Interviews Questions and Answers

The document contains questions and answers from two different interviews regarding electrical transformers, medium voltage distribution boards (MDB), cable types and installation, satellite TV systems (SMATV and MATV), and fiber optic cabling. Key details include: the maximum load for a 1500KVA transformer using heat exchanger water is 850KW; 11x1C 630mm XLPE/AWA cable connects a 1500KVA transformer to an MDB; XLPE, SWA, and PVC refer to types of cable insulation; the cable size for a 63A circuit breaker is 16mm2; the required breaker size for a 1600KVA transformer connected to an MDB is 2500A.
Copyright
© Attribution Non-Commercial (BY-NC)
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
525 views

Interviews Questions and Answers

The document contains questions and answers from two different interviews regarding electrical transformers, medium voltage distribution boards (MDB), cable types and installation, satellite TV systems (SMATV and MATV), and fiber optic cabling. Key details include: the maximum load for a 1500KVA transformer using heat exchanger water is 850KW; 11x1C 630mm XLPE/AWA cable connects a 1500KVA transformer to an MDB; XLPE, SWA, and PVC refer to types of cable insulation; the cable size for a 63A circuit breaker is 16mm2; the required breaker size for a 1600KVA transformer connected to an MDB is 2500A.
Copyright
© Attribution Non-Commercial (BY-NC)
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 4

interview dated 03/0

1- what is the transformers rating in Dubai?


500 KVA 21000 KVA 1500 KVA

what is the maximum load for 1500 KVA Transformer?

1200 KW

3- what is the maximum load if we are using HIELD WATER with this tra
850 KW

4- what is the connection between 1500 KVA transformer and MDB?


11* 1C 630mm XLPE/AWA

5- what is the type of insulation for the armoured cable?


XLPEL/SWA/PVC XLPE/AWA XLPE/SWA/LSOH

6- what is the meaning of that insulation type?


XLPE : cross linked poly ethelyen SWA : steel wired armoured

AWA : aluminum wired a

7- what is the cable size for 63A circuit breaker?


16mm

interview dated 15/06/2011 for


1- transformer 1600 KVA connected to MDB what the amper rating for the breacker? 1600 * 0.8 = 1280 KW 1280 = 3 * v* I * 0.8 = 3 * 400 * I * 0.8 I= 1280/544.25 2.351 * 1000 = 2351 A that is meaning the breacker 2500 A 2- what is the requirement to connect the cables to the MDB? CABLE GLAND

3- draw the cables on the cable tray and show the distance between the cables and between the tray

4- what is the requirement to install the cable trays? cable tray, c channel , threated rod , washer , fisher 5- what the type of screw which is using on the cable tray installation? mashroom screw. 6- what is the diffrence between SMATV and the MATV?

SMATV: sattalite master antena and it is using the dishes with the antena to connect to the multi swit MATV: only using the antenna 7- what is the diffrence between RF and IF system?

RF is meaning radio frequency system and it is connect the dishes polarrity to the RF end unit and it i IF is meaning intermediate frequency and it is connect the dishes polarity to the multiswitcher and it i 8-what is the type of cabling that using on SCS? cat5,cat5E,cat6,cat6A,fiber optic 9-what is the type of fiber optic cables? single mode , multi mode.

w dated 03/06/2011 at ETA company Al Quoze office

ER with this transformer?

r and MDB?

A : aluminum wired armoured

PVC : poly vinyle chloride

/06/2011 for Al Nasser Group KSA

nd between the tray edge?

nect to the multi switchers

e RF end unit and it is give limited no. of the channels multiswitcher and it is unlimited no of channels