Principles and Applications of Static Thyristor Controlled Shunt Compensators
Principles and Applications of Static Thyristor Controlled Shunt Compensators
discussed. Vei2l/3 and Vc = Ve-j41r/3 as shown in Figure la. The delta equivalent
INTRODUCTION of the load represented, for convenience, by admittances Yab, Ybc,
and Yca is shown in Figure lb. Impedances Za, Zb, and Zc (or
Shunt compensators are used to control (or regulate) the admittances Yab, Ybc, Yca) are, in general, functions of time. In order
transmission voltage at a given terminal and to provide power factor to establish the basic compensation requirements, it will be assumed
correction. Two types of compensation problems are normally that the three load impedances are time-invariant and different from
encountered in practical applications. The first is load compensation each other, that is, they represent a general steady state unbalanced
where the requirements are usually to reduce or cancel the reactive load. This assumption does not exclude the eventual consideration of
power (VAr) demand of large, and fluctuating industrial loads, such as
time varying impedances. Indeed, the three steady state impedances
electric arc furnaces, rolling mills, etc., and to balance the real power may be viewed as representing the load at a particular time instant. A
drawn from the ac supply lines. These types of heavy industrial loads series of "steady state" impedances, representing the load at discrete
are normally concentrated in one plant and served from one network
time instants appropriately close to one another, can reconstruct a
terminal, and, therefore, can be handled best by a local compensator time varying load (having rates of change sufficiently below the ac
connected to the same terminal. The second type of compensation is supply frequency) just as a chain of still pictures can faithfully
related to the voltage support of transmission lines at a given terminal describe a moving object.
in the face of disturbances of both loads and generation. Here the
load is not localized; several load areas and generator units may be tied
by a transmission network and the objective is simply to regulate (or
control) the voltage at the compensated terminal.
Static shunt compensators are essentially controllable VAr
sources - or VAr generators - functionally similar to the traditional
rotating synchronous condenser. Several types of static compensators,
with different operating features, can be realized using various power
conversion concepts and thyristor circuits.6'9 In this paper only the
variable impedance types, that is those which essentially function as
Fig. 1- la) General three-phasewye connected load represented by
variable reactances (capacitive and inductive impedances), are con- impedances (b) Delta equivalent represented by admittances
sidered. Regardless of the type of shunt compensators employed the
basic compensation principles are the same, requiring the generation With the above assumption, the compensation problem becomes
of controllable VArs to supply the reactive and negative-sequence load that of finding a reactive'admittance network which when combined
currents (load compensation) or to induce an appropriate voltage with the load admittance will present a real and balanced load to the
across the ac system impedance to regulate the terminal voltage supply terminal.
(voltage support). Using the delta equivalent representation of Figure lb, the three
In this paper theoretical bases for both load compensation and load admittances can be compensated separately as if they were three
transmission line voltage support are investigated. The intention is the single-phase loads. Consider for example phase ab. If admittance Yab
derivation of analytical relationships that are applicable to the control is composed of a real component (conductance) and reactive
of practical shunt compensator schemes using thyristor circuitry. component (susceptance), that is
LOAD COMPENSATION Yab = Gab + j Bab (1)
the reactive part can, as a first step of the compensation, be cancelled
There are usually two main reasons for compensating large, by an appropriate compensating susceptance, -Bab, connected in
fluctuating loads: (1) the ac system is too weak to maintain the parallel with Yab as illustrated in Figure 2.
