Multimeter

M1M 15
User manual

M1M 15 User manual 2CSG445071D0201


M1M 15 MULTIMETER USER MANUAL 3

Table of Contents

1.General information.............................................................................................. 5
1.1.Use and storage of the manual..............................................................................5
1.2.Copyright...................................................................................................................5
1.3.Liability disclaimer...................................................................................................5
1.4.General safety warnings.........................................................................................5
1.5.Cyber Security Disclaimer.......................................................................................6

2.Packaging contents............................................................................................... 7

3.Technical characteristics......................................................................................8
3.1.Description of the device.......................................................................................8
3.2.Main functionalities.................................................................................................8
3.3.Versions......................................................................................................................8
3.4.Overall dimensions..................................................................................................9
3.5.Technical data.........................................................................................................10

4.Installation........................................................................................................... 11
4.1.Assembly.................................................................................................................. 11
4.2.Disassembly............................................................................................................ 12
4.3.Wiring diagrams..................................................................................................... 13

5.Access to device.................................................................................................. 16
5.1.Display...................................................................................................................... 16
5.2.Buttons.................................................................................................................... 17
5.3.Data entry................................................................................................................18

6.First commissioning........................................................................................... 21
6.1.Password for the first use (PASS)....................................................................... 21
6.2.Wiring (WIR)............................................................................................................22
6.3.CT ratio (Ct P, Ct S)................................................................................................22
6.4.VT ratio (Vt P, Vt S)................................................................................................23

7.Configuration (CONF)..........................................................................................24
7.1.Unit (UNIT)...............................................................................................................25
7.2.Installation (INST)...................................................................................................27
7.3.I/O LED pulse (PUL) ..............................................................................................27
7.4.Communication (COM).........................................................................................28
4 M1M 15 MULTIMETER USER MANUAL

8.Data reading (READ)...........................................................................................30


8.1.Realtime (REAL)..................................................................................................... 30
8.2.Energy (ENRG)........................................................................................................32
8.3.Notifications (NOTF).............................................................................................33
M1M 15 MULTIMETER USER MANUAL 5

1.General information

1.1.Use and storage of the manual

Carefully read this manual and adhere to the indications described prior to using the device.

This manual contains all of the safety information, the technical aspects and the operations necessary to
ensure the correct use of the device and maintain it in safe conditions.

1.2.Copyright
The copyright of this manual is the property of ABB LV Installation Materials Co. Ltd. Beijing.
This manual contains texts, designs and illustrations of a technical nature which must not be disclosed
or transmitted to third parties, even partially, without the written authorisation of ABB LV Installation
Materials Co. Ltd. Beijing.

1.3.Liability disclaimer
The information contained in this document is subject to change without notice and cannot be
considered as an obligation by ABB LV Installation Materials Co. Ltd. Beijing. ABB LV Installation Materials
Co. Ltd. Beijing is not liable for any errors that may appear in this document. ABB LV Installation Materials
Co. Ltd. Beijing is not liable under any circumstances for any direct, indirect, special, incidental or
consequential damage of any kind that may arise from using this document. ABB LV Installation Materials
Co. Ltd. Beijing is also not liable for incidental or consequential damage that may arise from using the
software or hardware mentioned in this document.

1.4.General safety warnings

Non-adherence to the following points can lead to serious injury or death.

Use the suitable personal protection devices and adhere to the current regulations governing electrical
safety.
• This device must be installed exclusively by qualified personnel who have read all of the information relative
to the installation.
• Check that the voltage supply and measurement are compatible with the range permitted by the device.
• Ensure that all current and voltage supplies are disconnected prior to carrying out any controls, visual
inspections and tests on the device.
• Always assume that all circuits are under voltage until they are completely disconnected, subjected to tests
and labelled.
• Disconnect all of the power supply prior to working on the device.
• Always use a suitable voltage detection device to check that the supply is interrupted.
• Pay attention to any dangers and carefully check the work area ensuring that no instruments or foreign
objects have been left inside the compartment in which the device is housed.
• The correct use of this device depends on a correct manipulation, installation and use.
• Failure to adhere to the basic installation information can lead to injuries as well as damage to the electric
instruments or to any other product.
• NEVER connect an external fuse in by-pass.
• Disconnect all of the input and output wires before carrying out a dielectric rigidity test or an insulation test
on an instrument in which the device is installed.
• The tests carried out at a high voltage can damage the device’s electronic components.
• The device has to be installed inside a switchboard.
• Installation of M1M shall include a switch or circuit breaker for the connection of auxiliary supply and voltage
measurement. The switch or circuit breaker must be suitably located and easily reachable and must be
marked as the disconnecting device for M1M.
• Switch off circuit breaker or switch before disconnecting from the auxiliary supply and voltage
measurement or connecting to the auxiliary supply or voltage measurement.
6 M1M 15 MULTIMETER USER MANUAL

