RTU500 Series Training

Portfolio & Engineering


RTU560 Product Line
System concept Rack solution
RTU560 Product Line – System Concept

▪ Cabinets and Racks


▪ Power Supply Units
▪ Communication Units
▪ Bus Connection Units
▪ System Structure
▪ Assembly Options
▪ Number of Data Points

© ABB Group
RTU500 Series Training R12
04_1_System_Concept_Rack
2
Swing Frame Cabinet

© ABB Group
RTU500 Series Training R12
04_1_System_Concept_Rack
3
Front side wiring cabinet

© ABB Group
RTU500 Series Training R12
04_1_System_Concept_Rack
4
Cabinets, Side view
Swing frame Mounting plate
Swing Frame Rack 560SFR02

Mounting Plate Rack 560MPR03

Door Door
SFR MPR
Pos. 0 Pos. 0
Cable
duct
SFR
Pos. 1
MPR
Power Pos. 1
and SFR Pos. 2
Communication Process Cable
Connection duct
SFR MPR
Pos. 3 Power Pos. 2
and
SFR Communication
Pos. 4

MPR Pos. 3
SFR Pos. 5

© ABB Group
RTU500 Series Training R12
04_1_System_Concept_Rack
5
Standard 19-inch-rack for Swing Frame - 560SFR02

Rear View

18-pole sub-connector

© ABB Group
RTU500 Series Training R12
04_1_System_Concept_Rack
6
Rack for Swing Frame - 560SFR02

Example:

▪ process wiring
▪ 23ET23 / 23ET24:
previous version
of 560SFR02

© ABB Group
RTU500 Series Training R12
04_1_System_Concept_Rack
7
Rack for Swing Frame - 560SFR02

DIN-F connector with


cutout for row 22 - 32

View from cable


Sub-connector
entry side
© ABB Group
RTU500 Series Training R12
04_1_System_Concept_Rack
8
Rack for Swing Frame - 560SFR02

Crimp Tool
23XS41 R0001

Connector housing
23XS40 R1001 (100 pcs)

Removal
Snap-in contacts Tools … … for contacts
23XS40 R2001 (500 pcs) … for housing 23XS42 R0001
© ABB Group
23XS43 R0001
RTU500 Series Training R12
04_1_System_Concept_Rack
9
Standard 19-inch Mounting Plate Rack - 560MPR03

© ABB Group
RTU500 Series Training R12
04_1_System_Concept_Rack
10
Mounting Plate Rack - 560MPR03

▪ Example, previous version, rack 23TP21 / 23TP22


© ABB Group
RTU500 Series Training R12
04_1_System_Concept_Rack
11
Rack - Blanking front plate to cover free slots

Front Plate for Rack

560FPR01 R1002

(100 pieces per package)

© ABB Group
RTU500 Series Training R12
04_1_System_Concept_Rack
12
Rack structure - 560MPR03 / 560SFR02
DIN position 1 … 84
1 9 13 17 21 25 29 33 37 41 45 49 53 57 61 65 69 73 77 81

OFF
1 2 3
4
P1 P2 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
RTU560 slot number (part of the hardware address)

▪ 2 Power supplies (PSU), P2 optional with S18 ▪ Up to 8 communication units


▪ Slot P2 cannot be used for other modules per rack
▪ Up to 18 or 17 slots for modules ▪ Up to 2 racks only with CMUs
© ABB Group
RTU500 Series Training R12
04_1_System_Concept_Rack
13
Racks - functionality and addressing
▪ Communication Racks, max. two Racks per RTU
• Equipped only with communication units
• Range of addresses: 0, 1
▪ Composite Racks, max. one Rack per RTU
• rack with communication units and I/O modules
• Range of addresses: 1 … 7
▪ Input / Output Racks, max. seven racks per RTU
• equipped only with I/O modules, without CMUs
• Range of addresses: 1 … 7
▪ If a rack contains at least one CMU, the name of the rack
is “560xxx…A (see chapter “Bus Connection Units”):
• 560MPR03A (use of 560BCU04)
• 560SFR02A (use of 560BCU05)

© ABB Group
RTU500 Series Training R12
04_1_System_Concept_Rack
14
Racks, Power Supply Supervision
▪ The status of the power supply unit is available on the contacts
X11/X12.

