CCIP HowToDetailing Jan22
CCIP HowToDetailing Jan22
10. Detailing
O Brooker BEng, CEng, MICE, MIStructE, MCS J Burridge MA CEng MIStructE MICE
Introduction
This chapter is intended for use by detailers to prepare reinforcement drawings
for projects that have been designed using Eurocode 21. It provides a summary
of the requirements of the Eurocode and simplifies them where appropriate.
Table 1
Notation for steel reinforcement
Cover
Type of steel reinforcement Notation The nominal cover should generally be specified by the designer
For f ≤ 12 mm, Grade B500A, Grade B500B or Grade B500C H and full details of how to determine this are given in Chapter 2. The
conforming to BS 4449:2005. For f > 12 mm, Grade B500B or nominal cover should be shown on the drawings and should refer to
Grade B500C conforming to BS 4449:2005
the reinforcement nearest to the surface of the concrete e.g. the links
Grade B500A conforming to BS 4449: 2005 A
in a beam.
Grade B500B or Grade B500C conforming to BS 4449: 2005 B
Also, the cover to the main bar should be at least equal to the size of
Grade B500C conforming to BS 4449: 2005 C
that bar, plus the allowance for deviations, Dcdev. Where there are no
Reinforcement of a type not included in the above list having X
material properties that are defined in the design or contract links the nominal cover should be at least equal to the size of the bar
specification. plus Dcdev, this may be significant for bar diameters greater than
Note 12 mm. Dcdev may be 5 or 10 mm depending on the quality assurance
In the Grade description B500A, etc., ’B’ indicates reinforcing steel.
system assumed for the project. If the cover needs to be increased to
meet these requirements, the detailer should consult with the designer.
Figure 1
Description of bond conditions
‘Good’ bond conditions ‘Poor’ bond conditions All reinforcement should be anchored so that the forces in it are safely
transmitted to the surrounding concrete by bond without causing
Table 2
Anchorage and lap lengths for concrete class C25/30 (mm)
Concrete class C20/25 C28/35 C30/37 C32/40 C35/45 C40/50 C45/55 C50/60
Factor 1.16 0.93 0.89 0.85 0.80 0.73 0.68 0.63
90
10. Detailing
cracking or spalling. The design anchorage length, lbd, (which can be Bars in compression
obtained from Table 2) is measured along the centreline of the bar In addition to the rules for bars in tension (Figure 6a), one bar of the
(see Figure 2). The anchorage of links is shown in Figure 3. transverse reinforcement should be placed outside each end of the lap
length of bars in compression and within 4f of the ends of the lap
length (see Figure 6b).
Arrangement of laps
Figure 2
Where possible laps in a member should be staggered (see Figure 4) Design anchorage length lbd, for any shape measured along the
centreline
and not located in areas of high stress. The arrangement of lapped bars
should comply with Figure 5, as set out below:
1. The clear distance between lapped bars should not be greater than
4f or 50 mm, otherwise the lap length should be increased by a
lbd f
length equal to the clear distance.
2. The longitudinal distance between two adjacent laps should not be
less than 0.3 times the lap length, l0. Where this is not the case, the
bars should be considered as being lapped in one section. Figure 3
Anchorage of links
3. In case of adjacent laps, the clear distance between adjacent bars
should not be less than 2f or 20 mm. 5f, but 10f, but
≥ 50 mm ≥ 70 mm
Figure 4
Transverse reinforcement Percentage of lapped bars in one lapped section
l0
Bars in tension
Transverse tensile stresses occur at the ends of lapped bars. Where the bar 1
If more than 50% of the bars are lapped in one location and the
distance, a, between adjacent laps at a section is ≤ 10f (see Figure 5) a
Fs ≥ 2f
transverse reinforcement should be formed by links or U-bars anchored ≥ 20 mm Fs
into the body of the section. Fs
Fs
91
How to design concrete structures using Eurocode 2
Beams Figure 7
Illustration of curtailment of longitudinal reinforcement
lbd lbd
al = 1.125d
lbd lbd
For beams designed using the co-efficients given in Table 3 of Chapter 4,
the simplified rules shown in Figure 8 may be used. However, the
simplifications are conservative and economies can be achieved by Sagging reinforcement
Figure 6 Figure 8
Transverse reinforcement for lapped splices Simplified detailing rules for beams
≤ 150 mm 30%
Fs
Fs
0.30l – al
Position of 100%
b) Bars in compression l0
effective
support Reinforcement for maximum sagging moment
4f l0/3 l0/3 4f
Table 3
Bar sizes for transverse reinforcement
50%
92
10. Detailing
93
How to design concrete structures using Eurocode 2
Similar to beams, even when simple supports have been assumed in not exceed 320 MPa for a typical slab. Where the slab supports office
design, end supports of slabs should have top reinforcement equal to or residential areas it is unlikely that ss will exceed 280 MPa. ss may
at least 25% mid-span bottom reinforcement and this reinforcement be estimated using Figure 6 on page 15.
should extend at least 20% of the span from the face of support.