1.5.Cyber Security Disclaimer


M1M 15 multimeter is designed to be connected and to communicate information and data via a network
interface, which should be connected to a secure network. It is your sole responsibility to provide and
continuously ensure a secure connection between the product and your network or any other network
(as the case may be) and to establish and maintain appropriate measures (such as but not limited to
the installation of firewalls, application of authentication measures, encryption of data, installation
of antivirus programs, etc.) to protect the M1M 15 multimeter product, the network, its system and
interfaces against any kind of security breaches, unauthorized access, interference, intrusion, leakage
and/or theft of data or information. ABB LV Installation Materials Co. Ltd. Beijing and its affiliates are not
liable for damages and/ or losses related to such security breaches, unauthorized access, interference,
intrusion, leakage and/or theft of data or information.
Although ABB LV Installation Materials Co. Ltd. Beijing provides functionality testing on the products
and updates that we release, you should institute your own testing program for any product updates or
other major system updates (to include but not limited to code changes, configuration file changes, third
party software updates or patches, hardware change out, etc.) to ensure that the security measures that
you have implemented have not been compromised and system functionality in your environment is as
expected.
M1M 15 MULTIMETER USER MANUAL 7

2.Packaging contents

M1M Calibration Certificate

Contact us
 4.HMI 4.HMI
RTC
ABB S.p.A. RTC

2
Electrification Business
Viale dell’Industria, 18
20010 Vittuone (MI) Italy

July 2020
https://new.abb.com/low-voltage
Menu Icon
Warning! Installation by person 菜单 Test
with electrotechnical expertise Test Conditions图标 Test Description Accuracy
only. Result
警告! 只能由具有电气技术专业知识 Data Area
V1 V2 V3 I1 I2 I3

2CSG445090D1001
的人安装。 数据区
No. PF Results Limit
[V] [V] [V] [A] [A] [A]
QR Code for online Verification –
#1 230 230 230 6 6 6 1 -0,01% ±0,5% Passed
User Manual. Active energy (Import)
在线二维码
用户手册。
M1M 30 #2 230 230 230 0,9
Energy LED
0,9 0,9 1
Verification –
-0,01% ±0,5% Passed
1 2 3 4 图标 Active energy (Import)
© Copyright 2019 ABB S.p.A. All rights power meter
reserved. Specification subject to change Verification –
without notice. INSTALLATION MANUAL Button #3
Functions 230 230 230
按键 0,15 0,15
描述 0,15 1 -0,01% ±0,5% Passed