Power
Supervision

▪ The status of a redundant pair of power supply units (PSF1/2) is


available on X13/X14/X15.
▪ X13 / X14 is to be used within an alarm-loop.
▪ X15 may be connected to a binary input board.
▪ A redundant pair of power supply units is supervised by the
RTU-system only, if a Communication Unit and a 560BCU04/05
is present in the rack. (System-event #059)
© ABB Group
RTU500 Series Training R12
04_1_System_Concept_Rack
15
Racks, Power Supply Supervision, Logic

© ABB Group
RTU500 Series Training R12
04_1_System_Concept_Rack
16
Racks, Serial Bus Termination
▪ On the last rack of a bus segment, the I/O-Bus (SPB) has
to be terminated (R = 1 kΩ ).
▪ After delivery, this resistor is connected.
▪ Termination on Rack 1 is done by the CMU.

Rack #1 The termination on the racks 1 … (n-1)


within a bus segment has to be
Remove !
removed.

Rack #2
Remove !
To remove the termination:
interrupt the electrical connection of
the resistor by drilling a hole on
Rack #3 position X4 on the back plane.
Keep Resistor !

© ABB Group
RTU500 Series Training R12
04_1_System_Concept_Rack
17
Racks, Potential Isolation
▪ After delivery, the potential isolation is not active, i.e.
GND (=0V) and PE (= process earth) are connected.

To disconnect GND from PE (for


potential isolation), drill a hole on
position X5 on the back plane.

(Diagram for Rack 23ET24 / 23TP22)

© ABB Group
RTU500 Series Training R12
04_1_System_Concept_Rack
18
RTU560 Product Line – System Concept

▪ Cabinets and Racks


▪ Power Supply Units
▪ Communication Units
▪ Bus Connection Units
▪ System Structure
▪ Assembly Options
▪ Number of Data Points

© ABB Group
RTU500 Series Training R12
04_1_System_Concept_Rack
19
Power Supply Units

▪ LEDs for output voltage

▪ Electronic power limiter

▪ Short circuit protection

▪ Load sharing

▪ Alarm output (PSF)


4 different power supply units for rack solutions:
▪ 560PSR00 R0001
▪ 560PSU01 R0001 *) phased out
▪ 560PSU01 R0002
▪ 560PSU02 R0001
© ABB Group
RTU500 Series Training R12
04_1_System_Concept_Rack
20
Power Supply Units
560PSR00 560PSU01 560PSU02
Input R0001 *) phased out
Voltage 24 … 60 V DC 24 … 60 V DC
R0002
110 … 220 V DC 48 … 220 V DC
Power 44 W 44 W 84 W

Output 5 V: 5.5 A 5 V: 5.5 A 5 V: 15 A


Current DC 24 V: 0.7A 24 V: 0.7A 24 V: 0.4 A

Efficiency 85 % 62 % 74 %
No. of 4 4 8
CMUs
▪ Because of the ‘load sharing‘ feature,
the types must not be mixed within one rack.
© ABB Group
RTU500 Series Training R12
04_1_System_Concept_Rack
21
RTU560 Product Line – System Concept

▪ Cabinets and Racks


▪ Power Supply Units
▪ Communication Units
▪ Bus Connection Units
▪ System Structure
▪ Assembly Options
▪ Number of Data Points

