Vacon100 Flow Ethernet (Modbus TCP) With Modbus Poll
Vacon100 Flow Ethernet (Modbus TCP) With Modbus Poll
PC can be connected to Frequency Converter Vacon100FLOW via local Ethernet network (router) or directly to PC.
Material
- Ethernet cable
- Vacon 100FLOW
- PC
M1 (Main Menu) => M5 (I/O and Hardware) => M5.9 (Ethernet) =>
M5.9.1 (common settings) => M5.9.1.6 (Fixed IP:
Classified
1/6
as Business
5. Set “Read/Write Definition”
• Slave ID always 255
• Reading Registers: 3 or 4 Address: 2100
• Writing registers: 5 or 6 Address: 2000
• Quantity: 10
• Scan rate: 10
• Click on Read/Write Enabled
We read value “Energy counter” from. For this action we use the ID number that each parameter or monitor value has
got. Read application manual to find it.
Result:
2290 (2291-1) = 9792= 979.2 kWh
Classified
2/6
as Business
7. Example “Function 06:Write Single Register”
We adjust parameter “Maximum frequency” to 60Hz. For this action we use the ID number that each parameter or
monitor value has got. Read application manual to find it.
Result:
Classified
3/6
as Business
8. “Function 23: Read/Write multiple registers” example
Classified
4/6
as Business
• SlaveID: 255
• Write Address: 2000
• Write Quantity: 10
• Read Address: 2100
• Read Quantity:10
Write:
2000 (FB Control word)= 1 => RUN
11=> RUN + Reverse
2002 (FB Speed Reference)= 5000 (50%) = 25 Hz
Read result:
2100= 163 (FB Status Word)
2102= 5000 = 50% (FB Actual Speed)
2103= 2500= 25% (Output frequency) PDOUT1
2104= 750 rpm (Motor speed) PDOUT2
2105= 0A (Motor current) PDOUT3
2106= -3% (Motor torque) PDOUT4
2107= 0% (Motor power) PDOUT5
2108= 2008=200,8V (Motor voltage) PDOUT6
2109= 661V (DC-Link voltage) PDOUT7
We can change Process data out values in parameter menu using own ID number of monitor value that we can read
Classified
5/6
as Business
9. Examples with Control Word and Status word
Classified
6/6
as Business