1
Access the menu and
Active energy (Import)
功率计 1 Menu 1 菜单 访问菜单和导航
navigation Verification –
安装说明书 2 Up Navigate in the#4 230
measurements
or change a configuration value
230
2 向上 230 导航变更和更改配置值
6 6 6 0,5 ind.
Active energy (Import)
-0,01% ±0,5% Passed
Navigate in the measurements
3 Down or change a configuration value 3 向下 导航变更和更改配置值 Verification –
#5 and 230 230 230 0,9 0,9 0,9 0,5 ind. -0,01% ±0,5% Passed
1.Packaging Content 1.包装清单 4 Enter Confirm an action
navigation 4 确认 确认配置和导航 Active energy (Import)
• A M1M product attached with a fixed clips • 一台配有安装夹的M1M Verification –
• A Installation Manual
• 安装说明书 #6 230 230 230 0,15 0,15 0,15 0,5 ind. -0,01% ±0,5% Passed
• A Calibration Certificate Active energy (Import)
• A pack of wiring terminals (power source, • 校准证书 5.First Commissioning 5.初始配置
• 接线端子 Verification –
voltage port, I/O ports and RS-485 port) #7
To start to use the analyzer it 230
is mandatory 230 230 1,5 1,5
初次使用M1M需要进行初始基本配置。 1,5 1 -0,01% ±0,5% Passed
to configure the basic setting (password, Active energy (Import)
type of network, CT ratio and VT ratio).
Verification –
5.1.Setting password #8 230 230 230 0,2 0,2 0,2 1 -0,01% ±0,5% Passed
2.Installation 2.设备安装 5.1.密码设置 Active energy (Import)
The password is composed by 4 numerical 设备密码是由四位数字组成. 通过向上键或向下
2.1.Assembly characters. In order to select each numerical 按键修改数值,使用确认键确定每一位密码.
Verification –
2.1.安装 #9 button230
character, it is necessary to use ‘Up’ 230 230 1,5 1,5 1,5 0,5 ind. -0,01% ±0,5% Passed
or ‘Down’ and confirm every selection with
Active energy (Import)
‘Enter’.
Verification –
92-0+0,8 #10 230 230 230 0,2 0,2 0,2 0,5 ind. -0,01% ±0,5% Passed
mm Default password is 0000. At Active energy (Import)
first use, the password shall be 默认密码是0000。若初始密码设置为
2 0000,则密码功能则被禁用。
defined. In order to#11
disable the Verification –
password, please enter 0000.
230 230 230 6 6 6 0,5 ind. -0,01% ±0,5% Passed
Active energy (Import)
1
Verification –
#12 230 230 230 0,9 0,9 0,9 0,5 ind. -0,01% ±0,5% Passed

92-0+0,8 mm
Active energy (Import)
Verification –
#13 230 230 230 0,15 0,15 0,15 0,5 ind. -0,01% ±0,5% Passed
Active energy (Import)
Verification –
#14 58 58 58 6 6 6 1 -0,01% ±0,5% Passed
Active energy (Import)
5.2.Type of network 5.2.连接类型设置 Verification –
#15 58 58 58 6 6 6 0,5 ind. -0,01% ±0,5% Passed
Select the type of network among the 请从下列连接类型中进行选择设置, Active energy (Import)
following ones
Verification –
3.Wiring Diagram 3.接线 #16 230 230 230 6 - 6 1 -0,01% ±0,5% Passed
Type Description 类型 描述 Active energy (Import)
3-Phase 4-wire network with 3CTs 三相四线 3个电流互感器 3N3T Three-phase, four-wire and three-transformer 3N3T 三相四线 3个互感器 Verification –
#17 230 230 230 0,9 - 0,9 1 -0,01% ±0,5% Passed
3 3T Three-phase, three-wire and three-transformer 3 3T 三相三线3个互感器 Active energy (Import)
3 2T Three-phase, three-wire and two-transformer 3 2T 三相四线2个互感器 Verification –
#18 230 230 230 0,15 - 0,15 1 -0,01% ±0,5% Passed
Active energy (Import)
3 1T Three-phase, three-wire and one-transformer 3 1T 三相三线1个互感器
Verification –
#19
1N1T Single-phase, two-wire and 230
one-transformer 230
1N1T 230 1个互感器
单相两线 6 - 6 0,5 ind. -0,01% ±0,5% Passed
Active energy (Import)
3-Phase 4-wire network with 1CT 三相四线 1个电流互感器
Verification –
#20 230 230 230 0,9 - 0,9 0,5 ind. -0,01% ±0,5% Passed
5.3.Current Transformer ratio 5.3.电流互感器设置 Active energy (Import)
1. Select the current transformer primary ratio 1. 选择电流互感器初级值,再按确认。
and confirm selection by ‘Enter’. Verification –
#21 230 230
2. 230 0,15 -
选择电流互感器次级值,再按确认。 0,15 0,5 ind. -0,01% ±0,5% Passed
2. Select the current transformer secondary Active energy (Import)
ratio and confirm selection by ‘Enter’

