Lecture18 UEE603 ProtectionSchemes
Lecture18 UEE603 ProtectionSchemes
then trip; else restrain. 𝜃 is the angle of transmission line. Based upon
legacy of electromechanical relays. 𝜆is also called
′torque angle
Converting primary impedance to secondary side
Converting primary impedance to secondary side
Numerical
.
Q1(a) Find out the value of Zn for a mho relay with torque angle 75o which has
to give 100% protection to a 50 km long 110 kV transmission line with
impedance 0.8 ohm per km and 80o.
Solution: ‘Mho relay' has two design parameters Zn, 𝝀.
The transmission line impedance Zline as on primary = 0.8x 50 = 40 ohm.
Since this value will not fall within the operating circle, the mho relay will not trip for this
load.
Principle of Differential Protection
• Differential protection is based on the fact that
any fault within an electrical equipment would
cause the current entering it, to be different,
from the current leaving it.
• Thus by comparing the two currents either in
magnitude or in phase or both we can determine
a fault and issue a trip decision if the difference
exceeds a predetermined set value.
Differential Protection for Transmission Line
• Fig. shows a short transmission line in which shunt charging can be neglected.
Then under no fault condition, phasor sum of currents entering the device is zero
i.e.
• Differential current under no fault condition is zero. However in case of fault in
the line segment AB, we get a non-zero differential current in presence of fault is
non-zero.
• On the other hand, if fault is on the bus (internal fault), this sum is
not zero.