terminal voltage with acceptable variations and (2) it is not econom-
ical, or practical, to supply the reactive power demand from the ac a
Yab =
Gab+ i ab
E
vzYabbGab
b'
B(ab) = Gab/ (3) Fig. 5 - Compensation of the single- phase load, Y by susceptances - Bbc. B (bc ) and B(bC)
is connected between phases c and a as shown in Figure
(Superscript (ab) is used to indicate that the susceptances are nee
to compensate phase ab). Since the single-phase real power supp
by the ac source before compensation
pk=(/y V)2 Gab= 3V2 Gab (4)
must be equal to the three-phase real power demand after compensa-
tion, the compensated load may, in effect, be represented as three wye P = 3V2 Gca
connected resistors, each with a conductance of Gab as shown in
Figure 3. The mechanism of compensation is depicted in Figure 4 Fig. 6- Compensation of the single-phase load, Yca, by susceptances - Bab and BbCOl
where a phasor diagram illustrates how two (capacitive and inductive)
susceptances transform the single-phase real load into a balanced
three-Phase real load. Complete compensation of the three-phase load is readily
obtained by adding all compensating susceptances in each phase as
B(COab)
0 =_
Ga
- _6b
c
illustrated in Figure 7. Thus, the resultant compensating susceptances
J _~t
B(ab), B(bc), and B(c) are simply the sums of the susceptances used to
compensate the individual phases, namely,
S --
Gab (
B(c)ab ab + B(bc)
Bab ab + B(ca)
ab
la Va Gab V Gab
B(B
= +B(ca)+ (Bab) (9)
Ib VbGab
C V Gb exp(- i/3)
=I It Vc Gab = V Gab eap (-j 4 /3
P = 3 V2 GC
B(c)
ca =B ca
+ B(ab) + B(bc)
ca ca
Fig. 3- Compensation (balancing) of the single-phase real (resistive) load. Gab, bytwo (capacitive and where superscript (c) stands for "compensating."
inductive) susceptances. 8 lab) and Blabl
C
ca.
V
L,ca 'C. bc
.0 a
o~~~~~~~~~~~~~~~~~~~~~~
55.0~ =b~~~~~~~~
CCGbCB
C.b opestn
b. bcurens aCbc, IL caRadlv urns a a I. L
rtentoki sca o = -n
(bcC)c 0 b ca (c)Ga G_
b5C
ca__
b5c
BabCI
3
-- -
aC. (
A prcdr
oc) = -+ Gab
iiabt htotie abovanRbe folc edt
otherFig. 7twoApplicadion
- phases. With ot Eqs.
of the principles (2),ab(3)
single- phase and to an unbalanced
toad compensation ab) bo(),tehe
th ree- phase load
and
BICnn bc+(ab -Gca) /O(0)
(7) a
Bca + Gbc Gab)! V
It can be seen that if the real part of the load is balanced, that is,
bca)= -ca Gab = Gbc Gca, the compensation problem
= is reduced to that of
simply cancelling the reactive part of the load in each phase. In
general, the compensating susceptances given in Eqs. (10) transform
respectively. The compensation of admittances Ybc and Yca is any linear unbalanced load into a balanced real load that, from the
illustrated in Figures 5 and 6 respectively. standpoint of the ac source, can be represented as three wye
1937
connected resistors, each with a conductance that is the sum of the I
conductances of the original delta load (G = Gab + Gbc + Gca). From I
this it follows that the power factor of the resultant load can be
changed from unity to any desired leading or lagging value by adding
the same capacitive or inductive susceptance to each compensating al = (la + alb +aIC) (14)
susceptance defined by Eqs. (10).
The fundamental considerations presented in this section lead to Ia2 = 13(3(Ia + aIb aI )
aI + ac)
the following conclusions:
where laO' Ial and Ia2 are the reference phasors of the zero, positive,
1. An arbitrary ungrounded unbalanced linear load can be trans- and negative-sequence current sets.
formed into a balanced three-phase load without changing the real Substitution of Eq. (13) into Eq. (14) gives the symmetrical
power exchange between load and source. components in terms of the load admittances:
2. The transformation requires appropriate modification of reactive
load power in each phase; this process is generally referred to as 'aO = 0
load compensation.