3-Phase 3-wire network with 3CTs 三相三线 3个电流互感器


1 This
2 Calibration Certificate may not be reproduced, in whole or in part,
without written permission of ABB

3-Phase 4-wire network with 3CTs and 3VTs 三相四线 3个电流互感器和3个电压互感器 5.4.Voltage Transformer ratio 5.4.变压器设置
1. Select the current transformer primary ratio 1. 选择变压器初级值,再按确认;
and confirm selection by ‘Enter’;
2. Select the current transformer secondary 2. 选择变压器次级值,再按确认。
ratio and confirm selection by ‘Enter’.

1 2
1-Phase 2-wire network with 1CT 单相两线 1个电流互感器

4
4

Packaging contents
1 Multimeter M1M 15
2 Installation manual
3 Calibration certificate
4 Installation accessories (removable terminals, fixing clips)

The number and type of removable terminals in the package varies according to the different versions.
8 M1M 15 MULTIMETER USER MANUAL

3.Technical characteristics

3.1.Description of the device


M1M series can help users accurately monitor energy efficiency while meeting their cost control
requirement.
Conforming to the international electric energy metering and monitoring accuracy standards, all M1M
series products are perfectly suitable for ABB electrical systems and solutions.

3.2.Main functionalities

Real-time Measurement
TRMS Current •
TRMS Voltage •
Frequency •
Active, Reactive and Apparent Power •
Power Factor •

Energy
Active, Reactive and Apparent Energy •

3.3.Versions

Product Name I/O Communication protocol


M1M 15 / /
M1M 15 MODBUS / Modbus RTU
M1M 15 MULTIMETER USER MANUAL 9

3.4.Overall dimensions

65,8 mm 19,2 mm
96 mm

90 mm
96 mm 85 mm

IEC 61554

92 -0+0,8 mm
92 -0+0,8 mm
10 M1M 15 MULTIMETER USER MANUAL

3.5.Technical data

Auxiliary power supply


Voltage 100-230 V AC/DC ±15%
Frequency 50 - 60Hz ±5%
Power consumption 5VA max
Installation category CAT III 300V class per IEC 61010-1 edition 3
Protection fuse T1 A-277 VAC

Measurement Accuracy
IEC 61557-12 IEC 61557-12 PMD/S/K55/1
Active energy IEC 61557-12 Class 1
Reactive energy IEC 61557-12 Class 2
Active power IEC 61557-12 Class 1
Reactive power IEC 61557-12 Class 2
Apparent power IEC 61557-12 Class 2
Voltage IEC 61557-12 Class 1
Current IEC 61557-12 Class 1
Frequency IEC 61557-12 Class 0.1

Voltage Measurement inputs


Voltage Range 80-265 VAC(L-N)
Type Single-phase, three-phase (3P, 3P+N)
Rated frequency 50Hz or 60Hz
Protection fuse T1 A-277 VAC

Current measurement inputs


Current input mode Indirect insertion with CT
Rated current at secondary side of CT 1A or 5A
Range without accuracy derating 50mA-6A

Mechanical properties
Overall Dimensions 96 mm x 96 mm x 85 mm
Front: IP51
IP degree of protection (IEC 60529)
Enclosure: IP20
Max. weight 315g

Climatic conditions
Operating temperature -5 to 55 °C (K55 IEC61557-12)
Storage temperature -25 to 70 °C (K55 IEC61557-12)
It is prohibited to use in the environment containing H2S, Cl2, NH3
Environment
and other harmful gases

Communication protocol
Modbus RTU M1M 15 MODBUS
Communication interface RS485 with optical isolation
Baud rate 9.6, 19.2, 38.4, 57.6, 115.2 kbps
Parity number Odd (1 stop bit), Even (1 stop bit), None (1 or 2 stop bits)
Address 1-247
Connector 3 pole terminal

Standards
Power metering and monitoring devices
IEC 61557-12
(PMD)
EMC IEC 61326-1
Electrical safety IEC 61010-1
M1M 15 MULTIMETER USER MANUAL 11

4.Installation

4.1.Assembly

92-0+0,8
mm
IEC 61554

92-0+0,8 mm

2 3
12 M1M 15 MULTIMETER USER MANUAL

4.2.Disassembly

92-0+0,8
mm
IEC 61554

2
92-0+0,8 mm
M1M 15 MULTIMETER USER MANUAL 13

4.3.Wiring diagrams
The operations to carry out for the correct connection of the device, based on the type of electric line
available, are described in this section.