Minimum areas of reinforcement
Minimum spacing requirements The minimum area of reinforcement to be provided varies with the
The minimum clear distance between bars (horizontal or vertical) concrete strength (see Table 4).
should not be less than the bar size, b, (dg + 5 mm), or 20 mm, where
dg is the maximum size of aggregate. Maximum area of longitudinal reinforcement
Outside lap locations, the maximum area of tension or compression
Maximum spacing of reinforcement reinforcement, should not exceed As,max = 0.04Ac. At lap locations
For slabs less than 200 mm thick the following maximum spacing As,max = 0.08Ac.
rules apply (h is the depth of the slab):
■ For the principal reinforcement: 3h but not more than 400 mm.
■ For the secondary reinforcement: 3.5h but not more than 450 mm.
Edge reinforcement
The exception is in areas with concentrated loads or areas of Along a free (unsupported) edge, a slab should normally contain longitudinal
maximum moment where the following applies: and transverse reinforcement, generally arranged as shown in Figure 11.
■ For the principal reinforcement: 2h but not more than 250 mm.
■ For the secondary reinforcement: 3h but not more than 400 mm.
For slabs 200 mm thick or greater, the spacing requirements are given Flat slabs
in Table 5. Where the designer has not specified the required spacing
A flat slab should be divided into column and middle strips (see
or provided the steel stress, ss, it can generally be assumed that ss will
Figure 12); the division of the moments between the column and
middle strips is given in Table 6.
Figure 10
Simplified detailing rules for slabs Figure 11
Edge reinforcement for slab
Face of support Reinforcement for
100% maximum hogging moment
≥ 2h
a) Continuous member, top reinforcement
Table 5
40% Maximum bar size or spacing to limit crack width
94
10. Detailing
The minimum area of a link leg for vertical punching shear reinforcement is
ly /4
1.5Asw,min /(sr s t ) ≥ 0.08√fck fyk
ly /4 which can be rearranged as:
Asw,min ≥ (s r s t )/F
Middle strip = ly /2 ly
where
sr = the spacing of the links in the radial direction
Column strip = ly /2 s t = the spacing of the links in the tangential direction
F = factor obtained from Table 7
Figure 13
Effective width, be of a flat slab
fyk has been taken as 500 MPa > 2000 mm +5, –25
Table 11
Table 8 Deductions to bar dimensions to allow for deviations between two
Requirements for column reinforcement concrete faces when using BS EN 136709,10
Bar dia. (mm) 12 16 20 25 32 40 Distance between concrete faces T (mm) Total deduction (mm)
Max spacinga (mm) 144b 192b 240b 240b 240b 240b ≤200 5
Min link dia. (mm) 6 c 6c 6c 8 8 10 ≤400 10
Key ≤1000 15
a At a distance greater than the larger dimension of the column above or below a ≤2000 20
beam or slab, dimensions can be increased by a factor of 1.67. >2000 30
b But not greater than minimum dimension of the column.
c 6 mm bars are not readily available in the UK. Note: The above deductions are to be used to determine bending
dimensions. An additional 10mm should be deducted when determining
the cutting length of straight bars whose ends are to be placed between
96 concrete surfaces.
10. Detailing
Figure 15 lr = the greater of the distances (in m) between the centres of the
Lapping of welded fabric columns, frames or walls supporting any two adjacent floor
spans in the direction of the tie under consideration
Fs Fs
Ft = (20 + 4n0) ≤ 60 kN (n0 is the number of storeys)
l0
The maximum spacing of internal ties is 1.5lr.
a) Intermeshed fabric (longitudinal section)
Fs
Fs
Minimum radii and end
projections
l0
The minimum radii for bends and length of end projections are given
Table 12
Minimum scheduling radii and bend allowances
At each floor and roof level an effectively continuous peripheral tie
should be provided within 1.2 m from the edge; this need not be
additional reinforcement. In practice, for most buildings, according to
≥ 5d
the UK National Annex to BS EN 1992, the tie should resist a tensile r P
force of 60 kN. An area of reinforcement of 138 mm2 is sufficient to
resist this force.