'al =(Yab+Ybc+Yca)V (15)
3. In general, load compensation involves two separable acts; one is
power factor correction and the other is load balancing. If both are
carried out, they determine together the total reactive power Ia2 =- (a2 Yab + Ybc + a Yca) V
needed for compensation. The objectives of load compensation can be stated in terms of
4. Any unbalanced linear steady state load can be compensated by the symmetrical line-current components as follows:
three appropriate reactive impedances (capacitive or inductive 1. Eliminate the negative-sequence components (balancing).
reactances) connected between the three phases. 2. Eliminate (reduce) the reactive part of the positive sequence
5. If the load changes in time, the compensation requires variable components (power-factor correction).
reactances (or other controllable VAr sources) that can be adjusted The results of the previous section indicate that these objectives
in sympathy with the load variation.
can be achieved by a delta connected compensating network formed
Compensation Requirements in Terms of the Symmetrical of reactive circuit elements (susceptances) as shown in Figure 8. The
Components of Load Current purpose of the present investigation is to find relationships between
the compensating susceptances and the symmetrical components of
In this section the compensation requirements of a general load current.
unbalanced load in terms of symmetrical components are investigated. The symmetrical components of current drawn by the delta-
This investigation complements the fundamental considerations in the connected compensating network can be expressed in terms of the
previous section and provides a different interpretation of the results compensating susceptances in forms similar to those given in Eqs.
obtained. (15):
Consider again the general unbalanced three-phase load fed from
a balanced three-phase (ungrounded) source as shown in Figure 1. In the 1(c)
a0 = 0
present analysis the delta equivalent of the load, defined by
admittances Yab, Ybc, and Yca is used again for convenience, as
shown in Figure 8. i(c)=
al i (B(c) bc + B(c))
ab + B(C) ca
V (16)
I(c)
a2
-j (a2 B(c) +
=
ab bc
+a
ca
B(c) B(c))
V
The compensation requirements (load balancing and power-
factor correction) can be formulated mathematically as follows:
Ia2 + a(c) 0 (17)
and
ImIal al - (18)
Compensator Load Inspection of Eqs. (15) and (16) indicates that both Ia2 and l(c)
a2
Fig. 8- Three-phase unbalanced load represented hy delta connected admittances and
the delta connected compensator generally have a real and imaginary part, while Im lal and I a)(c)
are, by
As stated, the source voltages are assumed balanced with a definition, imaginary. Therefore, the condition given in (17) repre-
positive phase rotation, that is sents two equations, namely
Va = V, Vb = aV, VcaV (1 1)
ReIa2+ReI(C)=0 (19)
ImNdaCe ~ X 'C _, CE
a o c
4,
Fig. 10- Phasor diagrams illustrating load current compensation In terms of the symmetrical components.
a a
ta) A set of three unbalanced load currents I4*1a and Ib and IC C
with the a system voltages Va,
a'bVh.
and Vc hi Balancing of the ioad currents by the negative- sequence compensating currents I a2c Ib2c
b b Load aI 5t2. and C) = a I a2 (c) Elimanation of the reactive compionents from the balanced load currents
Positive- Sequence Negative- Sequence
Compensator Cornpensator by the positive- sequence compensating currentsIal Ibl= aI 2 1c1 and Icl aIal a
B(cl B(c) B(c)
P ab P, bc P, N
Bc)IC)8() 06(c) =o
NB ab + N bc+ N, ca
Compensation Requirements in Terms
Pig. 9- Representation of the compensator by positive- sequeece and negative- sequence admittance deltas of Load Current and Power Quantities
The susceptances of the "positive-sequence delta" and "negative-
sequence delta" can be expressed in terms of the real and imaginary In the previous two sections, the compensating susceptances are
parts of the load admittances from Eqs. (21) with the use of Eqs. (15), expressed in terms of the load admittances or the symmetrical
namely components of load currents. While both types of expressions can
provide bases for practical control approaches, equations relating the
(c) (c) (c) 1 compensating susceptances to directly measurable load currents and
BP,ab BP,bc = Bp,ca = - ab + Bbc + Bca) (22) powers are often preferred in actual compensating systems. Several
different types of expressions can be derived (with more or less labor)
B(c) 2 1 1 from either of the two basic sets of relationships given in Eqs. (10)
N,ab 3 Bab + 3 Bbc + Bca + 1 (Gca Gbc) and (21). (As already indicated, these equations themselves can be
converted into each other). Four sets of equations which appear to be
particularly attractive for practical implementation are now presented.
