Controller CLVR02EXT-FICHA - ING
Controller CLVR02EXT-FICHA - ING
• 2 zones control panel with extinguishing functionality for conventional detectors and call points use.
• Third additional zone configurable as an alarm and detection zone for conventional detectors and call
points or as a monitoring input of an external fire protection system.
• Same technical features as conventional CLVR control panels (2 general sounder outputs, 1 alarm output,
1 fault output, 230Vdc outputs, test mode, threshold setup, metallic cabinet, etc).
• 3 modes of operating extinction:
- Standard mode: Output R1 of pre-warning is activated with Zone 1 or Zone 2 in alarm status.
- Consecutive mode: Output R1 is activated intermittently (1 second with Zone 1 or Zone 2 in
alarm status, 0,5 seconds with Zones 1 and 2 in alarm status, and continuing once the output R2
delay is finished).
- Simultaneous mode: Output R1 is activated with Zones 1 and 2 in alarm status.
• Stop and activation extinguishing button directly in the control panel.
• Possibility to install manual stop and activation buttons near the flood zone.
• 1 extinction output (”R2”) supervised, temporized supervised, temporized between 0 and 60 seconds,
protected by a resettable fuse.
• Delay for R2 extinguishing output reset after extinguishing activation temporized between 0 and 30
minutes.
• MODBUS protocol over RS485 on demand.
• Possibility of ON-LINE software in a PC using the MODBUS functionality.
• CONTACTID on demand.
• Certified according EN 54-2, EN 54-4 and EN 12094-1 with CE mark.
TECHNICAL FEATURES
Supply voltage 110/230VAC 50/60Hz End of line capacitor 4 K7
Output voltage 21 V Nominal Sounder output voltage 30 V/DC
Max. consumption 70 VA at 230 V/AC Environmentals conditions -10ºC +50ºC
Batteries 2 x 12 V 7 Ah SLA Size 363 x 331 x 96 mm
Extinction fuse R1/R2 0,5A/0,75A autoreset Weight (without batteries) 4,3 Kg
Batteries charger 500 mA 27 V/DC 20ºC Standard EN 54-2, EN 54-4 & EN 12094-1
Devices par zone 32 30v max. current output 1,5 A
Control panel power supply 2,2 A Extinction module fuse 1,85 A autoreset
Max. current per zone 2 mA (in standby) S1 output sounder fuse 1,85 A autoreset
S2 output sounder fuse 0,75 A autoreset
www.cofem.com
[email protected]
EXTINCTION
Wiring diagram
SYSTEMS
C NC NO C NO
S2 S1 ALARM FAULT 30V 30V 30V BAT Z1 Z2 Z3 Z4 R1 R2 24V
R1 R2 24V
C NC NO C NO
S2 S1 ALARM FAULT 30V 30V BAT Z1 Z2 Z3 Z4
*Note 1: The wiring diagram of the thermal probe depends of the model.
**Note 2: Zone 3 used for monitoring the pressure switch.
Example of wiring diagram with flame detectors, thermal probes and pressure switches