The installation and the cabling of the device must be carried out by qualified personnel.

Danger of electrocution, burning and electric arc.


Use the personal protection devices suitable to adhere to the current regulations governing electrical safety.
Prior to carrying out any connections check the sectioning of the electric supply with the voltage detection
device.

• M1M 15 MODBUS

• M1M 15
14 M1M 15 MULTIMETER USER MANUAL

Type of network
M1M 15 can be used on different type of network (please refer to chapter “7.Configuration (CONF)” for
the configuration on the device).
According to the type of network that has been chosen, the parameters visualized on the device HMI
change.
Below the wiring diagrams are shown:

• 3-phase 4-wire network with 3CTs (3N3T)

• 3-phase 3-wire network with 3CTs (3 3T)

• 3-phase 3-wire network with 2CTs (3 2T)

• 3-phase 3-wire network with 1CT (3 1T)


M1M 15 MULTIMETER USER MANUAL 15

• 1-phase 2-wire network with 1CT (1N1T)


16 M1M 15 MULTIMETER USER MANUAL

5.Access to device

This chapter gives a detailed introduction of the device’s HMI, including how to read data and configure
related parameters.

5.1.Display

Front panel
The front panel of M1M is shown below:

2
3

Operator panel
1 Display
2 Function buttons
3 Energy pulse LED
4 LEDs for indication of parameters
M1M 15 MULTIMETER USER MANUAL 17

Display content
Display is divided into 4 different areas, as shown in the figure below:

N Area Description
1 Parameters Indication of electrical parameters
2 Measurements Specific measured value
3 Magnitude Indication of unit magnitude (k, M) or total parameters (Tot)
4 Notifications Indication of warnings and errors

5.2.Buttons
Each M1M is provided with 4 pushbuttons as per below picture:

2 3

1 4

Functions of each button might change according to the displayed page on the meter. See below for a
complete description:

# Button Functions
1 Menu Go to the main menu; go back; or return to the default screen
Page up and enter numerical value in cyclic and ascending way and decimal point;
2 Up and when pressed continuously, page is up continuously or numerical value ascends
automatically
Page down and move to higher-order numerical value and confirm the decimal
3 Down point; and when pressed continuously, page is down or numerical value moves to
higher order continuously until zero clearing
Go to the next menu, confirm the numerical value or option input, and read the
4 Enter
average of the parameter measurements
18 M1M 15 MULTIMETER USER MANUAL

5.3.Data entry
Some of the pages require the entry of numerical characters (0-9) in the Configuration mode. In these
cases the display will show an active field identified by a flashing number.

Data entry procedure


The data entry procedure is as follows:

1
x5

1. Press “Up” to increase the numerical characters from 0 to 9, until the required character is obtained.
• How to: Go back to a previous number

x8

If during the data entry the desired number is exceeded by mistake, it is needed to increase the displayed
number until data entry starts again from 0.

• Add a second digit

2
x1

2. Press “Down” to move the cursor in order to add a second digit to the number;
M1M 15 MULTIMETER USER MANUAL 19

• How to: Enable the comma

x10

Some device configurations allow entering the comma. Comma can be displayed by increasing the
number with “Up” , after character 9 and before data entry starts again from character 0.

• Confirm number

1
x5

2
x1

3
x1

3. Repeat the operations described in steps 1 and 2 until the desired number is obtained, press “Enter”
to confirm the number.
20 M1M 15 MULTIMETER USER MANUAL

• How to: Enter the magnitude

Some device configurations allow entering the magnitude (k, M).