© ABB Group
RTU500 Series Training R12
04_1_System_Concept_Rack
22
Communication Units, 560CMR02
560CMR02
▪ 2 Ethernet interfaces
E1, E2
10 / 100 Mbit/s
Per interface 2 LEDs for:
▪ A = Activity, L = Link
▪ 6 serial Interfaces
CP1, CP2, CP3, CP4, CP5,
CP6
Per Interface 2 LEDs for:
▪ TxD, RxD
▪ 3 serial peripheral busses(SPB)
▪ CP1, CP2
▪ Backplane connector
▪ USB-Interface for Configuration
▪ 128MB Ram + 4GB SD-card
▪ CPU: ARM cortex A8,
AM3352, 800 MHz
▪ Power consumption ~3.1 W
© ABB Group
RTU500 Series Training R12
04_1_System_Concept_Rack
23
Communication Units, 560CMR01
560CMR01
▪ 2 Ethernet interfaces
E1, E2
10 / 100 Mbit/s
Per interface 2 LEDs for:
▪ A = Activity, L = Link
▪ 2 serial Interfaces
CP1, CP2
Per Interface 2 LEDs for:
▪ TxD, RxD
▪ 1 Serial Peripheral Bus (SPB)
▪ Backplane connector
▪ USB-Interface for Configuration
▪ 128MB Ram + 4GB SD-card
▪ CPU: ARM cortex A8,
AM3352, 800 MHz
▪ Power consumption ~3.1 W

© ABB Group
RTU500 Series Training R12
04_1_System_Concept_Rack
24
Communication Units, 560CMR02 / 560CMR01
RTU System Bus 10/100 MB LAN Only 560CMR02:
CP
E1 E2 3 4 5 6 Serial Interfaces
RS232 / RS485
RTU Bus
Ethernet
Controller Controller USART ▪ CP = communication port

MPU Processor Bus ▪ USART = Universal


Synchronous / Asynchronous
MPU RAM /
Flash Memory
Receiver / Transmitter

RAM ▪ MPU = Main processing unit

PBP
Backplane: SPB ▪ PBP = Peripheral bus
processor
UART = Universal
CP1 CP2 Serial Interfaces Asynchronous Receiver /
RS232 / RS485 Transmitter
or SPB = Serial peripheral bus /
I/O-Bus
© ABB Group
Serial Peripheral Bus
RTU500 Series Training R12
04_1_System_Concept_Rack
25
Communication Units, 560CMU05 R0002
560CMU05
▪ 2 Ethernet interfaces
E1, E2
10 / 100 Mbit/s
Per interface 2 LEDs for:
▪ A = Activity, L = Link
▪ 4 serial Interfaces
CP1, CP2, CPA, CPB
Per Interface 2 LEDs for:
▪ TxD, RxD
▪ Serial Peripheral Bus (SPB)
may be configured on:
▪ CPA, CPB, Backplane
connector via CPB
▪ 64MB Ram + 128MB CF-Card
▪ CPU: AMD Élan520, 133Mhz,
base: Intel Pentium 80586
▪ Power consumption 11W

© ABB Group
RTU500 Series Training R12
04_1_System_Concept_Rack
26
Communication Units, 560CMU05 R0002
RTU System Bus 10/100 MB LAN CP Communication Port
1 2 Serial Interfaces
RS232 / RS485
RTU Bus
Ethernet
Controller Controller USART ▪ CP = communication port

MPU Processor Bus ▪ USART = Universal


Synchronous / Asynchronous
MPU RAM /
Flash Memory
Receiver / Transmitter

RAM ▪ MPU = Main processing unit

PBP ▪ PBP = Peripheral bus


Serial Interfaces processor
RS232 / RS485 UART = Universal
A B Asynchronous Receiver /
CP or Transmitter
Serial Peripheral Bus SPB = Serial peripheral bus /
I/O-Bus
© ABB Group
RTU500 Series Training R12
04_1_System_Concept_Rack
27
Communication Units, 560CMU02 R0002
560CMU02
▪ 2 Ethernet interfaces
E1, E2
10 / 100 Mbit/s
Per interface 2 LEDs for:
▪ A = Activity, L = Link
▪ 2 serial Interfaces
CP1, CP2
Per Interface 2 LEDs for:
▪ TxD, RxD
▪ Serial Peripheral Bus (SPB)
may be configured on:
▪ Backplane connector
▪ 64MB Ram + 128MB CF-card
▪ CPU: AMD Élan520, 133Mhz,
based on Intel Pentium 80586
▪ Power consumption 11W