Nominal Minimum Minimum end projection, P
Internal ties should be provided at each floor and roof level in two size of bar, radius for
d (mm) scheduling, General (min 5d Links where bend
directions approximately at right angles. They should be effectively r (mm) straight), including < 150° (min 10d
continuous throughout their length and should be anchored to the links where bend > straight) (mm)
150° (mm)
peripheral ties at each end, unless continuing as horizontal ties to columns
8 16 115a 115a
or walls. The internal ties may, in whole or in part, be spread evenly in 10 20 120a 130
the slabs or may be grouped at or in beams, walls or other appropriate 12 24 125a 160
positions. In walls they should be within 0.5 m from the top or bottom of 16 32 130 210
floor slabs. In each direction, internal ties should be capable of resisting a 20 70 190 290
design value of tensile force Ftie,int (in kN per metre width): 25 87 240 365
32 112 305 465
Ftie,int = [(qk + gk)/7.5](lr/5)(Ft) ≥ Ft kN/m
40 140 580
where Key
(qk + gk) = sum of the average permanent and variable floor loads a The minimum end projections for smaller bars is governed by the practicalities of
bending bars.
(in kN/m2)
References
1 BRITISH STANDARDS INSTITUTION. BS EN 1992, Eurocode 2: Design of concrete structures. BSI (4 parts).
2 BRITISH STANDARDS INSTITUTION. BS 4449: Specification for carbon steel bars for the reinforcement of concrete. BSI, 2005.
3 BRITISH STANDARDS INSTITUTION. BS EN 10080: Steel for the reinforcement of concrete – Weldable reinforcing steel – General. BSI, 2005.
4 BRITISH STANDARDS INSTITUTION. BS 8666: Scheduling, dimensioning, bending and cutting of steel reinforcement for concrete – Specification. BSI, 2005.
5 INSTITUTION OF STRUCTURAL ENGINEERS/CONCRETE SOCIETY. Standard method of detailing structural concrete. ISE/CS, 2006.
6 CONSTRUCT. National structural concrete specification Construct, 4th Edition, 2010.
7 CONSTRUCT. A guide to contractor detailing of reinforcement in concrete. BCA, 1997.
8 THE CONCRETE SOCIETY. Technical report 62: Self-compacting concrete. CCIP–001. The Concrete Society, 2005.
9 BRITISH STANDARDS INSTITUTION (2008) EN 13670: Execution of concrete structures, London: BSI
10 GOODCHILD, C AND TOPLIS, P. Bar schedule dimensions: deductions for permitted deviations. The Structural Engineer, December 2013
97
How to design concrete structures using Eurocode 2
Table 13
Anchorage and lap lengths
50% lapped in one Good 370 510 660 970 1270 1640 2100 2860 66f
location (a6 = 1.4) Poor 530 730 950 1380 1810 2350 3000 4080 94f
Lap length,
l0 100% lapped Good 400 550 710 1030 1360 1760 2250 3060 70f
in one location (a6 = 1.5)
Poor 510 790 1010 1480 1940 2320 3220 4370 100f
Concrete class C25/30
Good 230 320 410 600 780 1010 1300 1760 40f
Straight bars only
Anchorage Poor 330 450 580 850 1120 1450 1850 2510 58f
length, lbd Good 320 410 490 650 810 1010 1300 1760 40f
Other bars
Poor 460 580 700 930 1160 1450 1850 2510 58f
50% lapped in one Good 320 440 570 830 1090 1420 1810 2460 57f
location (a6 = 1.4) Poor 460 630 820 1190 1560 2020 2590 3520 81f
Lap length,
l0 Good 340 470 610 890 1170 1520 1940 2640 61f
100% lapped
in one location (a6 = 1.5) Poor 490 680 870 1270 1670 2170 2770 3770 87f
Concrete class C28/35
Good 210 300 380 550 730 940 1200 1630 37f
Straight bars only
Anchorage Poor 300 420 540 790 1030 1340 1720 2330 53f
length, lbd Good 300 380 450 600 750 940 1200 1630 37f
Other bars
Poor 420 540 650 860 1070 1340 1720 2330 53f
50% lapped in one Good 300 410 530 770 1010 1320 1680 2280 52f
location (a6 = 1.4) Poor 420 590 760 1100 1450 1880 2400 3260 75f
Lap length,
l0 Good 320 440 570 830 1090 1410 1800 2450 56f
100% lapped
in one location (a6 = 1.5) Poor 450 630 810 1180 1550 2010 2570 3470 80f
Concrete class C30/37