Nbc 3Bab1 + Bbc
c) j 2 +- Bca1 +71 (Gb Gca) (23)
In these sets of equations the compensating susceptances (or corre-
sponding currents and reactive powers) are given in terms of in-phase
N,ca 3 Bab bbc ca + bc a) and quadrature components of load currents (measured with respect
to appropriate line-to-line or line-to-neutral voltages) or corresponding
where subscripts P and N stand for positive-sequence and negative- real and reactive power quantities. The first two sets satisfy the
sequence, respectively. It can be observed that the sum of Eqs. (22) conditions for zero in-phase voltage drop [Eq. (25)] and zero
and (23) results in the same total compensating susceptances given in negative-sequence supply current [Eqs. (19) and (20)]
Eqs. (10) derived by a different approach. It is pointed out here that,
for economic reasons, the compensating network is normally not
K Re Vb*c) I-K
b-K2 R(Va
broken into two deltas. Indeed, there is no apparent reason to do so
since one compensating delta with controllable susceptances can
Bab(c) 1kVXr3/jVI ReoV/ I a
provide both the positive and negative-sequence currents required for
the compensation.
The fact that compensation of the positive-sequence and B(CC)
( XV) = K1 Re
c
V Ic K2Re (b))b (26a)
negative-sequence load currents can be carried out independently (by
a single controllable compensating delta) makes control of the reactive
power provided for the ac supply quite simple. This may be required
in practice for power factor adjustment and compensation of voltage
drop across the supply (ac network) impedance.
B(ca)(/V) = - K1Re\Vt Ia- K2Re V\vjIc
Frequently, the compensation requirement is not simply cancel-
lation of the reactive component of the positive-sequence load where K1 = 1/ -/3 - R/3X, K2 = 1/V + R/3X, R is the real part and
current, as stipulated in Eq. (18), but, rather, the reduction of the X is the imaginary part of the supply impedance, and Vat, VbC*, VcA
in-phase voltage drop across the balanced supply impedance to zero. are conjugates of the line-to-line voltages, that is, Vat = (Va - Vb3
The condition for this can be written simply as Vb* = (Vb - Vc)* and Vca = (Vc - Va)*. Expressions Va*/Nj3V,
Re [(I + I(c)) (R +jX)l = 0 (24) Vbc/NF V, and Vc*al/v3V represent unit phasors. Thus, the real part of
each phasor product in Eqs. (26a) gives a component of the relevant
or load current that is in-phase with the line-to-line voltage in question.
For example, Re (Va*b Ia)/V3`V specifies the component of load
R
Re Ial Im Ial I(a)= 0
current 'a that is in phase with line-to-line voltage Vab.
1939
Equations (26a) can be written in a different form, which implies dva/dt > dvb/dt > 0 dvc/dt >0
a way to measure the load current components sought, by converting The expressions ia(t) va = ,lib(t) -b=0 , ic(t) v =Q
the phasor quantities into appropriate time functions. Thus
mean to take the value of each load current at the instant of time
vca > 0
a(b B= -K1I ib (t) when the corresponding voltage is zero, and its derivative is positive,
vbc
/V)
dvbc/dt o -K
K2 ia(t) dvca/dt =
0
that is, at those zero crossings at which the voltage changes from
negative to positive. (At negative-going zero crossings the signs of Eqs.
t)vca (28b) should be changed). Of course, these values represent the
BgC)B(c
> 0
vab >O
(,/3V)
(V/V) i K
ib(t) (2b
= - K1 ic(t) dv
ca/dt K2 amplitudes of reactive load current components.