© ABB Group
RTU500 Series Training R12
04_1_System_Concept_Rack
28
Communication Units, 560CMU02 R0002
RTU System Bus 10/100 MB LAN CP
1 2 Serial Interfaces
RS232 / RS485
RTU Bus
Ethernet
Controller Controller USART ▪ USART = Universal Synchronous /
Asynchronous Receiver /
MPU Processor Bus Transmitter

MPU RAM /
Flash Memory
▪ MPU = Main processing unit
RAM

PBP ▪ PBP = Peripheral bus processor


SPB ▪ SPB = Serial peripheral bus
I/O-Bus
Backplane only
Internal: CPB

© ABB Group
RTU500 Series Training R12
04_1_System_Concept_Rack
29
Communication Units
▪ The serial peripheral bus (SPB) on CP B may be routed to
the back-connector (depending on the system
configuration)

560CMU05 560CMU02

Peripheral Peripheral
Bus Bus
Processor Processor
(PBP) (PBP/SLI
CP A

CP B

© ABB Group
RTU500 Series Training R12
04_1_System_Concept_Rack
30
Communication Units, 560CMU05 R0002
▪ Rules for configuration of communication protocols on
the serial interfaces CPA/CPB:

▪ If one of the two interfaces CPA or CPB is configured for the


serial peripheral bus (SPB), the other interface is configured
automatically also as SPB

▪ All UART-character based protocols can be mixed on CPA/CPB

▪ Non-UART character based protocols cannot be mixed:


• Only one type of Non-UART character based protocol types can
be configured on both interfaces at the same time

▪ Synchronous communication protocols cannot be configured

© ABB Group
RTU500 Series Training R12
04_1_System_Concept_Rack
31
Communication Units, 560CMU05 R0002
560CMU05
Possible:
ERR

The SPB always


E1

E2
uses both interfaces
A E 1 CPA/CPB
B E 2

SPB SPB

560CMU05
Possible: 560CMU05
Not possible:
ERR ERR

Modbus, SPAbus To mix two


E1

E2
are both UART E1

E2
non-UART
A E 1 character based A E 1 character
B E 2 protocols B E 2 based
protocols
Modbus SPAbus I21 Hitachi
© ABB Group
RTU500 Series Training R12
04_1_System_Concept_Rack
32
Communication Units, Migration of CPUs
▪ There is a migration facility in RTUtil500:
Release 10: 560SLI02 and 560ETH0x no more
supported
Release 11: 560CMU04 no more supported
Release 12: Replace 560CMU05 by 560CMR02, replace
560CMU02 by 560CMR01

A CMU can be migrated to Firmware Release 10/11 only


one time. But the step back to an older release is always
possible.
© ABB Group
RTU500 Series Training R12
04_1_System_Concept_Rack
33
RTU560 Product Line – System Concept

▪ Cabinets and Racks


▪ Power Supply Units
▪ Communication Units
▪ Bus Connection Units
▪ System Structure
▪ Assembly Options
▪ Number of Data Points

© ABB Group
RTU500 Series Training R12
04_1_System_Concept_Rack
34
Bus Connection Units
▪ A Bus Connection Unit (BCU) 560BCU0x provides
the RTU500 system bus (in one or two racks).

▪ The system bus is the internal communication between


the communication units of the RTU560 product line

BCU type Used in rack type Connects …


560BCU04 560MPR03 up to 8 (16) CMUs
560BCU05 560SFR02 up to 8 (16) CMUs
560BCU02 *) 560MPR01*) up to 2 CMUs

*) = phased out in Q1/2018

© ABB Group
RTU500 Series Training R12
04_1_System_Concept_Rack
35
Bus Connection Unit 560BCU04 (rack 560MPR03)
▪ One Basic Module with connection to the back plane of the rack
▪ 1 … 7 Extension Modules (with termination on the last one)
▪ Ordering Information:
• 1 Basic Module, 1 Extension Module with Termination (R0001)
• 10 Extension Modules without Termination (R0002)
• Termination only (R0003)
Basic Module
R0001

Extension
Module R0001
with termination Termi- Terminination
nation Module R0003
© ABB Group
RTU500 Series Training R12
04_1_System_Concept_Rack
36
Bus Connection Unit 560BCU04
Mounting of the 560BCU04 in the rack 560MPR03