Good 210 280 360 530 690 900 1150 1560 36f
Straight bars only
Anchorage Poor 290 400 520 750 990 1280 1640 2230 51f
length, lbd Good 290 360 430 580 720 900 1150 1560 36f
Other bars
Poor 410 520 620 820 1030 1280 1640 2230 51f
50% lapped in one Good 290 390 510 740 970 1260 1610 2180 50f
location (a6 = 1.4) Poor 410 560 720 1050 1380 1790 2290 3110 72f
Lap length,
l0 Good 310 420 540 790 1040 1350 1720 2340 54f
100% lapped
in one location (a6 = 1.5) Poor 430 600 780 1130 1480 1920 2460 3340 77f
Concrete class C32/40
Good 200 270 350 510 660 860 1100 1490 34f
Straight bars only
Anchorage Poor 280 380 500 720 950 1230 1570 2130 49f
length, lbd Good 270 350 420 550 690 860 1100 1490 34f
Other bars
Poor 390 490 590 790 980 1230 1570 2130 49f
50% lapped in one Good 270 380 490 710 930 1200 1540 2090 48f
location (a6 = 1.4) Poor 390 540 690 1010 1320 1720 2200 2980 69f
Lap length,
l0 Good 290 400 520 760 990 1290 1650 2240 51f
100% lapped
in one location (a6 = 1.5) Poor 420 570 740 1080 1420 1840 2350 3200 73f
98
10. Detailing
50% lapped in one Good 260 360 460 670 870 1130 1450 1970 45f
location (a6 = 1.4) Poor 370 510 650 950 1250 1620 2070 2810 65f
Lap length,
l0 100% lapped Good 280 380 490 710 940 1210 1550 2110 48f
in one location (a6 = 1.5)
Poor 390 540 700 1020 1340 1730 2220 3010 69f
Concrete class C40/50
Good 170 230 300 440 570 740 950 1290 30f
Straight bars only
Anchorage Poor 240 330 430 620 820 1060 1350 1840 42f
length, lbd Good 240 300 360 480 600 740 950 1290 30f
Other bars
Poor 340 430 510 680 850 1060 1350 1840 42f
50% lapped in one Good 240 330 420 610 800 1040 1330 1800 41f
location (a6 = 1.4) Poor 340 460 600 870 1140 1480 1890 2570 59f
Lap length,
l0 Good 250 350 450 650 860 1110 1420 1930 44f
100% lapped
in one location (a6 = 1.5) Poor 360 500 640 930 1220 1590 2030 2760 63f
Concrete class C45/55
Good 160 220 280 400 530 690 880 1190 27f
Straight bars only
Anchorage Poor 220 310 400 580 760 980 1250 1700 39f
length, lbd Good 220 280 330 440 550 690 880 1190 27f
Other bars
Poor 310 390 470 630 780 980 1250 1700 39f
50% lapped in one Good 220 300 390 560 740 960 1230 1670 38f
location (a6 = 1.4) Poor 310 430 550 800 1060 1370 1750 2380 55f
Lap length,
l0 Good 230 320 420 600 790 1030 1310 1780 41f
100% lapped
in one location (a6 = 1.5) Poor 330 460 590 860 1130 1470 1880 2550 58f
Concrete class C50/60
Good 150 200 260 380 490 640 820 1110 26f
Straight bars only
Anchorage Poor 210 290 370 540 700 910 1170 1580 37f
length, lbd Good 200 260 310 410 510 640 820 1110 26f
Other bars
Poor 290 360 440 590 730 910 1170 1580 37f
50% lapped in one Good 210 280 370 530 700 900 1160 1570 36f
location (a6 = 1.4) Poor 290 400 520 760 990 1290 1650 2240 51f
Lap length,
l0 Good 220 300 390 560 740 960 1230 1660 39f
100% lapped
in one location (a6 = 1.5) Poor 310 430 550 800 1050 1370 1750 2370 55f
Notes
1 Cover to all sides ≥ 25 mm distance between bars ≥ 50mm (i.e. a2 < 1).
2 a1 = a3 = a4 = a5 = 1.0. For the beneficial effects of shape of bar, cover and confinement see Eurocode 2, Table 8.2.
3 Design stress has been taken at 435 MPa. Where the design stress in the bar at the position from where the anchorage is measured, ssd, is less than 435 MPa the figures in this
table can be factored by ssd/435. The minimum lap length id given in cl 8.7.3 of Eurocode 2.
4 The anchorage and lap lengths have been rounded up to the nearest 10 mm.
5 Where 33% of bars are lapped in one location, decrease the lap lengths for '50% lapped in one location' by a factor of 0.82.
99
10. Detailing
Table 14
Sectional areas of groups of bars (mm2)
Table 15
Sectional areas per metre width for various spacings of bars (mm2)
Table 16
Mass of groups of bars (kg per metre run)
Table 17
Mass in kg per square metre for various spacings of bars (kg per m2)
100