Once the number has been entered as after step 3, keys “Up” and “Down” allow enabling the magnitude
“K” (kilo) or not. Press “Enter” to confirm the magnitude. Follow the steps below when the buttons are
used to enter numbers:

x1

x1
M1M 15 MULTIMETER USER MANUAL 21

6.First commissioning

When the device is started up for the first time, the basic parameters need to be set, and the wizard
program will guide the user to configure the device by following the steps below:

First commissioning wizard

Set password (PASS)

Set Wiring (WIR)

Set CT ratio (CT)

Set VT ratio (VT)

6.1.Password for the first use (PASS)


A password can be set by the user to protect the Configuration menu and avoid any unwanted
modification to the device settings.

At the first use it is mandatory to define a password.

The password comprises 4 digits, and Button “Up” and Button “Down” can be used to enter numbers,
and Button “Enter” can be used to confirm the user’s settings and Button “Menu” used to drop the user’s
settings.

In order to disable the password, please set the new password as 0000.

The password can be changed this way:


1. go to CONF/UNIT/PASS,
2. press “Enter” to start changing password.
22 M1M 15 MULTIMETER USER MANUAL

6.2.Wiring (WIR)
In order to configure the type of network it is needed to choose one of the available options according to
the installation conditions.

CONF INST WWIR

1. Scroll the list of fields “Up” or “Down”


2. Select one option by pressing “Enter”

Type Description
3N3T Three-phase, four-wire and 3 CTs
3 3T Three-phase, three-wire and 3 CTs
3 2T Three-phase, three-wire and 2 CTs
3 1T Three-phase, three-wire and 1 CT
1N1T Single-phase, two-wire and 1 CT

6.3.CT ratio (Ct P, Ct S)


M1M is capable to measure current only via indirect connection by means of current transformers
CTs.../5A or .../1A.
It is needed to set the transformation ratio of the installed current transformers.
In order to configure the current transformers ratio it is possible to set the primary (Ct P) and secondary
(Ct S) of the current transformer.

CONF INST CT P CT S

1. When the number of the primary CT is set, press Button


“Enter”
2. Use Button “Up” and Button “Down” to select the
magnitude
3. Press button “Enter” to confirm the setting of the
primary CT
4. Press button “Down” to go to the setting of the
secondary CT
5. Select the secondary CT among 1 and 5A
6. Press button “Enter” to confirm the setting of the
secondary CT
M1M 15 MULTIMETER USER MANUAL 23

6.4.VT ratio (Vt P, Vt S)


M1M is capable to measure voltage via direct connection up to 265 VL-N, or via indirect connection by
means of voltage transformers.
In order to configure the voltage transformer ratio it is needed to enter manually the values of both
primary (Vt P) and secondary (Vt S).

CONF INST UT P UT S

1. When the number of the primary VT is set, press Button


“Enter”
2. Use Button “Up” and Button “Down” to select the
magnitude
3. Press button “Enter” to confirm the setting of the
primary VT
4. Press button “Down” to go to the setting of the
secondary VT
5. When the number of the secondary VT is set, press
Button “Enter”
6. Press button “Enter” to confirm the setting of the
secondary VT

In case of direct insertion without voltage transformers, please set VT ratio as 230/230 (default)
24 M1M 15 MULTIMETER USER MANUAL

7.Configuration (CONF)

When entering the CONF section, in order to change any configuration of the device, it is mandatory
to enter the password. The password is valid as soon as the user remains in the Configuration section
and for max. 5 minutes of idle. After quitting the Configuration section, it is needed to enter again the
password.
In order to read only the configurations, it is possible to simultaneously press “Enter” and “Up” buttons.
In case of wrong entering of the password for three times in a row, user will have to wait for 5 minutes
until he can enter the password once again.
CONF includes the following menus:

Menu Description
UNIT Settings related to the device itself
INST Settings related to the installation conditions
I/O Settings related to the pulse LED
COMM Settings related to the embedded communication protocols of the M1M version
M1M 15 MULTIMETER USER MANUAL 25

7.1.Unit (UNIT)
UNIT includes the following sub-menus:

Menu Description
PASS Change the existing password
REST Full or partial reset of the meter
INFO Device information

Modify password (PASS)


PWD shares the same interface and setting way with password setting. For details, see “6.1.Password for
the first use (PASS)”.