RTU500 System Bus

TSO
To the rack

TSI
WRN
ALR

Extension SPB
with termination Extensions Basic
© ABB Group
RTU500 Series Training R12 Module
04_1_System_Concept_Rack
37
Bus Connection Unit 560BCU05 (rack 560SFR02)
▪ One Basic Module with connection to the back plane of the rack.
▪ Termination resistor located on the basic module
▪ 1 … 8 Adaptor Cables
▪ Ordering Information:
• 1 Basic Module with 2 cables (R0001)
• 10 Extension Cables (R0002)
• Termination only (R0003)

TSI, TSO, ALR, WAR SPB


RTU500 System Bus

Basic Module

Adaptor Cables

© ABB Group
RTU500 Series Training R12
04_1_System_Concept_Rack
38
Bus Connection Units – Additional functions

▪ (ALR) Relay output for system alarm


• External contact, set by the software of the CMUs
▪ (WRN) Relay output for system warning
• External contact, set by the software of the CMUs
▪ (TSI) Time synchronization input
• Isolated input for an external minute interrupt signal
▪ (TSO) Time synchronization output
• 24 V DC filtered output for the minute interrupt signal
▪ Watch dog supervision
• Timer, which must be retriggered by the software cyclically
▪ Supervision of a redundant pair of power supply units by
the communication units (560BCU04 / 560BCU05 only)

© ABB Group
RTU500 Series Training R12
04_1_System_Concept_Rack
39
Bus Connection Units – error signalization
▪ System Alarm:
▪ Severe error in the system, which affects the functionality of ( a
part of ) the system.
▪ Examples:
• Missing configuration data
• missing CMU
• PLC not running, …

▪ System Warning:
▪ Smaller error in the system, which influences the functionality of
a part of the system.
▪ Examples:
• Faulty / missing input/output device
• live zero violation, …
▪ In case of an alarm, also the warning relay is activated.
© ABB Group
RTU500 Series Training R12
04_1_System_Concept_Rack
40
RTU560 Product Line – System Concept

▪ Cabinets and Racks


▪ Power Supply Units
▪ Communication Units
▪ Bus Connection Units
▪ System Structure
▪ Assembly Options
▪ Number of Data Points

© ABB Group
RTU500 Series Training R12
04_1_System_Concept_Rack
41
Product line RTU560 – System Structure
560CMR02
560CMR01
Communication Units .... 16 hosts
560CMU05 Host -
RTC CMU CMU 560CMU02
E1, E2, Communi
CPx cation
Max. 16 CMUs per RTU
CPx 32 sub-
or Backplane device-
lines
System Bus (560BCUxx)
1 or 2 system-racks, 32 devices
max. 8 CMUs per rack, rack-address {0,1} per subline

32 Bus-Segments
I/O-Boards .... 7 Racks per Segment
rack-address {1...7} Number of datapoints
18 / 17 I/O-Boards per Rack (including sublines + PLC)
by license:
50, 250, 750, 5.000

I/O-Bus : Serial Peripheral Bus - SPB : RS485

© ABB Group
RTU500 Series Training R12
04_1_System_Concept_Rack
42
Product Line RTU560, I/O-Boards and Datatypes
Type Board name Datatype Explanation No. of Bits
SPI Single Point Input 1
DPI Double Point Input 2
DI 23BE23 DMI Digital Measurement Input 8, 16
Digital Input 560BIR01 STI Step position Input 8
BSI Bit String Input 8, 16, (32)
ITI Integrated Total Input 1
SCO Single Command Output 1
DCO Double Command Output 2
DO 23BA20
RCO Regulation Command Output 2
Digital Output 560BOR01
DSO Digital Set point Output 8, 16
BSO Bit String Output 1, 2, 8, 16

AI 23AE23 AMI Analogue Measurement Input


Analog Input 560AIR01 MFI Measurement Floating-point Input
AO ASO Analogue Set point Output
23AA20
Analog Output FSO Floating Value Set point Output

© ABB Group
RTU500 Series Training R12
04_1_System_Concept_Rack
43
RTU560 Product Line – System Concept

