Application
The screw-type cold (WFK..) and hot water (WFW..) meters as well as cold water measuring
capsule (WMK..) The hot water meter (WMW..) is compact in design and used for measuring
physical cold or hot water consumption. The meter consists of a flow element and a totalizer.
Functions
The compact, single-jet impeller type meters (screw-type water meter) or multi-jet impeller
meter (measuring capsule water meter) is used for drinking water (cold or hot) and consists
of a flow element and a totalizer with LCD display.
In most cases, the single-pipe connection piece (EAT) is already present and embedded in
the masonry.
The totalizer can be rotated 360° on the fitting.
The flow measuring section on the screw-type water meter is made of brass and includes a
sieve at the input to collect larger dirt particles.
The water flows through the flow measuring section to drive the single-jet impeller. The
speed is sampled inductively via coils to provide low wear and long-term stable measuring.
Incorrect direction of flow is detected and indicated by an error message on the display.
The resulting volume is added up, displayed and can be transmitted via RF to a data
processing system. A long-life battery powers the processor for up to 10 years with 1 year of
reserve capacity.
Dry rotor
The water meter is a dry rotor with high pressure resistance.
This prevents the totalizer from exposure to the medium and protects against dirt. The
impeller has double bearings and the meter is protected against external magnetic influence
to guarantee the highest accuracy and security under all installation conditions.
Infrared interface
The water meters can be read out on site via optical close-range interface. The meter is read
out and configured with the WFZ.IRDA-USB optical reading head and associated
configuration software.
Communication
The water meter sends parallel AMR and walk-by data telegrams in S-mode or C-mode. You
can switch from S-mode to C-mode with the configuration software. RF is activated using the
WFZ.PS tool, ACT50 software or automatically after consuming 50 liters.
The AMR telegrams are automatically collected and saved by a network node WTT662.. or
WTT561... RF converter. The walk-by telegram can be collected during a walk by a the
mobile data logger. The customer can remotely read out all plant consumption data.
Leakage detection
The meter generates an alarm if detects flow (between 4 and 5 liters per hour depending on
the version) over a long period (factory setting of 24 hours).
A leak is indicated on the display by 'LEAC'. At the same time, an error message is
transmitted via RF.
The threshold value can be adapted to between 1 and 24 hours using the configuration
software.
2
Smart Infrastructure A6V12128928_en--_b
2022-08-16
Tampering
The meters are tested against electromagnetic and magnetic disturbances
per EN ISO 4064-2.
Function check
The flow is acquired continuously. The volume is displayed in real time. Any errors are
immediately displayed. Meters conducted the following self-tests:
● Leakage detection
● Reverse flow
● Error detection
Display
Water consumption is continuously cumulated. The current state is stored at 11:59 PM am
on the next due date.
The due date is factor set to 31.12, but can be configured with the ACT50 software.
The water meter calculates a checksum when saving the annual consumption. Self-readers
can notify the responsible office together with the read out on the due date to verify the
correct read out of the display. The stored due date remains in place for one year.
The water meter has a display loop. The following data can be read from the water meter's
displayr:
● Error code
● Error date
● Current total consumption
● Due date
● Due date value
● Checksum
● RF mode
3
Smart Infrastructure A6V12128928_en--_b
2022-08-16
The following parameters can be read out and/or configured using the configuration software
via the IrDA interface:
Device information
● Device name/password
● Current flow rate
Meter states
● Current meter state
● Reverse volume indication
● Last due date
● Meter state on last due date
● Next due date
● Maximum flow rate
● Leakage
Statistical values
● 13 monthly values
RF settings
● RF mode
● RF system
● Walk-by readout type (S-mode only)
● Walk-by transmission delay (S-mode only)
● Walk-by transmission timeframe (S-mode only)
● Walk-by transmission-free days (S-mode only)
Configuration:
General
● Mounting place
● Display loop
● Leakage detection
4
Smart Infrastructure A6V12128928_en--_b
2022-08-16
Due date
● Next due date
Device information
● Device name/password
RF settings
● RF mode
● RF system
● Walk-by readout type (S-mode only)
● Walk-by transmission delay (S-mode only)
● Walk-by transmission timeframe
● Walk-by transmission-free days (S-mode only)
Error messages
2 Operating hours expired Replace the device during the next service
appointment.
5
Smart Infrastructure A6V12128928_en--_b
2022-08-16
Technical design
0.1
0.01
0.001
0.0001
0.01 0.1 1 10
RF features in S-mode
The following values are transmitted by default in the RF telegram in S-mode:
Transmission delay (Offset) Time delay for sending out telegrams after the due date
Time delay for sending out telegrams after the start of the
month in days (Default = 0 days)
Transmission response
Walk-by telegrams Every 128 seconds, 10 hours a day (from 8:00 am to 6:00
pm)
6
Smart Infrastructure A6V12128928_en--_b
2022-08-16
RF features in C-mode
The following values are transmitted by default in the RF telegram in C-mode:
AMR telegrams Every 7.5 hours, 24 hours a day, 365 days a year
Walk-by telegrams Every 112 seconds, 10 hours a day (from 8:00 am to 6:00
pm)
365 days a year
Change of mode
You can switch between S-mode and C-mode any time with the help of the configuration
software and the infrared read head WFZ.IRDA-USB.