CONF UNIT PASS

Reset (REST)

CONF UNIT REST

If the user selects “YES” and presses Button “Enter”, all parameters will be reset, i.e. restoring all
parameters to their factory default.

RESET sub-menu includes the following pages:

Menu Description
RESET FACT Reset factory settings
RESET ENRG Clear energy value
RESET NOTF Clear notifications

• RESET FACT

Reset Factory settings restores parameters to default values, including communication parameters,
notifications, etc.

CONF UNIT REST FACT

• RESET ENRG

Reset energy will clear the energy to 0.

CONF UNIT REST ENRG


26 M1M 15 MULTIMETER USER MANUAL

• RESET NOTF

All notifications will be cleared after the Reset Notification, including alarms, warnings, and faults.

CONF UNIT REST NOTF

If the user selects “YES” and presses Button “Enter”, all parameters will be reset, i.e. restoring all
parameters to their factory default.

Device info (INFO)


INFO includes firmware version, product model and peripheral functions, etc.

CONF UNIT INFO

Menu Description
APP Firmware version
CNFC Parameter configuration counter
15 Product model and peripheral functions
M1M 15 MULTIMETER USER MANUAL 27

7.2.Installation (INST)
INST includes the following sub-menus:

Menu Description
WIR Set the type of network and number of wires on which the device is installed
CT Set the ratio of current transformers for current measurement
VT Set the ratio of voltage transformers for voltage measurement, if any

The three items must be set during the first startup. For details, see “6.2.Wiring (WIR)”, “6.3.CT ratio (Ct
P, Ct S)” and “6.4.VT ratio (Vt P, Vt S)”.

7.3.I/O LED pulse (PUL)


I/O includes selection of energy variables of panel LED indicator and energy pulse ratio.

CONF IO PUL

The output energy variables of LED indicator include:

Electricity Variable Description


PEN Active energy
QEN Reactive energy
OFF Off

The setting range of pulse output ratio is: 0.001 ... 9999. The formula guiding this parameter setting is:
1 pulse = X Wh (varh/VAh)
X is the set number.
28 M1M 15 MULTIMETER USER MANUAL

7.4.Communication (COM)
Communication menu allow to set all the parameters related to the communication protocol available
for a specific product version. The embedded communication protocol varies according to the different
product versions. Please refer to “3.3.Versions” for the details on the embedded communication
protocols.
Based on product version following configuration menu is available:

Communication Protocol Parameter Description


ADDR Bus address
Modbus RTU BAUD Baud rate
BYTE Byte format

Modbus RTU (M1M 15 Modbus)

• Address (ADDR)

For the devices that adopt the Modbus RTU protocol, a unique address on the bus needs to be set.

CONF COMM ADDR

The address range is 1-247.

• Baud rate (BR)

BR represents data transmission baud rate. The higher the BR, the faster the data transmission.

CONF COMM BR

The optional Baud rates include 9600, 19200, 38400, 57600 and 115200 bps.
M1M 15 MULTIMETER USER MANUAL 29

• Byte format (BYTE)

BYTE comprises three parts – bits per byte, parity bit and stop bit.

CONF COMM BYTE

The optional byte formats include:

BYTE Description
8E1 8 even parity bits and 1 stop bit
8O1 8 odd parity bits and 1 stop bit
8N1 8 No Parity bits and 1 stop bit
8N2 8 No Parity bits and 2 stop bits
30 M1M 15 MULTIMETER USER MANUAL

8.Data reading (READ)

READ section allows to visualize all the parameters measured by M1M.