▪ Cabinets and Racks


▪ Power Supply Units
▪ Communication Units
▪ Bus Connection Units
▪ System Structure
▪ Assembly Options
▪ Number of Data Points

© ABB Group
RTU500 Series Training R12
04_1_System_Concept_Rack
44
RTU560 Assembly options – Example 1
▪ 1 or 2 power supply unit
▪ Up to 8 communication units
▪ Up to 18/17 slots for I/O modules (and others)
▪ Bus connection unit 560BCU04/05
▪ Example: Rack with one module 560CMU05
▪ Max. 2 I/O-bus segments possible
560PSU02 23BE23 23BE23 23BE23 23BA20 23BA20 23AE23 23AE23 23AE23 560CMU05

24 V ST ST ST ST ST ST ST ST ERR
PST PST

OFF
1 2 3
5V
1 9 1 9 1 9

4
2 10 2 10 2 10
3 11 3 11 3 11 E1
UE + 4 12 4 12 4 12
5 13 5 13 5 13 E2
UE -
6 14 6 14 6 14
PE 7 15 7 15 7 15
8 16 8 16 8 16 A 1
E
ON

CO CO B E 2
OFF

560SFR02A = 560SFR02 + 560BCU05


© ABB Group
560MPR03A = 560MPR03 + 560BCU04
RTU500 Series Training R12
04_1_System_Concept_Rack
45
RTU560 Assembly options – Example 2
▪ 1 or 2 power supply units
▪ No communication unit
▪ No bus connection unit
▪ Up to 18/17 slots for I/O
▪ Slot 19 remains empty

560PSU02 23BE23 23BE23 23BE23 23AE23 23AE23 23AE23 23BA20 23BA20

24 V ST ST ST ST ST ST ST ST
PST PST

OFF
1 2 3
5V
1 9 1 9 1 9

4
2 10 2 10 2 10
3 11 3 11 3 11
UE + 4 12 4 12 4 12
5 13 5 13 5 13
UE -
6 14 6 14 6 14
PE 7 15 7 15 7 15
8 16 8 16 8 16
ON

CO CO

OFF

560SFR02
© ABB Group
560MPR03
RTU500 Series Training R12
04_1_System_Concept_Rack
46
RTU560 Assembly options – Example 3
▪ System with Extension Rack
560PSU01 560PSU01 23BE23 23BE23 23BE23 23BE23 23BE23 23BE23 23BE23 23AE2 23AE2 560CMU05 560CMU05 560CMU05
3 3
24 V 24 V ST ST ST ST ST ST ST ST ST ER ER ER
R R R

OFF
1 2 3
5V 5V
1 9 1 9 1 9 1 9 1 9 1 9 1 9

4
2 10 2 10 2 10 2 10 2 10 2 10 2 10
3 11 3 11 3 11 3 11 3 11 3 11 3 11 E1 E1 E1
UE + UE + 4 12 4 12 4 12 4 12 4 12 4 12 4 12
5 13 5 13 5 13 5 13 5 13 5 13 5 13 E2 E2 E2
UE - UE - 6 14 6 14 6 14 6 14 6 14 6 14 6 14
PE PE 7 15 7 15 7 15 7 15 7 15 7 15 7 15
8 16 8 16 8 16 8 16 8 16 8 16 8 16 A E 1 A E 1 A E 1
ON ON

B E 2 B E 2 B E 2
OF OF
F F

560SFR02A, 560MPR03A
560PSU01 560PSU01 23BE23 23BE23 23BE23 23BE23 23BE23 23AE2 23AE2 23AE2 23AE2 23AE2 23AE2 23BA2 23BA2 23BA2
3 3 3 3 3 3 0 0 0

Serial Peripheral Bus


24 V 24 V ST ST ST ST ST ST ST ST ST ST ST ST ST ST
PST PST PST

OFF
1 2 3
5V 5V
1 9 1 9 1 9 1 9 1 9

4
2 10 2 10 2 10 2 10 2 10
3 11 3 11 3 11 3 11 3 11
UE + UE + 4 12 4 12 4 12 4 12 4 12
5 13 5 13 5 13 5 13 5 13
UE - UE - 6 14 6 14 6 14 6 14 6 14
PE PE 7 15 7 15 7 15 7 15 7 15
8 16 8 16 8 16 8 16 8 16
ON ON
CO CO CO
OF OF
F F