The following two similar equations express the compensating
susceptances in terms of the reactive phase powers of the load.
B(ca(c (.3V) =-K1 ia (t) |dvab/dt
> >0
0 K2 ic(t) dvbc/dt =
vab vbc
/V iat
0
B(c) (3V2) = - Im
(Va 1a) - Im V 1b) + Im (Vc* Ic (29a)
Alternatively
The expression, for example, ib(t) dvbc /dt 0 simply means to take
ab( ( 2) T f [vbc(t) ia(t) + vca (t) ib(t) - vab(t) ic(t)] dt
the value of current ib(t) at the instant of time when the derivative of (T) (29b)
vbc(t) is zero and vbc(t) is positive, or, in practical terms, to sample
the current ib(t) at the positive peak of voltage vbc(t). Evidently, the
quantity so obtained is the amplitude of the component of current
ib(t) that is in phase with voltage vbc(t). (Note that the sampling can TRANSMISSION LINE VOLTAGE SUPPORT
also be carried out at the negative peak of the voltage if the signs in
equations (26b) are changed from negative to positive.) In the previous sections the compensating susceptances are
Inspection of Eqs. (26a) indicates that, by multiplying both sides expressed as functions of the quantities (admittances, currents) that
with V/3V, the compensating susceptance (and reactive compensating characterize the load to be compensated. These relationships, as will
power) can be expressed in terms of average real power quantities. be seen, provide useful bases for practical control strategies in those
Furthermore, since the expressions specifying the three compensating cases where the compensation of a single load (or load group) is
susceptances are identical, except for the subscripts a, b, c and ab, bc, required.
ca, which follow a natural cyclic sequence, it is enough to write only In a multi-terminal electrical transmission network tying several
load areas and generation units, these relationships may not be
the equation for B(C).ab
The other two can be obtained simply by applicable. It may not be possible, or practical, to measure the
commuting the (phase related) subscripts. Thus quantities that would meaningfully characterize the load. Similarly,
the compensation objectives usually cannot be defined in terms of the
B( (3V2) = - K1 Re(VbIb) - K2 Re (Vc* la) (27a) transmission line currents. The primary interest at the terminal of a
transmission line is generally the voltage because (1) it determines the
where again K1 = 1/ V3
R/3X, K2 = l/V/3 + R/3X and expressions
-
Re (Vbc lb) and Re (Vc* Ia) evidently define average real (in-phase)
available or transmittable power, and (2) it may have to meet some
quality requirements for consumers. For this reason, transmission-
power quantities in phases bc and ca corresponding to currents Iband network compensation requires a different approach than load
Ia respectively. compensation. In the case of load compensation the objective is to
Equation (27a) can also be written in an equivalent form in transform the current drawn by an unbalanced and generally
which the currents and voltages are expressed as real time functions, non-unity power factor load into a balanced set of (real) line currents.
namely The quantities characterizing the load are measured, and the line
currents are controlled. The impedance of the ac system plays no
B(c) (3V2)m I 1T vab(t) ib(t) dt -
K2 T l vca(t) ia(t) dt significant part in the compensation since the terminal voltage itself is
(T) (T) not controlled. By contrast, the principal objective of transmission
line compensation is regulation (support) and, in some cases, balancing
where T is the period time. (27b)
of the terminal voltages without regard to the actual cause of their
As Eqs. (26) and (27) show, each compensating susceptance is variation and unbalance. The compensating susceptances (or currents)
expressed in terms of two in-phase (line-to-line) load current compo- must therefore be expressed in terms of the terminal voltages.
