the controller will start to control using
the new parameters.
14. Once this process is completed, you should get good control. It should really only be done once
more when the system is in full operation (i.e. under normal working conditions with the process in
VT26 MANUAL QIS 2 V6 11
full swing) if you are not happy with the control results.
15. When doing this on a barrel of an extrusion machine, or on a mould where there is more than one
temperature being controlled in close proximity to another, where they may interfere with each other,
always let them all stabilize and then choose the most stable zone and do that one first. Only ever
do one zone at a time, let it finish and then do the next most stable zone next to the one you have
already done.
The controller can also be set to ON/OFF, PI, PD and P control mode. Set Pb = 0 for ON/OFF control mode.
Set ti = 0 for PD control mode. Set td = 0 fro PI control mode and ti, td = 0 fro P control mode. The Hysteresis
(dead band) 0f ON/OFF control can be set as follow:
ON
OFF
SP-HYST ▲ SP+HYST
SP
When the second control output (output 2 cooling) is fitted it will behave as shown below. Bear in mind that
when using Proportional or PID control there may be an overlap between the heating and cooling depending
on the auto PID algorithm calculations. This is perfectly normal. You can make both heating and cooling
proportional band = 0 then it will ensure that between the two nothing is switched on.
Output
Heating Cooling
PV
Overlap Dead
Band Band
The PID parameters determined by the above procedures are just rough values. If the control results are unsatisfactory.
The following rules may be used to further adjust the PID parameters.
Manual control allows the user to manually force the output percentage from 0.0 through 100.0% (usually used
for testing purposes). To access the manual control mode, set the “ “ parameter to ”yes”, the rightmost
decimal (MA) on SV display will flash. Then the ” “ parameter will display alternately ” “ and
process value. The output percentage then can be adjusted by using up or down key to increase or decrease
the temperature. To abort the manual control just simply set the ” “ to ” “. BE AWARE THAT THE
CONTROLLER CANNOT MAKE ANY CORRECTIONS SHOULD THE TEMPERATURE GET TOO HOT
WHILE YOU HAVE IT IN MANUAL MODE.
There are two independent alarm outputs available in VT20 series controllers. Each alarm can be set to
function in one of six alarm function modes below. (Process high, process low, deviation high, deviation low,
band high and band low) for or . When the alarm output is not used, set to “ ” to prevent
unwanted alarm action.
1. When it is required to have “Heat” and “Cooling” as for example on an extrusion barrel, you can use the
alarm setting as the “cooling setpoint”.
2. The alarm based cooling will be on/off and not proportional.
1. If your controller has been supplied with a remote setpoint you will only be able to change the
setpoint via the remote input signal.
a. You can wire the main output through the “alarm 1” output and use the alarm in a timer
function to control a “dwell” time after which the output will be cut off.
c. Now check the parameter which allows you to choose between hours and minutes or
minutes and seconds for the time setting when setting
a. When choosing the Master Slave options you are choosing controllers that are pre-set to have
the Master controller set point transmitted by RS485 comms to the slave units.
b. Each slave unit will have the same setpoint as the master.
c. This is useful when having a series of zones along which all set points should be the same. All
you need to do is change the Master unit and all others follow.
d. You can in fact use the Spof setting and create a profile all based on the master setpoint but in
those with a Spof value being different by that amount.
9. SPECIFICATIONS