© ABB Group
RTU500 Series Training R12 560SFR02, 560MPR03
04_1_System_Concept_Rack
47
RTU560 Assembly options – Example 4
▪ 1 or 2 power supply unit
▪ Up to 8 communication units
▪ Up to 18/17 slots for I/O
▪ Bus connection unit 560BCU04/05
▪ Example: two modules 560CMU02 R0002
▪ Only ONE I/O-bus segment possible
560PSU01 23BE23 23BE23 23BE23 23BE23 23BE23 23BE23 23BE23 23AE23 23AE23 23AE23 23BA20 23BA20 23BA20 560CMU02 560CMU02
R0002 R0002

24 V ST ST ST ST ST ST ST ST ST ST ST ST ST ERR ERR
PST PST PST

OFF
1 2 3
5V
1 9 1 9 1 9 1 9 1 9 1 9 1 9

4
2 10 2 10 2 10 2 10 2 10 2 10 2 10
3 11 3 11 3 11 3 11 3 11 3 11 3 11 E1 E1
UE + 4 12 4 12 4 12 4 12 4 12 4 12 4 12
5 13 5 13 5 13 5 13 5 13 5 13 5 13
UE - E2 E2
6 14 6 14 6 14 6 14 6 14 6 14 6 14
PE 7 15 7 15 7 15 7 15 7 15 7 15 7 15
8 16 8 16 8 16 8 16 8 16 8 16 8 16 1 1
ON

CO CO CO 2 2

OFF

560SFR02A = 560SFR02 + 560BCU05


© ABB Group
560MPR03A = 560MPR03 + 560BCU04
RTU500 Series Training R12
04_1_System_Concept_Rack
48
RTU560 Assembly options – Example 5
▪ Pure communication rack
▪ Up to two communication racks possible
▪ 1 or 2 power supply units
▪ Up to 8 communication units
▪ Bus connection unit 560BCU04/05
▪ Example: max. 6 I/O-bus segments possible
560PSU02 560PSU02 560CMU02 560CMU02 560CMU05 560CMU05 560CMU05
R0002 R0002

24 V 24 V ERR ERR ERR ERR ERR

OFF
1 2 3
5V 5V

4
E1 E1 E1 E1 E1

UE + UE +
E2 E2 E2 E2 E2
UE - UE -
PE PE
1 1 A 1 A 1 A 1
E E E
ON ON
2 2 B E 2 B E 2 B E 2

OFF OFF

560SFR02A = 560SFR02 + 560BCU05


© ABB Group
560MPR03A = 560MPR03 + 560BCU04
RTU500 Series Training R12
04_1_System_Concept_Rack
49
RTU560 Product Line – System Concept

▪ Cabinets and Racks


▪ Power Supply Units
▪ Communication Units
▪ Bus Connection Units
▪ System Structure
▪ Assembly Options
▪ Number of Data Points

© ABB Group
RTU500 Series Training R12
04_1_System_Concept_Rack
50
Number of Data Points
▪ The number of process data points is calculated as
follows:
▪ Number of directly connected data points on I/O modules
▪ Number of ‘virtual data points’ as result of a ‘logic function’ or a
‘PLC function’
▪ Number of data points of subordinated devices

▪ The total number of data points is displayed by RTUtil


▪ Dialogue: Build RTU Files

© ABB Group
RTU500 Series Training R12
04_1_System_Concept_Rack
51
Further documentation
For additional information please see:
▪ RTU500 series Function Description, Release 12
Part 2, Rack Mounted Solutions

▪ RTU500 series Function Description, Release 12


Part 4, Hardware Modules

▪ RTU500 series Hardware Data Sheets

▪ RTU500 series Connections and Settings

© ABB Group
RTU500 Series Training R12
04_1_System_Concept_Rack