nents or two real power quantities. From these relationships [or from Consider a general network compensation problem illustrated
the original ones given in Eqs. (10) and (21)] additional sets of schematically in Figure 11. A number of transmission lines are tied
equations can be derived in which each compensating susceptance is together at a terminal, the voltage of which is to be regulated and
expressed in terms of the actual quadrature components of all three balanced. Generators as well as loads may be connected to each
load currents, or the three corresponding reactive phase powers. These transmission line.
equations do not adhere to the condition of maintaining zero in-phase
voltage drop across the supply impedance [Eq. (25)], rather, they Transmission SW
satisfy the condition of keeping the positive-sequence reactive current Unes Compensator
in the supply lines zero [Eq. (18)]. Terminal Sequence Voltages Compensator Sequence Currents
/V aOt' atVt a2at
) (SW open) 1c1) I'c)
a2 (SW closed)
The first two equations given below (again for B(c))
ab
express the
VaO Val Va2 (SW closed)
compensating susceptances in terms of the reactive components of
load currents. They are analogous to, and can be derived from Eqs.
(26a) and (26b) if the R/X ratio is set to zero. Fig. 11 - A general transmission network terminal with a compensator
Thyristor- a
Inductor Current IL Desired
Controlled To Firing Angle Inductor Current
Susceptance Computer ErrTo
Erronq Thyristor
PErroEsr
Converter
i Generator F ring Angle Controlled Load
Converter Susceptances
Laszlo, Gyugyi was born in Tamasi, Hungary on January 16, Semiconductor Division. In 1972, he joined the Switchgear Division as
1933. He received his basic technical education at the University of Sales Manager of Regulator Products and Power Electronics. In 1974,
Technology, Budapest, further studied mathematics at the University he was named Product Manager for that department, the position he
of London and electrical engineering both at the University of presently holds.
Pittsburgh, Pennsylvania, where he received an M.S.E.E. (1967), and
at the University of Salford, England, where he received a Ph.D. Mr. Otto is a member of the IEEE. He is also a member of the
(1970). Power Generation Excitation Systems Subcommittee.
He began his career at the Epsylon Research and Development Thomas H. Putman (SM '68) was born in Pittsburgh, Pennsylva-
Co., Ltd., England, in 1958, then joined the Westinghouse Research nia on Nov. 22, 1930. He received the B.S. degree from Union College,
Laboratories in 1963, where he is now Manager of the Solid-State Schenectady, New York in 1952, and the S.M. and ScD. degree from
Power Controls Section. In this position he has been responsible for Massachusetts Institute of Technology, Cambridge, Massachusettt in
the research and development of a variety of solid-state power control 1954 and 1958 respectively.
and conversion equipment, including static VAR compensation
systems for both industrial and utility applications. Upon completion of his work at M.I.T., Dr. Putman joined the
Westinghouse Research Laboratories as a Senior Engineer in the
Dr. Gyugyi is co-author of the book "Static Power Frequency Electromechanics Department and subsequently became manager of
Changers" (Wiley, 1976), and author of the section "Power Frequency that activity in 1967. In 1974 Dr. Putman was appointed Consulting
Changers" in the Electronics Engineer's Handbook (McGraw Hill, Engineer in the Electrical Sciences Division of the Westinghouse
1975). He has written several technical papers, holder of 32 patents, Research Laboratories.
and is a Fellow in the Institution of Electrical Engineers.
Dr. Putman's technical activities encompass the analysis and
Richard Otto was born July 15, 1932, in Watertown, Wisconsin. design of electrical, mechanical and hydraulic systems. He serves on
He received both a Bachelor of Business Administration degree in the Industrial Drives Committee of the IEEE and is also a member of
1954, and a BS degree in Electrical Engineering in 1959 from the the Society of Naval Architects and Marine Engineers serving on the
University of Wisconsin at Madison. Ships' Machinery Committee Panel M-20. Dr. Putman is a member of
Sigma Xi and is a Registered Professional Engineer in the State of New
He joined Westinghouse in 1959 and after several field sales York.
assignments, he became Applications Manager at that company's
1945