Type summary
Rated pressure PN 16
Display m3
7
Smart Infrastructure A6V12128928_en--_b
2022-08-16
Screw-on cold water meter in C-mode
8
Smart Infrastructure A6V12128928_en--_b
2022-08-16
Chilled water mechanical capsule counter in S-mode
9
Smart Infrastructure A6V12128928_en--_b
2022-08-16
Accessories
Spacer
Adapter pieces
10
Smart Infrastructure A6V12128928_en--_b
2022-08-16
Installation sets
Other
11
Smart Infrastructure A6V12128928_en--_b
2022-08-16
Single-pipe connecting piece JXF:WME.L22/OV/H WME.L22/OV/H
without cover, without seal,
without seal and plastering
aid, compatible with EAS and
VAS 2" systems, external
threading ¾" or soldered
connector, mounting length
130 mm
12
Smart Infrastructure A6V12128928_en--_b
2022-08-16
Other
Ordering
When ordering, please provide the quantity, description, type, and stock no.
Product documentation
Product inserts
Two flat gaskets, a seal with sealing wire, and mounting instructions in the following
languages are provided with the water meters:
Bulgarian, German, English, Finnish, French, Greek, Dutch, Italian, Croatian, Lithuanian,
Norwegian, Polish, Romanian, Russian, Slovakian, Slovenian, Spanish, Czech, Turkish, and
Hungarian.
Related documents such as the environmental declarations, CE declarations, etc., can be
downloaded from the following Internet address:
https://siemens.com/bt/download
13
Smart Infrastructure A6V12128928_en--_b
2022-08-16
Notes
Installation
Note the following:
● The water meter can be installed horizontally or vertically.
● Ensure there is sufficient space for installation.
● Horizontal installation is more accurate (i.e. a higher meteorological class).
● The meter must be easily accessible for readout.
● Settling paths are not required, neither upstream of nor downstream from the meter.
● Install the flow measuring section between 2 shutoff valves; the arrow must be in the
direction of the flow.
● During construction, install a spacer (screw-on meter) or cover (measuring capsule
meter).
● Thoroughly flush the plant prior to installing the meter.
● Comply with all local regulations and potable water permits on the use of water meters
(installation, sealing, etc.)
Device sealing
● After mounting the meter, seal all components to prevent tampering (observe national
regulations):
● Flow measuring section with fitting (inlet)
Maintenance
The meters are maintenance-free. Comply with all national calibration regulations.
Disposal
This symbol or any other national label indicate that the product, its
packaging, and, where applicable, any batteries may not be disposed of as
domestic waste. Delete all personal data and dispose of the item(s) at
separate collection and recycling facilities in accordance with local and
national legislation.
See Siemens disposal information for additional information.
Warranty service
The technical data are only guaranteed in connection with Siemens products listed in "Type
summary" and "Accessories". Siemens rejects any and all warranties in the event that third-
party products are used.
14
Smart Infrastructure A6V12128928_en--_b
2022-08-16
Technical data
Power supply
Display
Communication
Optical interface
● Protocol Per EN13757-2,3,7
RF:
Meterological class
● Horizontal R80 R80 R80
● Vertical R40 R40 R40
Response threshold (typical) l/h ca. 4-5 l ca. 4-5 l approx. 5-6
15
Smart Infrastructure A6V12128928_en--_b
2022-08-16
Cikd water/hot water screw-type meters
Measuring range
● Cold water meter WFK636.. 5 °C…≤30 °C
● Hot water meter WFW636.. 30 °C… ≤90 °C
Meterological class
● Horizontal R80
● Vertical R40
Measuring range
● Cold water meter WMK636.. 5 °C… ≤30 °C
● Hot water meter WMW636.. 30 °C… ≤90 °C
Housing type
Degree of protection
16
Smart Infrastructure A6V12128928_en--_b
2022-08-16
Ambient conditions
Environmental compatibility
Dimensions
See "Dimensions"
Housing material
Totalizer Plastic
Housing colors
Totalizer Transparent
17
Smart Infrastructure A6V12128928_en--_b
2022-08-16
Weight screw-type meter WF.636..
Device packed complete with inserts IST: 2.5 m3/h / G2": 0,279 kg
TE1: 2.5 m3/h / M62 x 2: 0,233 kg
A34: 2.5 m3/h / M77 x 15: 0,523 kg
18
Smart Infrastructure A6V12128928_en--_b
2022-08-16
Dimensions
69.7
64.4
26.4
37.2
73.9
75.1
G 3/4
G 3/4
7.9 7.9 43.6
80
69.7
64.4
26.4
37.2
73.9
75.1
G 3/4
G 3/4
110
19
Smart Infrastructure A6V12128928_en--_b
2022-08-16
Q3 = 4 m3/h, L = 130 mm
71
69.7
64.4
26.4
37.2
73.9
78.4
G1
G1
12 12 43.6
130
69.7 80
64.4 76.2
27
35.3
37.2
59.6
10.8
8.4
74.9
89.1
G2
64
70.1
20
Smart Infrastructure A6V12128928_en--_b
2022-08-16
Typ AL, connecting thread M77 x 1,5 mm"
77
70.8 80
64.4 76.2
27
35.3
38.3
49.8
11.9
82.8
96.1
18
45.3
37
24.3
13.3
50.7
62.8
71.6
M77x1.5
27
35.3
38.3
49.7
11.9
18
74.9
78.5
8.4
52.2
M62x2
71.2
21
Smart Infrastructure A6V12128928_en--_b
2022-08-16
Issued by
© Siemens Switzerland Ltd, 2020
Siemens Switzerland Ltd
Technical specifications and availability subject to change without notice.
Smart Infrastructure
Global Headquarters
Theilerstrasse 1a
CH-6300 Zug
+41 58 724 2424
www.siemens.com/buildingtechnologies
Document ID A6V12128928_en--_b
Edition 2022-08-16