Specifically, it includes the following menus:

Menu Description
REAL Real-time measurements
ENRG Energy measurements
P QT Power quality
NOTF Notification message

8.1.Realtime (REAL)
REAL means the real-time data of the current electric energy, including the following items:

READ REAL
M1M 15 MULTIMETER USER MANUAL 31

REAL Description
Summary data, including total three-phase voltage, three-phase current and active
SUMM
power
VLN Phase voltage; when WIRI is selected as “3 3T”, “3 2T” or “3 1T”, this data is absent
VLL Line voltage
I Current
P Per phase active power; when WIRI is selected as “1N1T”, this data is absent
Q Per phase reactive power; when WIRI is selected as “1N1T”, this data is absent
S Per phase apparent power; when WIRI is selected as “1N1T”, this data is absent
PT Total active power
QT Total reactive power
ST Total apparent power
F Frequency
32 M1M 15 MULTIMETER USER MANUAL

8.2.Energy (ENRG)
READ ENRG

ENRG means the current energy data, including the following items:

ENRG Description
+PEN Total imported active energy
-PEN Total exported active energy
+QEN Total imported reactive energy
-QEN Total exported reactive energy
SEN Apparent energy

Power Quality (P QT)

READ P QT

PWQT means the current power quality data, including the following items:

PWQT Description
Power factor; when WIRI is selected as “3 3T”, “3 2T”, “3 1T” or “1N1T”, this data is
PF
absent
PFT Total power factor
M1M 15 MULTIMETER USER MANUAL 33

8.3.Notifications (NOTF)
NOTF includes the following items:

Menu Description
WAR Warnings list, related to installation conditions and device settings.
ERR Errors list, related to the device and to its self-diagnostics.

Warnings (WAR)
Warnings are generated when the device detects the operating conditions. When there is a WARN
notification, the warn indicator will be on; and when the user checks all warn messages, the warn
indicator will be off.
Warnings comprise warn count and specific warn message.

READ NOTF WAR

Warning Definition
VOL REVES Voltage Reverse
U1 MISS Voltage 1 Missing
U2 MISS Voltage 2 Missing
U3 MISS Voltage 3 Missing
I1 MISS Current 1 Missing
I2 MISS Current 2 Missing
I3 MISS Current 3 Missing
I1 REVES Current 1 Reverse
I2 REVES Current 2 Reverse
I3 REVES Current 3 Reverse
I12 REVES Current 1 with 2 Reverse
I23 REVES Current 2 with 3 Reverse
I31 REVES Current 3 with 1 Reverse
34 M1M 15 MULTIMETER USER MANUAL

Errors (ERR)
Errors are generated when the device detects operating conditions. When there is an ERROR notification,
the error indicator will be on and it will not be off until the error is solved.
Errors comprise error count and specific error message.

READ NOTF ERR

Error Definition
UNCONFIG EEPROM Missing
FWUP FAIL Firmware update Failure (only M1M with communication)
REPROVED Product not Approved
..........................................................................................................................................................................................................................................

..........................................................................................................................................................................................................................................

..........................................................................................................................................................................................................................................

..........................................................................................................................................................................................................................................

..........................................................................................................................................................................................................................................

..........................................................................................................................................................................................................................................

..........................................................................................................................................................................................................................................

..........................................................................................................................................................................................................................................

..........................................................................................................................................................................................................................................

..........................................................................................................................................................................................................................................

..........................................................................................................................................................................................................................................

..........................................................................................................................................................................................................................................

..........................................................................................................................................................................................................................................

..........................................................................................................................................................................................................................................

..........................................................................................................................................................................................................................................

..........................................................................................................................................................................................................................................

..........................................................................................................................................................................................................................................

..........................................................................................................................................................................................................................................

..........................................................................................................................................................................................................................................

..........................................................................................................................................................................................................................................

..........................................................................................................................................................................................................................................

..........................................................................................................................................................................................................................................

..........................................................................................................................................................................................................................................

..........................................................................................................................................................................................................................................

..........................................................................................................................................................................................................................................

..........................................................................................................................................................................................................................................

..........................................................................................................................................................................................................................................

..........................................................................................................................................................................................................................................

..........................................................................................................................................................................................................................................

..........................................................................................................................................................................................................................................

..........................................................................................................................................................................................................................................

..........................................................................................................................................................................................................................................

..........................................................................................................................................................................................................................................

..........................................................................................................................................................................................................................................

..........................................................................................................................................................................................................................................
ABB LV Installation Materials Co. Ltd. Beijing
Electrification Business Area
No. 17 Kangding Street , Beijing
Economic-Technological Development Area 100176